Selco M2500 Installation Manual

Page 1
SELCO A/S M2500 Installation Manual
Revision: 23-04-2012 Page 1
M2500 Engine Controller
Installation Manual
Page 2
SELCO A/S M2500 Installation Manual
Revision: 23-04-2012 Page 2
Contents
4.2.1 Connection of Mode Selector Switch .................................................................................. 8
4.2.2 Remote Start (terminal 8) ..................................................................................................... 9
4.2.3 Remote Stop (terminal 9) ..................................................................................................... 9
4.2.4 Override (terminal 10) ....................................................................................................... 10
4.2.5 Crank Disconnect (terminal 11) ......................................................................................... 10
4.2.6 Reset (terminal 12) ............................................................................................................. 10
4.2.7 COM (terminal 13) ............................................................................................................ 11
4.3.1 Connection of magnetic pick-up ........................................................................................ 11
4.3.2 Connection of PNP pick-up ............................................................................................... 12
4.3.3 Connection of NPN pick-up ............................................................................................... 12
4.4.1 Connection of a normally open sensor without cable monitoring ..................................... 13
4.4.2 Connection of a normally closed sensor without cable monitoring ................................... 14
4.4.3 Connection of a normally open sensor with cable monitoring .......................................... 14
4.4.4 Connection of a normally closed sensor with cable monitoring ........................................ 15
4.4.5 COM (terminal 13) ............................................................................................................ 15
4.5.1 Analogue inputs (terminals 27 to 34) ................................................................................. 16
4.5.2 COM (terminal 13) ............................................................................................................ 16
5.1.1 Connection of Engine Status Outputs ................................................................................ 17
5.1.2 Ready (terminal 36) ........................................................................................................... 18
5.1.3 Start warning (terminal 37) ................................................................................................ 18
5.1.4 Engine running (terminal 38) ............................................................................................. 18
5.1.5 Cool Down (terminal 39) ................................................................................................... 18
5.1.6 REF 1 (terminal 40) ........................................................................................................... 18
5.2.1 Connection of Engine Control Outputs .............................................................................. 19
5.2.2 Auxiliary Lubrication Pump (terminal 41) ........................................................................ 19
5.2.3 Crank (terminal 42) ............................................................................................................ 20
5.2.4 C/B trip (terminal 43) ......................................................................................................... 20
5.2.5 Air Intake Valve (terminal 44) ........................................................................................... 20
5.2.6 REF 2 (terminal 45) ........................................................................................................... 20
Page 3
SELCO A/S M2500 Installation Manual
Revision: 23-04-2012 Page 3
5.3.1 Connection of alarm outputs .............................................................................................. 21
5.3.2 Common Alarm (terminal 46) ........................................................................................... 21
5.3.3 Shutdown (terminal 47) ..................................................................................................... 21
5.3.4 Cable break (terminal 48) .................................................................................................. 21
5.3.5 CAN (terminal 49) ............................................................................................................. 21
5.3.6 REF3 (terminal 50) ............................................................................................................ 21
5.4.1 Connection of digital outputs ............................................................................................. 22
5.4.2 Digital Outputs Out 1 to Out 12 (terminals 51 to 62) ........................................................ 23
5.4.3 REF 4 (terminal 50) ........................................................................................................... 23
5.5.1 Engine Stop Output (terminal 64 and 65) .......................................................................... 23
5.5.2 Run/ Stop Solenoid (terminal 66 and 67) .......................................................................... 24
5.6.1 Connection of the Siren Relay ........................................................................................... 26
6.1.1 CAN J1939 Connector: ...................................................................................................... 27
6.1.2 CAN cable .......................................................................................................................... 27
6.1.3 RS485 MODBUS ............................................................................................................... 28
6.1.4 RS485 cable ....................................................................................................................... 28
7.2.1 Alarm flowchart: ................................................................................................................ 32
7.3.1 Shutdown flowchart: .......................................................................................................... 34
Page 4
SELCO A/S M2500 Installation Manual
Revision: 23-04-2012 Page 4
1 Preface
The M2500 - Engine Controller is designed for control and monitoring of marine engines. Together with the optional M2600 - Shutdown Unit the M2500 - Engine Controller forms a
complete alarm, control and protective safety system for marine engines. Typical applications are marine generator engines such as auxiliary generators, emergency
generators, harbour generators and propulsion engines. The M2500 is designed for assembly in the main switchboard or at the engine. This manual describes the installation of the M2500 - Engine Controller.
