
904 N9MP1 & N9MP2
SingleStage *9MPD
SAFETY REQUIREMENTS
Recognize safety information. This is the safety-alert symbol/ ._\. When you see this symbol on the furnace and in instructions or manuals be alert
to the potential for personal injury.
Understand the signal words DANGER, WARNING, or CAUTION. These words are used with the safety-alert symbol. DANGER identifies the
most serious hazards, those that will result in severe personal injury or death. WARNING signifies a hazard that could result in personal injury or
death. CAuT__N is used t_ identify unsafe _ractices that c_u_d resu_t in min_r _ers_na_ injury _r _r_duct and _r__erty damage.
Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified personnel should
install, repair, or service heating equipment.
Untrained service personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be
performed by trained service personnel. When working on heating equipment, observe precautions in the literature, on tags, and on labels attached
to or shipped with the unit and other safety precautions that may apply.
Follow all safety codes. In the United States, follow all safety codes including the current edition National Fuel Gas Code (NFGC) NFPA No.
54/ANSIZ223.1. InCanada, refer tothecurrent editionofthe NationalStandard Canada CAN/CGA-B149.1- and.2-M91 NaturalGasand Propane
InstallationCodes (NSCNGPIC). Wearsafetyglassesandworkgloves. Havefireextinguisher availableduringstart-upandadjustment procedures
and service calls.
These instructions cover minimum requirements and conform to existing national sta nda rds and safety codes. In some insta rices, these instructions
exceed certain local codes and ordinances, especially those that may not have kept up with changing residential construction practices. We requre
these instructions as a minimum for a safe installation.
A
FAN ASSISTED, DIRECT VENT GAS FURNACE
International Comfort Products Corporation (USA)
Lewisburg, TN 37097
Manufactured by:
Table of Contents
1.SafeInstallationRequirements................. 4
2.Installation................................ 5
3.Combustion&VentilationAir .................. 8
4.Vent&CombustionAirPiping ................ 11
5.GasSupply andPiping...................... 30
6.ElectricalWiring ........................... 33
PrintedinU.S.A. LPI 12/03/2002 440 01 1114 (00)
7.DuctworkandFilter ........................ 34
8. ChecksandAdjustments.................... 38
9.FurnaceMaintenance ....................... 39
10.SequenceofOperation&Diagnostics.......... 40
11.ConcentricVentTermination................. 44
12.TechSupport andParts ..................... 49
FIRE OR EXPLOSION HAZARD
This furnace is not designed for use in mobile
homes, trailers or recreational vehicles.
Such use could result in death, bodily injury
and/or property damage.

N9MP1 - Indoor combustion air (1 pipe only)
N9MP2 - Direct Vent ONLY (2 pipe only)
*9MPD - Dual Certified Venting (1 or 2 pipes)
*Denotes Brand
JellJill _1
* 9
Brand
Brand Identifier
8 = Non-Condensing, 80+% Gas Furnace
9 = Condensing, 90+% Gas Furnace
Installation Configuration
UP = Upflow
DN = Downflow
UH = Upflow/Horizontal
HZ = Horizontal
DH = Downflow/Horizontal
MP = Multiposition, Upflow/Downflow/Horizontal
Major Design Feature
1 = One (Single) Pipe
2 = Two Pipe
D = 1 or 2 Pipe
L = Low NOx
* Denotes Brand
N = Single Stage
P = PVC Vent
T = Two Stage
V = Variable Speed
MP D 0 75 F 12 A #
Engineering Rev.
Denotes minor changes
MarketingDigit
Denotes minor change
Cooling Airflow
08 = 800 CFM
12 = 1200 CFM
14 = 1400 CFM
16 = 1600 CFM
20 = 2000 CFM
Cabinet Width
B = 15.5" Wide
F = 19.1" Wide
J = 22.8" Wide
L = 24.5" Wide
Input (NominalMBTUH)
440 01 1114 00 Printed in U.S.A.

Dealer Name:
START-UP CHECK SHEET
For 90+ Furnace
(Keep this page for future reference)
Address:
City, State(Province), Zip or Postal Code:
Phone:
Owner Name:
Address:
City, State(Province), Zip or Postal Code:
Model Number:
Serial Number:
Type of Gas: Natural:
Which blower speed tap is used?
(Heating) (Cooling).
LP:
Business Card Here
Manual Gas Shut-Off Upstream
of Furnace/Drip- Leg?
Condensate Drain Connected?
Condensate Drain Trapped? YES [_
Transition Pressure switch hose relocated for U/D/H
Application? YES [_ NO [_
Blower Speed Checked? YES [_ NO [_
All Electrical Connections Tight? YES [_ NO [_
Gas Valve OK? YES [_ NO [_
Measured Line Pressure When Firing Unit:
YES [_
YES [_
NOE_
NO
NO
Temperature of Supply Air:
Temperature of Return Air:
Rise (Supply Temp.-Return Temp.): (°F) or(°C)__
Filter Type and Size:
Fan "Time ON" Setting:
Fan "Time OFF" Setting:
Dealer Comments:
44001111400
(°F). or(°C)
(°F) or(°C)
Calculated Firing Rate:(See Checks andAdjustments Sec-
tion).
Temperature Rise (supply-return temperature):(°F)__
Measured Manifold Gas Pressure:
Static Pressure (Ducts): Supply Air Return
Date of Start-Up:
CO?
CO2 ?

1. Safe Installation Requirements
Installation or repairs made by unqualified persons can
result in hazards to you and others. Installation MUST
conform with local codes or, in the absence of local
codes, with codes of all governmental authorities
havingjurisdiction.
The information contained in this manual is intended
for use by a qualified service technician who is
experienced in such work, who is familiar with all
precautions and safety procedures required in such
work and is equipped with the proper tools and test
instruments.
Failure to carefully read and follow all instructions in
this manual can result in furnace malfunction, death,
personal injury and/or property damage.
NOTE: This furnace is design certified by the Canadian Stan-
dards Association (CSA) for installation in the United States and
Canada. Refer to the appropriate codes, along with Figure 1 or
Figure 2 and this manual, for proper installation.
• Use only the Type of gas approved for this furnace (see
Rating Plate on unit). Overfiring will result in failure of
heat exchanger and cause dangerous operation. (Fur-
naces can be converted to L.E gas with approved kit.)
• Install this furnace only in a location and position as speci-
fied in "lnstallation"pg 5 of these instructions.
• Provide adequate combustion and ventilation air to the
furnace as specified in "Combustion and Ventilation Air"
on pg 8 of these instructions.
• Combustion products must be discharged outdoors. Con-
nect this furnace to an approved vent system only, as spe-
cified in "Combustion and Ventilation Air"on pg 8 of these
instructions.
• Never test for gas leaks with an open flame. Use a com-
mercially available soap solution made specifically for the
detection of leaks to check all connections, as specified in
"Gas Supply and Piping"on pg 32 of these instructions.
• Always install furnace to operate within the furnace's in-
tended temperature-rise range with a duct system which
has an external static pressure within the allowable rat-
ings, as specified in "Technical Support Specifications"
pgs 49 - 51 of these instructions.
• When a furnace is installed so that supply ducts carry air
circulated by the furnace to areas outside the space con-
taining the furnace, the return air shall also be handled by
duct(s) sealed to the furnace casing and terminating out-
side the space containing the furnace.
• A gas-fired furnace for installation in a residential garage
must be installed as specified in "Installation Require-
ments"pg 7 of these instructions.
• This furnace is not to be used for temporary heating of
buildings or structures under construction.
• This furnace is NOT approved for installation in mo-
bile homes, trailers or recreation vehicles.
• Seal around supply and return air ducts.
• Install correct filter type and size.
• Unit MUST be installed so electrical components are pro-
tected from direct contact with water.
NOTE: It is the personal responsibility and obligation of the end
user to contact a qualifted installer to ensure that the installation is
adequate and conforms to governing codes and ordinances.
Safety Rules
Your unit is built to provide many years of safe and dependable
service provided it is properly installed and maintained. However,
abuse and/or improper use can shorten the life of the unit and
create hazards for you, the owner.
A. The U.S. Consumer Product Safety Commission recom-
mends that users of gas-burning appliances install carbon
monoxide detectors. There can be various sources of car-
bon monoxide in a building or dwelling. The sources could
be gas-fired clothes dryers, gas cooking stoves, water
heaters, furnaces, gas-fired fireplaces, wood fireplaces,
and several other items. Carbon monoxide can cause seri-
ous bodily injury and/or death. Therefore, to help alert
people of potentially dangerous carbon monoxide levels,
you should have carbon monoxide detectors listed by a na-
tionally recognized agency (e.g. Underwriters Laborato-
ries or CSA International) installed and maintained in the
building or dwelling (see Note below).
Carbon monoxide or "CO" is a colorless and odorless gas
produced when fuel is not burned completely or when the
flame does not receive sufficient oxygen.
B. There can be numerous sources of fire or smoke in a build-
ing or dwelling. Fire or smoke can cause serious bodily inju-
ry, death, and/or property damage. Therefore, in order to
alert people of potentially dangerous fire or smoke, you
should have fire and smoke detectors listed by Underwrit-
ers Laboratories installed and maintained in the building or
dwelling (see Note below).
Note: The manufacturer of your furnace does not test any de-
tectors and makes no representations regarding any brand
or type of detector.
C. To ensure safe and efficient operation of your unit, you
should do the the following:
1. Thoroughly read this manual and labels on the unit.
This will help you understand how your unit operates and
the hazards involved with gas and electricity.
2. Do not use this unit if any part has been under water.
Immediately call a qualified service technician to inspect
the unit and to replace any part of the control system and
any gas control which has been under water.
3. Never obstruct the vent grilles, or any ducts that pro-
vide air to the unit. Air must be provided for proper com-
bustion and ventilation of flue gases.
Frozen Water Pipe Hazard
FROZEN AND BURST WATER PIPE HAZARD
Furnace may shut down. Do not leave your home
unattended for long periods during freezing weather
without turning off water supply and draining water
pipes or otherwise protecting against the risk of frozen
pipes.
Failure to do so may result in burst water pipes, serious
property damage and/or personal injury.
Your furnace is designed solely to provide a safe and comfortable
living environment. The furnace is NOT designed to ensure that
water pipes will not freeze. It is equipped with several safety de-
vices that are designed to turn the furnace off and prevent it from
restarting in the event of various potentially unsafe conditions.
E_ 44001 111400

Ifyourfurnaceremainsoffforanextendedtime,thepipesinyour
homecouldfreezeandburst,resultinginseriouswaterdamage.
Watermaycreateaconditioninwhichmoldcangrowinyour
home.Certaintypesofmoldhavebeenreportedtocauserespi-
ratoryproblemsorotherserioushealthrisks.Remedialactions,
includingimmediatelydryingallwetitems,shouldbetakenquick-
lytohelppreventthedevelopmentofmoldinyourhome.
Ifthe structure will be unattended during cold weather you should
take these precautions.
Turn off the water supply to the structure and drain the wa-
ter lines if possible and add an antifreeze for potable water
to drain traps and toilet tanks. Open faucets in appropriate
areas.
-or-
Have someone check the structure frequently during cold
weather to make sure it is warm enough to prevent pipes
from freezing. Instruct them on a service agency to call to
provide service, if required.
-or-
2. Installation
CARBON MONOXIDE POISONING HAZARD
Failure to properly vent this furnace or other appliances
can result in death, personal injury and/or property
damage.
This furnace can NOT be common vented or connected to
any type B, BW or L vent or vent connector, nor to any
portion of a factory-built or masonry chimney. If this
furnace is replacing a previously common-vented
furnace, it may be necessary to resize the existing vent
and chimneyto prevent oversizing problems for the other
remaining appliance(s). See Venting and Combustion Air
Check in Gas Vent Installation section. This furnace
MUST be vented to the outside.
3. Install a reliable remote sensing device that will notify
somebody of freezing conditions within the home.
Winter Shutdown
If you go away during the winter months and do not leave the heat
on in your home, the plastic transition box and the condensate
trap on the furnace must be protected from freeze damage.(See
Figure 8 trough Figure 17)
1. Disconnect the 5/8" OD rubber hose from the vent drain fit-
ting that is located downstream of the combustion blower.
Insert a funnel into the hose and pour four(4) ounces of
sanitary type (RV) antifreeze into the condensate trap. Re-
connect the 5/8" OD rubber hose to the stub on the vent
drain fitting. Secure with the hose clamp.
2. Disconnect the 3/4" OD rubber hose from the condensate
trap. Insert a funnel into the hose and and pour four(4)
ounces of sanitary type (RV) antifreeze into the plastic
Transition box. Squeeze the hose together near the end
and quickly reconnect the 3/4" OD rubber hose to the stub
on the condensate trap. Secure with the hose clamp.
When you return home, your furnace will be ready to start, as it is
not necessary to drain the antifreeze from the furnace.
Do NOT operate furnace in a corrosive atmosphere
containing chlorine, fluorine or any other damaging
chemicals. Refer to Combustion & Ventilation Air section,
Contaminated Combustion Air.
Typical Upflow Installation
Aluminum or non-rusting shield recommended. (See
Vent Termination Shielding for dimensions).
8" Min. _ _lnletPipe
- _ _ (not used on
Insame _ Single Pipe
20' Max.
atmospheric <_> model)
zone
Couplingon endsol
exhaust pipe.Total
pipe&couplingout-
Location and Clearances
4. RefertoFigure lorFigure 2fortypicalinstallationandba-
sic connecting parts required. Refer to Figure 4 for typical
horizontal direct vent installation and basic connecting
parts required. Supply and return air plenums and duct are
also required.
5. If furnace is a replacement, it is usually best to install the
furnace where the old one was. Choose the location or
evaluate the existing location based upon the minimum
clearance and furnace dimensions (Figure 3).
CAUTION
Special precautions MUST be made if installing furnace in an
area which may drop below freezing. This can cause
improper operation or damage to equipment. If furnace
environment has the potential of freezing, the drain trap and
drainline must be protected. The use of electric heat tape or
RV antifreeze is recommended for these installations. (See
"Condensate Trap Freeze Protection Section ")
44001 111400 [_
Increase minimum from 8" to 18" for cold climates (sustained temperatures
below 0 o F). 25-23-33
Min.
Max.
ameatmospheric
zone
8"

Typical Downflow Installation
See VentTermination
Shieldingin VentSection.
I_ "8" Min.
InletPipe _ [_ 20' Max.
(not usedon _ in same
Single Pipe-------_ k,_k atmospheric zone
model) _
VentPi_c ; MUSTbe
supl Horizonta
andVertically
* Increase minimum from 8" to 18" for cold climates (sustained temperatures
below O°F), 25-23-33a
Coupling on inside
and outside of wall
to restrain vent pipe
8" Min.
Min.
Max.
same
zone
Installation Requirements
1. Install furnace level.
This furnace is NOT to be used for temporary heat of build-
ings or structures under construction.
3,
Install furnace as centralized as practical with respect to the
heat distribution system.
4.
Install the vent pipes as short as practical. (See Ventand
Combustion Air Piping section).
5.
Maintain clearance for fire safety and servicing. A front
clearance of 30" is required for access to the burner, con-
trols and filter.
6. Use a raised base for upflow furnace if the floor is damp or
wet at times.
For downflow installations, non combustible subbase must
be used under the furnace unless installation is on a non
combustible floor surface. This requirement applies even
when a coil box or cabinet is used.
FIRE HAZARD
Failure to install unit on noncombustible subbase can
result in death, personal injury and/or property damage.
Place furnace on noncombustible subbase on down-
flow applications, unless installing on non-combus-
tible flooring.
8. For horizontal installations, line contact is permissible only
between lines formed by intersection of back and two sides
of furnace jacket, and building joists, studs or framing.
9,
Residential garage installations require:
Burners and ignition sources installed at least 18" above
the floor.
Located or physically protected from possible damage by
a vehicle.
10. Local codes may require a drain pan under the entire fur-
nace and condensate trap when the furnace is installed in
attic application.
Installation Positions
This furnace can be installed in an upflow, horizontal (either left or
right) or downflow airflow position. DO NOT install this furnace on
its back. For the upflow position, the return air ductwork can be
attached to either the left or right side panel and/or the bottom. For
horizontal and downflow positions, the return air ductwork must
be attached to the bottom. The return air ductwork must never be
attached to the back of the furnace.
Furnace Installation Considerations
The installation of the furnace for a given application will dictate
the position of the furnace, the airflow, ductwork connections,
vent and combustion air piping. Consideration must be given to
the following:
Condensate Trap and Drain Lines
The supplied condensate trap must be attached to the furnace
side panel on either the left or right side. For horizontal installa-
tions, the drain trap is vertically attached to the side panel below
the furnace. A minimum clearance of 6" below the furnace is re-
quired for the condensate trap. Downward slope of the conden-
sate drain line from the condensate trap to the drain location must
be provided. Adequate freeze protection of the drain trap and the
drain line must be provided. See "Condensate Drain Trap"section
for further details.
Leveling
Proper leveling of the furnace must be provided to insure proper
drainage of the condensate from the furnace. The furnace must
be level to within 1/4" from front to back and from side to side for
upflow and downflow installations or top to bottom for horizontal
installations.
Vent and Combustion Air Connections
On the Dual Certified furnace, the vent and combustion air pipes
attach to the furnace through the top panel for the upflow and hori-
zontal installations. For the downflow installation, the vent and
combustion air pipes attach to the furnace through the alternate
locations on the furnace side panels.
Note: On the Direct Vent furnace, the vent pipe attaches to the fur-
nace through the side panels. The combustion air pipe attaches to
the top panel or to the alternate location on the side panel.
On the Single Pipe furnace, the vent pipe attaches to the furnace
through the furnace side panels.
Note: Repositioning of the combustion blower is required for the
vent pipe connection to the furnace through the "right side" panel.
See "Vent and Combustion Air Piping"section for further details.
44001 111400

