TROUBLESHOOTING
Problem:
• Door does not lock
• Status LED is not illuminated
Door locks, but can be easily forced open
Delay in door releasing
No relay output
Delay in door relocking
Possible cause:
No power
Poor contact between electromagnet and armature plate
Incorrect voltage setting
• A secondary diode was installed across the electromagnet
• No power
• Misalignment
• Check timer
Solutions:
• Check to make sure the wires are securely tightened to the terminal block.
• Check that the power supply is connected and operating.
• Make sure the lock switch is wired correctly.
• Make sure the electromagnet and armature plate are properly aligned.
• Make sure the contact surfaces of the electromagnet and armature plate are clean and free from rust.
• Check the power leads with a meter, and make sure 12VDC or 24VDC is present.
• The electromagnet is fitted with a metal oxide varistor to prevent interference, so do not install a secondary diode.
• Check that the power is connected and operating.
• Make sure the lock is aligned properly.
• Make sure the NO/NC/COM are wired properly.
• Make sure timer is adjusted to desired delay time.
REGULAR MAINTENANCE
• Clean the contact surfaces of the electromagnet or armature plate with a soft cloth and non-abrasive, non-corrosive cleaner.
• Apply a light coat of a silicon lubricant to prevent rust. Wipe away the excess.
• Check that the armature plate is securely attached to the door, yet can pivot slightly around the armature screw.
• Check that the electromagnet is securely attached to the door frame.
ELECTROMAGNETIC LOCK Installation Manual
Installation Manual
ECS O
SECO
SECOSECO
E-941SA-1K2PD
1200 Pound Holding Force Electromagnetic Lock with status sensor, LED status display and adjustable time delay.
Also available:
E-941DA-1K2P
E-941SA-1200 E-941SA-600 E-941SA-300
HOW IT WORKS
When power is applied to the magnetic lock, it turns on the unit's powerful built-in electromagnet. This electromagnet is attracted to the steel armature plate which is mounted on a door, holding the door fast against unauthorized entry. When power to the magnetic lock is turned off, the electromagnet releases the armature plate, allowing the door to open. In addition, the E-941SA-1K2PD has built-in LEDs to show electromagnet status, plus a status sensor to monitor whether the door is securely closed, and a built-in adjustable-delay locking timer.
-
L R
-
LAR
--
L RLAR
-
Double-door 1200 lb. maglock with status sensor and LED
-
1200 lb. maglock without status sensor
-
600 lb. maglock without status sensor
-
300 lb. maglock without status sensor
M
M
MM
LIFETIME LIMITED WARRANTY: This SECO-LARM product is warranted against defects in
material and workmanship while used in normal service for the lifetime of the product. SECO-LARM’s obligation is limited to the repair or replacement of any defective part if the unit is returned, transportation prepaid, to SECO-LARM. Under no circumstances will SECO-LARM be responsible for any costs or charges for removal, installation, or reinstallation.
This Warranty is void if damage is caused by or attributed to acts of God, physical or electrical misuse or abuse, neglect, repair, or alteration, improper or abnormal usage, or faulty installation, or if for any other reason SECO-LARM determines that such equipment is not operating properly as a result of causes other than defects in material and workmanship.
The sole obligation of SECO-LARM, and the purchaser’s exclusive remedy, shall be limited to repair or replacement only, at SECO-LARM’s option. In no event shall SECO-LARM be liable for any special, collateral, incidental, or consequential personal or property damages of any kind to the purchaser or anyone else. This lifetime limited warranty is for products sold and installed in the United States and Canada. For all other countries the warranty is 1 (one) year.
NOTICE: The information and specifications printed in this manual are current at the time of publication. However,
the SECO-LARM policy is one of continual development and improvement. For this reason, SECO-LARM reserves the right to change specifications without notice. SECO-LARM is also not responsible for misprints or typographical errors. Copyright © 2011 SECO-LARM U S A., Inc. All rights reserved. This material may not be reproduced or copied, in whole or in part, without the written permission of SECO-LARM.