Page 5
SELCO A/S M2500 Installation Manual
Revision: 23-04-2012 Page 5
2 Installation
The M2500 is designed for flush mounting to the front panel of the switchboard. It is secured by 6 mounting brackets which are supplied with the M2500.
The panel cut out dimension is 138mm x 210mm
Page 6
SELCO A/S M2500 Installation Manual
Revision: 23-04-2012 Page 6
3 Terminal Connections
Primary and back-up power supply
Inputs for activation of operation modes, Inputs for remote start and stop
Input for magnetic, NPN or PNP pick­up for speed detection
Digital sensor inputs for alarms and shutdowns
Analogue sensor inputs for alarms and shutdowns
Outputs for indication of engine state (e.g. to PMS)
Control outputs
Common alarm outputs
Programmable outputs for indication of alarms and shutdowns
Engine stop relay
Programmable output for stop or run solenoid with cable monitoring
Siren relay
RS485 Modbus
Adjustment of display contrast
Interface for CANJ1939
Slot for SD card for read out of log and configuration
USB interface for configuration and read out of alarm log
Future use
Page 7
SELCO A/S M2500 Installation Manual
Revision: 23-04-2012 Page 7
4 Inputs
4.1 Power Supply
Redundant Power Supply (2x 24V DC, -30 % / +30 %) Alarm in case any power supply fails (common alarm + display text). Primary supply will not be monitored during cranking, as the battery voltage will drop during this
process.
Nr.
Description
01
Primary Supply +
02
Primary Supply -
03
Primary Supply +
04
Primary Supply -
4.2 Mode/ Control Inputs
Nr.
Description
Logic (NO/NC)
05
Remote Mode
NO
06
Local Mode
NO
07
Off Mode
NO
08
Remote Start
NO
09
Remote Stop
NO
10
Override
NO
11
Crank disconnect
NO
12
Reset
NO
13
COM
Common reference for control inputs
Page 8
SELCO A/S M2500 Installation Manual
Revision: 23-04-2012 Page 8
4.2.1 Connection of Mode Selector Switch
The external mode selector switch is used for switching the M2500 into OFF, REMOTE or LOCAL mode.
4.2.1.1 Local Mode (terminal 5)
The local mode input is considered active when connected to COM, inactive when open. When active the M2500 will be in local mode. This means start and stop are only available from the
push buttons on the front panel. The remote start and stop terminals are disabled. The LOCAL LED on the front panel will be lit. Not ready LED on the front panel will be lit and READY output terminal 36 will be deactivated indication that the engine is not available for remote start.
4.2.1.2 Remote Mode (terminal 6)
The remote mode input is considered active when connected to COM, inactive when open. When active the M2500 will be in remote mode. This means start and stop are only available from
the REMOTE START and REMOTE STOP terminals. The Local start and stop push buttons are disabled.
Provided no alarm, shutdown or Off command is active, the green REMOTE LED on the front panel will be lit and the engine is ready for remote start.
4.2.1.3 Off (terminal 7)
The off input is considered active when connected to COM, inactive when open. When activated, the M2500 will initiate a stop procedure. Engine start will be blocked as long as
this input is active. Not ready LED on the front panel will be lit indicating that the engine is not available for remote
start.
Page 9
SELCO A/S M2500 Installation Manual
Revision: 23-04-2012 Page 9
4.2.2 Remote Start (terminal 8)
The Remote Start input is considered active when connected to COM, inactive when open. It can be a pulse or continuous signal.
The input is only enabled in remote mode.
When activated, the M2500 will generate a start signal to the engine. The pre-configured number of start attempts is available. During the start attempt the green Engine Running LED on the front panel will be fast flashing. During the rest periods between start attempts this LED will be slow flashing. When the engine is running, the LED will be lit continuously.
If the engine does not start the M2500 will initiate a stop procedure and a Start Fail Alarm. The red ALARM LED on the front panel will be lit. The alarm text “START FAILURE” will be shown on the display.
4.2.3 Remote Stop (terminal 9)
The Remote Stop input is considered active when connected to COM, inactive when open. It can be a pulse or a continuous signal.
The input is only enabled in remote mode.
When activated, the M2500 will initiate a stop procedure. During the stop procedure the green Running LED will be slow flashing. The Stopping LED will be lit. If the engine does not stop the M2500 will generate a Stop Fail Alarm. The red ALARM LED on the front panel will
be lit. The alarm text “STOP
FAILURE” will be shown on the
display. The engine will be blocked for start as long as the stop input is active. When activated
simultaneously, Stop overrides Start.
