1. User manual
This instruction manual contains information and instructions to enable the user to work safely, correctly and
economically on the unit. Understanding and adhering to the manual can help one:
Avoid any dangers.
Reduce repair costs and stoppages.
Extend and improve the reliability and working life of the unit.
PLEASE ENSURE TO USE THE RIGHT VERSION OF THE INSTRUCTION MANUAL SUITABLE FOR YOUR
UNIT.
Conditions of use
The unit is to be used exclusively for the dissipation of heat from control cabinets and enclosures in order to
protect temperature sensitive components in an industrial environment. To meet the conditions of use, all the
information and instructions in the instruction manual must be adhered to.
General danger
Indicates compulsory safety regulations which are not
covered by a specific pictogram such as one of the following.
High electric voltage
Indicates electric shock danger.
Important safety instruction
Indicates instructions for safe maintenance and operation of
the unit.
Attention
Indicates possible burns from hot components.
Attention
Indicates possible damage to the unit.
Instruction
Indicates possible danger to the environment.
2. Legal regulations
Liability
The information, data and instructions contained in this instruction manual are current at the time of going to
press. We reserve the right to make technical changes to the unit in the course of its development. Therefore,
no claims can be accepted for previously delivered units based on the information, diagrams or descriptions
contained in this manual. No liability can be accepted for damage and production caused by:
Version Nr. 1-2 - 09.08.2019Doc. Nr. 9940508702 / 12
Disregarding the instruction manual
Operating error
Inappropriate work on or with the unit
The use of non-specified spare parts and accessories
Unauthorised modifications or changes to the unit by the user or his personnel
The supplier is only liable for errors and omissions as outlined in the guarantee conditions contained in the main
contractual agreement. Claims for damages on any grounds are excluded.
3. Safety instructions
Upon delivery the unit is already meeting current technical standards and can therefore be safely taken into
operation. Only authorised personnel is allowed to work on the unit. Unauthorised personnel must be prohibited
from working on the unit. Operating personnel must inform their superiors immediately of any malfunction of
the unit.
Please note that before starting to work on or with the unit, a procedure must be carried out inside the cabinet
on which the unit is to be mounted.
Before commencing work inside the cabinet, the control cabinet manufacturer's instruction must be read with
regards to:
Safety instructions.
Instructions on taking the cabinet out of operation.
Instructions on the prevention of unauthorised cabinet reconnection.
The electric equipment meets the valid safety regulations. One can find dangerous voltages (above 50 V AC or
above 100 V DC)
Behind the control cabinet doors.
On the power supply in the unit housing.
The unit has to be operated according to the type plate and the wiring diagram, and must be protected
externally from overloading and electrical faults via suitable protective devices such as ground fault protection
breakers.
Danger through incorrect work on the unit
The unit can only be installed and maintained by technical competent and qualified
personnel, using only supplied material according to the supplied instructions.
Danger from electrical voltage
Only specialised personnel are allowed to maintain and clean the unit. The personnel must
ensure that for the duration of the maintenance and cleaning, the unit is disconnected from
the electrical supply.
Attention
Damage to the unit through the use of inappropriate cleaning materials. Please do not use
aggressive cleaning material.
Instruction
Damage to the environment through unauthorised disposal. All spare parts and associated
material must be disposed according to the environmental laws.
Version Nr. 1-2 - 09.08.2019Doc. Nr. 9940508703 / 12
4. Controller functions
The cooling unit is intended to be used as a complementary accessory to larger industrial equipment. The unit
is used where heat needs to be dissipated from electrical control cabinets or similar enclosures in order to
protect heat sensitive components. It is not intended for household use. The unit has two completely separate
air circuits which ensure that the clean cabinet air does not come into contact with the ambient air which may
well be dirty or polluted. Control cabinet cooling units can dissipate large quantities of heat from sealed
enclosures such as electrical enclosures into the ambient air and at the same time reduce the cabinet internal
temperature to below that of the ambient air.
The unit can function without problems in extreme ambient conditions (e.g. dusty and oily air) with a standard
operating temperature ranging between -20°C and +55°C. Units can be ordered with an additional electrical
cabinet heater. For the cooling capacities and evironmental ratings please refer to the type plate data.
