Securitron AQU243-8C1R Specsheet

AQU243-8C1R
FEATURES:
Clean, steady, accurate power output for best performance of access control equipment
Compact modules for smaller footprint
Universal transformer compatible with most international power
Works in AC brownout down to 60 VAC
Faster battery recharging under full load
Automatic low-battery disconnect prevents deep discharge, maintains battery life
Self-resetting circuit breakers for common conditions including:
o Overcurrent o Thermal runaway o Reverse battery hookup
Fuse protected against surge for AC input and DC output
Eight (8) channel power distribution with fire relay trigger
o Channels individually selectable to ON/OFF/Always ON in response to fire relay o Power limited protected outputs, each with a green status LED indicator o Main power green/red LED indicates AC, DC or Reversed DC input o Main fuse/power pull to disconnect board from input powe r o Latching or non-latching
SPDT Form C output for remote monitoring of:
o AC failure o Low battery
Made in USA
MagnaCare Lifetime Replacement No Fault Warranty
UL and ULC Listed
Power Supply
The AQU243-8C1R power supply with battery charger/backup and supervision is a single voltage power supply with a fire transfer relay that uses any AC power source from 90-240VAC/47-63Hz to provide up to 3 Amps @ 12VDC continuous output.
Electrical
Environment
SPECIFICATIONS: AQU243-8C1R
Regulatory
Power Module: AQU243
Distribution Board: -8C1R
Electrical
Transfer Relay: 15Amps max
Mechanical
*Use gauge appropriate for output voltage and wiring distance.
Input Voltage Operating Range
90-240VAC 47-63Hz
Maximum Output Voltage
79.2 VA
3.3 Amps @ 12VDC
Continuous Output Voltage
72 VA 3 Amps @ 12VDC
Voltage Range
9.8 – 13.67VDC/ 13.65 typical
Operating Fr e quency
27KHz
Onboard Power Output
One (1) Output
Fuse Protection
Battery: PTC 3 Amp Current Overload: PTC, self-resetting Thermal Runaway: PTC, self-resetting
Supervision/Monitoring
AC ON LED indicator: 6mA DC ON LED indicator: 6mA AC Fail notification: SPDT Form C 2 Amp Low Battery: SPDT Form C 3 Amp
PTC Circuit breakers hold current at 130˚F
Maximum Ou t p ut Per Channe l
8 channels @ 1.23A/channel, Power Limited
Supervision
Trouble/Triggered Form C: 2A Green LED per channel
Fuses
Output: PTC 1.23A/channel Holds current at 130°F Main Fuse/Power Pull: 20A ATO
Relay
Reverse Polarity Trigger: Input: 30VDC max Voltage Trigger: +/-20% input voltage
EOL Trigger: Input: 2.2K ohms Trigger: +/- 50% resistance on wire pair
Operating Temperature: -4 to +104˚F [-20 to +40˚C] Humidity: 95% RH non condensing
UL 294, UL 603, ULC S318-96
RoHS lead free
Dimensions
Enclosure: 14”x 9” x 3.5” Power Module: 6.4” x 3.95” x 2.35”
Mounting: 5.36” x 3.54” Fire Transfer Relay: 3.88” x 4.84” x .75”
Mounting: 3.41” x 4.50” Shipping Weight: 7.65 lbs
Loading...