Page 10
SELCO A/S M2500 Installation Manual
Revision: 23-04-2012 Page 10
4.2.4 Override (terminal 10)
The Override input is considered active when connected to COM, inactive when open.
When activated all shutdowns that are marked override will be disabled, meaning the engine will continue running despite of a shutdown. If the override is deactivated while a shutdown is present, shutdown will be executed immediately.
4.2.5 Crank Disconnect (terminal 11)
The Cranck Disconnect input is considered active when connected to COM, inactive when open.
This input is only used in case there is no pick-up for speed detection. The input is a contact from a tacho-relay that signals that the speed of the engine is above ignition speed. When receiving the Crank Disconnect signal the M2500 will deactivate the crank output after a start attempt. If the M2500 looses this signal without a stop procedure, the ALARM LED will be lit and a Tacho Fail Alarm will be displayed.
4.2.6 Reset (terminal 12)
This Reset is considered active when connected to COM, inactive when open.
When activated, this input will reset the siren and the alarm/ shutdown.
Page 11
SELCO A/S M2500 Installation Manual
Revision: 23-04-2012 Page 11
4.2.7 COM (terminal 13)
The COM is the common reference for all digital inputs.COM and power supply minus are internally connected.
4.3 Speed detection
Speed detection
Remark
14
Pick-up
Supply voltage for PNP or NPN pick-up
15
Pick-Up signal input
16
Reference for pick-up signal
4.3.1 Connection of magnetic pick-up
The magnetic pick-up is connected as follows:
For use of magnetic pick-up the DIP switches 3 and 4 on the rear side of M2500 must be in OFF position. The DIP switches are placed between the RS485 and CAN connectors on the rear side of M2500.
DIP Switch Position
1 OFF 2 OFF
Page 12
SELCO A/S M2500 Installation Manual
Revision: 23-04-2012 Page 12
4.3.2 Connection of PNP pick-up
The NPN pick-up is connected as follows:
For use of PNP pick-up the DIP switch 3 on the rear side of M2500 must be in ON position, DIP switch 4 must be in OFF position. The DIP switches are placed between the RS485 and CAN connectors on the rear side of M2500.
DIP Switch Position
1 ON 2 OFF
4.3.3 Connection of NPN pick-up
The NPN pick-up is connected as follows:
For use of NPN pick-up the DIP switch 3 on the rear side of M2500 must be in OFF position, DIP switch 4 must be in ON position. The DIP switches are placed between the RS485 and CAN connectors on the rear side of M2500.
DIP Switch Position
1 OFF 2 ON
Page 13
SELCO A/S M2500 Installation Manual
Revision: 23-04-2012 Page 13
4.4 Digital sensor inputs
Nr.
Description
Remark
17
Digital input 1
Sensor input for digital sensor 1
18
Digital input 2
Sensor input for digital sensor 2
19
Digital input 3
Sensor input for digital sensor 3
20
Digital input 4
Sensor input for digital sensor 4
21
Digital input 5
Sensor input for digital sensor 5
22
Digital input 6
Sensor input for digital sensor 6
23
Digital input 7
Sensor input for digital sensor 7
24
Digital input 8
Sensor input for digital sensor 8
25
Digital input 9
Sensor input for digital sensor 9
26
COM
Common reference for digital
sensor inputs
The Digital sensor inputs are used for the connection of the digital sensors. Digital sensors can be Normally Open (NO) or Normally Closed (NC) logic. Cable break and short circuit monitoring is available.
4.4.1 Connection of a normally open sensor without cable monitoring
The following example shows the Connection of a normally open sensor without cable monitoring.
The sensor is considered active when connected to COM, inactive when open.
When activated, the input generates an alarm or shutdowns or a control signal, depending on the configuration.
Page 14
SELCO A/S M2500 Installation Manual
Revision: 23-04-2012 Page 14
4.4.2 Connection of a normally closed sensor without cable monitoring
The following example shows the Connection of a normally closed sensor without cable monitoring.
The sensor is considered active when open, inactive when connected to COM.
When activated, the input generates an alarm or shutdowns or a control signal, depending on the configuration.
4.4.3 Connection of a normally open sensor with cable monitoring
The following example shows the Connection of a normally open sensor with cable monitoring.
The sensor is considered active when connected to COM, inactive when open.