5. Functional principle
The cooling unit for enclosures works on the basis of a refrigeration circuit consisting of four main
components: compressor (1), evaporator (2), condenser (3) and expansion device (4).
The circuit is hermetically sealed and R134a refrigerant circulates inside it (R134a is chlorine free and has an
Ozone Destruction Potential [ODP] of 0 and a Global Warning Potential [GWP] of 1430). The compressor
compresses the refrigerant (thus taking it to high pressure and high temperature), and pushes it through the
condenser, where it is cooled by ambient air thus passing from the gas to the liquid state. At the liquid state it
then passes through the capillary pipe being a much lower pressure the refrigerant arrived to the evaporator
where it absorbs the necessary heat to change from liquid to gas state. The gas is then drawn back into the
compressor completing the cycle.
1. Air intake, cabinet side 7. Radial fan, ambient side
2. Radial fan, cabinet side 8. Condenser
3. Evaporator9. Air outlet, ambient side
4. Air outlet, cabinet side 10. Filter dryer
5. Compressor11. Capillary pipe
6. Air intake, ambient side
Version Nr. 1-2 - 09.08.2019Doc. Nr. 9940508704 / 12
6. Technical data
Order Number4050870
Cooling capacity L35L354.5 kW
Heating capacity2000 W
CompressorRotary piston compressor
Refrigerant / GWPR134a / 1430
Refrigerant charge3625 g / 128 oz
High / low pressure
Temperature range-20°C - +40°C
Air volume flow (system / unimpeded)
MountingExternal
Housing MaterialMild steel, powder coated
Dimension HxWxD1,900 x 900 x 620 mm
Weight185 kg
Voltage / Frequency
Current L35L355.1 A
Starting current31 A
Max. current31 A
Nominal power L35L352,5 kW
Max. power3,5 kW
Fuse3 x 10 A (T)
ConnectionWAGO 9-pole connector, male
Ingress protection
ApprovalsCE, EX, RoHS
40 / 10 bar
580 / 150 psig
Ambient air circuit: 1770 / 4443 m³/h
Cabinet air circuit: 1770 / 2000 m³/h
380/415 V - 50 Hz 3~
400/460 V - 60 Hz 3~
Internal IP 20
Ambient IP 54
Version Nr. 1-2 - 09.08.2019Doc. Nr. 9940508705 / 12
7. Mounting
Always disconnect the power supply before opening the unit.
The heat load to be dissipated from enclosure should not exceed specific cooling output of the unit at any
condition. At cooling unit selection always cater for a safety margin of at least 15% extra cooling output in the
worst conditions. Air inlets and outlets must be completely free from obstruction.
Ensure that flows of air leaving and entering the cooling unit, internal and external, are not obstructed. Cooling
unit enclosure air suction hole must be installed in the highest possible point. When installing the unit on a door
ensure it can take the weight.
Before drilling the enclosure ensure the fixing elements and couplings will not interfere with the equipment
inside the enclosure itself. Disconnect power before starting any work inside the enclosure. Following this 1:1
Scale Drilling Template drill the holes and make the required cuts on the enclosure. This template may have
been affected by storage conditions, please check this template by verifying values of the largest dimensions
before drilling. Fit the sealing strip on the cooling unit on the side connected to the enclosure and follow the
installation diagram.
This AC unit can only be mounted to a suitably Type rated enclosure to maintain it's Type rating. The Type and
IP rating of the enclosure should be the same or higher than that of the unit.
Version Nr. 1-2 - 09.08.2019Doc. Nr. 9940508706 / 12
Version Nr. 1-2 - 09.08.2019Doc. Nr. 9940508709 / 12
Version Nr. 1-2 - 09.08.2019Doc. Nr. 99405087010 / 12
11. Taking into operation
Attention!
The unit can be damaged by lack of lubricant. To ensure that the compressor is adequately lubricated the oil,
which has been displaced during transport, must be allowed to flow back into it. The unit must therefore be
allowed to stand for at least 30 min. before being connected to the mains and taken into operation.
The unit / system must be protected with a MCB Type D or K.
Upon connection the internal fan will start working. If the temperature inside the enclosure is higher than the
set value of the controller both the compressor and external air fan start working. Once the air inside the
enclosure reaches the set temperature the compressor and external fan will stop.
The unit is pre-set at 35°C, which is suitable for most of the electronic devices.