Dimensions & Clearances
t3!4
F
| ]jAI. I.TAKE
_ /VENTrgMPD)
TOP
1
LEFT SIDE I_ _
TRAP (COUNTERFLOW) _ _
AiRI.TAKE ¢"
(ALTERNATE)_ J
TRAP 4131164 C
UPFLOWIHORIZONTAL
• THERMOSTAT/J_T-_ 7_
I
/ELECTRICAL
-- 11/16
13/8 2! /8
213/4
I
624
Cabinet to Combustible Clearances
TOP BOT. RH LH BACK FRONT FLUE
1' O' O' O' O' 3' O'
Horizontalposition:Linecontactispermissibleonlybetween lines
formedby intersectionsoftop andtwo sidesof furnacejacket, and
buildingjoists,studsor framing,
--A--
-- B--
FRONT
1311/16
1/16
1913116
17/8
C
Unit
Capacity
N9MP1050B12A
N9MP1075B12A
N9MP1080F16A
NgMP1100F14A
N9MP1100J20A
N9MP1125J20A
N9MP2050B12A
N9MP2075B12A
N9MP2080F16A
N9MP2100F14A
N9MP2100J20A
N9MP2125J20A
*9MPD050F12A
*9MPD075F12A
*9MPD080J16A
*9MPD100J14A
*9MPD100J20A
*9MPD125L20A
21518 47/8
24
BOTTOM
23118
Cabinet Bottom
GAS
i
21/4
191/4
17/8
24
25=23-36b
44001 111400

Horizontal Furnace Installation
This furnace can be installed horizontally in an attic, basement,
crawl space, alcove, or suspended from a ceiling in a basement or
utility room. See Figure 4. Do not install furnace on its back or in
the reverse airflow positions as safety control operation will be ad-
versely affected.
_ _!'i [ Typical Horizontal Installation
Inlet Pipe (not used on Single Pipe model)
Vent
C_
Condensate
Trap
25-23-34
NOTE: 6"bottomclearancerequiredfor condensatetrap.
If the furnace is to be suspended from the floor joists in a crawl
space or the rafters in an attic, it is necessary to use steel pipe
straps or an angle iron frame to rigidly attach the furnace to pre-
vent movement. These straps should be attached to the furnace
with sheet metal screws and to the rafters or joists with bolts. The
preferred method is to use an angle iron frame bolted to the rafters
or joists. (Take caution to allow door panels to be removed for
maintenance)
If the furnace is to be installed in a crawl space, consult local
codes. A suitable concrete pad or blocks are recommended for
crawl space installation on the ground.
NOTE: 6" bottom clearance required for condensate trap.
Thirty (30) inches between the front of the furnace and adjacent
construction or other appliances MUST be maintained for service
clearance.
Keep all insulating materials clear from Iouvered door. Insulating
materials may be combustible.
The horizontal furnaces may be installed directly on combustible
wood flooring or supports as long as all required furnace clear-
ances are met. See Figure 4.
This furnace MUST NOT be installed directly on carpeting or tile
or other combustible material other than wood flooring or sup-
ports.
For horizontal installation over a finished living space. A field fab-
ricated auxiliary drain pan with drain pipe is required to prevent
damage by overflow due to blocked condensate drain.
3. Combustion & Ventilation Air
For Single Pipe Installation
CARBON MONOXIDE POISONING HAZARD
Failure to provide adequate combustion and ventilation
air can result in death and/or personal injury.
Use methods described here to provide combustion and
ventilation air.
Furnaces require ventilation openings to provide sufficient air for
proper combustion and ventilation of flue gases. All duct or open-
ings for supplying combustion and ventilation air must comply
with National Fuel Gas Code, NFPA54/ANSI Z223.1, 2001 (or
current edition) and applicable provisions of local building codes.
This furnace can NOT be common vented or connected to any
type B, BW or L vent or vent connector, nor to any portion of a fac-
tory-built or masonry chimney. If this furnace is replacing a pre-
viously common-vented furnace, it may be necessary to resize
the existing vent and chimney to prevent oversizing problems for
the other remaining appliance(s). See "Venting and Combustion
Air Check"in this section, This furnace MUST be vented to the
outside.
Air OpeningsandConnectingDucts
1. Total input rating for all non direct vent gas appliances
MUST be considered when determining free area of open-
ings.
2. Connect ducts or openings directly to outside.
3. When screens are used to cover openings, they MUST be
no less than 1/4" mesh.
4. The minimum dimension of rectangular air ducts MUST
NOT be less than 3".
5. When sizing grille or louver, use the free area of opening. If
free area is NOT stamped or marked on grill or louver, as-
sume a 20% free area for wood and 60% for metal.
Confined Space Installation
NOTE: A confined space is defined as an area with less than 50
cubic feet per 1,000 BTUH input rating for all gas appliances
installed in the area.
Requirements
Provide confined space with sufficient air for proper com-
bustion and ventilation of flue gases using horizontal or ver-
tical ducts or openings.
Figure 5 illustrate how to provide combustion and ventila-
tion air. A minimum of two permanent openings, one inlet
and one outlet, are required.
One opening MUST be within 12" of the floor and the se-
cond opening within 12" of the ceiling.
E_ 44001 111400

Outside Air (This is ONLY a guide. SubJect to codes of country havingjurisdiction.)
ThisinstallationNOTapprovedin Canada GasVen_,
Gas Vent
i,
_, let Air (1) ._1 Gable Vent ,_
G, re. _ I_ .i II II II II Outlet
Outlet Air (1) Soffit Vent f / "_- .. • I I I I I I I I I
_ "_Ventilated Attic_ Outlet I II Air(2)
-- /TopAbovelnsulation "_ ,_lrtl) I _ .LL II II
................................II I= II II
1- I'Outle;Air '1' I1 I Soffit Vent In.let _ ........ I _: - _ Inlet
F°I A ; / -- ] r_ II I Minimum Onelnlet and One Outlet Air Supply is Required
Ventilated Crawl S . _ I I_'%] _ .
alternateInlet Air (1)
:_ Inlet ' d ,m_,, I I _* I I I I Inlet Air Opening Must be Within12" of floor
4. Size openings and ducts per Table 1.
Horizontal duct openings require I square inch of free area
per 2,000 BTUH of combined input for all gas appliances in
area (see Table 1).
Vertical duct openings or openings directly to outside re-
quire 1 square inch of free area per 4,000 BTUH for com-
bined input of all gas appliances in area (see Table 1).
ii_i!iiii_i_i_!i_i_i_!i_i_i_!i_i_i_!i_i_i_!i_i_i_!i_i_i_!i_i_i_!i_i_i_!i_i_i_!i_i_i_!i_i_i_!i_i_i_!i_i_i_!i_i_i_!
BTUH
Input Horizontal Duct
Rating (2,000 BTUH)
50,000 25 sq. in.
75,000 37.5sq. in.
1OO,OOO 50sq. in.
125,000 62.5sq. in.
150,000 75 sq. in.
MinimumFreeArea Required for Each Opening
Free Area
VerticalDuctoropenings
to outside(4,000BTUH)
12.5sq. in.
18.75 sq. in.
25sq. in.
31.25 sq. in.
37.5sq. in.
EXAMPLE: Determining Free Area
Appliance 1 Appliance 2 Total Input
100,000 + 30,000 = (130,000 + 4,000) = 32.5 Sq. In. Vertical
Appliance 1 Appliance 2 Total Input
100,000 + 30,000 = (130,000 + 2,000) = 65 Sq. In. Horizontal
One permanent opening, commencing within 12" of the top of the
enclosure, shall be permitted where the equipment has clear-
ances of at least 1" from the sides and back and 6" from the front
of the appliance. The opening shall directly communicate with the
outdoors or shall communicate through a vertical or horizontal
duct to the outdoors or spaces (crawl or attic) that freely communi-
cate with the outdoors, and shall have a minimum free area of:
1 sq. in per 3000 Btu per hr. of the total input rating of all
equipment located in the enclosure, and
Not less than the sum of the areas of all vent connectors in
the confined space.
/ I I I H I MaybeinanyCombinationShown
Air(l) I_ I I"°'1 E:_h_r _ilei2 ) Outlet Air Opening Must be Withinl2" of ceiling
Unconfined Space Installation
Round Duct
(4,000BTUH)
4"
5"
6"
7"
7"
An unconfined space is defined as an area having a minimum vol-
ume of 50 cubic feet per 1,000 Btuh total input rating for all gas
appliances in area. Refer to Table 2 for minimum area required.
................................................................................................................I Minimum Area in Square Feet
EXAMPLE: NOTE: Square feet is based on 8 foot ceilings.
28,000BTUH X 50CubicFt, = 1,400 = 175Sq, Ft.
NOTE: Refer to definitions in section titled Unusually Tight
Construction. If any oneofthe conditions apply, the space MUST
be considered confined space regardless of size.
1. Adjoining rooms can be considered part of an unconfined
2. An attic or crawl space may be considered an unconfined
(1)1SquareInchper4000BTUH
(2)1SquareInchper2000BTUH
CARBON MONOXIDE POISONING HAZARD
Failure to supply additional air by means of ventilation
grilles or ducts could result in death and/or personal
injury.
An unconfined space or homes with tight construction
may not have adequate air infiltration for proper
combustion and ventilation of flue gases.
Most homes will require additional air.
I Unconfined Space
BTUH Input Minimum Area in Square Feet
Rating
50,000 312
78,000 490
114,000 712
155,000 968
1,000 8' Ceiling Height
area if there are openings without doors between rooms.
space provided there a re adequate ventilation openings di-
rectly to outdoors. Openings MUST remain open and NOT
have any means of being closed off. Ventilation openings to
outdoors MUST be at least 1" square of free area per 4,000
BTUH of total input rating for all gas appliances in area.
44001 111400 [_

3. Installairintakeaminimumof12"abovemaximumsnow
levelandclearofanyobstruction.Ductorventilationopen-
ingrequiresonesquareinchoffreeareaper4,000BTUH
oftotal input rating for all gas appliances in area.
4. Air inlet MUST be screened with not less than 1/4" mesh
screen.
Unusually Tight Construction
In unconfined spaces, infiltration may be adequate to provide air
for combustion, ventilation and dilution of flue gases. However, in
buildings with unusually tight construction, additional air MUST
be provided using the methods described in section titled Con-
fined Space Installation:
Unusually tight construction is defined as: Construction with
1. Walls and ceilings exposed to the outside have a continu-
ous, sealed vapor barrier. Openings are gasketed or
sealed and
2,
Doors and openable windows are weather stripped and
3.
Other openings are caulked or sealed. These include joints
around window and door frames, between sole plates and
floors, between wall-ceiling joints, between wall panels, at
penetrations for plumbing, electrical and gas lines, etc.
Ventilation Air
Some provincial codes and local municipalities require ventilation
or make-up air be brought into the conditioned space as replace-
ment air. Whichever method is used, the mixed return air temper-
ature across the heat exchanger MUST not fall below 60 °F or flue
gases will condense in the heat exchanger. This will shorten the
life of the heat exchanger and possibly void your warranty.
Venting and Combustion Air Check
The following information is supplied to allow the installer to make
adjustments to the setup of existing appliances, IF REQUIRED,
based on good trade practices, local codes, and good judgement
of the installer. Manufacturer does NOT take responsibility for
modifications made to existing equipment.
NOTE: If this installation replaces an existing furnace from a
commonly vented system, the original venting system may no
longer be sized to properly vent the attached appliances. An im-
properly sized venting system may cause the formation of con-
densate in the vent and the leakage or spillage of vent gases. To
make sure there is adequate combustion air for all appliances,
MAKE THE FOLLOWING CHECK.
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being placed
into operation, while all other appliances connected to
the venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal
pitch, as required in the National Fuel Gas Code, ANSI
Z223,1/NFPA 54 or CSA B149. 1, Natural Gas and Pro-
pane Installation Codes and these instructions. Deter-
mine that there is no blockage or restriction, leakage, cor-
rosion and other de to ensure there is no blockage or re-
striction, leakage, corrosion and other deficiencies which
could cause an unsafe condition.
3. As far as practical, close all building doors and windows
and all doors between the space in which the appliance(s)
connected to the venting system are located and other
spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected
to the venting system. Turn on any exhaust fans, such as
range hoods and bathroom exhausts, so they will operate
at maximum speed. Do not operate a summer exhaust
fan.
6. Followthe lighting instructions. Place the appliance being
inspected into operation. Adjust thermostat so appliance
is operate continuously.
7. Test for spillage from draft hood equipped appliances at
the draft hood relief opening after 5 minutes of main burner
operation. Use the flame of a match or candle. (Figure 6)
8. If improper venting is observed, during any of the above
tests, the venting system must be corrected in accor-
dance with the National Fuel Gas Code, ANSI
Z223,1/NFPA 54 or CSA B149. 1, Natural Gas and Pro-
pane Installation Codes.
9. After it has been determined that each appliance con-
nected to the venting system properly vents when tested
as outlined above, return doors, windows, exhaust fans,
fireplace dampers and any other gas-fired burning ap-
pliance to their previous conditions of use.
Vent Check
For Two Pipe Installation
VentPipe --_1 [ A/ Draft Hood
Typical Gas
Water Heater,_ f [ [ _ _,_._. Match
I
If flame pulls towards draft hood, this indicates suffi-
cient venting.
E_ 44001 111400
!
This furnace can NOT be common vented or connected to any
type B, BW or L vent or vent connector, nor to any portion of a fac-
tory-built or masonry chimney. If this furnace is replacing a pre-
viously common-vented furnace, it may be necessary to resize
the existing vent and chimney to prevent oversizing problems for
the other remaining appliance(s). See "Venting and Combustion
Air Check"in this section. This furnace MUST be vented to the
outside.

4. Vent and Combustion Air Piping
CARBON MONOXIDE POISONING, FIRE AND EXPLO-
SION HAZARD
Failure to properly vent this furnace can result in death,
personal injury and/or property damage.
Read and follow all instructions in this section.
• Printing inks, paint removers, varnishes, etc.
• Hydrochloric acid.
• Sulfuric Acid.
• Solvent cements and glues.
• Antistatic fabric softeners for clothes dryers.
• Masonry acid washing materials.
Single Pipe (N9MP1Models)
This furnace is certified as a category IV appliance. This furnace
requires ventilation openings to provide air for proper combustion
and ventilation of flue gases. All duct or openings for supplying
combustion and ventilation air must comply with the gas codes or
in absence of local codes, the applicable national codes.
When the installation is complete, see the "Venting and Com-
bustion Air Checl4' in this manual.
Direct Vent (N9MP2 Models)
This furnace is certified as a category ]V appliance. This furnace
uses outside air for combustion ONLY, it MUST be taken from the
same atmospheric pressure zone as the vent pipe. See Con-
fined Space Installation in the Combustion and Ventilation
Air in this manual.
Dual Certified ('gMPD Models)
This furnace is certified as a category ]V appliance. This furnace
can be installed as a direct vent furnace using outside air for com-
bustion or the furnace can use air from inside the structure for
combustion. The INLET air pipe is optional. If combustion air
comes from inside the structure, adequate make up air MUST be
provided to compensate for oxygen burned. See Confined
Space Installation in the Combustion and Ventilation Air
chapter. If combustion air is drawn from outside the structure, it
MUST be taken from the same atmospheric pressure zone as the
vent pipe.
Contaminated Combustion Air
Installations in certain areas or types of structures will increase
the exposure to chemicals or halogens that may harm the fur-
Race.
The following areas or types of structures may contain or have ex-
posure to the substances listed below. The installation must be
evaluated carefully as it may be necessary to provide outside air
for combustion.
• Commercial buildings.
• Buildings with indoor pools.
• Furnaces installed in laundry rooms.
• Furnaces installed in hobby or craft rooms.
• Furnaces installed near chemical storage areas.
• Permanent wave solutions for hair.
• Chlorinated waxes and cleaners.
• Chlorine based swimming pool chemicals.
• Water softening chemicals.
• De-icing salts or chemicals.
• Carbon tetrachloride.
• Halogen type refrigerants.
• Cleaning solvents (such as perchloroethylene).
44001 111400
Vent and Combustion Air Piping Guidelines
This furnace is approved for venting with Schedule 40 PVC,
CPVC, ABS, Cellular Core pipe fittings and SDR-26 PVC.
NOTE: All PVC, CPVC, ABS, and Cellular Core pipe fittings, sol-
vent cement, primers and procedures MUST conform to Ameri-
can National Standard Institute and American Society for Testing
and Materials (ANSI/ASTM) standards.
• Pipe and Fittings - ASTM D1785, D2241, D2466, D2661,
D2665, F-891, F-628
• PVC Primer and Solvent Cement- ASTM D2564
• Procedure for Cementing Joints - Ref ASTM D2855
NOTE: All vent piping MUST be installed in compliance with local
codes or ordinances, these instructions, good trade practices,
and codes of country having jurisdiction.
1. Determine the best routing and termination for the vent
pipe and air inlet pipe by referring to all of the instructions
and guidelines in this Section.
2. Determine the size required for the vent pipe and air inlet
pipe.
3. Loosely assemble all venting parts without adhesive (pipe
joint cement) for correct fit before final assembly.
4. Use of vertical piping is preferred because there will be
some moisture in the flue gases that may condense as it
leaves the vent pipe (See Special Instruction For Horizon-
tal Vents).
5. The vertical vent pipe MUST be supported so that no
weight is allowed to rest on the combustion blower.
6. Exhaust vent piping or air inlet piping diameter MUST NOT
be reduced.
7. All exhaust vent piping from the furnace to termination
MUST slope upwards. A minimum of 1/4" per foot of run is
required to properly return condensate to the furnace drain
system.
8. Use DWV type long radius elbows whenever possible, as
they provide for the minimum slope on horizontal runs and
they provide less resistance in the vent system. If DWV el-
bows cannot be used, use two, 45 ° elbows when possible.
On horizontal runs the elbows can be slightly misaligned to
provide the correct slope.
9. All horizontal pipe runs MUST be supported at least every
five feet with galvanized strap or other rust resistant materi-
al. NO sags or dips are permitted.
10. All vertical pipe runs MUST be supported every six feet
where accessible.
11.
The minimum pipe run length is 2'.
12.
The piping can be run in the same chase or adjacent to sup-
ply or vent pipe for water supply or waste plumbing. Itcan
also be run inthe same chase with a vent from another 90+
furnace.
NOTE: In NO case can the piping be run in a chase where
temperatures can exceed 140 ° F. or where radiated heat
from adiacent surfaces would exceed 140 ° F.

