Secure SES 302, SES 303 User And Installation Instructions Manual

SES 302 and SES 303
Temperature & Humidity Sensor
User and Installation Instructions
BGX501-923-03
SES 302 and SES 303
The SES 302 a nd SES 303 are fully compliant Z-Wav e Plus™ devices which will work with other manu fac turer’s Z-Wave devices.
2
External Pip e and Tank Temperature Sensors (Optional)
The SES 302/303 can support either 1-thermi stor (SE S 0 01) or up to 4-external d igital temperature se nsors (SES 002/003).
Please take note of the f oll owing:
1. Refer “Produ ct Order ing Code s” sect ion for order detai l s.
2. The connector for exter nal probes is on th e rear w all plate.
3. The conne ctor is only for connecting external sensors .
4. Do not connect to the mains.
3
W all P late
TOPTOP
1 2 3 4 5
Conne ctor for
External Sensors
5. Refer to t he P ip e/ Ta nk t emperature sensor (SES 00x) manua l for the c on nection diagram.
4
Installation
Keep the SES 302 / SES 303 in its sealed pack until all dust and debris have been cleared away prior to ma king connections .
Remove the wall p late f rom t he rear of t he SES 302/303.
a) The w all plate ca n be released by
pressing the spri ng clips on the bott om of the wall plate
b) While pres s ing spring cl ips, swing the
wall plate out and down to remove.
5
a) Push spri ng cli ps to r elease b) Sw ing wal lpl ate out and dow n
Wallplate
6
Choose the positi on where the unit is to be mounted (refer to the following layout).
Avoid locati ons alongsi de or behind large metal surfaces tha t could i nterfere with th e lo w po wer rad io signals between the unit
1.5 m
7
and the controlle r. The sensor shou ld be mounted on an internal wall, appr oximately
1.5 me tres (5 f eet) ab ov e floor level and
away from draughts, direct heat sources and sunlight.
Mak e sure th at th ere is suffic ien t spac e around the unit to all ow easy access to the two retai ning spring cli ps on the base of the wall plate.
It may be necessary to move the sensor around to ensure good communication.
Do n ot attempt to m ount it on the wall until it has been i ncluded on the net work.
Note: Inclusion means add and exclusion means delete.
8
Including and Excluding a Device
Fit 2 x A A
1.5V
batteries
Check
correct
polarity
Fit t he tw o sup plied AA b at teries. The b attery compart ment i s m arked with a plus and minus sign. Ensure that eac h battery is c orrectly ali gn ed. The SES 302/303 will now power up.
9
Step 1: On the Z-Wave controller, s elec t Include if yo u are ad ding a dev ic e to the network or select Exclude if yo u are removing a device from the network. Check with the controller manu fac turer’s manual .
Button
LED
K
A
Step 2: O n the SES 302 or SES 303, press the button, ho ld a nd relea se a fter 1 s econ d
10
to send a re quest (Network Information Frame) to jo in the network.
On succe ss fu l inclusion the LED will flash 2 times.
The total proces s can ta ke u p to 2 0 seconds; refer to the “Radio” section for details.
If t he LED flashes 4-times this means that the inclusion proce ss ha s f ailed, so try moving the SES 302/SES 303 to a nother position a nd re peat the Incl usion steps. If the inclusion process fails again, the device may be alre ady included in another n etwo r k. So first exclude and then include the device.
11
The controller will show when the incl usion/ Exclusion operation is successful.
Asso ciati ng a Device on a Z-Wave Network
Association process is applicable only after devi ce included onto n etwork) Pleas e no te th at some cont rol lers ca n automatic ally associate. Al ways check with the manufacturer’s manual.
Step 1: Put the contr oller int o Association Mode.
Step 2: Press and hold SES 302/ SES 303 button for more than 1 second and the n release.
12
Step 3: The controller will confirm association when the process is successfully completed.
RF commu ni cat ion check after installation
Press button for less than 1 se cond. The SES 302/SES 303 will send temperature report of onboard sensor.
Note: this fe ature only works when the device has been inc lud ed in netw ork a nd the nodes associated.
Se nding Node Information - Pr ess an d hold SES 302/303 button for more than 1 second and then re le ase .
13
Device E ndpoints details
End Point No.
Reports to the nodes at the Endpoint
1
Measured Temperature report.
Measured Humidity report.
Low battery Alarm report.
2
Temperature report external digital sensor 01 or thermistor.
3
Temperature report external digital sensor
02.