Resistor R1 is used for cable break monitoring.
Resistor R2 is used for short circuit monitoring.
It is very important that both resistors are mounted close to the sensor.
Page 15
SELCO A/S M2500 Installation Manual
Revision: 23-04-2012 Page 15
4.4.4 Connection of a normally closed sensor with cable monitoring
The following example shows the connection of a normally closed sensor with cable monitoring.
The sensor is considered active when open, inactive when connected to COM.
Resistor R1 is used for short circuit monitoring.
Resistor R2 is used for cable break monitoring.
It is very important that both resistors are mounted close to the sensor.
4.4.5 COM (terminal 13)
The COM is the common reference for all digital inputs.COM and power supply minus are internally connected.
4.5 Analogue sensor inputs
Analogue sensor inputs are used for temperature and pressure measurements. All analogue sensors use 4-20mA signals.
Analogue Sensor Inputs
Remark
27
4mA -20mA
Analogue input 1
28
4mA -20mA
Analogue input 2
29
4mA -20mA
Analogue input 3
30
4mA -20mA
Analogue input 4
31
4mA -20mA
Analogue input 5
32
4mA -20mA
Analogue input 6
33
4mA -20mA
Analogue input 7
34
4mA -20mA
Analogue input 8
35
COM
Common reference for
analogue sensor inputs
Page 16
SELCO A/S M2500 Installation Manual
Revision: 23-04-2012 Page 16
4.5.1 Analogue inputs (terminals 27 to 34)
The analogue sensor inputs are for generating alarms and shutdowns. In case the input signal is below 3mA or above 25mA the M2500 will generate a sensor fail alarm. Cable Error LED will be lit.
Delay times can be programmed for alarms and shutdowns.
4.5.2 COM (terminal 13)
The COM is the common reference for all digital inputs.COM and power supply minus are internally connected.
Page 17
SELCO A/S M2500 Installation Manual
Revision: 23-04-2012 Page 17
5 Outputs
All outputs are relay contacts.
5.1 Engine Status Outputs
Nr.
Description
Type
Rating
36
Ready/ Not Ready
NO Relay
1A
37
Start warning
NO Relay
1A
38
Engine Running
NO Relay
1A
39
Cool down
NO Relay
1A
40
REF1
Common reference for engine status outputs
5.1.1 Connection of Engine Status Outputs
Following example shows the connection of an external relay for the engine running signal:
Page 18
SELCO A/S M2500 Installation Manual
Revision: 23-04-2012 Page 18
5.1.2 Ready (terminal 36)
Normally Open Relay output. The Ready output indicates the availability of the engine for remote start e.g. for a power management system. The output can be configured as “Engine Ready” or “Engine Not Ready”. The output is activated when closed to COM (terminal) 40.
Note: Configuration as Ready Output:
The output is activated when the engine is available for remote start. The output is de-activated in all other conditions (e.g. M2500 in Local mode shutdown error or start blocking) (normally de-energized output).
Note: Configuration as Not Ready output:
The output is activated when the engine is not available for remote start (e.g. M2500 in Local mode shutdown error or start blocking). The output is de-activated when the output is ready for remote start (normally energized output).
5.1.3 Start warning (terminal 37)
Normally Open Relay output. This output is activated for a preconfigured time before each start attempt. The output is activated when closed to COM (terminal) 40. The relay is normally de­energized.
5.1.4 Engine running (terminal 38)
Normally Open Relay output. This output indicates that the engine is running. The output is activated when closed to COM (terminal) 40. The relay is normally de-energized.
5.1.5 Cool Down (terminal 39)
Normally Open Relay output. This output indicates that the engine is in cool down mode. After receiving the engine stop command, the M2500 will trip the C/B. The engine will continue running for the duration of the cool down time. After expiration of the cool down time the M2500 will stop the engine. The cool down time can be configured. Cool Down only applies to remote mode and only for normal stops. Shutdowns will be executed immediately.
Note:
Purpose of this output is to give a signal to a synchronizer in order to avoid re-synchronization.
The output is activated when closed to COM (terminal) 40. The relay is normally de-energized.
5.1.6 REF 1 (terminal 40)
Common reference for all output relays terminals 36 to 39.
Page 19
SELCO A/S M2500 Installation Manual
Revision: 23-04-2012 Page 19
5.2 Engine Control Outputs
Nr.