13.The vent outlet MUST be installed to terminate in the same
atmospheric pressure zone as the combustion air inlet.
14. The vent system can be installed in an existing unused
chimney provided that:
• Both the exhaust vent and air intake run the length of the
chimney.
• No other gas fired appliance or fireplace (solid fuel) is
vented into the chimney.
• The top of the chimney MUST be sealed flush or crowned
up to seal against rain or melting snow so ONLY the piping
protrudes.
• The termination clearances shown in Figure 7 are main-
tained.
15.
Furnace applications with vertical vents requiring vent di-
ameter increaser fittings must have increaser fittings
installed in vertical portion of the vent. Condensate will be
trapped in the vent if the vent diameter is increased prior to
having an elbow turned upward. This could cause nui-
sance tripping of the pressure switch.
PipingInsulation Guidelines
NOTE: Use closed cell, neoprene insulation or equivalent. If Fi-
berglass or equivalent insulation is used it must have a vapor bar-
rier. Use R values of 7 up to 10', R-11 if exposure exceeds 10'. If
Fiberglass insulation is used, exterior to the structure, the pipe
MUST be boxed in and sealed against moisture.
When the vent or combustion air pipe height above the roof
exceeds 30", or if an exterior vertical riser is used on a hori-
zontal vent to get above snow levels, the exterior portion
MUST be insulated.
When combustion air inlet piping is installed above a sus-
pended ceiling, the pipe MUST be insulated with moisture
resistant insulation such as Armaflex or other equivalent
type of insulation.
Pipe Diameter Table
N9MP1 & *9MPD Models
50,000, 75,000 & 80,000 Btuh Furnaces
40' & (5) 90° elbows with 2" PVC pipe or
70' & (5) 90 ° elbows with 3" PVC pipe
100,000 Btuh Furnace
40' & (5) 90° elbows with 3" PVC pipe or
70' & (5) 90 ° elbows with 3" PVC pipe &
Long Vent Kit (See Tech. Manual)
125,000 Btuh Furnace
40' & (5) 90 ° elbows with 3" PVC pipe
Elbows are DWV Long Radius Type for 2" and 3" vents,
If more than five elbows are required, reduce the length of
both the inlet and exhaust pipes 5' for each additional elbow
used.
NOTE: It is allowable to use larger diameter pipe and fitting than
shown in the tables but not smaller diameters than shown.
Pipe Diameter Table
N9MP2 Models
50,000 & 80,000 Btuh Furnaces
40' & (5) 90° elbows with 2" PVC pipe or
70' & (5) 90 ° elbows with 3" PVC pipe
75,000 Btuh Furnaces
25' & (3) 90° elbows with 2" PVC pipe or
40' & (5) 90° elbows with 2" PVC pipe &
Long Vent Kit (See Tech. Manual) or
70' & (5) 90 ° elbows with 3" PVC pipe
100,000 Btuh Furnace
40' & (5) 90° elbows with 3" PVC pipe or
70' & (5) 90° elbows with 3" PVC pipe &
Long Vent Kit (See Tech. Manual)
125,000 Btuh Furnace
40' & (5) 90 ° elbows with 3" PVC pipe
Elbows are DWV Long Radius Type for 2" and 3" vents.
If more than five elbows are required, reduce the length of
both the inlet and exhaust pipes 5' for each additional elbow
used.
For "Concentric Termination Kit" Venting table, see
"Section 11" in this manual.
Vent Termination Clearances
Insulate combustion air inlet piping when run in warm, hu-
mid spaces such as basements.
Sizing Combustion Air and VentPipe
Consult Table 3 or Table 4 to select the proper diameter exhaust
and combustion air piping. Exhaust and combustion air piping is
sized for each furnace Btuh size based on total lineal vent length
(on inlet or outlet side), and number of 90 ° elbows required. Two
45 ° elbows can be substituted for one 90 ° elbow. The elbow or el-
bows used for vent termination outside the structure ARE
counted, including elbows needed to bring termination above ex-
pected snow levels. The elbow inside the furnace on the *9MPD
IS NOT included in the count.
[_ 44001 111400
CARBON MONOXIDE POISONING, FIRE AND EXPLO-
SION HAZARD
Inlet and outlet pipes may NOT be vented directly above
each other.
Failure to properly vent this furnace can result in death,
personal injury and/or property damage.
1. Determine termination locations based on clearances spe-
cified in following steps and as shown in Figure 7,
Figure 19, through Figure 27.
For "Concentric Termination Kit" clearances, see Figure 45,
Figure 46, Figure 47, Figure 48 and Figure 49 in "Section 10"
in this manual.
2. The vent termination must be located at least 12" above
ground or normally expected snow accumulation levels.

3. DoNOTterminate over public walkways. Avoid areas
where condensate may cause problems such as above
planters, patios, or adjacent to windows where steam may
cause fogging.
4. The vent termination shall be located at least 4' horizontally
from any electric meter, gas meter, regulator, and any relief
equipment. These distances apply ONLY to U.S. installa-
tions.
The vent termination is to be located at least 3' above any
forced air inlet located within 10' ; and at least 10' from a
combustion air intake of another appliance, except another
direct vent furnace intake.
In Canada, the Canadian Fuel Gas Code takes prece-
dence over the preceding termination instructions.
Vent Termination Clearances
(United States Only)
In Canada See Canadian Fuel Gas Code
OtherThan
OtherThan
DirectVent
Terminal
\
plastic cap and clamp. This will prime both the vent and the transi-
tion sides of the trap.
The condensate drain trap supplied with the furnace MUST be
used. The drain connection on the condensate drain trap is sized
for 3/4" PVC or CPVC pipe, however alternate 1/2" CPVC (nomi-
nal 5/8" O.D.) or vinyl tubing with a minimum inner diameter (I.D.)
of 5/8" may also be used, as allowed by local codes. Alternate
drain pipes and hoses may be used as allowed by local codes.
The drain line must maintain a 1/4" per foot downward slope to-
ward the drain. 1/4" per foot is recommended. Installation of an
overflow line is recommended when the 1/4" per foot slope to the
condensate drain cannot be maintained. See Figure 1 for proper
routing and installation of the overflow.
DO NOT trap the drain line in any other location than at the con-
densate drain trap supplied with the furnace.
FROZEN AND BURST WATER PIPE HAZARD
If a condensate pump is installed, a plugged condensate
drain or a failed pump may cause the furnace to shut
down. Do not leave the home unattended during freezing
weather without turning off water supply and draining
water pipes or otherwise protecting against the risk of
frozen pipes.
Failure to do so may result in burst water pipes, serious
property damage and/or personal injury.
Condensate Drain Trap
This furnace removes both sensible and latent heat from the prod-
ucts of combustion. Removal of the latent heat results in con-
densation of the water vapor. The condensate is removed from
the furnace through the drains in the plastic transition and the vent
fitting. The drains connect to the externally mounted condensate
drain trap on the left or right side of the furnace.
The startup of a new furnace will involve a cycle or two of the fur-
nace to properly prime the condensate trap with water. Until the
trap is fully primed, some condensate will be pulled into the com-
bustion blower. The furnace may cycle on the pressure switch
connected to the plastic transition box due to condensate buildup.
After the trap is primed, the condensate will start draining from the
furnace. The combustion blower will clear out any remaining con-
densate in the blower housing through the vent fitting down-
stream of the blower. Note that the condensate trap can also be
primed by pouring water into the vent drain side of the trap. Re-
move the small plastic cap and clamps from the unused drain stu b
on the vent drain side of the condensate trap. Connect a section of
the 518" OD hose with a funnel to the drain stub and pour eight (8)
ounces of water into the trap. Remove the hose and replace the
If possible DO NOT route the drain line where it may freeze. The
drain line must terminate at an inside drain to prevent freezing of
the condensate and possible property damage.
1. A condensate sump pump MUST be used if required by lo-
cal codes, or if no indoor floor drain is available. The con-
densate pump must be approved for use with acidic
condensate.
A plugged condensate drain line or a failed condensate
pump will allow condensate to spill. If the furnace is
installed where a condensate spill could cause damage, it
is recommended that an auxiliary safety switch be installed
to prevent operation of the equipment in the event of pump
failure or plugged drain line. If used, an auxiliary safety
switch should be installed in the R circuit (low voltage)
ONLY.
3. If the auxiliary switch in the condensate pump is used, the
furnace may shut down due to a blocked condensate line or
failed pump. To prevent frozen water pipes see the "Frozen
Water Pipe Hazard" section on Page 4 of this manual.
Condensate Drain Trap Freeze Protection
Special precautions MUST be made if installing furnace in an
area which may drop below freezing. This can cause improper op-
eration or damage to the equipment. If the the furnace environ-
ment has the potential of freezing, the drain trap and drain line
must be protected. Use 3 to 6 watt per foot at 115 volt, 40 ° F self-
regulating shielded and waterproof heat tape. Wrap the drain trap
and drain line with the heat tape and secure with the ties. Follow
the heat tape manufacturer's recommendations.
44001 111400 [_

Upflow Installations (Dual Certified *9MPD-A4 Models)
YellowPlasticCap
Vent Pipe
Air
Supply _ _
Vent P )eGrommet
Rubber Coupling Gas Pipe
Sls"Hose &
Clamps
PlasticCap
Grommet
NOTE: TRAP MUST BE PRIMED BEFORE OPERATION
Combustion Air
TOP Venting Pipe (optional on
some models)
Coupling
Pressure Switch
Hose, Blower
/ Plastic Cap
Rubber Hose
Some Models have
one pressure switch
Blower
Pressure Switch
Hose, Transition
CondensateTrap & Connectionsonallmodels
Gasket (Leftor Right except125
Side)
_ Component Identification for Illustration for
Figure 8 thru Figure 17 for specifies
NOTE: DO NOT make connections until the hose routing and
lengths have been determined. Remove the condensate trap and
drain hoses from the furnace and secure the drain hoses to the
drain stubs on the trap with the hose clamps (position the clamps
as shown in Figure 8). Install the condensate trap/hose assem-
blyto the furnace casing. Hook one side ofthe"clamp ears" on the
drain stub through the hole in the casing and push the condensate
trap into position. Secure with the two screws. Reconnect the
drain hoses to the stubs on the vent fitting and the plastic transi-
tion and secure with the clamps.
Mount the condensate drain trap in a vertical position to either the
left or right side of the furnace using the two screws and gasket
that are provided. If needed, remove the hole plugs from the fur-
nace side panel and relocate to the open set of holes in the oppo-
site side panel.
NOTE: All gaskets and seals must be in place for sealed combus-
tion applications.
SinglePressureSwitch
Transition
Box
Switch,
DrainLine
Return Air
Transition
25-24-11
_n "Clamp
ears"
Poin,ed
/ _ (_///Preassemble &
_. /_/ y/ inseri into fur-
Ensure that the vent fitting and the 90 ° elbow are securely at-
tached to the combustion blower using the clamps. Note for prop-
er alignment of the vent pipe through the furnace, the 90 ° elbow
must be installed with the "UPFLOW" lettering on the 90 ° elbow
facing out.
NOTE: The 90 ° elbow is approved for use inside the furnace
ONLY.
Plug the upper drain stub on the vent fitting with the yellow plastic
cap.
For left side venting, remove 90 ° elbow from the vent fitting by
loosening the clamp on the vent fitting. Securely attach vent fitting
to combustion blower.
NOTE: For left side venting, the vent fitting MUST be installed
with the airflow marking arrow pointed toward the vent pipe, with
the drain stub at a 5° to 10 ° downward slope.
Connect the PVC vent extension pipe to the vent fitting. This pipe
has a built-in channel to assist vent condensate disposal.
Align the arrow on the PVC pipe with the airflow marking arrow on
the ventfittin . See label on the PVC i efor ro erinstallation.
nace
44001 111400

Thispipemayonlybeshortenedifanelbowisusedtoconnectthe
PVCventextensiontubetofield-installedventpipe.Securelyat-
tachthePVCventextensionpipetotheventfittingwiththeclarap.
Thisconfigurationallowsleftsideventingfromthefurnace.Ifright
sideventingisrequired,thecombustionblowermustberelocated
ontheplastictransitionbox.Loosenthefour(4)screwsthatse-
NOTE:Forrightsideventing,theventfittingMUSTbeinstalled
withtheairflowmarkingarrowpointedtowardtheventpipe,with
thedrainstubata5°to10°downwardslope.(SeeFigure9)
Plug the upper drain stub on the vent fitting with the yellow plastic
cap.
Connect the PVC vent extension pipe to the vent fitting. This pipe
has a built-in channel to assist vent condensate disposal.
Align the arrow on the PVC pipe with the airflow marking arrow on
the vent fitting. See label on the PVC pipe for proper installation.
This pipe may only be shortened if an elbow is used to connect the
PVC vent extension tube to field-installed vent pipe. Securely at-
tach the PVC vent extension pipe to the vent fitting with the cla rap.
up.ow,nsta.a.ons(Dua,Cer..ed"gMPD-A4Mode,s)
iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii
RIGHT Side Venting
NOTE: TRAP MUST BE PRIMED BEFORE OPERATION
cure the blower to the transition approximately 112". Rotate the
blower 180 ° and secure with the four(4) screws. Note that some
combustion blowers have plastic spacers on the mounting legs of
the blower located at the 6 and 12 o'clock positions (blower snout
to the left or right) that are required for proper fit up of the blower to
the transition. Use caution to not over tighten the screws to pre-
vent stripping out of the plastic mounting holes.
For left side mounted condensate trap, connect the 3/4" OU rub-
ber hose with the 90 ° bend to the large drain stub on the conden-
sate trap and secure with a 3/4" clamp.
Route the hose to the drain stub on the bottom of the plastic transi-
tion box. Cut off excess hose and discard. Connect the hose to the
drain stub on the transition and secure with a 3/4" clamp.
For right side mounted condensate trap, connect the 3/4" OD rub-
ber hose with the 90 ° bend to the bottom of the plastic transition
box and secure with a 3/4" clamp.
Route the hose to the large drain stub on the condensate trap. Cut
off excess hose and discard. Connect the hose to the drain stub
on the condensate trap and secure with a 3/4" clamp.
Trap Connection
"Clampears"
ointedOUT •
eassemble
dinsert
MountingScrews(4)
forRotatingCombustion_
Blower _
DRAIN SIDE VIEW _
_ Rotate downward
5° to10°
J
NOTE!"Fuilt-inchannelwillbe
angled 5°to10° also.
Supply Air
onepressureswitch
"_ Optional on
/ somemodels
c .._
) ) / Extension Pipe _ _ c
__ _ PVC Vent
Vent
Drain
25-24-05
c
2 Pressure Switch
Connectionon 125models
©
For left or right side mounted condensate trap, the pressure
tap on the condensate trap MUST be connected to the unused
pressure tap located on the upper right hand corner of the plastic
transition box. Remove the plastic caps from the pressure taps on
the condensate trap and the plastic transition and connect with
the 5/16" OD rubber hose. (See Figure 8 and Figure 9)
Connect the 5/8" OD rubber hose with the 90 ° bend to the lower
44001 111400 [_
drain stub on the vent fitting and secure with a 5/8" clamp.
Route the hose to the small drain stub on the condensate trap. Cut
off excess hose and discard. Connect the hose to the drain stub
on the trap and secure with a 5/8" clamp.
NOTE: Route hoses to the condensate trap with no kinking or
binding for proper condensate drainage.

