Seifert OC-4050EX-400V User Manual

Table of Content 4050870
1. User manual 2 ..................................................................................................................................
2. Legal regulations 2 .........................................................................................................................
3. Safety instructions 3 ......................................................................................................................
4. Controller functions 4 .....................................................................................................................
5. Functional principle 4 .....................................................................................................................
6. Technical data 5 ..............................................................................................................................
8. Mounting Principle 7 .......................................................................................................................
9. Controller Layout Description 8 ....................................................................................................
10. Wiring diagram 9 ...........................................................................................................................
11. Taking into operation 11 ..............................................................................................................
12. Trouble shooting 11 ......................................................................................................................
13. Maintenance & Cleaning 11 .........................................................................................................
14. Transport & Storage 12 ................................................................................................................
15. Parts supplied 12 ..........................................................................................................................
Version Nr. 1-2 - 09.08.2019 Doc. Nr. 994050870 1 / 12

1. User manual

This instruction manual contains information and instructions to enable the user to work safely, correctly and economically on the unit. Understanding and adhering to the manual can help one:
Avoid any dangers.
Reduce repair costs and stoppages.
Extend and improve the reliability and working life of the unit.
PLEASE ENSURE TO USE THE RIGHT VERSION OF THE INSTRUCTION MANUAL SUITABLE FOR YOUR UNIT.
Conditions of use 󰾬The unit is to be used exclusively for the dissipation of heat from control cabinets and enclosures in order to
protect temperature sensitive components in an industrial environment. To meet the conditions of use, all the information and instructions in the instruction manual must be adhered to.
General danger
Indicates compulsory safety regulations which are not covered by a specific pictogram such as one of the following.
High electric voltage
Indicates electric shock danger.
Important safety instruction
Indicates instructions for safe maintenance and operation of the unit.
Attention
Indicates possible burns from hot components.
Attention
Indicates possible damage to the unit.
Instruction
Indicates possible danger to the environment.

2. Legal regulations

Liability
The information, data and instructions contained in this instruction manual are current at the time of going to press. We reserve the right to make technical changes to the unit in the course of its development. Therefore, no claims can be accepted for previously delivered units based on the information, diagrams or descriptions contained in this manual. No liability can be accepted for damage and production caused by:
Version Nr. 1-2 - 09.08.2019 Doc. Nr. 994050870 2 / 12
Disregarding the instruction manual Operating error Inappropriate work on or with the unit The use of non-specified spare parts and accessories Unauthorised modifications or changes to the unit by the user or his personnel
The supplier is only liable for errors and omissions as outlined in the guarantee conditions contained in the main contractual agreement. Claims for damages on any grounds are excluded.

3. Safety instructions

Upon delivery the unit is already meeting current technical standards and can therefore be safely taken into operation. Only authorised personnel is allowed to work on the unit. Unauthorised personnel must be prohibited from working on the unit. Operating personnel must inform their superiors immediately of any malfunction of the unit. Please note that before starting to work on or with the unit, a procedure must be carried out inside the cabinet on which the unit is to be mounted. Before commencing work inside the cabinet, the control cabinet manufacturer's instruction must be read with regards to:
Safety instructions. Instructions on taking the cabinet out of operation. Instructions on the prevention of unauthorised cabinet reconnection.
The electric equipment meets the valid safety regulations. One can find dangerous voltages (above 50 V AC or above 100 V DC)
Behind the control cabinet doors. On the power supply in the unit housing.
The unit has to be operated according to the type plate and the wiring diagram, and must be protected externally from overloading and electrical faults via suitable protective devices such as ground fault protection breakers.
Danger through incorrect work on the unit
The unit can only be installed and maintained by technical competent and qualified personnel, using only supplied material according to the supplied instructions.
Danger from electrical voltage
Only specialised personnel are allowed to maintain and clean the unit. The personnel must ensure that for the duration of the maintenance and cleaning, the unit is disconnected from
󰾬
the electrical supply.
Attention
Damage to the unit through the use of inappropriate cleaning materials. Please do not use aggressive cleaning material.
Instruction
Damage to the environment through unauthorised disposal. All spare parts and associated material must be disposed according to the environmental laws.
Version Nr. 1-2 - 09.08.2019 Doc. Nr. 994050870 3 / 12