Description
Type
Rating
41
Auxiliary lubrication pump
NO Relay
1A
42
Crank
NO Relay
1A
43
Circuit breaker trip
NO Relay
1A
44
Air intake valve
NO Relay
1A
45
REF 2
Common reference for the control
outputs
5.2.1 Connection of Engine Control Outputs
Following example shows the connection of an external relay for the C/B trip signal:
5.2.2 Auxiliary Lubrication Pump (terminal 41)
Normally Open Relay output. When the engine is stopped the output becomes active every 30 min for 2 min. Immediately after stop the first lubrication period is after 20 min. The interval and duration times can be configured.
The relay is normally de-energized.
Page 20
SELCO A/S M2500 Installation Manual
Revision: 23-04-2012 Page 20
5.2.3 Crank (terminal 42)
Normally Open Relay output. This is the start output of the M2500. It activates for each start attempt and remains active until either the engine has fired or the crank time has expired or a stop command has been activated at the M2500.
The relay is normally de-energized.
5.2.4 C/B trip (terminal 43)
Normally Open Relay output. This output trips the circuit breaker before the engine stops. It is always activated after a stop command has been received or a shutdown has been activated.
The relay is normally de-energized.
5.2.5 Air Intake Valve (terminal 44)
Normally Open Relay output. This is an alternative stop output. The output is activated immediately when a stop procedure is activated, regardless if this is a normal stop or a shutdown.
The relay is normally de-energized.
5.2.6 REF 2 (terminal 45)
Common reference for all output relays terminals 41 to 44.
5.3 Alarm Outputs
Nr.
Description
Type
Rating
46
Common Alarm
NO Relay
1A
47
Shutdown
NO Relay
1A
48
Cable Break
NO Relay
1A
49
Communication Error
NO Relay
1A
50
REF 3
Common reference for the alarm outputs
Page 21
SELCO A/S M2500 Installation Manual
Revision: 23-04-2012 Page 21
5.3.1 Connection of alarm outputs
Following example shows the connection of an external relay for signaling a shutdown to an external alarm system:
5.3.2 Common Alarm (terminal 46)
Normally Open Relay output. This output becomes energized for each alarm and shutdown. The relay is normally de-energized. In case a new alarm/ shutdown appear while the relay is already
energized, the alarm will de-energize for two seconds and then energize again.
5.3.3 Shutdown (terminal 47)
Normally Open Relay output. This output becomes active for each shutdown. The relay is normally de-energized.
5.3.4 Cable break (terminal 48)
Normally Open Relay output. This output becomes active for each cable break at the digital inputs or sensor fails at the analogue inputs.
The relay is normally de-energized.
5.3.5 CAN (terminal 49)
Normally Open Relay output. This output becomes active in case a communication error on the CAN J1939 is detected.
The relay is normally de-energized.
5.3.6 REF3 (terminal 50)
Common reference for all output relays terminals 46 to 49.
Page 22
SELCO A/S M2500 Installation Manual
Revision: 23-04-2012 Page 22
5.4 Digital Outputs
Nr.
Description
Type
Rating
51
Digital Output 1
(start fail in default config)
NO Relay
1A
52
Digital Output 2
(stop fail in default config)
NO Relay
1A
53
Digital Output 3
NO Relay
1A
54
Digital Output 4
NO Relay
1A
55
Digital Output 5
NO Relay
1A
56
Digital Output 6
NO Relay
1A
57
Digital Output 7
NO Relay
1A
58
Digital Output 8
NO Relay
1A
59
Digital Output 9
NO Relay
1A
60
Digital Output 10
NO Relay
1A
61
Digital Output 11
NO Relay
1A
62
Digital Output 12
NO Relay
1A
63
REF 4
Common reference for
the digital outputs
5.4.1 Connection of digital outputs
Following example shows the connection of an external relay to digital output 2:
Page 23
SELCO A/S M2500 Installation Manual
Revision: 23-04-2012 Page 23
5.4.2 Digital Outputs Out 1 to Out 12 (terminals 51 to 62)
Normally Open Relay output. These are programmable alarm and shutdown outputs. It is also possible to program these outputs to activate with any of the alarms generated from the analogue measurements.
Note:
In factory default configuration Digital Output 1 (terminal 51) is the START FAILURE OUTPUT. In factory default configuration Digital Output 2 (terminal 52) is the STOP FAILURE OUTPUT.
5.4.3 REF 4 (terminal 50)
Common reference for all output relays terminals 51 to 62.
5.5 Control Relays
Nr.