HorizontalLeftInstallations (Dual Certified *9MPD-A4 Models)
NOTE: TRAP MUST BE PRIMED BEFORE OPERATION
Model shown with two
ipe Combustion Air
Pipe,(optional)
Supply
Air
Vent Pipe
PVCVent
Extension Pipe
Vent Fitting
& Clamps Yellow RubberCouplings
Plastic & Clamps 90° Elbow
& Clamps 2" PVCPipe _tate downward
Grommet
& Clamps Plastic Cap
11" Section
5/16" OD
Rubber
pressure switches
DRAIN SIDE VIEW
Horizontal Trap Connection
Blower
Transition
3/4" Hose & Clamps
"Clamp ears"
Pointed OUT
Preassembleand
insert intofurnace
Return Air
25-24-12
Condensate
Trap & Gasket
(Field Supplied) DrainLine_: _
angled5° to10° also.
Horizontal Left Installations - (Dual Certified *9MPD) (See Figure 10)
Note: DO NOT make hose connections until the hose routing and
lengths have been determined. Remove the condensate trap and
drain hoses from the furnace and secure the drain hoses to the
drain stubs on the trap with the hose clamps (position the clamps
as shown in Figure 10). Install the condensate trap/hose assem-
blyto the furnace casing. Hook one side ofthe"clamp ears" on the
drain stub through the hole in the casing and push the condensate
trap into position. Secure with the two screws. Reconnect the
drain hoses to the stubs on the vent fitting and the plastic transi-
tion and secure with the clamps.
Relocate the plastic cap and clamp from the vertical transition
drain stub to the horizontal transition drain stub on the conden-
sate drain trap. Secure the clamps tightly to prevent condensate
leakage. Do not change the cap and clamp on the vent drain stub.
Mount the condensate drain trap in a vertical position to the left
side of the furnace using the two screws and gasket that are pro-
vided. Note: The condensate trap will be located under the fur-
nace in a vertical position when the furnace is placed horizontally
on the left side. Ifneeded, remove the hole plugs from the furnace
side panel and relocate to the open set of holes in the opposite
side panel.
NOTE: All gaskets and seals must be in place for sealed combus-
tion applications.
Remove the 90 ° elbow and vent fitting from the combustion blow-
er by loosening the clamps on the vent fitting. Connect the 90 ° el-
bow to the combustion blower using the rubber coupling and
cla raps. Note for proper alignment of the vent pipe through the fur-
nace, the 90 ° elbow must be installed with the "HORIZONTAL"
lettering on the 90 ° elbow facing out. Connect a 11" section of 2"
PVC pipe (field supplied) to the 90 ° elbow using the rubber cou-
pling and clammps. The PVC pipe will extend through the top pa n-
el a bout 11/2". Connect the vent fitting to the end of the 11" section
of PVC pipe using the clamp.
NOTE: The 90 ° elbow is approved for use inside the furnace
ONLY.
NOTE: The vent fitting MUST be installed with the airflow marking
arrow pointed toward the vent pipe, with the drain stub at a 5° to
10 ° downward slope.
Plug the upper drain stub on the vent fitting with the yellow plastic
cap.
Connect the PVC vent extension pipe to the vent fitting. This pipe
has a built-in channel to assist vent condensate disposal.
Align the arrow on the PVC pipe with the airflow marking arrow on
the vent fitting. See label on the PVC pipe for proper installation.
This pipe may only be shortened if an elbow is used to connect the
Single Pressure Switch
Connections on
All models except 125
[_ 44001 111400

PVCventextensiontubetofield-installedventpipe.Securelyat-
tachthePVCventextensionpipetotheventfittingwiththeclarap.
Connectthe 5/8" OD rubber hose with the 90 ° bend to the lower
drain stub on the vent fitting and secure with a 5/8" clamp.
Route the hose to the horizontal drain stub on the condensate
trap. Cut off excess hoses and discard. Connect the hose to the
drain stub on the condensate trap and secure with a 5/8" clamp.
Connect the 3/4" OD rubber hose with the 90 ° bend to the large
drain stub on the condensate trap and secure with a 3/4" clamp.
Route the hose to the drain stub on the bottom of the plastic transi-
i i
Horizontal Right Installations (Dual Certified *9MPD-A4 Models)
iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii
tion box. Cut off excess hose and discard. Connect the hose tothe
drain stub on the transition and secure with a 3/4" clamp.
The pressure tap on the condensate trap MUST be connected to
the unused pressure tap located on the top of the plastic transition
box. Remove the plastic caps from the pressure taps on the con-
densate trap and the plastic transition and connect with the 5/16"
OD rubber hose.
NOTE: This will require drilling a 5/16" OD hole in the furnace cas-
ing next to the condensate trap.
NOTE: Ensure hoses maintain a downward slope to the conden-
sate trap with no kinking or binding for proper condensate drain-
age.
NOTE: TRAP MUST BE PRIMED BEFORE OPERATION
DRAIN SIDE VIEW Vent Fitting Yellow Coml_ustion.
Y "sot:W:w"ward C'aop ..astic Cap Von.Pip°__ A.r..pe<ept.oT.
/ _ / /__ PVCVent _. h_ _ /
_,_ "/ _ _ Extension Pipe \__ /
NOT .JBu_be _' /_ Vent Fitting /
angled5o toiOO also. &Ruc__:pCso upling.........._ _ _ _ /&C/lamps\ _ "_
/
Model shown with two _/_ _, _ _ Supply Air I
Hor,zonta.TrapConne.ion '.
X_ --_ \ Po,n_eaOUT /7_ \ _e.spre SwitchHose. _ ;X3L/\ Si.g.ePre...reSwitch
/_ _-_ / ' s14" Hose &Clamps Transition / _ _ _-- Connections on
/ _/°7// _ / _, " ............ /_ AII models except125
[ I/J_ _ I )/ Condensate Trap / _ /I _ ))
\ J_-&j "_/) / /J & Gasket / Drain [/
and insert into furnace
Horizontal Right Installations - (Dual Certified *9MPD) (See Figure 11)
Note: DO NOT make hose connections until the hose routing and
lengths have been determined. Remove the condensate trap and
drain hoses from the furnace and secure the drain hoses to the
drain stubs on the trap with the hose clamps (position the clamps
as shown in Figure 11). Install the condensate trap/hose assem-
bly to the furnace casing. Hook one side ofthe"clamp ears" on the
drain stub through the hole in the casing and push the condensate
trap into position. Secure with the two screws. Reconnect the
drain hoses to the stubs on the vent fitting and the plastic transi-
tion and secure with the clamps.
"Clamp ears" Plastic Cap//_..__J \ \ '_
Relocate the plastic caps and clamps on the condensate drain
trap from the vertical drain stub to the horizontal drain stubs. Se-
cure the clamps tightly to prevent condensate leakage.
Mount the condensate drain trap in a vertical position to the right
side of the furnace using the two screws and gasket that are pro-
vided. Note: The condensate trap will be located under the fur-
nace in a vertical position when the furnace is placed horizontally
on the right side. If needed, remove the hole plugs from the fur-
nace side panel and relocated to the open set of holes in the oppo-
site side panel.
44001 111400 [_

NOTE:Allgasketsandsealsmustbein place for sealed combus-
tion applications.
Remove the 90 ° elbow and vent fitting from the combustion blow-
er by loosening the clamps on the vent fitting. Connect the 90 ° el-
bow to the combustion blower using the rubber coupling and
cla raps. Note for proper alignment of the vent pipe through the fur-
nace, the 90 ° elbow must be installed with the "HORIZONTAL"
lettering on the 90 °elbow facing out. Connect the vent fitting to the
end of the 90 ° elbow using the clamp.
NOTE: The 90° elbow is approved for use inside the furnace
ONLY.
NOTE: The vent fitting MUST be installed with the airflow marking
arrow pointed toward the vent pipe, with the drain stub at a 5° to
10° downward slope.
Plug the upper drain stub on the vent fitting with the yellow plastic
cap.
Connect the PVC vent extension pipe to the vent fitting. This pipe
has a built-in channel to assist vent condensate disposal.
Align the arrow on the PVC pipe with the airflow marking arrow on
the vent fitting. See label on the PVC pipe for proper installation.
This pipe may only be shortened if an elbow is used to connect the
PVC vent extension tube to field-installed vent pipe. Securely at-
tach the PVC vent extension pipe to the vent fitting with the clamp.
Remove the pressure switch hose from the upper stub on the
plastic transition box.
Relocate the plastic caps on the stubs of the plastic transition box
from the lower stubs to the upper stubs and secure tightly with the
clamps.
Route the pressure switch hose to the lower stub on the plastic
transition box. Cut off excess hose and discard. Connect the pres-
sure switch hose to the lower stub on the plastic transition box.
Ensure that the hose is routed above the stub on the transition box
sothat condensate does not collect in the hose. NOTE: Failure to
correctly install the pressure switch hose to the transition can ad-
versely affect the safety control operation.
Connect the 3/4" OD rubber hose with the 90 ° bend to the large
drain stub on the condensate trap and secure with a 3/4" clamp.
Route the hose to the drain stub on the bottom of the plastic tran-
sition box. Cut off excess hose and discard. Connect the hose to
the drain stub on the transition and secure with a 3/4" clamp.
Connect the 5/8" OD rubber hose with the 90 ° bend to the lower
drain stub on the vent fitting and secure with a 5/8" clamp.
Route the hose to the smaller drain stub on the condensate trap.
Cut off excess hose and discard. Connect the hose to the drain
stub on the trap and secure with a 5/8" clamp.
NOTE: Route hoses to the condensate trap with no kinking or
binding for proper condensate drainage.
E_ 44001 111400

iiiiM!!iMiIiii_iIiiiiiiiiIiiii(iii?iiiiiii:i;;ijIiiiiiHii
that are provided. If needed, remove the hole plugs from the fur-
nace side panel and relocated to the open set of holes in the oppo-
site side panel.
NOTE: All gaskets and seals must be in place for sealed combus-
tion applications.
For both right and left side vent, remove the 90 ° elbow from the
vent fitting by loosening the clamp on the vent fitting.
Ensure that the vent fitting is securely attached to the combustion
blower using the rubber coupling and clamps.
Connect the PVC vent extension pipe to the vent fitting. This pipe
has a built-in channel to assist vent condensate disposal.
Align the arrow on the PVC pipe with the airflow marking arrow on
the vent fitting. See label on the PVC pipe for proper installation.
This pipe may only be shortened if an elbow is used to connect the
PVC vent extension tube to field-installed vent pipe. Securely at-
tach the PVC vent extension pipe to the vent fitting with the cla rap.
This configuration allows left side venting from the furnace. If right
side venting is required, the combustion blower must be relocated
on the plastic transition box. Loosen the four(4) screws that se-
cure the blower to the transition approximately 1/2". Rotate the
blower 180 ° and secure with the four(4) screws. Note that some
combustion blowers have plastic spacers on the mounting legs of
the blower located at the 6 and 12 o'clock positions (blower snout
to the left or right) that are required for proper fit up of the blower to
the transition. Use caution to not over tighten the screws to pre-
vent stripping out of the plastic mounting holes.
NOTE: The vent fitting MUST be installed with the airflow marking
arrow pointed toward the vent pipe, with the drain stub at a 5° to
10 ° downward slope.
Plug the upper drain stub on the vent fitting with the yellow plastic
cap.
Connect the PVC vent extension pipe to the vent fitting. This pipe
has a built-in channel to assist vent condensate disposal.
Align the arrow on the PVC pipe with the airflow marking arrow on
the vent fitting. See label on the PVC pipe for proper installation.
This pipe may only be shortened if an elbow is used to connect the
PVC vent extension tube to field-installed vent pipe. Securely at-
tach the PVC vent extension pipe to the vent fitting with the clamp.
Remove the pressure switch hose from the upper stub on the
plastic transition box.
Relocate the plastic caps on the stubs of the plastic transition box
from the lower stubs to the upper stubs and secure tightly with the
clamps.
Route the pressure switch hose to the lower stub on the plastic
transition box. Cut off excess hose and discard. Connect the pres-
sure switch hose to the lower stub on the plastic transition box.
NOTE: Failure to correctly install the pressure switch hose to the
transition box can adversely affect the safety control operation.
Connect the 3/4" OU rubber hose with the 90 ° bend to the drain
stub on the bottom of the plastic transition box and secure with a
3/4" clamp.
Route the hose to the large drain stub on the condensate trap. Cut
off excess hose and discard. Connect the hose to the drain stub
on the transition and secure with a 3/4" clamp.
Connect the 518" OD rubber hose with the 90 ° bend to the lower
drain stub on the vent fitting and secure with a 518" clamp.
Route the hose to the smaller stub on the condensate trap. Cut off
excess hose and discard. Connect the hose to the drain stub on
the trap and secure with a 5/8" clamp.
For left side or right side mounted condensate trap, the pres-
sure tap on the condensate trap MUST be connected to the un-
used pressure tap located on the top of the plastic transition box.
Remove the plastic caps from the pressure taps on the conden-
sate trap and the plastic transition and connect the 5/16" OD rub-
ber hose. (See Figure 12)
NOTE: Route hoses to the condensate trap with no kinking or
binding for proper condensate drainage.
[_ 44001 111400

Upflow Installations (Single Pipe N9MP1 & Direct Vent N91VIP2-A4 Models)
NOTE: TRAP MUST BE PRIMED BEFORE OPERATION
DRAIN SIDE VIEW VentFitting
/,/_a te & Clampsdownward
PVC Vent
Extension Pipe
NOTE_. Built-in channel will
be angled 5° to 10° also.
LEFT Side Venting
Trap Connection
lamp ears '_
inted OUT
Preassemble & insert
into furnace
Single Pressure Switch
Connections on all
models except 125
Upflow Installations - (Single Pipe & Direct Vent N9MP1
NOTE: DO NOT make hose connections until the hose routing
and lengths have been determined. Remove the condensate trap
and drain hoses from the furnace and secure the drain hoses to
the drain stubs on the trap with the hose clamps (position the
clamps as shown in Figure 13). Install the condensate trap/hose
assembly to the furnace casing. Hook one side ofthe"cla mp ears"
on the drain stub through the hole in the casing and push the con-
densate trap into position. Secure with the two screws. Recon-
nect the drain hoses to the stubs on the vent fitting and the plastic
transition and secure with the clamps.
Mount the condensate drain trap in a vertical position to either the
left or right side of the furnace using the two screws and gasket
that are provided. If needed, remove the hole plugs from the fur-
nace side panel and relocate to the open set of holes in the oppo-
site side panel.
NOTE: All gaskets and seals must be in place for sealed combus-
tion applications.
Ensure that the vent fitting is securely attached to the combustion
blower using the rubber coupling and clamps.
NOTE: For left side venting, the vent fitting MUST be installed
with the airflow marking arrow pointed toward the vent pipe, with
the drain stub at a 5° to 10 ° downward slope.
Connect the PVC vent extension pipe to the vent fitting. This pipe
has a built-in channel to assist vent condensate disposal.
Align the arrow on the PVC pipe with the airflow marking arrow on
44001 111400
dwg 25-24-06
& N9MP2 Models) (See Figure 13)
the vent fitting. See label on the PVC pipe for proper installation.
This pipe may only be shortened if an elbow is used to connect the
PVC vent extension tube to field-installed vent pipe. Securely at-
tach the PVC vent extension pipe to the vent fitting with the cla rap.
This configuration allows left side venting from the furnace. If right
side venting is required, the combustion blower must be relocated
on the plastic transition box. Loosen the four(4) screws that se-
cure the blower to the transition approximately /2'. Rotate the
blower 180 ° and secure with the four(4) screws. Note that some
combustion blowers have plastic spacers on the mounting legs of
the blower located at the 6 and 12 o'clock positions (blower snout
to the left or right) that are required for proper fit up of the blower to
the transition. Use caution to not over tighten the screws to pre-
vent stripping out of the plastic mounting holes.
NOTE: For right side venting, the vent fitting MUST be installed
with the airflow marking arrow pointed toward the vent pipe, with
the drain stub at a 5° to 10 ° downward slope. (See Figure 14)
Plug the upper drain stub on the vent fitting with the yellow plastic
cap.
Connect the PVC vent extension pipe to the vent fitting. This pipe
has a built-in channel to assist vent condensate disposal.
Align the arrow on the PVC pipe with the airflow marking arrow on
the vent fitting. See label on the PVC pipe for proper installation.
This pipe may only be shortened if an elbow is used to connect the
PVC vent extension tube to field-installed vent pipe. Securely at-
tach the PVC vent extension pipe to the vent fitting with the cla rap.
1 ,

Forleftsidemountedcondensatetrap,connectthe3/4"ODrub-
berhosewiththe90°bendtothelargedrainstubontheconden-
satetrapandsecurewitha3/4"clamp.
Routethehosetothedrainstubonthebottomoftheplastictransi-
tionbox.Cutoffexcesshoseanddiscard.Connectthehosetothe
drainstubonthetransitionandsecurewitha3/4"clamp.
Upflow Installations (Single Pipe N9MP1 & Direct Vent N9MP2-A4 Models)
RIGHTSideVenting NOTE: TRAP MUST BE PRIMED BEFORE OPERATION
Supply Air
N9MP; ONLY
Forrightsidemountedcondensatetrap,connectthe3/4"ODrub-
berhosewiththe90°bendtothebottomoftheplastictransition
boxandsecurewitha3/4"clamp.
Routethehosetothelargedrainstubonthecondensatepump.
Cutoffexcesshoseanddiscard.Connectthehosetothedrain
stubonthecondensatetrapandsecurewitha3/4"clamp.
(Rotate 180° for Left Side)
Combustion Blower
Screws (4)
Models shown
have two
pressure switch
Combustion Blower
(Rotate 100°
DRAIN SIDE VIEW
5° to 10°
Vent
Drain
3uiit-in channel will
angled 5° to 10 ° also.
For left side or right side mounted condensate trap, the pres-
sure tap on the condensate trap MUST be connected to the un-
used pressure tap located on the upper right hand corner of the
plastic transition box. Remove the plastic caps from the pressure
taps on the condensate trap and the plastic transition and connect
with the 5/16" OD rubber hose. (See Figure 13 and Figure 14)
Connect the 5/8" OD rubber hose with the 90 ° bend to the lower
Single Pressure Switch
Connections on all
models except 125
25-24-05
drain stub on the vent fitting and secure with a 5/8" clamp.
Route the hose to the smaller drain stub on the condensate trap.
Cut off excess hose and discard. Connect the hose to the drain
stub on the trap and secure with a 5/8" clamp.
NOTE: Route hoses to the condensate trap with no kinking or
binding for proper condensate drainage.
[_ 44001 111400

