SECO-LARM USA EAP-5D1 User Manual

EAP-5D1
1 Output, 5A@12VDC, 4.5A@24VDC
Features:
AC power failure supervision relay. Battery failure supervision relay. Selectable 2.2K-Ohm End-of-Line (EOL) resistor for AC failure and battery failure supervision relays. Selectable delay timer (5 sec., 5 min., 5 hours) for AC failure supervision relay. LED overload indicator and automatic shutdown for short­circuit protection. Over-current fuse-protected AC input. Built-in back-up battery charger Automatically switch to back-up battery if AC fails.
Dimensions: 12-3/16" x 12-7/16" x 3-9/16"
Individual AC input and DC output LED status indicators.
Power
Field selectable for 12VDC or 24VDC output. Operating voltage input 110~240 VAC. Adjustable voltage range (11~15 VDC, 23~26 VDC) to compensate for voltage drop. Supply current: 5 Amps @ 12VDC, 4.5 Amps @ 24VDC. AC input fuse rating 3.15 Amps (glass fuse). DC output overload sensing with red LED indicator and automatic shutdown during short circuit.
Enclosure
Heavy-duty steel case to protect the power connections. Removable steel cover for easy access. Ventilation holes to prevent heat build-up. Enclosure has enough room for two 7AH batteries. 6-foot power cord and battery leads included. Dimensions: 12-3/16” x 12-7/16” x 3-9/16”. Knock-out on the cover for optional cam lock.
AccessControlPowerSupply.cdr
+
AC input LED
status indicator
DC output
terminal block
DIP switch
for 12 or 24 VDC
output selection
VR1 rotary knob
for DC output voltage range
adjustment
AC failure delay timer DIP switch
End-of Line (EOL) 2.2K Ohm resistor DIP switch
Battery presence
and low battery
monitor DIP switch
1.949.261.2999 (CA & Int’l) 1.800.662.0800 Fax: 1.949.261.7326 Email: info@seco-larm.com Website: www.seco-larm.com
Connections:
110~240 VAC
INPUT
Battery failure & low battery Supervision Relay Output to
Audio/Visual warning device
SL-126A
Power Supply
Power Supply
AC failure Supervision
Relay Output to
Audio/Visual
warning device
DC output LED status indicator*
Copyright 2007 SECO-LARM U.S.A., Inc. All rights reserved.
The SECO-LARM policy is one of continual development. For that reason, SECO-LARM reserves the right to change prices and specifications without notice. SECO-LARM is not responsible for misprints.
Back-up
battery terminal
AC input fuse
-
12 VDC Battery
(Optional)
16842 Millikan Avenue, Irvine, CA 92606
®
Loading...