All Noble Air Purifiers are designed to address Heating and
Air Conditioning air handling units. Noble air purifiers use
ultraviolet germicidal light at a frequency of 254 nanometers to disinfect biological growth in return or supply air
stream . Some key features of the Noble Air series:
• Aluminum and Steel enclosure
• Multiple lamp lengths (9 and 18 inches)
• UL/CUL Listed
• Electronic start 120-277 VAC power supply
• Improves efficiency, reduces maintenance
• High intensity lamps
• Over 9000 hours lamp expectancy
• Lifetime unit warranty
• One year lamp warranty
Troubleshooting
Warranty
Please read all instructions carefully to help ensure a correct and SAFE installation of your Noble Ultraviolet Germicidal Air Purifier. Failure to do so could damage the equipment or cause harm to yourself or others. Only qualified Heating Ventilation and Air Conditioning (HVAC) technicians should perform the installation.
6
6 & 7
READ ALL WARNINGS AND CAUTIONS
WA RN IN G
Ultraviolet (UV) light can be harmful to eyes and skin,
causing loss of sight and sunburn. When installing, do
not put unit in an area that allows the UV lamp to be
visible . Turn off electrical service before servicing
unit.
Electrical shock hazard from 120/277 VAC may cause
serious injury or death. Disconnect power before starting installation or maintenance.
Each UV lamp contains a small amount of mercury. In
case of breakage use proper disposal techniques.
(pg.5)
Wear protective gloves and safety glasses when handling lamp. To prevent injury, unplug lamp connector
and allow to cool for 10 minutes before servicing.
CAUTION
1. Ultraviolet (UV) light can cause the degradation
of plastics, rubber, and other non-metallic materials with out uv-inhibitors, used in the HVAC system.
• Install unit in location that prevents exposure to
plastics, rubber, and other non-metallic materials
to UV light, or shield such materials with aluminum tape, sheet metal, or metal conduit.
• If equipment or components are not made of UV
resistant materials, shield with aluminum tape or
sheet metal.
2. Ultraviolet lamps
• Do not install lamp inside coil.
• Do not install lamp below any water source.
• Failure to remove fingerprints from lamp could
shorten lifespan. (clean with denatured alcohol)
• Dispose of broken and replacement lamps at your
local waste management office. For information
on local disposal laws refer to
www.lamprecycle.org
2
1. Install the lamp where you have easy access.
2. Make sure before drilling into equipment that there is nothing in the way that would be damaged.
3. The lamp should be installed a minimum of 2-3 inches, maximum 36 inches away from the coil or pan
surface.
4. When looking for a mounting location, try to install the unit away from non UV resistant plastics, rubber,
and other non metallic materials. Shield these components using sheet metal, aluminum tape, or metal conduit.
• Electric Drill
• Phillips screwdriver
• 2”-2.25” hole cutter
• 3/32” drill bit
• Eye protection
• Tape measure
• Aluminum tape and sealant
• Number 10 nut driver
• Multimeter
3