Horizontal Left Installations (Single Pipe N9MP1 & Direct Vent N9MP2-A4 Models)
NOTE: TRAP MUST BE PRIMED BEFORE OPERATION
Models shown have
two pressure switch
_._lastic Cap
Supply _
Air ,_
_> Inlet
/
Combustion
AirPipe,
N9MP2ONLY
2_
VentFitting
tPipe &Clamps
VentFitting&Clamps
"Hose & Clamps
Condensate
Trap & Gasket
Transition
518" Hose & Clamps
Return
Air
)Connection
25-23-58
"Clamp ears"
, Pointed OUT
Single Pressure Switch and insert
Connections on all _L, into furnace
models except 125
Drain Line
V
Horizontal Left Installations - (Single Pipe & Direct Vent N9MP1 & N9MP2 Models) (See Figure 15)
NOTE: DO NOT make hose connections until the hose routing
and lengths have been determined. Remove the condensate trap
and drain hoses from the furnace and secure the drain hoses to
the drain stubs on the trap with the hose clamps (position the
clamps as shown in Figure 15). Install the condensate trap/hose
assembly to the furnace casing. Hook one side of the "clamp ears"
on the drain stub through the hole in the casing and push the con-
densate trap into position. Secure with the two screws. Recon-
nect the drain hoses to the stubs on the vent fitting and the plastic
transition and secure with the clamps.
Relocate the plastic caps and clamps on the condensate drain
trap from the vertical drain stubs to the horizontal drain stubs. Se-
cure the clamps tightly to prevent condensate leakage.
Mount the condensate drain trap in a vertical position to the left
side of the furnace using the two screws and gasket that are pro-
vided. Note: The condensate trap will be located under the fur-
nace in a vertical position when the furnace is placed horizontally
on the left side. Ifneeded, remove the hole plugs from the furnace
side panel and relocated to the open set of holes in the opposite
side panel.
NOTE: All gaskets and seals must be in place for sealed combus-
tion applications.
Relocate the combustion blower on the plastic transition box. Re-
move the four(4) screws that secure the blower to the transition
box. Rotate the blower 180 ° so the blower snout is pointing up and
secure with the four(4) screws. Note that some combustion blow-
ers have plastic spacers on the mounting legs of the blower lo-
cated at the 6 and 12 o'clock positions (blower snout to the left or
right) that are required for proper fit up of the blower to the transi-
tion. Use caution to not over tighten the screws to prevent strip-
ping out of the plastic mounting holes.
Ensure that the vent fitting is securely attached to the combustion
blower using the rubber coupling and clamps.
NOTE: The vent fitting MUST be installed with the airflow marking
arrow pointed toward the vent pipe.
Plug the left drain stub on the vent fitting with the yellow plastic
cap.
Connect the 3/4" OD rubber hose with the 90 ° bend to the large
drain stub on the condensate trap and secure with a /4' clamp.
Route the hose to the drain stub on the bottom of the plastic transi-
tion box. Cut off excess hose and discard. Connect the hose tothe
drain stub on the transition and secure with a 3/4" clamp.
Connect the 518" OD rubber hose with the 90 ° bend to the right
drain stub on the vent fitting and secure with a 518" clamp.
Route the hose to the smaller drain stub on the condensate trap.
Cut off excess hose and discard. Connect the hose to the drain
stub on the vent fitting and secure with a 5/8" clamp,
NOTE: Route hoses to the condensate trap with no kinking or
binding for proper condensate drainage.
3 ,
44001 111400 [_

Horizontal Right Installations (Single Pipe & Direct Vent N9MP1 & N9MP2-A4 Models)
NOTE: TRAP MUST BE PRIMED BEFORE OPERATIONveni_ipls_lv__Plastic
Cap
518" Hose &\
Return
Air
Modelsshownhave__
twopressureswitches
Clamps _
Vent Fitting
& Clamps
\
\
Combustion
Air Pipe,
N9MP2 ONLY
\
%
Inlet
Supply
Air
dwg25-23-59a
Horizontal Trap Connection
"Clamp ears" Cap Switch, Transition ps
Pointed OUT
Preassemble
and insert
into furnace
Plastic Pressure 3/4" Hose
Condensate
Trap & Gasket Switch, Blower
Drain Line
Horizontal Right Installations - (Single Pipe & Direct Vent N9MP1 & N9MP2 Models) (SeeFigure16)
NOTE: DO NOT make hose connections until the hose routing
and lengths have been determined. Remove the condensate trap
and drain hoses from the furnace and secure the drain hoses to
the drain stubs on the trap with the hose clamps (position the
clamps as shown in Figure 16). Install the condensate trap/hose
assembly to the furnace casing. Hook one side of the "clamp ears"
on the drain stub through the hole in the casing and push the con-
densate trap into position. Secure with the two screws. Recon-
nect the drain hoses to the stubs on the vent fitting and the plastic
transition and secure with the clamps.
Relocate the plastic caps and clamps on the condensate drain
trap from the vertical drain stub to the horizontal drain stubs. Se-
cure the clamps tightly to prevent condensate leakage.
Mount the condensate drain trap in a vertical position to the right
side of the furnace using the two screws and gasket that are pro-
vided. Note: The condensate trap will be located under the fur-
nace in a vertical position when the furnace is placed horizontally
on the right side. If needed, remove the hole plugs from the fur-
nace side panel and relocate to the open set of holes in the oppo-
site side panel.
NOTE: All gaskets and seals must be in place for sealed combus-
tion applications.
Ensure that the vent fitting is securely attached to the combustion
blower using the clamps.
NOTE: The vent fitting MUST be installed with the airflow marking
arrow pointed toward the vent pipe.
Plug the left drain stub on the vent fitting with the yellow plastic
cap.
Remove the pressure switch hose from the upper stub on the
plastic transition box.
Relocate the plastic ca ps on the stubs of the plastic transition from
the lower stubs to the upper stubs and secure tightly with the
clamps.
Route the pressure switch hose to the lower stub on the plastic
transition box. Cut off excess hose and discard. Connect the
pressure switch hose to the lower stub on the plastic transition
box. Ensure that the hose is routed above the stub on the transi-
tion box so that condensate does not collect in the hose. NOTE:
Failure to correctly install the pressure switch hose to the transi-
tion can adversely affect the safety control operation.
Pressure Switch
Hose, Transition
Connections on all
models except 125
Single Pressure Switch
[_ 44001 111400

Connectthe 3/4" OD rubber hose with the 90 ° bend to the large
drain stub on the condensate trap and secure with a 3/4" clamp.
Route the hose to the drain stub on the bottom of the plastic transi-
tion box. Cut off excess hose and discard. Connect the hose to the
drain stub on the transition and secure with a 3/4" clamp.
Connect the 5/8" OD rubber hose with the 90 ° bend to the right s-
Downflow Installations (Single Pipe N9MP91 & Direct Vent N9MP2-A4 Models)
tub on the vent fitting and secure with a 5/8" clamp.
Route the hose to the smaller drain stub on the condensate trap.
Cut off excess hose and discard. Connect the hose to the drain
stub on the trap and secure with a 5/8" clamp.
NOTE: Route hoses to the condensate trap with no kinking or
binding for proper condensate drainage.
VentFitting
&Clampi
PVCVent
Extension
Condensate
Trap & Gasket
LEFT Side Ventin_
<C>
Return Air
Combustion Blower) Plastic
(Rotate 180°)
Modelshown have
two pressure
switches
Pressure Switch
Hose, Transition
RIGHT Side Venting
ReturnAir
Air Intake
Combustion
Air Pipe,
PVC Vent
Extension
Pipe
Yellow VentFitting
2PressureSwitch
Connectiononall125
models
Connectionsonall
models except 125
Single PressureSwitch beangled 5° to10° also.
NOTE: TRAP MUST BE PRIMED BEFORE OPERATION
Downflow Installations - (Single Pipe & Direct Vent N9MP1 &
NOTE: DO NOT make hose connections until the hose routing
and lengths have been determined. Remove the condensate trap
and drain hoses from the furnace and secure the drain hoses to
the drain stubs on the trap with the hose clamps (position the
clamps as shown in Figure 17). Install the condensate trap/hose
assembly to the furnace casing. Hook one side ofthe"cla mp ears"
on the drain stub through the hole in the casing and push the con-
densate trap into position. Secure with the two screws. Recon-
SupplyAir
DRAIN SIDE VIEW
5° to10°
dwg25-24-04
N9MP2 Models) (See Figure 17)
nect the drain hoses to the stubs on the vent fitting and the plastic
transition and secure with the clamps.
Mount the condensate drain trap in a vertical position to either the
right or left side of the furnace using the two screws and gasket
that are provided. If needed, remove the hole plugs from the fur-
nace side panel and relocated to the open set of holes in the oppo-
site side panel.
44001 111400 [_

NOTE:Allgasketsandsealsmustbein place for sealed combus-
tion applications.
Ensure that the vent fitting is securely attached to the combustion
blower using the rubber coupling and clamps.
Connect the PVC vent extension pipe to the vent fitting. This pipe
has a built-in channel to assist vent condensate disposal.
Align the arrow on the PVC pipe with the airflow marking arrow on
the vent fitting. See label on the PVC pipe for proper installation.
This pipe may only be shortened if an elbow is used to connect the
PVC vent extension tube to field-installed vent pipe. Securely at-
tach the PVC vent extension pipe to the vent fitting with the cla rap.
This configuration allows left side venting from the furnace. If right
side venting is required, the combustion blower must be relocated
on the plastic transition box. Loosen the four(4) screws that se-
cure the blower to the transition approximately 1/2". Rotate the
blower 180 ° and secure with the four(4) screws. Note that some
combustion blowers have plastic spacers on the mounting legs of
the blower located at the 6 and 12 o'clock positions (blower snout
to the left or right) that are required for proper fit up of the blower to
the transition. Use caution to not over tighten the screws to pre-
vent stripping out of the plastic mounting holes.
NOTE: The vent fitting MUST be installed with the airflow marking
arrow pointed toward the vent pipe, with the drain stub at a 5 ° to
10 ° downward slope.
Plug the upper drain stub on the vent fitting with the yellow plastic
cap.
Connect the PVC vent extension pipe to the vent fitting. This pipe
has a built-in channel to assist vent condensate disposal.
Align the arrow on the PVC pipe with the airflow marking arrow on
the vent fitting. See label on the PVC pipe for proper installation.
This pipe may only be shortened if an elbow is used to connect the
PVC vent extension tube to field-installed vent pipe. Securely at-
tach the PVC vent extension pipe to the vent fitting with the cla rap.
Remove the pressure switch hose from the upper stub on the
plastic transition box.
Relocate the plastic caps on the stubs of the plastic transition box
from the lower stubs to the upper stubs and secure tightly with the
clamps.
Route the pressure switch hose to the lower stub on the plastic
transition box. Cut off excess hose and discard. Connect the pres-
sure switch hose to the lower stub on the plastic transition box.
NOTE: Failure to correctly install the pressure switch hose to the
transition box can adversely affect the safety control operation.
Connect the 3/4" OD rubber hose with the 90 ° bend to the drain
stub on the bottom of the plastic transition box and secure with a
3/4" clamp.
Route the hose to the large drain stub on the condensate trap. Cut
off excess hose and discard. Connect the hose to the drain stub
on the transition and secure with a 3/4" clamp.
Connect the 5/8" OD rubber hose with the 90 ° bend to the left
drain stub on the vent fitting and secure with a 5/8" clamp.
Route the hose to the smaller stub on the condensate trap. Cut off
excess hose and discard. Connect the hose to the drain stub on
the trap and secure with a 5/8" clamp.
For left side or right side mounted condensate trap, the pres-
sure tap on the condensate trap MUST be connected to the un-
used pressure tap located on the top of the plastic transition box.
Remove the plastic caps from the pressure tap on the condensate
trap and the plastic transition and connect the 5/16" OD rubber
hose. (See Figure 17)
NOTE: Route hoses to the condensate trap with no kinking or
binding for proper condensate drainage.
Connecting Vent and Combustion Air Piping
CARBON MONOXIDE POISONING HAZARD
Failure to properly seal vent piping can result in death,
personal injury and/or property damage.
Cement or mechanically seal all joints, fittings, etc. to
prevent leakage of flue gases.
Refer to the Figure 8 through Figure 17 that corresponds to the
installation position of the furnace for the application.
Preassemble the vent and combustion air piping from the furnace
to the vent termination. Do not cement the pipe joints until the pipe
preassembly process is complete.
Combustion Air Pipe Connection (Dual Certified or
Direct Vent)
Install the air intake coupling and gasket to the furnace with the
four(4) screws.
Note: The air intake coupling and gasket can be installed to the
top panel to the alternate air intake locations on either the left or
right side panels of the furnace.
For downflowinstallation, the air intake coupling and gasket must
be installed to the alternate air intake location on either the left or
right side panels. Remove the 3" hole plug from the side panel and
relocate to the air intake hole in the top panel. Use four screws to
seal the four(4) mounting holes in the top panel next to the hole
plug. Drill four(4) 7/64" diameter holes in the casing using the air
intake coupling as the template.
The air intake coupling is sized for 2" PVC pipe.
Install the combustion air pipe to the air intake coupling using RTV
sealant to provide for future serviceability.
Vent Pipe Connection
Install the vent pipe grommet to the furnace panel. Locate the
grommet in the furnace panel at a location directly away from the
vent fitting on the combustion blower. The grommet snaps intothe
3" hole plug from the furnace panel. NOTE: Depending on the
installation position, the vent pipe grommet will be installed to the
top panel or tothe alternate location on the side panels. If needed,
remove the 3" hole plug from the furnace panel and relocate to the
open hole in the furnace panel. (See Figure 12 or Figure 17)
Install the vent pipe to the rubber coupling, the vent fitting or the
PVC vent extension pipe. Securely attach using the clamp or PVC
cement as required.
Note: The vent fitting MUST be installed with the air flow
marking arrow pointed toward the vent pipe. (See Figure 18)
Some installations require the vent fitting to be installed with
a 5 ° to 10 ° downward slope. (See Figures 8 - 17)
[_ 44001 111400

Proper Sealing Procedure for
Combustion Blower
RubberCoupling J ._ VentPipe
& Clamps--__ ____ _ _ (Top Panel Exit)
tPipe _ NOTE: The 90 ° elbow is ap-
90° Elbow &Clamps
Vent Extension _'_.
Pipe (Side Panel
Exit)
DRAIN SIDE VIEW
_/_'ia te downward
NOIF.guilt-inchannelwill
beangled5°to 10° also.
proved for use inside the furnace
ONLY.
Joining Pipe and Fittings
Vent Fitting
Combustion
Blower
25-24-14
NOTE: Stir the solvent cement frequently while using. Use a natu-
ral bristle brush or the dauber supplied with the cement. The prop-
er brush size is one inch.
2. After checking pipe and socket for proper fit, wipe socket
and pipe with cleaner-primer. Apply a liberal coat of primer
to inside surface of socket and outside of pipe. Do NOT al-
low primer to dry before applying cement.
3. Apply a thin coat of cement evenly in the socket. Quickly
apply a heavy coat of cement to the pipe end and insert
pipe into fittings with a slight twisting movement until it bot-
toms out.
NOTE: Cement MUST be fluid while inserting pipe. If NOT, recoat
pipe.
4. Hold the pipe in the fitting for 30 seconds to prevent the ta-
pered socket from pushing the pipe out of the fitting.
5. Wipe all excess cement from the joint with a rag. Allow 15
minutes before handling. Cure time varies according to fit,
temperature and humidity.
Connecting Vent Pipes and Termination
NOTE: Combustion air intake and vent MUST terminate in the
same atmospheric pressure zone. If installation is in a cold cli-
mate (sustained temperatures below 0 °F), increase the minimum
distance between vent pipe and air intake from 8" to 18".
CAUTION
Maintain a minimum of 36" between combustion air inlet and
clothes dryer vent. Terminate the combustion air intake as
far as possible from any air conditioner, heat pump,
swimming pool, swimming pool pumping, chlorinator or
filtration unit.
FIRE HAZARD
Observe all cautions and warnings printed on material
containers to prevent possible death, personal injury
and/or property damage.
Provide adequate ventilation and do NOT assemble near
heat source or open flame. Do NOT smoke while using
solvent cements and avoid contact with skin or eyes.
This furnace is approved for venting with Schedule 40 PVC,
CPVC, ABS, Cellular Core pipe fittings and SDR-26 PVC.
NOTE: All PVC, CPVC, ABS, and Cellular Core pipe fittings, sol-
vent cement, primers and procedures MUST conform to Ameri-
can National Standard Institute and American Society for Testing
and Materials (ANSI/ASTM) standards.
Pipe and Fittings - ASTM D1785, D2241, D2466, D2661,
D2665, F-891, F-628
• PVC Primer and 5olvent Cement- ASTM D2564
• Procedure for Cementing Joints - Ref ASTM D2855
NOTE: In order to create a seal that allows future removal of pipe,
RTV sealant MUST be used on the inlet pipe where itjoins to
the furnace. PVC, CPVC, ABS, and Cellular Core pipe and ce-
ment may be used on all other joints.
CAUTION
Do NOT use solvent cement that has become curdled, lumpy
or thickened and do NOT thin. Observe precautions printed
on containers. For applications below 32 ° F., use only low
temperature type solvent cement.
1. Cut pipe end square, remove ragged edges and burrs.
Chamfer end of pipe, then clean fitting, socket and pipe
joint of all dirt, grease, or moisture.
Install all couplings, nipples and elbows using proper pro-
cedures for Joining Pipe and Fittings and maintain spac-
ing between vent and combustion air piping as indicated in
Figure 19 through Figure 27.
Sidewall Termination 12" or More
Above Snow Level or Grade Level
MIN. _18" Minimum for cold climates
(substained below 0° F)
Horizontal Termination
Cuttwoholes. 2 /2' for 2"pipe, 3" for 2 /2' pipe, or3 /2' for
3" pipe. Do NOT make the holes oversized, or it will be nec-
essary to add a sheet metal or plywood plate on the outside
with the correct size hole in it.
1 , 1 ,
44001 111400 I_