12. Trouble shooting
FailureConditionCauseSolution
Internal fan does not work Power not connected. Verify power supply
Unit
doesn't
cool
Unit
doesn't
cool
Enclosure
temperature
too hot
Excessive
condensate
Internal fan works, external fan
and compressor don't work
Internal fan works, external fan
and compressor don't work.
Display shows alternating OFF
and temperature
External and internal fan work,
compressor does not work
Compressor works, external fan
doesn't work
Compressor and fans (external
and internal) work all the time
Compressor and external fan
work in alternating mode
(ON / OFF)
Enclosure door open
Enclosure door closed
Enclosure temperature is below
setting temperature (St)
Door switch contact is open Verify door switch
Controller doesn't work Replace controller
The sequence of the phases
inside the power supply
connector is incorrect
Compressor motor electrical
failure
Capacitor for compressor failed Replace capacitor
External fan needs to be
replaced
Cooling unit undersized
Thermal compressor protector
triggered
Refrigerant leakageContact dealer/service center
Ambient air gets into the
enclosure
Enclosure IP protection class
is below IP54
Damaged or misplaced sealing
strip
Verify values of parameter
"St"
Change phases inside power
supply connector
Have compressor replaced
by qualified service technician
Replace external fan
Enclosure needs a cooling
unit with with higher capacity
Verify if ambient temperature
is too high,clean condenser
Ensure door is closed, add
a door switch and connect
it to controller
Seal all openings of the
enclosure
Repair sealing strip
accordingly
13. Maintenance & Cleaning
Always switch power supply off before starting any maintenance on
the unit.
The cooling unit is generally maintenance free and can be operated without filters in most environments. For
units with filters these should be checked, cleaned and if necessary replaced on a regular basis. In addition the
unit should have regular functional tests (approx. every 2,000 hours depending on the grade of ambient
pollution).
Disposal.
The cooling unit contains R134a refrigerant and small quantities of lubricating oil. Replacement, repairs and
final disposal must be done according to the regulations of each country for these substances.
Version Nr. 1-2 - 09.08.2019Doc. Nr. 99405087011 / 12
14. Transport & Storage
Malfunction due to transport damage
On delivery the carton box containing the unit must be examined for signs of transport damage. Any transport
damage to the carton box could indicate that the unit itself has been damaged in transit which in the worst case
could mean that the unit will not function.
The unit can only be stored in locations which meet the following conditions:
temperature range: - 40°C to + 70°C
Relative humidity (at 25°C): max. 95 %
Returning the unit
To avoid transport damage the unit should be returned in the original packing or in a packing case and must be
strapped to a pallet. If the unit cannot be returned in the original packing please ensure that:
A space of at least 30 mm. must be maintained at all points between the unit and the external packing.
The unit must be shipped in the same position as it was mounted.
The unit must be protected by shock resistant padding (hard foam corner pieces, strips or cardboard
corner pieces).
15. Parts supplied
1 x Air Conditioner
1 x Instruction manual
1 x EC Declaration
1 x 9 - pole female connector
1 x Mounting gasket top
1 x Mounting gasket bottom
6 x Lifting hooks and washers
1 x Spare Nylon Mesh Filter (Ambient Inlet)
Seifert Systems GmbHSeifert Systems Ltd.Seifert Systems AGSeifert Systems Inc.Seifert Systems Pty Ltd.
Albert - Einstein Str. 3HF09/10 Wilerstrasse 1675 Circuit Drive105 Lewis Road
Hal-Far Industrial Estate North KingstownWantirna South
42477 RadevormwaldBirzebbuga, BBG 30004563 GerlafingenRI 02853152 Victoria
DeutschlandMaltaSwitzerlandUSAAustralia
Tel. +49 2195 68994-0Tel. +356 2220 7000Tel. +41 32 675 35 51Tel. +1 401-294-6960Tel. +61 3 98 01 19 06
Fax +49 2195 6899420Fax +356 2165 2009Fax +41 32 675 44 76Fax +1 401-294-6963Fax. +61 3 98 87 08 45
info.de@seifertsystems.com info@seifertsystems.com info.ch@seifertsystems.com info.us@seifertsystems.com info@seifertsystems.com.au
Version Nr. 1-2 - 09.08.2019Doc. Nr. 99405087012 / 12
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.