4. Controller functions

The cooling unit is intended to be used as a complementary accessory to larger industrial equipment. The unit is used where heat needs to be dissipated from electrical control cabinets or similar enclosures in order to protect heat sensitive components. It is not intended for household use. The unit has two completely separate air circuits which ensure that the clean cabinet air does not come into contact with the ambient air which may well be dirty or polluted. Control cabinet cooling units can dissipate large quantities of heat from sealed enclosures such as electrical enclosures into the ambient air and at the same time reduce the cabinet internal temperature to below that of the ambient air. The unit can function without problems in extreme ambient conditions (e.g. dusty and oily air) with a standard operating temperature ranging between -20°C and +55°C. Units can be ordered with an additional electrical cabinet heater. For the cooling capacities and evironmental ratings please refer to the type plate data.

5. Functional principle

The cooling unit for enclosures works on the basis of a refrigeration circuit consisting of four main components: compressor (1), evaporator (2), condenser (3) and expansion device (4). The circuit is hermetically sealed and R134a refrigerant circulates inside it (R134a is chlorine free and has an Ozone Destruction Potential [ODP] of 0 and a Global Warning Potential [GWP] of 1430). The compressor compresses the refrigerant (thus taking it to high pressure and high temperature), and pushes it through the condenser, where it is cooled by ambient air thus passing from the gas to the liquid state. At the liquid state it then passes through the capillary pipe being a much lower pressure the refrigerant arrived to the evaporator where it absorbs the necessary heat to change from liquid to gas state. The gas is then drawn back into the compressor completing the cycle.
1. Air intake, cabinet side 7. Radial fan, ambient side
2. Radial fan, cabinet side 8. Condenser
3. Evaporator 9. Air outlet, ambient side
4. Air outlet, cabinet side 10. Filter dryer
5. Compressor 11. Capillary pipe
6. Air intake, ambient side
Version Nr. 1-2 - 09.08.2019 Doc. Nr. 994050870 4 / 12

6. Technical data

Order Number 4050870 Cooling capacity L35L35 4.5 kW Heating capacity 2000 W Compressor Rotary piston compressor Refrigerant / GWP R134a / 1430 Refrigerant charge 3625 g / 128 oz
High / low pressure
Temperature range -20°C - +40°C
Air volume flow (system / unimpeded)
Mounting External Housing Material Mild steel, powder coated Dimension HxWxD 1,900 x 900 x 620 mm Weight 185 kg
Voltage / Frequency
Current L35L35 5.1 A Starting current 31 A Max. current 31 A Nominal power L35L35 2,5 kW Max. power 3,5 kW Fuse 3 x 10 A (T) Connection WAGO 9-pole connector, male
Ingress protection
Approvals CE, EX, RoHS
40 / 10 bar 580 / 150 psig
Ambient air circuit: 1770 / 4443 m³/h Cabinet air circuit: 1770 / 2000 m³/h
380/415 V - 50 Hz 3~ 400/460 V - 60 Hz 3~
Internal IP 20 Ambient IP 54
Version Nr. 1-2 - 09.08.2019 Doc. Nr. 994050870 5 / 12

