Power Supply
The AQD3-8F8R power supply with battery
charger/backup and supervision is a dual voltage
switching power supply with a fire transfer relay that
uses any AC power source from 90-240VAC/43-63Hz
to provide up to 3 Amps @ 12VDC or 1.5 Amps @
24VDC total output.
• Clean, steady, accurate power output for best performance of access control equipment
• Field-se lectable dual voltage 3A/1.5A @ 12/24VDC
• Compact modules for smaller footprint
• Universal transformer compatible with international power, operates down to 60 VAC
• Faster battery recharging under full load
• Automatic low-battery disconnect prevents deep discharge, maintains battery life
• Self-resetting circuit breakers for common conditions including: Overcurrent, Thermal
runaway, reverse battery hookup
• Class 2 power limited output
• Eight (8) channel power distribution with access control and fire transfer relays
o Channels individually configurable to enable/disable with fire trigger
o Heavy duty relay per output with status LED, or group outputs by jumper
o Can provide dry contacts, Normally Open/Normally Closed selected via jumper
o Individual input for each output
o Power-limited, fuse-protected outputs, each with a green status LED indicator
o Main power LED indicates input power status
o Trigger LED indicates Fire Relay status
o Pluggable terminal b locks by channel and func t io n
• Fuse protected against surge for AC input and DC output
• SPDT Form C outputs for remote monitoring of: AC failure, Low ba ttery
• Made in USA
• MagnaCare Lifetime Replacement No Fault Warranty
• UL Listed

SPECIFICATIO N S: AQD3-8F8R
Access Control Module: -8F8R
*Use gauge appropriate for output voltage and wiring distance.
Input Voltage Operating Range
90-240VAC
47-63Hz
Maximum Output Voltage
36 VA
3 Amps @ 12VDC
1.5 Amps @ 24VDC
Continuous Output Voltage
33.5 VA
2.8 Amps @ 12VDC
1.4 Amps @ 24VDC
Voltage Range
9.8 – 13.7VDC/ 13.65 typical
20.0 – 27.5VDC/ 27.3 typical
Operating Fr e quency
66KHz
Onboard Power Output
One (1) Class 2 Power Limited
Universal 11-29VDC operation
Max board power use: 208mA
Output Wire Gaug e Ra ng e
14-22AWG*, 5mm spacing
Fuses
Size: 050 Standard 3AGC
Output: .5A
Relays
Input Relays: 20ma required for activation
Output Relays: contacts rated 7A 125VAC
max
Triggers
EOL: +/-60% of 2.2K ohms
Fuse Protection
AC fuse: GMA-2 2 Amp
Battery: PTC 3 Amp
Current Overload: PTC, self-resetting
Thermal Runaway: PTC, self-resetting
Supervision/Monitoring
AC ON LED indicator: 6mA
DC ON LED indicator: 6mA
AC Fail notification: SPDT Form C 2 Amp
Low Battery: SPDT Form C 3 Amp
UL 294
UL 603
ULC-S318-96
RoHS lead free
Enclosure: 14”x 9” x 3.5”
Power Board: 3.73”x 4.84” x 2”
Mounting: 3.41” x 4.5”
Module: 4.82” x 3.84” x 1.4”
Mounting: 3.4” x 4.5”