Power Supply
Features
• Small – Light – Efficient – Clean Power
• Field Selectable AC Input: 120/240 VAC
• Tolerates brownout or overvoltage input ± 15% of nominal voltage
• High efficiency: up to 90% at 24V output, full load
• Battery Charger Maximum Charge Current: 1.5A
• Dedicated Constant Current/ Constant Voltage battery charging circuit for
Wet, AGM, and Sealed Lead Acid Batteries
• Power Limited Output with Thermal Protection
• Reverse Battery Protection
• Battery Online, No Drop or Switchover with AC Power Fail
• UL Listed Access Control & Burglar Alarm Systems
• Set of Form “C” Relay Contacts Indicates AC Power Status
• Set of Form “C” Relay Contacts Indicates Low Battery
• Amber LED Indicates Power Normal
• Available Class II Power Limited Outputs
• Lifetime Warranty
Description
The AQS series are heavy-duty, self-contained, efficient, clean, offline switching power supplies, with linear-type performance. The AQS
series have a dedicated lead acid battery(s) charger that obtains maximum battery life while providing 12 VDC or 24 VDC uninterruptible
power for access control security systems. The field selectable AC input on AQS models allows these power supplies to be powered
anywhere in the world. The AQS series have exceptional brownout capability with operation down to 85% of nominal voltage. The AQ series
have an extensive filtering system that provides linear output performance, and they are electronically protected against battery reversal,
shorting, or overloading. All variants are Power limited output with thermal protection when used with a distribution board. Each of these
protective features will self-restore.
NOTE: Before connecting load and battery(s), ensure the 12V/24V jumper is moved to the desired voltage.
CAUTION: Damage can occur when switching the DC output voltage. Proper voltage must be confirmed before connecting devices.
500-25015_2
1

The AQS series are UL Listed and have additional supervisory features:
UL recorded output range for compatibility
on battery
Caution: To avoid spark, AC must be applied before connecting battery cable to battery
• Battery disconnect relay when battery(s) are depleted
• Set of Form “C” relay contacts that indicate AC power failure
• Set of Form “C” relay contacts that indicate low battery(s)
• Green LED for local “AC” on indication.
• DC Output is Class II power limited when used with distribution boards.
Note: If no distribution boards are used, Class 1 wiring is required on all outputs. If there is power limited and non-power limited wire there
shall be a min of ¼ inch spacing between the power limited and non-power limited wire.
Depending on load, low battery trouble indicates 50–75% battery capacity remaining. Input wiring to the unit should be enclosed in conduit
secured firmly to the enclosure. The AQS cannot be used to power a mercantile bell.
Specifications
Model AQS1210 AQS1216 AQS2410
AC Input
AC Input Terminals
AC Frequency 50 to 60 Hz
AC Fuse Rating 15A / 32V ATM 20A / 32V ATM 15A / 32V ATM
CAUTION: To prevent damage, the power supply board must be configured for the proper voltage before applying line voltage
CAUTION: for continued protection against risk of fire, replace only with fuse of the same type and having the same electrical ratings.
L,N,G -3P Terminal Block. Safety block Safety block with recessed hardware insulation
accepts up to 12 AWG
120 / 240 VAC (696W) 120 / 240 VAC (624W)
Note: There is a removable link on the top of the power supply board. This link is cut and removed to convert to 240VAC. Once cut,
there is no conversion back to 120 VAC
DC Outputs 1 output, 2 Pin terminal block
Note: There is up to a 10 second delay for initial turn on
Output voltage nominal 12 VDC 24 VDC
Output voltage typical 12.5 VDC 25.5 VDC
Output range with rated load 12.5 VDC 25.5 VDC
9.8 - 13.2 VDC 18.7 – 26.4 VDC
Output continuous current rating 10 16 10
Load regulation no load to max (no battery) ±0.2%
Current overload short circuit protection Yes Yes Yes
Thermal runaway protection Yes Yes Yes
Power limited Output Yes Yes Yes
Note: Current overload and thermal shutdown will auto-restart without removing load
Ambient operating temperature range "+4F to +122F (-20C to +50C)
Note: UL verified +32F to +120F (0C to +49C), not evaluated for outdoor use
DC LED Indicator Green
Battery Charging 2 spade terminal block marked "-Bat+"
Fault reporting relay rating 30VDC, 240VAC, 3A, resistive load only
The battery charger is precision set to float charge 12V or 24V sealed or wet lead acid batteries. A 12-inch battery cable assembly is
provided that plugs from module to battery: Red (+), Black (–) Neg.
Battery(s), any type of lead acid 12V / 24V, 4 AH–40 AH
UL evaluated battery 120 Ah 120 Ah 2 x 120 Ah
Battery(s) recharge 1.5A max 1.5A max 1.5A max
Battery(s) average recharging current 1A 1A 1A
Battery(s) PTC self-resetting circuit breaker 2A 2A PTC 4A PTC
Battery(s) Reverse hookup protection Yes, 500mA PTC Yes, 1A PTC Yes, 2A PTC
2