7. Mounting

Always disconnect the power supply before opening the unit.
The heat load to be dissipated from enclosure should not exceed specific cooling output of the unit at any condition. At cooling unit selection always cater for a safety margin of at least 15% extra cooling output in the worst conditions. Air inlets and outlets must be completely free from obstruction. Ensure that flows of air leaving and entering the cooling unit, internal and external, are not obstructed. Cooling unit enclosure air suction hole must be installed in the highest possible point. When installing the unit on a door ensure it can take the weight. Before drilling the enclosure ensure the fixing elements and couplings will not interfere with the equipment inside the enclosure itself. Disconnect power before starting any work inside the enclosure. Following this 1:1 Scale Drilling Template drill the holes and make the required cuts on the enclosure. This template may have been affected by storage conditions, please check this template by verifying values of the largest dimensions before drilling. Fit the sealing strip on the cooling unit on the side connected to the enclosure and follow the installation diagram.
This AC unit can only be mounted to a suitably Type rated enclosure to maintain it's Type rating. The Type and IP rating of the enclosure should be the same or higher than that of the unit.
Version Nr. 1-2 - 09.08.2019 Doc. Nr. 994050870 6 / 12
1 Nut 2 Toothed washer 3 Flat washer 4 Enclosure 5 Mounting gasket top 6 M10 Lifting hook 7 PVC washer 8 Cooling unit 9 M8 Bolt 10 Mounting gasket bottom

8. Mounting Principle

Version Nr. 1-2 - 09.08.2019 Doc. Nr. 994050870 7 / 12

9. Controller Layout Description

FDP_PP Full display port and programming port TB Test button AC Alarm control TC Temp Control ETS External temp sensor AO Alarm output
PS
FK Fans klixon CC Compressor contactor GC Ground connection T Transformer SDP Simple display port DP Diagnose port
Power supply input and power distribution to a/c fans
Version Nr. 1-2 - 09.08.2019 Doc. Nr. 994050870 8 / 12

10. Wiring diagram

CSB Current Sensor board ABCR AMB Blower Current Relay CBAB Relay AMB Blower VTDM VIB/TRIP DISP module ZB Zener Barrier VS VIB Sensor AB Ambient Blower AZ ATEX ZONE 22 SZ SAFE ZONE ITS Internal Temp Sensor (to H/E) OPT Optional: For setup including heat exchanger IB Internal Blowers ITS Internal Temp. Sensor ATS Ambient Temp. Sensor PTS PP Temp. sensor TB Test button IH Internal Heater Comms Communication (flat cable DISP Display VSAS Vibration Sensor – Alarm signal CRABTS Current Relay – Ambient blower trip signal VSABTS Vibration Sensor – Ambient blower trip signal CBC Relay compressor CCR Compressor current relay SP Surge protector C Compressor #1 L1 L1 Live to H/E #2 L2 L2 Live to H/E #3 L3 L3 Live to H/E #4 Earth 1 L1 Live 2 L2 Live 3 L3 Live
PE Earth
5 T1 Door contact (bridged with T2) 6 T2 Door contact (bridged with T1)
7 P1 Alarm contact 8 P2 Alarm contact 9 P3 Alarm contact
Normal (switched on)
Alarm (switched on)
Kabelfarbe
BK Black BU Blue BN Brown
GNYE Green/yellow
GY Grey PK Pink RD Red VT Violet
WH White
Version Nr. 1-2 - 09.08.2019 Doc. Nr. 994050870 9 / 12
Version Nr. 1-2 - 09.08.2019 Doc. Nr. 994050870 10 / 12

11. Taking into operation

Attention!
The unit can be damaged by lack of lubricant. To ensure that the compressor is adequately lubricated the oil, which has been displaced during transport, must be allowed to flow back into it. The unit must therefore be allowed to stand for at least 30 min. before being connected to the mains and taken into operation. The unit / system must be protected with a MCB Type D or K. Upon connection the internal fan will start working. If the temperature inside the enclosure is higher than the set value of the controller both the compressor and external air fan start working. Once the air inside the enclosure reaches the set temperature the compressor and external fan will stop. The unit is pre-set at 35°C, which is suitable for most of the electronic devices.

