Securitron AQD3-1R Specsheet

AQD3-1R
FEATURES:
Power Supply
The AQD3-1R power supply with battery charger/backup and supervision is a dual voltage switching power supply with a fire transfer relay that uses any AC power source from 90-240VAC to provide up to 3 Amps @ 12VDC or 1.5 Amps @ 24VDC total output.
Clean, steady, accurate power output for best performance of access control equipment
Field-se lectable dual voltage 3A/1.5A @ 12/24VDC
Compact modules for smaller footprint
Universal transformer compatible with most international power
Works in AC brownout down to 60 VAC
Faster battery recharging under full load
Automatic low-battery disconnect prevents deep discharge, maintains battery life
Self-resetting circuit breakers for common conditions including:
Class 2 power limited output with LED status indicator
Fire Transfer Relay
Fuse protected against surge for AC input and DC output
SPDT Form C outputs for remote monitoring of:
Made in USA
MagnaCare Lifetime Replacement No Fault Warranty
UL and ULC Listed
o Overcurrent o Thermal runaway o Reverse battery hookup
o Normally ON and Normally OFF output o Power shifts from ON output to OFF output when triggered o Latching or Non-latching mode o LED trigger status indicators o Multiple ways to trigger o Provides ground fault detection
o AC failure o Low battery o Trigger status
Electrical
Electrical
SPECIFICATIONS: AQD3-1R
Power Module: AQD3
Dimensions
Regulatory
RoHS lead free
*Use gauge appropriate for output voltage and wiring distance.
Fire Transfer Relay: -1R
Mechanical
Input Voltage Operating Range
90-240VAC 47-63Hz
Maximum Output Voltage
36 VA 3 Amps @ 12VDC
1.5 Amps @ 24VDC
Continuous Output Voltage
33.5 VA
2.8 Amps @ 12VDC
1.4 Amps @ 24VDC
Voltage Range
9.8 – 13.7VDC/ 13.65 typical
20.0 – 27.5VDC/ 27.3 typical
Operating Fr e quency
66KHz
Onboard Power Output
One (1) Class 2 Power Limited
Board power with no output load: 70mA Output: 2 output terminal blocks
- 1 Normally ON
- 1 Normally OFF
Output Wire Gaug e
10-28AWG*
Supervision
Trouble/Triggered Form C: 3A Trigger Status LED: 6mA
Relay
Input Trigger OVR: Normally Closed 14-28AWG Input Trigger AUX-IN: Normally Closed 14­28AWG EOL Trigger: Input: 2.2K ohms Trigger: +/- 60% resistance on wire pair Reset Input: 14-28AWG
Transfer Relay: Rated 12Amps max
Fuse Protection
AC fuse: GMA-2 2 Amp Battery: PTC 3 Amp Current Overload: PTC, self-resetting Thermal Runaway: PTC, self-resetting
Supervision/Monitoring
AC ON LED indicator: 6mA DC ON LED indicator: 6mA AC Fail notification: SPDT Form C 2 Amp Low Battery: SPDT Form C 3 Amp
UL 294
UL 603 ULC-S318-96 ULC-5533-02
Enclosure: 14”x 9” x 3.5”
Power Board: 3.73”x 4.84” x 2” Mounting: 3.41” x 4.5”
Fire Transfer Relay: 2.23” x 3.75” x .8”
Mounting: 1.89” x 3.41” Shipping Weight: 7.87 lbs