2. Checkholesizesbymakingsureitissmallerthan the cou-
plings or elbows that will be installed on the outside. The
couplings or elbows MUST prevent the pipe from being
pushed back through the wall.
3. Extend vent pipe and combustion air pipe through the wall
3/4" to 1" and seal area between pipe and wall.
4. Install the couplings, nipple and termination elbows as
shown and maintain spacing between vent and combus-
tion air piping as indicated in Figure 19 and Figure 20.
A metal shield is recommended 18" x 18" min. or 18" rain. diame-
ter around the vent termination at the exterior wall to protect the
house exterior materials from flue product or condensation (freez-
ing) damage.
UsingExterior Risers
1. Install elbows and pipe to form riser as shown in Figure 20.
2. Secure vent pipe to wall with galvanized strap or other rust
resistant material to restrain pipe from moving.
3. Insulate pipe with Armaflex or equivalent moisture resis-
tant closed cell foam insulation or Fiberglass insulation if
boxed in and sealed against moisture.
ii Sidewall Termination with Exterior
Fi_2_ : Risers to Get Above Snow Level or
Grade Level
8" _ _ / 18 Mmtmumfor coldchmates
MIN. J / _-_ (substainedbelow0° F)
20' _'_
Rooftop Termination
A = 12" Above roofor snow accumulationlevel
B= 8" Min.,20' Maximum,except in areaswith extreme coldtemperatures
(sustainedbelow0°% the 18" Min.
Vent Termination Shielding
Under certain wind conditions some building materials may be af-
fected by flue products expelled in close proximity to unprotected
surfaces. Sealing or shielding of the exposed surfaces with a cor-
rosion resistant material (such as aluminum sheeting) may be re-
quired to prevent staining or deterioration. The protective material
should be attached and sealed (if necessary) to the building be-
fore attaching the vent terminal.
Multi Vent Termination Clearances
: =
%. / 8NOW LEVEL _=Sq30-04F
Vertical Termination
1. Figure 21 shows the proper installation and clearances for
vertical vent termination. The vertical roof termination
should be sealed with a plumbing roof boot or equivalent
flashing. The inlet of the intake pipe and end of the exhaust
vent must be terminated no less than 12" above the roof or
snow accumulation level, and 12" away from a vertical wall
or other protrusion.
2. If the vent system is installed in an existing chimney make
sure clearances shown in Figure 21 are maintained. Hori-
zontal section before the termination elbow can be ex-
tended on the inlet air to provide necessary clearance.
When two (2) or more furnaces are vented near each other, each
furnace must be individually vented.
Two (2) vent terminations may be installed as shown in
Figure 22, Figure 23, Figure 24, Figure 25, Figure 26 and
Figure 27, but the next vent termination must be at least 36" away
from first 2 terminations. It is important that vent terminations be
made as shown to avoid recirculation of flue gases.
Concentric Vent and Combustion-
Air Roof Termination
12"Min. Gradeorl
Snow Level
Combustion
Air
Dimension "A" is touching or 2" maximum separation.
[_ 44001 111400

Concentric Vent and Combustion-
Air Sidewall Termination
Rooftop Inlet Vent and Exhaust-
Air Termination
1"Maximum
Exhaust
Dimension "A" is touching or 2" maximum separation.
J jJ
Sidewall Inlet Vent and Exhaust-
Air Termination
20'Max.
18" Min.for
Cold Climates
(Sustained Below0° F)
12"Min. Grade or
Snow Level
25-22-02d
8"Min.
18"Min. for Cold Climates _
12" Min.
Level
_e;i_271 Recommended Alternate
:) 8" Min. \
Inlet 20' Max.
Installation for Sustained Cold
Weather (-O° F & below)
EXH_T
INLET
Exhaust
/
25-22-43
_mension "A" is touching or 2" maximum separation.
Sidewall Inlet Vent and Exhaust-Air
Termination with Exterior Risers
18"Min. for Cold Climates
(Sustained Below 0° F)
J
Dimension "A" is touching or 2" maximum separation.
8"Min.
12" Min.
Grade or Snow
Inlet Level
FRONT VIEW
l Same Joist _
Space
12" MIN.Ground Level
-- _'_ OR Snow Level
SIDE VIEW
12"
12"
_J
25-23-73
44001 1114O0 [_

5. Gas Supply and Piping
Gas Pressures Below 2000'
CARBON MONOXIDE POISONING, FIRE AND EXPLO-
SION HAZARD
Models designated for Natural Gas are to be used
with Natural Gas Only, unless properly converted
to use with LP gas.
Furnace operating with the wrong fuel result in death,
personal injury and/or property damage.
NOTE: The rating plate is stamped with the model number, gas
type and gas input rating. In addition, models manufactured for
sale in Canada have orifice size information stamped on the rat-
ing plate.
AlternateBTUHInputRatings(USA Only)
The input rating of these furnaces can be changed from the stan-
dard input rating to the alternate input rating shown in Table 5, by
changing the main burner orifices. NOTE: The input rating ot
80,000 BTUH models cannot be changed from the standard in-
put. Changing of burner orifices MUST be done by a qualified ser-
vice technician. See section on changing orifices or following
page.
Alternate Input Ratings, USA ONLY.
BTUH BTUH Natural LP
Standard Alternate Gas Gas
Rating Rating Orifice Orifice
50,000 40,000 #44 #55
75,000 60,000 #44 #55
100,000 80,000 #44 #55
125,000 100,000 #44 #55
SupplyPressure
FIRE HAZARD
Failure to properly set input pressure can result in
death, personal injury and/or property damage.
Do NOT set input rating above that shown on rating
plate.
1,
Supply pressure can be checked using the 1/8" NPT port
on the supply side of the gas valve.
2.
Gas input to burners MUST NOT exceed the rated input
shown on rating plate.
3.
Do NOT allow minimum gas supply pressure to vary down-
ward. Doing so will decrease input to furnace. Refer to
Table 6 for normal gas supply and manifold pressures.
Gas Supply Pressure
Type Recommended Max. Min.
Natural 3.5"
LP 10"
• With Propane gas, the rated input is obtained when the
BTU content is 2,500 BTU per cubic foot and manifold
pressure set at 10" W.C.
• If Propane gas has a different BTU content, orifices
MUST be changed by licensed Propane installer.
• Measured input can NOT exceed rated input.
• Any major change in gas flow requires changing burn-
er orifice size.
7" 14" 4.5"
11" 14" 11"
Important Note:
Manifold
Pressure
GasSupplyPressure
Gas supply pressure should be within minimum and maximum
values listed on rating plate. Pressures are usually set by gas sup-
pliers.
Manifold Gas Pressure Adjustment
NOTE: Make adjustment to manifold pressure with burners oper-
ating.
FIRE OR EXPLOSION HAZARD
Failure to turn OFF gas at shut off before connecting
manometer can result in death, personal injury and/or
property damage.
Turn OFF gas at shut off before connecting manometer.
1. Remove the burner compartment door.
2. With gas OFF, connect manometer to tapped opening on
gas valve. Use manometer with a 0 to 15" water column
range.
3. Turn gas ON and remove adjustment screw cover on gas
valve. Turn counterclockwise to decrease pressure and
clockwise to increase.
4. For altitudes up to 2000', set pressure to value shown in
Table 6, ± 0.3" water column.
5. Connect manometer to the tapped opening on the outlet
side of gas valve. Use manometer with a 0-15" min. water
column range.
6. Turn gas ON, fire the furnace and remove adjustment
screw cover on gas valve.
7. Turn counterclockwise to decrease pressure and clock-
wise to increase.
8. SetpressuretovalueshowninTable 6. Refertolmportant
Notes in Table 6. Pressure is also listed on furnace rating
plate.
9. When pressure is set, replace adjustment screw cover on
gas valve.
10. Replace the burner compartment door.
E_ 44001111400

MANIFOLDPRESSUREAND ORIFICESIZEFORHIGH ALTITUDEAPPLICATIONS
NATURAL GAS
Heat Value
BtulOu.Ft. 0-1999 2000-2999 3000-3999 4000-4999 5000-5999 6000-6999 7000-7999
ElevationAbove Sea Level
(".wc) (".wc) (" .wc) (".wc) (" .wc) (" .wc) (" .wc)
800 3.5 3.5 3.5 3.5 3.5 3.5 3.5
850 3.5 3.5 3.5 3.5 3.5 3.5 3.5
900 3.5 3.5 3.5 3.5 3.5 3.5 3.4
950 3.5 3.5 3.5 3.5 3.3 3.2 3.1
1000 3.5 3.4 3.3 3.2 3.0 2.9 2.8
1050 3.2 3.1 3.0 2.9 2.7 2.6 2.5
1100 2.9 2.8 2.7 2.6 2.5 2.4 2.3
Orifice Size * #42 Orifice size for 50,000, 75,000 100,00 & 125,000 BTUH models
• #44 Orifice size for 80,000 BTUH model
General Derating Rules
For operation with natural gas at altitudes above 2,000',
orifice change andlor manifold pressure adjustment may
be required to suit gas supplied. Check with gas supplier. If
orifice sizing is needed, it should be based on reducing the
input rating by 2% (natural) or 4% (LP) for each 1,000'
above sea level. See Table 7 and Figure 28 for required
pressure change andlor orifice change for high altitudes.
For operation with LP gas at altitudes above 2,000', gas ori-
fices MUST be changed and manifold pressure MUST be
maintained as per Table 6. For the 50,000, 75,000,
100,000 and 125,000 BTUH Orifice sizes are #54 for
0-2000' above sea level, #55 for 2000' -7000' above sea
level, and #56 for 7000' -8000' above sea level. For the
80,000 BTUH models, the orifice size is #55 for 0 - 4,000'
above seal level and #56 for 5,000' - 8,000' above sea lev-
el. Orifices can be ordered through your distributor. (See
Figure 28)
Changing Orifices
Measure from face of orifice
NOTE: The derating of these units at 2% (Natural) and 4% (L.P.)
has been tested and approved by AGA.
High Altitude Air Pressure Switch
Altitudes over 4,000' require a different air pressure switch than
the one installed at the factory. Check parts list for pressure switch
and consult your distributor for part number and availability. In
Canada, provincial codes may govern installation of switch.
Check with governing authorities.
Changing Orifices for HighAltitude
ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD
Failure to properly install orifices can result in death,
personal injury and/or property damage.
Turn OFF electric power (at disconnect) and gas supply
(at manual valve in gas line) when installing orifices.
Installation of orifices requires a qualified service
technician.
NOTE: Main burner orifices can be changed for high altitudes.
1. Disconnect gas line from gas valve.
2. Remove manifold from furnace.
3. Remove the orifices from the manifold and replace them
with properly sized orifices.
4. Tighten orifices so it is seated and gas tight. (See
Figure 28)
5. Reinstall manifold. Ensure burners do NOT bind on new
orifices.
44001 111400 [_

Typical Gas Piping for Upflow
Drip Legand Union,Union* should be outside the Gas (Single Pipe)
cabinet. Manual shut-off valve MUST heupstream of
dripleg, union, Manualshut- off
Useelbows and3" pipenippleto connectvalveto
pipingwhenusingright side gas pipe entry.
LP Lowpressure
switch. Optional
on some models.
nipp
* Union may be installed inside the cabinet when necessary because
valve
25-23-37b
Typical Gas Piping for Downflow
Use elbows and 3" pipe nipple to connect valve's-
to piping when using left side gas pipe entry.
Manualshut- off
LP Low pressure
switch. Optional LP
conversion.
Drip Leg and Union, Union* should
the cabinet. Manual shut-off valve MUST be
upstream of dripleg, union, and furnace.
*Union may be installed inside the cabinet when necessary (Single Pipe)
because of clearances.
valve
Gas Pipe Grommet
Natural Gas Input Rating Check
NOTE: The gas meter can be used to measure input to furnace.
Rating is based on a natural gas BTU content of 1,000 BTU's per
cubic meter. Check with gas supplier for actual BTU content.
1. Make sure burner compartment door is in place before per-
forming the following steps.
2. Turn OFF gas supply to all appliances and start furnace.
Natural Gas No.of Seconds | Time PerCubic BTUPer
BTU Content PerHour _ Footin Seconds Hour1,000 3,600 48 75,000
3. Time how many seconds it takes the smallest dial on the
gas meter to make one complete revolution. Refer to Ex-
ample.
25-23-39
Example
1,000 x 3,600 + 48 = 75,000 BTUH
[_ 44001 111400

4. Relightallappliancesandensureallpilotsareoperating.
NOTE: If meter uses a 2 cubic foot dial, divide results (seconds)
by two.
GasPiping Requirements
NOTE: The gas supply line must be installed by a qualified ser-
vice technician in accordance with all building codes, (In the state
of Massachusetts, gas supply connections MUST be performed
by a licensed plumber or gas fitter).
1. Properly size gas pipe to handle combined appliance load
or run gas pipe directly from gas meter or LP gas regulator.
Refer to NFGC and ANSI Z223.1 for proper gas pipe size.
2. Install correct pipe size for run length and furnace rating.
3. Measure pipe length from gas meter or LP second stage
regulator.
NOTE: Refer to Figure 29 or Figure 30 for the general layout at
the furnace. The rules listed apply to natural and LP gas pipe
installations.
NOTE: On the Dual Certified or Direct Vent models, install the gas
pipe grommet to the furnace side panel with the gas pipe entry. If
needed, remove the 2" hole plug and relocate to the open hole in
the furnace side panel.
If a flexible connector is required or allowed by
authority having jurisdiction, black iron pipe shall be
installed at gas valve and extended a minimum of 2"
outside furnace casing.
4. Use black iron or steel pipe and fittings or other pipe ap-
proved by local code.
NOTE: The use of copper tubing for gas piping is NOT approved
by the state of Massachusetts.
5. Use ground joint unions and install a drip leg no less than 3"
long to trap dirt and moisture before it can enter gas valve.
6. Use two pipe wrenches when making connections to pre-
vent gas valve from turning.
7. Install a manual shut-off valve external to furnace casing
and tighten all joints securely.
Additional LP Connection Requirements
1. Have a licensed LP gas dealer make all connections at
storage tank and check all connections from tank to fur-
Race.
2. If copper tubing is used, it MUST comply with limitation set
in National Fuel Gas Code or CGA codes.
3. Two-stage regulation of LP gas is recommended.
FinalCheck
1. The furnace and the gas valve must be disconnected from
the gas supply piping system during any pressure testing of
that system at test pressures in excess of 1/2" PSIG. Close
the manual shut-off valve before testing at such pressures.
2. When installation is complete, test all pipe connections for
leaks with the gas pressure less than /2' PSIG to the gas
valve.
3. Apply a commercial soap solution to all joints to test for
leaks. Correct any leaks indicated by bubbles.
Correct even the smallest leak at once.4,
5.
Check for leaks at gas valve and orifice connections to the
burner manifold along with the pilot tube connections to the
valve and pilot assembly while the furnace is operating.
1 ,
6. Electrical Wiring
ELECTRICAL SHOCK HAZARD
Failure to do so can result in death, personal inju-
ry and/or property damage.
Turn OFF electric power at fuse box or service
panel before making any electrical connections
and ensure a proper ground connection is made
before connecting line voltage.
Power SupplyWiring
The furnace MUST be electrically wired and grounded in accor-
dance with local codes, or in the absence of local codes with the
latest edition of The National Electric Code, ANSI NFPA 70 and/or
The Canadian Electric Code CSA C22.1.
Field wiring connections must be made inside the furnace con-
nection box. A suitable strain relief should be used at the point the
wires exit the furnace casing.
Copper conductors must be used. Line voltage wires should be
sized for the input amps stated on the rating plate. Furnace should
be connected to its own separate circuit.
Thermostat
Thermostat location has an important effect on the operation of
the unit. Follow instructions included with thermostat for correct
mounting and wiring.
Low voltage connections to furnace must be made on terminal
board to fan control.
44001 111400
Set thermostat heat anticipator in accordance with the Technical
Support Manual.
Optional Equipment
All wiring from furnace to optional equipment MUST conform to
local codes or, in the absence of local codes with the latest edition
of The National Electric Code, ANSI NFPA 70 and/or The Cana-
dian Electric Code CSA C22.1. Install wiring in accordance with
manufacturer's instructions. The wiring MUST have a minimum
temperature rating of 105 ° C.
Humidifier/Electronic Air Cleaner
The furnace is wired for humidifier and/or electronic air cleaner
connection.
CAUTION
Do NOT exceed 115V/0.8 amp. maximum current load for
both the EAC terminal and the HUM terminal combined.
NOTE: The humidifier will be powered when the furnace is fired
and the circulating air blower comes on. The electronic air cleaner
will be powered anytime the air circulating blower is energized.
However, the electronic air cleaner is NOT energized during con-
tinuous fan operation controlled by the electronic fan control.
Fan Control
The fan control is preset at the factory with a fixed blower ON
delay of 30 seconds in the heating mode. The blower OFF timing
is preset at 140 seconds. If desired, the fan OFF delay can be re-
set to obtain the longest delay times while still maintaining comfort
levels. See "Furnace Wiring Diagram".