Description
Type
Rating
Remark
1
Engine Stop
Energized to stop
1A
2
Engine Stop
3
Run/ Stop Solenoid
Energized to run or
energized to stop
24V DC / 6A
Cable monitoring
4
Run/ Stop Solenoid
Note: Cable break monitoring:
Cable break monitoring is required for the stop solenoid output. The nominal voltage for this output is 24V DC, 6A current when activated.
5.5.1 Engine Stop Output (terminal 64 and 65)
Terminals 64 and 65 are a normally open contact. This output will be activated for the stop procedure until the stop time has expired (energized to stop). The output is activated both for normal stops and shutdowns. It is active in parallel with the stop solenoid relay.
Purpose of this output is to give a potential free signal to the shut.
The relay is normally de-energized
Page 24
SELCO A/S M2500 Installation Manual
Revision: 23-04-2012 Page 24
5.5.2 Run/ Stop Solenoid (terminal 66 and 67)
This output can be configured for control of the fuel valve (run solenoid) or stop solenoid.
Output configured for control of stop solenoid
In this case terminals 66 and 67 are the output for control of the stop solenoid. This output will be activated for the stop procedure until the stop time has expired (energized to stop) or (in case magnetic pick up is used for speed detection) until the engine speed is down to 10rpm (value depending on what is practical), both for normal stops and shutdowns.
The relay is normally de-energized. This output includes cable monitoring for the stop solenoid.
Note:
The RUN/STOP solenoid can only be used with 24V DC. This can be either the same supply as for the controller or a separate power supply. Please observe correct polarity when connecting the fuel valve.
When deactivated there will be a current of 5mA on this output due to the cable monitoring circuit inside the M2500.
Note:
The coil connected to this output must require a current > 5mA for activating. Otherwise the stop solenoid could be activated by the cable monitoring circuit.
This is especially important in case the stop solenoid is not activated directly by the M2500 output but by an intermediate relay, that typically requires a much lower current to activate than the stop solenoid.
The cable monitoring on this output can be disabled in the configuration, however the 5mA limit still applies.
In case the connection to the stop solenoid is lost and cable monitoring is enabled an alarm will be activated.
Page 25
SELCO A/S M2500 Installation Manual
Revision: 23-04-2012 Page 25
Output configured for control of run solenoid (fuel valve)
In this case terminals 66 and 67 are a normally open contact for control of the fuel valve. This output will be activated during start and operation of the engine (energized to run). For engine stop the output will be de-activated. The relay is normally de-energized. This output includes cable monitoring for the run solenoid.
Note:
Please note that this output can only be used with 24V DC. This can be either the same supply as for the controller or a separate power supply. Please observe correct polarity when connecting the fuel valve.
When deactivated there will be a current of 5mA on this output due to the cable monitoring circuit inside the M2500.
Note:
The coil connected to this output must require a current > 5mA for activating. Otherwise the fuel valve could be activated by the cable monitoring circuit.
This is especially important in case the fuel valve is not activated directly by the M2500 output but by an intermediate relay, that typically requires a much lower current to activate than the fuel valve.
The cable monitoring on this output can be disabled in the configuration, however even then the 5mA limit still applies.
In case the connection to the fuel valve is lost and cable monitoring is enabled an alarm will be activated.
Page 26
SELCO A/S M2500 Installation Manual
Revision: 23-04-2012 Page 26
5.6 Siren Relay
Nr.
Description
Type
Rating
68
ND
Relay contact in de-energized position
1A
69
REF 5
Reference contact of alarm relay
1A
70
NE
Relay contact in energized position
1A
The siren relay is typically used for connection of a siren. It is normally energized. It will de-energize with any new alarm or shut-down. After pressing RESET the alarm relay will
energize again.
5.6.1 Connection of the Siren Relay
In below example the siren will activate with any new incoming alarm or shutdown.
Page 27
SELCO A/S M2500 Installation Manual
Revision: 23-04-2012 Page 27
6 Communication
6.1 CAN J1939 Bus
The M2500 can communicate directly with the engine ECU by CAN bus, SAE J1939 for a maximum distance 250m.
6.1.1 CAN J1939 Connector:
Pin 1: CAN H Pin 2: CAN L Pin 3: CAN COM
The CAN J1939 is to be terminated on both ends with a 120Ω resistor.
6.1.2 CAN cable
Unshielded twisted pair 2 x 2 x 0,22... 2 x 2 x 0,5 (e.g. Lapp Kabel UNITRONIC®, BUS CAN UL/CSA (CMX), part number 2170267).