SECO-LARM U.S.A., Inc. 16842 Millikan Avenue, Irvine, CA 92606
Tel: 800-662-0800 / 949-261-2999 Fax: 949-261-7326
., O A U c
Website: www.seco-larm.com
@
seco-larm.com
SECO-LARM U.S.A., Inc.Page 4
P TGW1
E-941SA-1K2PDc.pmd
SPECIFICATIONS
Power
Magnet Size
Armature Size
Holding Force
Status Sensor
Status LED (2-Color)
Timer Delay
Current Drain
Voltage Tolerance
Housing
Temperature
Weight
E-941SA-1K2PD
12/24 VDC
5
10½ x 1
/8 x 25/8 in. (268 x 42 x 67 mm)
1
7
/4 x 5/8 x 23/8 in. (185 x 16 x 61 mm)
1200-lb (545kg)
Relay, 3A @ 12VDC
Locked - Green, Unlocked - Red
1~78 seconds
500mA @ 12VDC, 250mA @ 24VDC
± 10%
Aluminum
14° ~ 131°F (-10° ~ 55°C)
11-lb (5.0 kg)
Page 1
ELECTROMAGNETIC LOCK Installation ManualELECTROMAGNETIC LOCK Installation Manual
+
Status Sensor Output
N O
SPDT rated 3A @ 12VDC
}
Control Device
Powe r
Supply
+
Relay
Status LED*
Timer
Adjust
COM
N C
Voltage Selection Jumpers
Filler Plate*
Standard Mounting
"Z" Bracket
For Inswing Doors
"L"
Bracket
* Note: may require more
than one filler plate.
MOUNTING THE E-941SA-1K2PD
A. Drill holes for the mounting plate and
armature plate (see fig. 1 and 2) by doing the following:
1. Fold the mounting template along the dotted line.
2. Close the door. Find a mounting location on the door frame near the upper free-moving corner of the door, as close to the corner of the door frame as possible.
3. Place the template against the door and frame.
4. Drill two holes in the door frame and three holes in the door as indicated on the template.
NOTE — A filler plate or an L-bracket or Z-bracket (optional) may be required for the electromagnet, depending on the door frame. See fig. 1.
B. Mount the armature plate to the door
using at least two steel and one rubber washer (fig. 2):
NOTE — Actual installation varies according to door style.
1. Put one rubber washer between two steel washers, and place them over the armature screw between the armature plate and the door. This will allow the armature plate to pivot slightly around the armature screw in order to compensate for door misalignment.
2. Tighten the sexnut bolt enough so the armature plate can withstand the force of someone attempting to break down the door while the electromagnet is engaged.
3. Do not tighten the armature plate
C. Screw the mounting plate to the door
D. Drill the cable access hole. E. Mount the electromagnet to the door
F. Connect the power leads (fig. 3):
G. Test the unit. H. Insert the tamper caps into the
against the door. The plate must be able to pivot around the armature screw.
4. Make sure the anti-spin guides are in the two guidepin holes.
frame or optional bracket:
1. Screw the two short self-tapping screws in the slotted holes of the mounting plate and adjust the position of the mounting plate so that it and the armature plate form a 90-degree angle.
2. Once the position is correct, use the long self-tapping screws to permanently mount the bracket.
3. Remove the two short screws.
frame (fig. 1) — Use the Allen wrench to screw the socket-head mounting screws through the bottom of the electromagnet into the mounting bracket.
1. Open the electromagnet.
2. Run two power leads from the power supply through the cable access hole into the electromagnet.
3. Connect the power leads to the terminal block.
4. Close the electromagnet.
mounting screw access holes. This should be the last step, as once the tamper caps are in place, they will be difficult to remove.
SECO-LARM U.S.A., Inc.Page 2
FIG.
1
FIG.
2
FIG. 3: Status
Sensor Output ­Connect to an alarm panel or other monitoring device.
Adjustable Timer Delay — For 1~78 seconds, turn clockwise to increase time. Timer starts when power is applied.
E-941SA-1K2PD
SECO-LARM
Voltage Selection
12VDC
Magnet set for 12VDC operation as supplied from factory.
24VDC
Position a jumper over the two middle pins for 24VDC operation.
Status Sensor Output — Monitors whether the protected door is open or closed.
N.C. — Door opened, red LED on.
N.O. — Door closed, green LED on.
Relay — 3A @ 12VDC.
* Status LED — Indicates
whether the magnetic lock is locked or unlocked. Green — Locked Red — Unlocked Off — No power
Page 3