Version Nr. 38 - 21.11.2016 Doc. Nr. 99571000001 13 / 15
14. Taking into operation
Attention!
The unit can be damaged by lack of lubricant. To ensure that the compressor is adequately lubricated
the oil, which has been displaced during transport, must be allowed to flow back into it. The unit must
therefore be allowed to stand for at least 30 min. before being connected to the mains and taken into
operation. Upon connection the internal fan will start working. If the temperature inside the enclosure
is higher than the set value of the controller both the compressor and external air fan start working.
Once the air inside the enclosure reaches the set temperature the compressor and external fan will
stop.
The unit is pre-set at 35°C, which is suitable for most of the electronic devices.
15. Repair
Failure Condition Cause Solution
Unit does
not cool
Internal fan does
not work
Power not connected. Verify power supply
Internal fan works,
external fan and
compressor don't
work
Enclosure temperature
is below setting
temperature (St)
Verify values of parameter
"St"
Door switch contact is
open
Verify door switch
Controller doesn't work Replace controller
Internal fan works,
external fan and
compressor don't
work Display shows
alternating "OFF"
and temperature
The sequence of
the phases inside the
power supply connector
is
incorrect
Change phases inside
power
supply connector
Unit does
not cool
External and internal
fan work,
compressor does not
work
Compressor
motor electrical failure
Verify external fan,
verify ambient temperature,
clean
condenser
Capacitor for
compressor
failed
Replace capacitor
Compressor works,
external fan doesn't
work
External fan needs to be
replaced
Replace external fan
Enclosure
over
heating
Compressor and
fans
(external and
internal)
work all the time
Unit cooling undersized Enclosure needs a bigger
cooling unit
Enclosure needs a
bigger
cooling unit
Thermal compressor
protector triggered
Verify ambient
temperature,
clean condenser
Refrigerant leakage Contact dealer/service
center
Excessive
condensate
Door enclosure open
Ambient air gets into
the enclosure
Ensure door is closed, add
a door switch and connect it
to controller
Door enclosure
closed
Enclosure IP degree
minimum IP54
Seal openings on enclosure
Damaged misplaced
sealing strip
Repair strip accordingly