One pair is to be used for CAN H and CAN L, one wire of the remaining pair is to be used for CAN com.
Page 28
SELCO A/S M2500 Installation Manual
Revision: 23-04-2012 Page 28
6.1.3 RS485 MODBUS
M2500 includes an RS485 interface MODBUS RTU communication. RS485 Connector:
Pin 1: RS485 A Pin 2: RS485 B Pin 3: RS485 COM
The RS485 Modbus is to be terminated on both ends with a 120Ω resistor.
6.1.4 RS485 cable
Unshielded twisted pair 2 x 2 x 0,22... 2 x 2 x 0,5 (e.g. Lapp Kabel UNITRONIC®, BUS CAN UL/CSA (CMX), part number 2170267).
One pair is to be used for RS485 A and RS485 B, one wire of the remaining pair is to be used for RS485 com.
Page 29
SELCO A/S M2500 Installation Manual
Revision: 23-04-2012 Page 29
7 Functional Description
7.1 Remote Mode
In remote mode (terminal 5 connected to com) Start and stop is only available from the REMOTE START (terminal 08) and REMOTE STOP (terminal 09) terminals.
Provided the engine is ready for remote start (Not Ready LED on the front panel of M2500 is off) the start procedure works as follows:
Remote Start flowchart:
Start Warning Fuel Valve on
Engine
running?
Cranking
All start
attempts
completed?
YES
NO
Start Fail
Not ready
Lube Pump
C/B Trip
Air Intake
Common Alarm
Engine Stop
Stop Solenoid
Alarm Relay
Engine ready for
REMOTE START
NO
Start Delay
Survey Delay
Run
Fuel Vanve
Cranking
Fuel Valve on
Rest Time
NO
YES
Engine Running
Run
Fuel Vanve
YES
Remote Start
Command
YES
NO
Lube pump
according config
Ready for remote
start
Page 30
SELCO A/S M2500 Installation Manual
Revision: 23-04-2012 Page 30
Remote Stop flowchart:
Run
Fuel Vanve
C/B Trip
Cool Down
YES
Stop Fail
Not ready
Run
Fuel Valve
Engine Running
NO
Cool Down Run
Remote Stop
Command
YES
NO
Run
Fuel Vanve
Cool Down
Time expired?
Stop Procedure
Engine Stop
Stop Solenoid
Stop Time
expired?
NO
Engine
stopped?
Ready
Lube Pump
according config
YES
NO
Engine stopped
and ready for start
Page 31
SELCO A/S M2500 Installation Manual
Revision: 23-04-2012 Page 31
7.2 Alarm Monitoring
The alarm monitoring is always active regardless of Local or remote mode.
Note:
Alarms are abnormal conditions that will be indicated and logged by the M2500, but they will not stop the engine.
Alarms can be set to continuous monitoring (regardless if the engine is running or not) or conditional monitoring (only monitored if the engine is running).
An individual programmable time delay is available for each alarm. A new incoming alarm will always shift the M2500 display to the Current Alarm display. At the
same time the Alarm LED on the front panel will be fast flashing, the common alarm output (terminal 46) will activate and the Siren Relay (terminals 68, 69 and 70) will de-energize. Depending on the configuration it is possible to activate one or more of the digital outputs.
The common alarm output will de-activate for 2s and re-activate when a new alarm appear. The siren relay (terminals 68, 69 and 70) will de-activate for 2s and re-activate when a new alarm
appear. After accepting an alarm (by pressing the Reset button or external reset terminal 12) the common
alarm LED will change to steady light, the common alarm output and the optional digital output will remain active, provided the alarm is still present on the input. The siren relay will energize again after pressing Siren Reset or Reset button or external reset terminal 12.
When the all alarms disappear from the inputs and alarms have been acknowledged, the common alarm LED will switch off, the common alarm output and the optional digital outputs will deactivate.
Page 32
SELCO A/S M2500 Installation Manual
Revision: 23-04-2012 Page 32
7.2.1 Alarm flowchart:
Engine Running
Alarm Procedure
Alarm input
activated?
YES
NO
Run
Fuel Vanve
Override activated AND Alarm marked
for override?
Alarm marked
for blocking?
NO
Monitoring
delay expired?
NO
YES
Running Fuel Valve Not Ready
Common Alarm
Alarm Relay de-
energized until
Reset
YES
Page 33
SELCO A/S M2500 Installation Manual
Revision: 23-04-2012 Page 33
7.3 Shutdown Monitoring
The shutdown monitoring is always active regardless of Local or remote mode.