12. Trouble shooting

Failure Condition Cause Solution
Internal fan does not work Power not connected. Verify power supply
Unit doesn't cool
Unit doesn't cool
Enclosure temperature too hot
Excessive condensate
Internal fan works, external fan and compressor don't work
Internal fan works, external fan and compressor don't work. Display shows alternating OFF and temperature
External and internal fan work, compressor does not work
Compressor works, external fan doesn't work
Compressor and fans (external and internal) work all the time
Compressor and external fan work in alternating mode (ON / OFF)
Enclosure door open
Enclosure door closed
Enclosure temperature is below setting temperature (St)
Door switch contact is open Verify door switch Controller doesn't work Replace controller
The sequence of the phases inside the power supply connector is incorrect
Compressor motor electrical failure
Capacitor for compressor failed Replace capacitor External fan needs to be
replaced
Cooling unit undersized
Thermal compressor protector triggered
Refrigerant leakage Contact dealer/service center
Ambient air gets into the enclosure
Enclosure IP protection class is below IP54
Damaged or misplaced sealing strip
Verify values of parameter "St"
Change phases inside power supply connector
Have compressor replaced by qualified service technician
Replace external fan
Enclosure needs a cooling unit with with higher capacity
Verify if ambient temperature is too high,clean condenser
Ensure door is closed, add a door switch and connect it to controller
Seal all openings of the enclosure
Repair sealing strip accordingly

13. Maintenance & Cleaning

Always switch power supply off before starting any maintenance on the unit.
The cooling unit is generally maintenance free and can be operated without filters in most environments. For units with filters these should be checked, cleaned and if necessary replaced on a regular basis. In addition the unit should have regular functional tests (approx. every 2,000 hours depending on the grade of ambient pollution).
Disposal.
The cooling unit contains R134a refrigerant and small quantities of lubricating oil. Replacement, repairs and final disposal must be done according to the regulations of each country for these substances.
Version Nr. 1-2 - 09.08.2019 Doc. Nr. 994050870 11 / 12

14. Transport & Storage

Malfunction due to transport damage
On delivery the carton box containing the unit must be examined for signs of transport damage. Any transport damage to the carton box could indicate that the unit itself has been damaged in transit which in the worst case could mean that the unit will not function. The unit can only be stored in locations which meet the following conditions:
temperature range: - 40°C to + 70°C Relative humidity (at 25°C): max. 95 %
Returning the unit
To avoid transport damage the unit should be returned in the original packing or in a packing case and must be strapped to a pallet. If the unit cannot be returned in the original packing please ensure that:
A space of at least 30 mm. must be maintained at all points between the unit and the external packing. The unit must be shipped in the same position as it was mounted. 󰾬The unit must be protected by shock resistant padding (hard foam corner pieces, strips or cardboard corner pieces).

15. Parts supplied

1 x Air Conditioner 1 x Instruction manual 1 x EC Declaration 1 x 9 - pole female connector 1 x Mounting gasket top 1 x Mounting gasket bottom 6 x Lifting hooks and washers 1 x Spare Nylon Mesh Filter (Ambient Inlet)
Seifert Systems GmbH Seifert Systems Ltd. Seifert Systems AG Seifert Systems Inc. Seifert Systems Pty Ltd.
Albert - Einstein Str. 3 HF09/10 Wilerstrasse 16 75 Circuit Drive 105 Lewis Road Hal-Far Industrial Estate North Kingstown Wantirna South 42477 Radevormwald Birzebbuga, BBG 3000 4563 Gerlafingen RI 0285 3152 Victoria Deutschland Malta Switzerland USA Australia Tel. +49 2195 68994-0 Tel. +356 2220 7000 Tel. +41 32 675 35 51 Tel. +1 401-294-6960 Tel. +61 3 98 01 19 06 Fax +49 2195 6899420 Fax +356 2165 2009 Fax +41 32 675 44 76 Fax +1 401-294-6963 Fax. +61 3 98 87 08 45 info.de@seifertsystems.com info@seifertsystems.com info.ch@seifertsystems.com info.us@seifertsystems.com info@seifertsystems.com.au