4
Temperature report external digital sensor
03
5
Temperature report external digital sensor 04
14
Te chnic a l Informa tion of Z-Wave
Plus command classes
Z-Wave Plus Device Classes
I mplemented Device Class Generic
Multilevel sensor
Specific
Routing Multilevel sensor
Basic
Routing Slave
Battery operated devices do not support routing functionality.
Command Class
Commands Suppor ted
Multilevel Sensor (V6) Get
Report
Used to report measured sensor values to associated nodes.
Manufacturer Specific
(V2)
Manufacturer Specific Get
Manufacturer Specific Report
Device Specific Get
Device Specific Report
15
Manufactur er ID = 0 x0059
Product Type ID = 0x000D Product ID = 0x0002 (SES 302)
Product ID = 0x0003 (SES 303)
Version (V2)
Get
Report
Version Command Class Get
Version Command Class Report
Batter y Le vel (V1) Get
Report
Battery report is issued on a battery change or when a low-level battery is detected.
Wake Up (V2)
Wake Up Interval Capabilities Get
Wake Up Interval Capabilities
Wake Up Interval Set
Wake Up Interval Get
Wake Up Interval Report
Wake Up Notification
16
Wake Up No More Information
Wakeup interval step is 60 seconds
Minimum wakeup interval is 2 minutes Maximum wakeup interval is 24 hours
Default wakeup interval is 24 hours
Association (V2)
Set
Get
Report
Remove
Supported Groupings Get
Supported Groupings Report
Specific Group Get Command
Specific Group Report Command
Product supports one group for each end point that have a maximum of 2 nodes.
Multi Channel (V3)
Multi Channel End Point Get
Multi Channel End Point Report
Multi Channel Capability Get
17
Multi Channel Capability Report
Multi Channel End Point Find
Multi Channel End Point Find
Multi Channel Command Encapsulation
18
Up to a maximum of five end points supported. The
number of end points on the product is detected based on the number of external sensors connected to the product at the time of Inclusion. I f external sensor not connected this command class is not supported.
Note: external digital sensors must have correct hardware address otherwise it will not work.
For example: If one external sensor is connected it should have HW address 1. If two external sensors are connected it should have HW address 1 and 2 Note: Refer to the Pipe/Tank temperature sensor (SES 00x) manual for device address setting.
19
Configuration (V1)
Set
Get
Report
For configuration details refer to the “Configuration Parameters” section.
Device Locally Reset (V1)
Report
Button press 3 times within 3 seconds will put the device
in factory default, that include setting all the configuration, Association to factory default and removing the device
from Z-Wave network.
Association
Group Info (V1)
Group Name Get
Group Name Report
Group Info get
Group Info Report
Group Command List Get
Group Command List Report
Only one association group is supported on each end point and its name is “Lifeline”.
20
Profile MSB -
ASSOCIATION_GROUP_INFO_REPORT_PROFILE_G ENERAL Profile LSB ­ASSOCIATION_GROUP_INFO_REPORT_PROFILE_G ENERAL_NA
Supported Command class and command :
1. COMMAND_CLASS_SENSOR_MULTILEVEL,
SENSOR_MULTILEVEL_REPORT_V6
2. COMMAND_CLASS_BATTERY,
BATTERY_REPORT
Z-Wave Plus Info (V2)
Get
Report
21
Role Type -
ROLE_TYPE_SLAVE_SLEEPING_REPORTING Node Type ­ZWAVEPLUS_INFO_REPORT_NODE_TYPE_ZWAVEP LUS_NODE I nstaller Icon­ICON_TYPE_SPECIFIC_SENSOR_MULTILEVEL_MUL TIDEVICE User Icon­ICON_TYPE_SPECIFIC_SENSOR_MULTILEVEL_MUL
TIDEVICE
Power Level (V1)
Power Level Set
Power Level Get
Power Level Report
Power Level Test Node Set
Power Level Test Node Get
Power Level Test Node Report
None
22
Configuration Parameters
No
Type
Unit
Resolution
Default
Value
Supported
Endpoints
1
Delta
Temp
°C 0.1 0°C 1 - 5
2
Temp
Reporting
Interval
Mins 1 5 Min 1 – 5
3
Delta
Humidity
RH
%
0.1
5
%Rh
1
4
Humidity
Reporting
Interval
Mins 1 5 Min 1
23
Common attributes:
Access Types = Read/ Write Size Bytes = 1, Min Value = 0, Max Value = 255 Zero configuration mean that the corresponding
functionality is disabled.