Note:
Shutdowns are abnormal conditions that will be indicated and logged by the M2500 and they will stop the engine.
Shutdowns can be set to continuous monitoring (regardless if the engine is running or not) or conditional monitoring (only monitored if the engine is running).
An individual programmable time delay is available for each shutdown. A new incoming shutdown will always shift the M2500 display to the Current Alarm display. At
the same time the shutdown LED on the front panel will be fast flashing, the common shutdown output (terminal 46) will activate and the Siren Relay (terminals 68, 69 and 70) will de-energize. Depending on the configuration it is possible to activate one or more of the digital outputs.
Note:
A shutdown will block the engine for start until it has been reset and the shutdown signal has disappeared.
After accepting a shutdown (by pressing the ACK button or external reset terminal 12) the Common shutdown LED will change to steady light. The shutdown output and the optional digital output will remain active provided the shutdown is still active on the input. The siren relay will energize again.
Page 34
SELCO A/S M2500 Installation Manual
Revision: 23-04-2012 Page 34
7.3.1 Shutdown flowchart:
YES
Stop Fail
Not ready
Engine Running
Shut Down
Procedure
Shut Down
input
activated?
YES
NO
Run
Fuel Vanve
Stop Time
expired?
NO
Engine
stopped?
Not Ready
Lube Pump
according config
Common Alarm
Shut Down
YES
NO
Engine stopped
and blocked for
start
Override
activated AND
Shutdown
marked for
override?
Shutdown
marked for
blocking?
NO
Monitoring
delay expired?
NO
YES
Not Ready
C/B trip
Air Intake
Common Alarm
Shut Down
Engine Stop
Stop Solenoid
Alarm Relay de-
energized until
Reset
YES
Reset?
Shutdown still
active and marked
for continuous
monitoring?
NO
YES
Engine ready for
AUTO START
Page 35
SELCO A/S M2500 Installation Manual
Revision: 23-04-2012 Page 35
7.4 Specification
Environmental conditions:
Operating temperature: -15°C to +70°C Humidity: 95% Vibration: DNV vibrations class B EMC: IEC 60945 Enclosure: IP44 (panel front only)
Supply:
Primary Supply: +24 V DC (-30 % / +30 %) Isolated, 500mA Backup Supply: +24 V DC (-30 % / +30 %) Isolated, 500mA
Pick Up Input:
Connection: Screw terminals Type: Magnetic (2-wire), NPN and PNP (3-wire), configurable via DIP switch.
Rated frequency 40.0 to 10000 Hz
Sensor inputs:
9 Digital inputs: Normally open contacts to COM (default) or normally closed
contacts to COM. Optional cable monitoring (short circuit and cable break).
8 Analogue inputs: 4-20mA -, with optional cable monitoring.
Mode / Control inputs:
Connection: Screw terminals (2,5mm2) Activation: Connect to COM
All relays (except where otherwise specified):
Relay response time: 20 ms (worst case) Contact set(s) 1 normally open Contact rating: AC: 1 A, 250 V AC, DC: 1 A, 35 V DC Function: Normally de-energized.
Run/ Stop Solenoid relay:
Relay response time: 20 ms (worst case) Contact set(s) 1 normally open Contact rating: AC: 8 A, 250 V AC, DC: 8 A, 35 V DC Function: Normally de-energized (Default) or normally energized Cable monitoring (cable break and short circuit).
System fault output relay (Siren):
Relay response time: 20 ms (worst case) Contact set(s) 1 change over Contact rating: AC: 1 A, 250 V AC, DC: 1 A, 35 V DC Function: Normally energized.
Page 36
SELCO A/S M2500 Installation Manual
Revision: 23-04-2012 Page 36
SAE J1939, CAN Bus:
Connection: Screw terminal connector, 3-wire with COM (Isolated) Distance: Max. 40m Protocol: SAE J1939 Speed: 250Kbit/s Termination: 120 ohm termination
RS485, Modbus:
Connection: Screw terminal connector, 3-wire with COM (Isolated) Distance: Max. 500m Protocol: Modbus RTU Speed: 19200 bit/s Termination: 120 ohm termination
USB:
Connection: USB type B socket (Female connector), USB 2.0 Full speed
Device, Mass storage device for configuration, inspection of log files and other diagnostics information.
Loading...