Fan Delay DIP Switch Settings
COOLONDELAY:6SEC.
COOLOFFDELAY:60 SEC.
HEATON DELAY:30 SEC.
HEAT OFF DELAY
Control Center Fuse
The 24V circuit contains a 5-amp, automotive-type fuse located
on fan timer board. (See Figure 32) Any electrical shorts of 24V
wiring during installation, service, or maintenance may cause
fuse to blow. If fuse replacement is required, use only a fuse of
identical size (5 amp.)
Fan Timer Connections
60SEC 100SEC 140SEC 180SEC
Electrical Connections
NOTE: Junction Box can be
mounted to either the left or right
side.
1_5V.aOHL
G_=_nd
[ LowVoltage
; Terl_nn_
:i
25-23-47
_- DIP Switch
FUSE_
¢& 25-23-41
25-23-42
7. Ductwork and Filter
CARBON MONOXIDE POISONING HAZARD
Failure to properly seal duct can result in death, personal
injury and/or property damage.
Do NOT draw return air from inside a closet or utility
room. Return air duct MUST be sealed to furnace casing.
Installation
NOTE: Design and install air distribution system to comply with
Air Conditioning Contractors of America manuals and/or NFPA
pamphlets 90A and 90B or other approved methods that conform
to local codes and good trade practices.
1. When furnace supply ducts carry air outside furnace area,
seal return air duct to furnace casing and terminate duct
outside furnace space.
2. Install air conditioning cooling coil (evaporator) on outlet
side of furnace.
3. For furnaces installed without a cooling coil it is recom-
mended that the outlet duct be provided with a removable
access panel. This panel should be accessible when the
furnace is installed so the exterior of the heat exchanger
can be viewed for inspections. The access panel MUST be
sealed to prevent leaks.
4. If separate evaporator and blower units are used, install
good sealing dampers for air flow control. Chilled air going
through the furnace could ca use condensation and shorten
the furnace life.
NOTE: Dampers (field supplied) can be either automatic or
manual. Manually operated dampers MUST be equipped with a
means to prevent furnace or air conditioning operation unless
damper is in the full heat or cool position.
E_ 44001 111400

CARBON MONOXIDE POISONING HAZARD
This could result in death, personal injury and/or
property damage.
Cool air passing over heat exchanger can cause
condensate to form resulting in heat exchanger failure.
Connections
NOTE: On upflow installations, return air can enter through either
side, both sides, orthe bottom. On horizontal or downflowinstalla-
tions the return air must enter through the knockout opening in the
lower panel of the furnace. Return air can not enter through rear
of the furnace. When the furnace is located in an area near or ad-
jacent to the living area, the system should be carefully designed
with returns to minimize noise transmission through the return
grille. Any blower moving a high volume of air will produce audible
noise which could be objectionable to when the unit is located
very close to living areas. It is advisable to route the return air
ducts under the floor or through the attic.
1. Forsideconnectionsusinga16"x25"filter, cutouttheem-
bossed area shown in Figure 33. This will provide a 141/2"
x 221/2" approximate opening.
i;[ :;; [
Side Return Air C UtO Ut
iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii
Height of Cutout for 16" x 25" Filter
AB==221/z"141/z"Width of Cutout for 16" x 25" Filter/_
Insulation
1. Insulate ductwork installed in attics or other areas exposed
to outside temperatures with a minimum of 2" insulation
and vapor barrier.
2. Insulate ductwork in indoor unconditioned areas with a
minimum of 1" insulation with indoor type vapor barrier.
Filters
A Filter must be used:
Filters are not supplied with these furnaces, but can be purchased
from dealer.
Use either filter type:
• Washable, high velocity filters are based on a maximum
air flow rating of 600 FPM.
• Disposable, low velocity filters are based on a maximum
air flow of 300 FPM when used with filter grille.
NOTE: Disposable, low velocity filters may be replaced with
washable, high velocity filter providing they meet the minimum
size areas. Washable, high velocity filters can be replaced ONLY
with same type and size.
Side Mounted Filter Rack
on Side of Furnace
Embossed Area _jmC e
NOTE: Furnaces with 5 TONS cooling rating require two(2) side
returns or one side return with bottom return.
2. Bottom returns can be made by removing the knockout
panel in the furnace base. Do NOT remove knock-out ex-
cept for a bottom return.
3. Installation of locking-type dampers are recommended in
all branches, or in individual ducts to balance system's air
flow.
4. Non-combustible, flexible duct connectors are recom-
mended for return and supply connections to furnace.
5. If air return grille is located close to the fan inlet, install at
least one, 90 ° air turn between fan and inlet grille to reduce
noise.
NOTE: To further reduce noise, install acoustical air turning vanes
and/or line the inside of duct with acoustical material.
Sizing
Existing or new ductwork MUST be sized to handle the correct
amount of airflow for either heating only or heating and air condi-
tioning.
25-20-90
Filter Installation using Optional Filter Rack
When installing or removing a bottom mounted filter, slide the two
side filter clips to the back of the furnace BEFORE installing or re-
moving. This will allow the filter to clear the front raised edge of the
furnace. Insert filter into side clips first and push filter back until it is
fully engaged into back clip. When filter is in place, slide clips back
into place midway on filter as shown in Figure 35.
Bottom Mounted Filter Rack
25-24-18
Slide filter clips towards back before removin_l
Refer to Figure 36 and for guidelines to install filters. Furnaces
which require larger filter media and have limited clearances on
44001 111400

onesideoffurnace,requireastandofffilterrack,seeFigure36,
availablefromyourdistributor.
StandoffFilterRack
HHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHHH
Using Optional /_/_
Standoff FilterRack _ /
_/ I _"_
25-21-45a
Downflow Furnace Installation
Non- Combustible Floor Installation
Fabricate a plenum to the dimensions given in Table 8, for the fur-
nace outlet. Plenum should be flanged, approximately 3/4" for
support.
Note: The three(3) screws in the top panel of the furnace next to
the duct flange MUST be removed to provide serviceability of the
primary heat exchangers in the downflow installation
1. Position plenum through the floor and set the furnace over
the opening in the floor. If necessary, grout around the base
to seal air leaks between the base and the floor.
Combustible Floor Installation
FIRE HAZARD
Failure to install unit on noncombustible subbase can
result in death, personal injury and/or property
damage.
Place furnace on noncombustible subbase on
downflow applications, unless installing on non-com-
bustible flooring.
;ubbase for Combustible Floor
CAUTION
If filters are only suitable for heating application, advise
homeowner that filter size may need to be increased if air
conditioning is added.
Addition Of Air Conditioning
When a refrigeration coil is used in conjunction with this unit, it
must be installed on the discharge side of the unit to avoid con-
densation on the heat exchanger. The coil installation instructions
must be consulted for proper coil location and installation proce-
dures. With a parallel flow arrangement, dampers must be
installed to prevent chilled air from entering the furnace. If manu-
ally operated dampers are used, they must be equipped with a
means to prevent operation of either unit unless the damper is in
full heat or full cool position.
A 3" clearance is required on the right side of the furnace in order
to run the condensate drain line. Copper, iron or plastic tubing
may be used for the condensate drain line.
NOTE: The three(3) screws in the top panel of the furnace next to
the duct flange MUST be removed to provide serviceability of the
primary heat exchangers in the downflow installation
Note: When using the subbase for combustible floors, the dis-
charge air duct flanges on the furnace MUST be broken down to
provide proper fit up to the subbase. Use duct pliers to bend the
duct flanges flat onto the furnace casing. DO NOT bend the duct
flanges inward (toward the heat exchangers) as air flow restric-
tions may occur.
The Subbase for Combustible Floors MUST be used when a
downflow furnace is set on a combustible floor, even when the fur-
nace is installed on a coil box.
1. Cut the opening in the floor according to Table 8. The hole
in the floor must be cut to the dimensions listed in Table 8
since the base is equipped with locating tabs that center the
base over the opening.
The opening in the base is 11/4" shorter and 11/8" narrower than
the recommended size of the opening in the floor. This is done to
maintain clearance between the floor and the plenum.
2. Fabricate the plenum to the dimensions given in Table 8.
Note that the dimensions given are outside dimensions.
E_ 44001 111400

ubbases,orCombus.bleF,oorsD,mens,ons
iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii
Subbase for Combustible
Floors Part Number
Furnace Subbase
NAHHOOISB
NAHHOO2SB
NAHHOO3SB
NAHHOIOSB
Subbase for Coil Cabinets
NAHHOO4SB
NAHHOO5SB
NAHHOO6SB
NAHHOO9SB
Outside Dimension
_ Base Spacer Side To Side
3.
Set the base over the opening in the floor, centering it over
the opening. Fasten the base to the floor with screws or
nails. See Figure 37, Figure 38 and Figure 39.
Subbase for Combustible
Floor Dimensions
H*
1511/16
195/16
225/16
24J/4
15]]/16
195/16
23
24]]/16
J_ K**
283/4 149/16 16
283/4 183/16 16
283/4 2113/16 16
28J/4 23u/16 16]/4
20u/16 14u/16 16]/4
209/16 183/16 161/4
209/16 2113/16 161/4
20u/16 23u/16 16
Opening In Floor
M N
161/4 145/8
16114 18114
161/4 21 t/8
161/4 23b/8
161/4 145/8
161/4 181/4
161/4 21 t/8
161/4 23_/8
Opening In Base
For Plenum
P R
15 131/2
15 171/8
15 193/4
15 221/2
15 13]/2
15 171/8
15 193/4
15 22]/2
Coil Cabinet Subbase
Typical Plenum
Dimensions
S T
15 131/2
15 171/8
15 193/4
15 221/2
15 131/2
15 171/8
15 193/4
15 221/2
Furnace Subbase
s
Plenum
Combustible
Floor Base
A - 4 1/4" Minimum clearance from back of hole
to wall or other obstruction.
4,
Drop the plenum through the opening in the base. The
flange of the plenum should rest on top of the subbase.
5.
Position furnace or coil cabinet and furnace on subbase so
it aligns between the locating tabs.
25-20-46
Plenum
Combustible
FloorBase
/
i
Wood c o;
This subbase for combustible floors has been designed so that
the height of the subbase raises the downflow coil off the floor to
allow easy installation of the condensate drain. See Figure 40.
44001 111400 [_

Condensate Line Raised by Base
8. Checks and Adjustments
25-20-52
Startup
NOTE: Refer to the start-up procedures in the "User's Informa-
tion Manual' or to the "Operating Instructions Label' on the fur-
nace.
CAUTION
If any sparks, odors or unusual noises occur, immediately
shut OFF power to furnace. Check for wiring errors or
obstruction to blower.
GasSupplyPressure
Gas supply pressure should be within minimum and maximum
values listed on rating plate. Pressures a re usually set by gas sup-
pliers.
Manifold Gas Pressure Adjustment
NOTE: Make adjustment to manifold pressure with burners oper-
ating.
FIRE OR EXPLOSION HAZARD
Failure to turn OFF gas at shut off before connecting
manometer can result in death, personal injury and/or
property damage.
Turn OFF gas at shut off before connecting manometer.
Pilot Burner
10-11-65
Main BurnerFlameCheck
Allow the furnace to run approximately 10 minutes then inspect
the main burner and pilot flames. See Figure 42.
Check for the following (Figure 42):
• Stable and blue flames. Dust may cause orange tips or
wisps of yellow, but flames MUST NOT have solid, yel-
low tips.
• Flames extending directly from burner into heat ex-
changer.
• Flames do NOT touch sides of heat exchanger.
If any problems with main burner flames are noted, it may be nec-
essary to adjust gas pressures, or check for drafts.
1. Remove the burner compartment door.
Main Burner
2. With gas OFF, connect manometer to tapped opening on
gas valve. Use manometer with a 0 to 15" water column
range.
3. Turn gas ON and remove adjustment screw cover on gas
valve. Turn counterclockwise to decrease pressure and
clockwise to increase.
4. For altitudes up to 2000', set pressure to value shown in
Table 6, 0.3 (8mm) water column. For altitudes of 2000'
to 8000', see Section 5 for correct pressure setting.
10-10-78
Adjust Pilot Burner
The furnace has a pilot flame to light the main burner. The flame
should surround 3/8" to 1/2" of the flame sensor. See Figure 41. To
adjust, remove cap from pilot adjusting screw on gas valve. Turn
screw counterclockwise to increase or clockwise to decrease
flame as re uired. Re lace adhJstin screw ca . tures.
E_ 44001 111400
Temperature Rise Check
The blower speed MUST be set to give the correct air temperature
rise through the furnace as marked on the rating plate. Tempera-
ture rise is the difference between supply and return air tempera-

Tochecktemperaturerise,usethefollowingprocedure:
1. Placethermometersinsupplyandreturnairregistersas
closetofurnaceaspossible,avoidingdirectradiantheat
fromheatexchangers.
2. Operatefurnacecontinuouslyfor15minuteswithallregis-
tersandductdampersopen.
3. Takereadingandcomparewithrangespecifiedonrating
plate.
4. IfthecorrectamountoftemperatureriseisNOTobtained,it
maybenecessarytochangeblowerspeed.Ahigherblow-
erspeedwilllowerthetemperaturerise.Alowerblower
speedwillincreasethetemperaturerise.
Changing Blower Speed
ELECTRICAL SHOCK HAZARD
Failure to do so can result in death and/or personal
injury.
Turn OFF power to furnace before changing speed taps.
NOTE: The speed taps that the manufacturer sets from the facto-
ry for this product are based on a nominal 400 CFM per ton cool-
ing and the basic mid range on the temperature rise for heating.
Since the manufacturer cannot establish the static pressure that
will be applied to the unit, it is the responsibility of the installer
dealer/contractor to select the proper speed taps for the applica-
tion when the unit is installed.
If it is necessary to change speeds, refer to steps below.
1. Refer to Furnace WiringDiagramfor location of the heating
and cooling speed taps located on the electronic fan control
as well as location of unused blower motor speed leads.
Use the chart (Table 9) to determine the blower motor
speed settings.
i;iiii ii ii ii ii ii ii ii ii ii ii ii ii ii ii ii ii ii
* Med-High speed may not be provided on all models.
_iiiii:! Blower Speed Chart
Wire Color
Black
Orange*
Blue
Red
Motor Speed
High
Med-High
Medium
Low
Change the heat or cool blower motor speed by removing
the motor lead from the "Heat" or "Cool" terminal and re-
place it with the desired motor speed lead from the "Un-
used Motor Lead" location. Connect the wire previously
removed from the "Heat" or "Cool" terminal to the vacated
"Unused Motor Lead" terminal.
If the same speed must be used for both heating and cool-
ing, remove the undesired motor speed lead from the
"Heat" or"Cool" terminal and connect that lead to the open
terminal at "Unused Motor Lead" location. Attach a jump-
er between the "Heat" and "Cool" terminals and the re-
maining motor speed lead.
Note: For motors with (4) speed leads, it will be necessary
to tape off the terminal of the motor speed lead removed
from the "Heat" or "Cool" terminal with electrical tape since
an open terminal will not be available at the "Unused Mo-
tor Lead" location.
Continuous Fan Operation
A terminal is provided on the electronic fan control located in the
circulating blower compartment for operation of the continuous
fan option. This connection is intended for the low speed motor
tap, and has a lower contact rating (8 amps) than the heat and
cool taps. When the low speed blower lead is connected to this
terminal, this will provide low speed blower operation whenever
the other two speeds (Heat or Cool) are not energized.
Thoroughly check the system after modification to ensure the
proper operation of the circulating air blower in all modes of opera-
tion.
Separate speed selections for Heat, Cool, and
Continuous Fan
Connect low speed lead from circulating motor to the "Cont." ter-
minal at the electronic fan control. The appropriate motor leads
should already be connected to the "Heat" and "Cool" terminals.
HeatingandContinuousBlowerSpeedthe
Same
If it is necessary to operate the heating speed and continuous
blower speed using the same blower speed, connect ajumper be-
tween the "Heat" and "Cont." terminals on the electronic fan con-
trol.
Note: There should be only ONE motor lead going to the "Heat"
and "Cont." terminals.
9. Furnace Maintenance
CAUTION
It is recommended that the furnace be inspected and
serviced on an annual basis (before the heating season) by a
qualified service technician.
44001 111400 [_
See "User "s Information Manual" and the "Service Manual".

10. Sequence of Operation & Diagnostics
The following is the normal operating sequence for the control system.
Cooling (¥) Request:
24 VAC signals applied to Y & G terminals of EFT (electronic fan timer) control.
• Cool motor speed energized after 6 second Cool Fan On Delay time.
Y & G signals removed from EFT.
• Cool motor speed de-energized after 60 second Cool Fan Off Delay time.
Circulating Fan (G) Request:
24 VAC signals applied to G terminals of EFT control.
• Heat motor speed energized without delay.
G signal removed from EFT.
• Heat motor speed de-energized without delay.
Heating (W) Request:
24 VAC signals applied to W terminal of EFT control.
• Inducer motor turns on.
• The gas valve solenoid energizes.
• Following a 3 second prepurge delay, the pilot valve opens and the ignitor begins to warm up.
• After the pilot lights, the main burners energize and light.
• Timed from the opening of the main gas valve, the control will delay 30 seconds before switching the fan to Heat speed.
W signal removed from EFT.
• The gas valve de-energizes and the main burners go out.
• The inducer runs at its present speed for a 30 second postpurge period.
• Timed from the gas valve de-energizing, the Heat fan speed de-energizes after the selected Heat Fan Delay time expires.
Heating Request with Gas Supply Line Shut Off:
24 VAC signals applied to W terminal of EFT control.
• Inducer motor turns on.
• The gas valve solenoid energizes.
• Following a 3 second prepurge delay, the pilot valve opens and the ignitor begins to warm up.
• The ignitor glows red-hot for 30 seconds, then turns off.
• The igniter stays off for 25 seconds, then begins to warm-up again.
• The igniter glows red-hot for 30 seconds, then turns off.
• The pilot valve closes 3 seconds after the igniter de-energizes.
• The inducer de-energizes 5 seconds after the pilot valve closes.
• The SmartValve proceeds to soft lockout and flashes error code 6.
• The control exits soft lockout after 5 minutes and begins
another ignition sequence.
Gas Valve Diagnostic Codes (See Figure 43)
OFF = Control not powered
Heartbeat = Normal Operation (Standby or call for heat)
1 Flash = Not used
2 Flashes = Pressure switch closed when should be open
3 Flashes = Pressure switch circuit was still sensed as open 30 seconds after the inducer was energized. System is
in 5 minute delay mode, with inducer off. After 5-minute delay, a new ignition sequence will be initiated.
(Note: SV9541M On/Off switch in off position during a call for heat will generate this diagnostic code)
4 Flashes = Limit switch string open
5 Flashes = Flame sensed out of sequence - Flame signal still present.
6 Flashes + 1 Note 1 = Soft Lockout -Maximum retry count exceeded (failed to light within 4 trials for ignition)
6 Flashes + 2 Notes 1,2 = Soft Lockout -Maximum recycle count exceeded - Last failure was Flame Sense Lost During Run
6 Flashes + 3 Notes 1,2 = Soft Lockout -Maximum recycle count exceeded - Last failure was Airflow Proving Circuit Opened
During Run
6 Flashes + 4 Notes 1,2 = Soft Lockout -Maximum recycle count exceeded - Last failure was Limit Circuit Opened During Run
7 Flashes = Soft Lockout Due to Limit Trips Taking Longer than 2 minutes to Reset; Auto Reset After 1 Hour if
Call for Heat Still Present. Reset by Cycling Call for Heat at Any Time.
NOTE 1: The 6 + X designation indicates a combination of flash codes: 6 flashes shows the control is in soft lockout, followed by X flashes
[_ 44001 111400

to indicate the reason the control went into soft lockout. When the 6+ X code is flashing, the SV9541 will attempt a new ignition sequence
after a five minute delay period, if the call for heat is still present. Reset of the thermostat will initiate a new ignition sequence immediately.
NOTE 2: Any combination of 5 'abnormal' events during a single call for heat will result in soft lockout. An 'abnormal' event is a Flame
Sense Failure During Run, Airflow Proving Circuit Open During Run, or Limit Circuit Open During Run. The flash code will indicate which
was the last 'abnormal' event that put the system into the soft lockout state based on the table above.
Typical Gas Valve Honeywell
Pilot Pressure
Adjustment
On\Off
Switch
Diagnostic Light
OUTLET
INLET
Manifold Pressure
Adjustment
dwg 25-23-31a
44001 111400 [_