Configuration value = Desired value/ Resolution. Example: To configure Delta temperature to 2 °C. The
value need to be configured in device is 2/0.1 = 20. IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128…255, the value sent in the application shall be equal to desired value minus 256. For example, to set Delta Temperature to 130, it may be needed to set a value 130256=−126.
Note: For more information about Z-Wave command classes and their use refer “SDS12652 Z-Wave Command Class Specification” ver 3 or above and “SDS12657 Z-Wave Command Class Specification” ver 2 or above.
24
Product Ordering Codes
SES
302
Z-Wave
Temperature
Sensor
NU2010302000
SES
303
Z-Wave
Temperature and Humidity
Sensor
NU2010303000 SES
001
Thermistor Temperature Sensor with 3m cable
BGX301-536
SES
002
Digital Pipe & Tank
Temperature Sensor with
1m cable
NU5680501000
SES
003
Digital Pipe & Tank
Temperature Sensor with
4m cable
NU5680601000
25
Technical Specifications
Specific at ion ap pl ies to b oth SE S 302 and SES 303 unles s otherw is e sta ted.
Electrical
Purpose of Control: Electronic Te mperature and
Humidity Sensor (Independently
Mounted) Software Class: Cla ss A Batter y operated device using two AA batteries. ** Do not use rechargeable batteries** Each battery: 1.5V Nominal Life: 2 years (with onboard & 4 wired
temp sensors with the default
configuration)
26
For 5-years battery life, delta reporting should be zero
and no external sensors: (1) SES 302: configure >15min reporting interval (2) SES 303: configure >1hour reporting interval
Measurement
SES 302:
Temperature Accuracy: ±0.5°C for 0°C to 40°C
SES 303:
Temperature Accuracy: ±0.5°C for 0°C to 40°C
Humidity Accuracy: ±3% RH for 20% RH to 80% RH
SES 001:
Accuracy of optional NTC temperature probe: ±1.0°C for 15°C to 85°C
SES 002 /
SES003:
Accuracy of optional pipe / tank sensor:
±0.5°C for 0°C to 65°C &±1°C for 66°C
to 85°C
27
Mechanical
Dimensions:
85x85x30 mm
Case Material:
Thermoplastic, fla me
retardant
Mounting
Wall mounting to fit a
single gang wall box
Weight (single unit
packing):
205 ± 30 g
Ball Pressure Test
Temperature:
75°C
After Care: Clean only with a clean damp cloth; do not use any aggressive cleaning agents. If cleaning agents are necessary, check compatibility before use.
28
Environmental
Storage temperature: -20°C to 55°C Operating temperature: 0°C to 40°C Environmental humidity range: 0%RH to 95%RH Atmospheric Range: 980 to 1035 hPa Pollution Degree: Degree 2 Enclosure protection: IP30
Radio
Receiver Category: Category 3 Power Class: Class B RF frequency Europe & UK: 868.42MHz ANZ: 921.42MHz RF range: 100m line of sight in
open air. Inclusion: If the Z-Wave controller does not respond within 2-seconds then the SES will try with NWI (Network Wise Inclusion). The total process can take up to 20 seconds.
29
This is a Z-Wave certified product and can be used with Z-Wave controllers that support its functionality. Please refer to the documentation provided by the gateway or controller manufacturer. See the Z-Wave alliance website www.z-wavealliance.org for certified controllers.
Compliance
HSR
O
IEC 61010-1 R&TTE directiv e ETSI EN 300 220-2 EN 301 489 part 1 & 3 EN 61000 – 4 -2 & 3.
30
NOTES
31
32
33
European Head Office
Secure Controls (UK) Ltd. South Bristol Business Park Roman Farm Road Bristol, BS4 1UP, UK e: info@securetogether.com www.securetogether.com
European Sales Office
CEWE Instrument AB Box 1006, 611 31 Nyköping t: +46 8 600 80 60 e: info@securetogether.com www.securetogether.com
34
Australia Sales Office
Secure Australasia Pty Ltd 258 Darebin Road Fairfield VIC 3078 Australia p: +61 3 9485 6000 f: +61 3 9485 6099 e: info@securetogether.com www.securetogether.com
Secure Meters Ltd
Pratapnagar Industrial Area Udaipur 313003 India p: +91 294 2492 300-05 f: +91 294 2492 310 e: mktg@securetogether.com www.securetogether.com
35
El egant Metering Solutions FZE
4EA 326, P.O. Box 54857 Dubai Airport Free Zone Dubai, UAE p: +971 50 6575166 f: +971 04 204 5619 e:
emsfze@emsdxb.ae
www.securetogether.com
Loading...