HONEYWELL SV9541M "SMART VALVE" Sequence of Operation
IPOWERAPPLIEDTO APPLIANCE
+
I THERMOSTATCALLS FORHEAT
I
¢
IPRESSURE SWITCHES PROVED OPEN?
ICOMBUSTIONBLOWER ENERGIZED
WAIT FORPRESSURESWITCHESTOOPEN
PRESSURESWITCHESCLOSEDWITHIN30 SEC-
ONDS?
_._ COMBUSTIONBLOWERDE-ENERGIZED
+
I 3SECONDPRE-PURGE
PILOTVALVEOPENS:
IGNITORPOWERED(1)
PILOTLIGHTSAND FLAME ISSENSED l'_Vl
DURING 90 SECOND TRAILFOR
IGNITION?
I YES
MAINVALVEOPENS,
HEATINGFAN"ON" DELAYBEGINS
+
IAFTERDELAY:CIRCULATINGBLOWERSTARTS I
FLAME SENSE LOST? I I
I
FAILURERECYCLEDELAY
THREESECONDFLAME ,J_
PILOTVALVE CLOSES;
PILOTIGNITOROFF
YES
PILOTAND MAINVALVECLOSE 1
J__ FIVEMINUTEWAITPERIOD
r
CIRCULATINGBLOWEROFF AFTER DELAY
+
THERMOSTATCALL FORHEAT ENDS
NO
PILOTAND MAINVALVECLOSE
+
COMBUSTIONBLOWER DE- ENERGIZEDAFTER30
SECONDPOST PURGE
+
ICIRCULATINGBLOWEROFFAFTER DELAY
I
I WAITFOR NEXTCALL FORHEAT
I
[_ 44001 111400
L FLAMESENSELOST MORETHAN FIVETIMESIN THIS CALL FORHEAT?
YES
(1) Ignitor "ON" for first 30 seconds of trial for ignition, then "OFF" for next 30 seconds. If the pilot has
not lit, it turns back "ON" for the final 30 seconds. The pilot valve remains energized during the entire
90 second trial for ignition.
NOTE: If main limit string opens and takes longer than 2 minutes to close, system goes into I hour wait
period.
I
COMBUSTIONAIRBLOWEROFF AFTERPOST
PURGE
NO

HONEYWELL SV9541M "SMART VALVE" Trouble shooting
The 6 + X designation indicates a combination of flash codes: 6 flashes shows the control is in soft lockout, followed by X flashes to
indicate the reason the control went into soft lockout. Last status code indicates repair to address first
LED
STATUS
Off No power to system control. Low voltage (24V) power at 24 VAC and COM terminals on ST9160B
Heartbeat Normal indication whenever the system is powered, unless some
Bright - Dim abnormal event has occurred. Net Applicable - Normal Operation (stand by or call for heat)
2 Flashes (i.e. when call for heat begins), open).
3 Flashes
4 Flashes
5 Flashes
6 Flashes+
1Flash
INDICATES CHECK/REPAIR
Line voltageinput at L1 and Neutral connectors on ST9160B FanTimer.
System wiring harness is in good condition and securely connected.
Pressure switches closed when it should be open Pressure switches stuck closed (system will wait for pressure switch to
(Combustion blower is not energized until pressure switches
opens) Pressure switches miswired erjumpered.
Pressure switches, openwhen they should be closed (i.e.longer
than 30 seconds after combustion blower/inducer is energized).
System goes into 5-minute delay period, with combustion blower/
inducer off. Atend ofthe 5-minute delay, another cycle will begin.
Main Limit or Roll Out Switch is open.
Combustion blower is energized, Circulating blower is energized
heat speed.
Flame signal sensed out of proper sequence.
Combustion blower is energized, Circulating blower is energized
heat speed after the "ON" delay.
Soft Lockout.
Failed to light pilot during 90 sec. trial for ignition
Combustion air blower is de-energized, Circulating blower isde-
energized after the "OFF" delay.
After 5-minute delay time, control system will reset and initiate a
new ignition sequence,
Ignition system control switch must be in the ON position.
Pressure switches operation, tubing, and wiring.
Restrictions in furnace air intake or vent piping.
Main limit switch.
Manual reset burner rellout switch.
Limit and rellout switch wiring is ingood condition and securely
connected.
Flame at pilot burner.
Gas supply off or pressure too low or high for appliance to operate.
Damaged or broken HIS element
Line voltage HOT leadwire not connected to L1 terminal on ST9160B.
Furnace not properly earth grounded.
Flame sense rod contaminated or in incorrect position.
Pilot burner located in incorrect position.
Pilot burner lead wires are in good condition and popery connected.
Pressure switches operation, tubing, and wiring.
SoftLockout.
Gas supply off orpressure too low or high for appliance to operate.
Line voltage HOT leadwire not connected to L1 terminal on ST9160B.
Furnace not properly earth grounded.
Flame sense rod contaminated or in incorrect position.
Pilot burner located in incorrect position.
Pilot burner lead wires are in good condition and properly connected.
Cycling, pressure switch
Condensate drain blocked
Pressure switches operation, tubing, and wiring.
6 Flashes+
2 Flashes
Last failure was Flame Sense lost during run.
Maximum recycle count exceeded
Combustion air blower is de-energized, Circulating blower is
de-energized after the "OFF" delay.
After 5-minute delay time, control system will reset and initiate a
new ignition sequence,
44001 1114O0 [_

HONEYWELL SV9541M "SMART VALVE" Trouble shooting continued
LED
STATUS
6 Flashes+
3 Flashes
INDICATES CHECK/REPAIR
Soft Lockout.
Last failure was pressure switch
Ignition system control switch must be in the ON position.
Maximum recycle count exceeded
Combustion air blower is de-energized, Circulating blower isde-
energized after the "OFF" delay.
After 5-minute delay time, control system will reset and initiate a
new ignition sequence,
Soft Lockout.
Pressure switches operation, tubing, and wiring.
Restrictions in furnace air intake or vent piping.
High winds blowing against vent.
Last failure was limit circuit opened during run.
6 Flashes+
4 Flashes
Combustion air blower is de-energized, Circulating blower is
de-energized after the "OFF" delay.
After 5-minute delay time, control system will reset and initiate a
new ignition sequence,
Soft Lockout.
Blowerfailure(typical)
7Flashes
Limittriptooklongerthan2 minutestoreset.
System will start a new ignition sequence after 1 hour, if call for
heat still present.
11. Concentric Termination
Vent Termination Clearances
CARBON MONOXIDE POISONING, FIRE AND EXPLO-
SION HAZARD
Failure to properly vent this furnace can result in
death, personal injury and/or property damage.
Inlet and outlet pipes may NOT be vented directly
above each other (standard vent terminals).
1. Determine termination locations based on clearances spe-
cified in following steps and as shown in Figure 7,
Figure 44 through Figure 49.
2. The vent termination must be located at least 12" above
ground or normally expected snow accumulation levels.
3. Do NOT terminate over public walkways. Avoid areas
where condensate may cause problems such as above
planters, patios, or adjacent to windows where steam may
cause fogging.
Main limit switch.
Limit and rollout switch wiring is ingood condition and securely
connected.
Restriction in duct work.
Dirty filter
Deadblower.
Blockedductwork.
4. The vent termination shall be located at least 4' horizontally
from any electric meter, gas meter, gas regulator, and any
relief equipment. These distances apply ONLY to U.S.
installations.
5. The vent termination is to be located at least 3' above any
forced air inlet located within 10' ; and at least 10' from a
combustion air intake of another appliance, except another
direct vent furnace intake.
6. In Canada, the Canadian Fuel Gas Code takes prece-
dence over the preceding termination instructions.
Concentric Vent Termination - Kit #
NAHA001CV& NAHA002CV
These kits are for vertical or horizontal termination of the combus-
tion air inlet and the exhaust vent pipes on Category IV gas-fired
condensing furnaces. The NAHAO01CV kit can be used for 3" di-
ameter pipe systems. The NAHAOO2CV kit can be used for 2"
diameter pipe system. Refer to Table 10 for the correct pipe size
for the furnace. Both the combustion air inlet and the exhaust vent
pipes must attach to the termination kit. The termination kit must
terminate outside the structure and must be installed per the
instructions outlined below for vertical or horizontal termination.
[_ 44001 111400

Verticalterminationispreferred.Fieldsuppliedpipeandfittings
arerequiredtocompletetheinstallation.
Kit Components
Kit Contents:
3" Rain Cap or 2" Rain Cap
3;;DiameterSDR-26 Pipe,191/2;;Long or
4 DiameterSDR-26 Pipe,371/8, Long,
2 DiameterSDR-26 Pipe,315/8 Long or
21/2"DiameterSDR-26 Pipe,24" Long,
3" Y Concentric Fittingor 2" Y ConcentricFitting
3"or4"Dia.
SDR-26Pipe
13/16"
{t :::i ;{i {}}i{
Concentric Vent Dimensional
Drawing
BPVC
\Ven haustI
11/2"
25-22-03
2" or3" Dia. 2 or 21/2"Dia.
¥ ConcentricFitting SDR-26Pipe
2"or3" Dia.
RainCap
25-22-03
Vertical & Horizontal Termination
1. Determine the pipe diameters required for the installation
from Table 10 and Table 11 and Figure 46.
2. Determine the best location for the termination kit. See
Figure45 for vertical termination or Figure 45 and
Figure 49 for horizontal termination. Roof termination is
preferred since it is less susceptible to damage, has re-
duced intake contaminants and less visible vent vapor. For
side wall termination, consideration should be given to: 1)
possible damage from the vapors to plants/shrubs, other
equipment and building materials, 2) possible damage to
the terminal from foreign objects, 3) wind effects that may
cause recirculation of flue products, debris or light snow
and 4) visible vent vapor.
3. Cut one 5" diameter hole through the structure for the
NAHA001CV Kit or one 4" diameter hole for the
NAHA002CV Kit.
4. Dimension D may be lengthened to 60" max. or shortened
by cutting the pipes to 12" min. Dimension A will change ac-
cording to D dimension. (See Figure 46)
Concentric Vent Roof Installation
Vent /_ Maintain12"min.clearanceabove
_Y
highestanticipatedsnowlevel.Max.
of24"aboveroof.
Combustion
Air
Roof Boot/
Flashing
Model A* B C D**
NAHAO01CV 38z/8 3 41/2 211/8
NAHAOO2CV 33s/8 2 31/2 16//8
= Dimension will change accordingly as dimension D is
lengthened or shortened.
_ = Dimension D may be lengthened to 60" may also be
shortened by cutting the pipes provided in the kit to 12"
minimum
i ' ;: ; Concentric Termination Kit
_bI_ 0 , NAHA001CV & NAHA002CV Venting
Table for *9MPD Models
50,000, 75,000 & 80,000 Btuh Furnaces
NAHAOO2CV - 35' & (4) 90° elbows with 2" PVC pipe or
NAHAOOICV - 65' & (4) 90° elbows with 3" PVC pipe
100,000 Btuh Furnace
NAHAOOICV - 35' & (4) 90° elbows with 3" PVC pipe or
NAHAOOICV - 65' & (4) 90° elbows with 3" PVC pipe &
Long Vent Kit (See Tech. Manual)
125,000 Btuh Furnace
NAHAOOICV - 35' & (4) 90 ° elbows with 3" PVC pipe
1. Do not include the field supplied 45 ° elbow in the total elbow
count,
2. If more than four elbows are required, reduce the length of
both the inlet and the exhaust pipes five feet for each
additional elbow used.
3, Elbows are DWV long radius type for 2" and 3" vents,
NOTE: Feet of pipe is whichever pipe run is the longest, either
inlet or outlet side,
Support
(Field Supplied)
(Field Supplied)
Vent
Combustion
Air 25-22-02
Note:
SUDDort must be field installed to secure termination kit to structure.
//
44001 111400 [_

Concentric Termination Kit
NAHA001CV & NAHA002CV Venting
.... Table for N9MP2 Models
50,000 & 80,000 Btuh Furnaces
NAHA002CV - 35' & (4) 90° elbows with 2" PVC pipe or
NAHA001CV - 65' & (4) 90° elbows with 3" PVC pipe
75,000 Btuh Furnaces
NAHA002CV - 20' & (2) 90° elbows with 2" PVC pipe or
NAHA002CV - 35' & (4) 90° elbows with 2" PVC pipe &
Long Vent Kit (See Tech. Manual) or
NAHA001CV - 65' & (4) 90° elbows with 3" PVC pipe
100,000 Btuh Furnace
NAHA001CV - 35' & (4) 90° elbows with 3" PVC pipe or
NAHA001CV - 65' & (4) 90° elbows with 3" PVC pipe &
Long Vent Kit (See Tech. Manual)
125,000 Btuh Furnace
NAHA001CV - 35' & (4) 90° elbows with 3" PVC pipe
1. Do not include the field supplied 45° elbow in the total elbow
count,
2. If more than four elbows are required, reduce the length of
both the inlet and the exhaust pipes five feet for each
additional elbow used.
3. Elbows are DWV long radius type for 2" and 3" vents,
NOTE: Feet of pipe is whichever pipe run is the longest, either
inlet or outlet side,
If assembly needs to be extended to meet height or side wall
thickness requirement, the two pipes supplied in the kit may be
replaced by using the same diameter solid, single (no coupling
connections) field supplied SDR-26 PVC (ASTM D2241) pipes.
Do not extend dimension D more than 60". (See Figure 46)
Do not use field supplied couplings to extend the pipes.
Airflow restriction will occur and the furnace pressure
switch may cause intermittent operation.
Partially assemble the concentric vent termination kit.
Clean and cement the parts using the procedures for Join-
ing Pipe and Fittings section of the manual. A) Cement the
Y Concentric fitting to the 4" diameter kit pipe. (See
Figure 47) B) Cement the 3" rain cap to the 21/2 " diameter
kit part. (See Figure 47) NOTE: A field supplied stainless
steel screw may be used to secure the rain cap to the pipe
instead of cementing when field disassembly is desired for
cleaning (See Figure 47)
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in death,
personal injury and/or property damage.
When using the alternate screw assembly method, drill a
clearance hole in the rain cap and a pilot hole in the vent
pipe for the screw size being used. Failure to drill
adequate holes may cause cracking of the PVC
components, allowing flue gases to be recirculated.
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in death,
personal injury and/or property damage.
Do not operate the furnace with the rain cap removed as
recirulation of the flue gases may occur. Water may also
collect inside the larger combustion air pipe and flow to
the burner enclosure.
Install the Y concentric fitting and the pipe assembly
through the structure's hole. For vertical termination, install
the parts through the field supplied roof boot/flashing.
NOTE: Do not allow insulation or other materials to accu-
mulate inside the pipe assembly when installing through
the structure's hole.
Secure the assembly to the structure as shown in
Figure 45 or Figure 49 using field supplied metal strap-
ping or equivalent material.
NOTE: Ensure the termination height is above the roof sur-
face or anticipated snow level as shown in Figure 45 for
vertical termination. Ensure the termination location clear-
ance dimensions are as shown in Figure 48 and Figure 49
for horizontal termination.
Concentric Vent and Combustion-
Air Side Termination
Roof Overhang
Rain Cap to Vent Pipe Assembly
Drill clearance hole in rain
cap and pilot hole in vent pipe.
Maintain 12" clearance above highest antici-
Stainless steel screw
(Field supplied)
[_ 44001111400
pated snow level or grade whichever is great-
er. 25-22-02

Concentric Vent Sidewall
Attachment
Strap
(Field Supplied) _,_////_ Combustion
\ Air
Vent
Combustion _ _ _///,//_
Air 45° Elbow _/////_
Note:
Securing strap mustbefieldinstalledtoprevent movementofterminationkitinsidewall.
(Field Supplied) 25-22-02
8. Install the rain cap and the small diameter pipe assembly in
the Y concentric fitting and the large pipe assembly. Ensure
that the small diameter pipe is bottomed out and securely
cemented in the Y concentric fitting.
9. Cement the furnace combustion air and vent pipes to the
concentric vent termination assembly. See Figure 45 or
Figure 49 for proper pipe attachment.
10. Operate the furnace through one heat cycle to ensure com-
bustion air and vent pipes are properly connected to the
concentric termination connections.
44001 1114O0 [_

[_ 440011114O0

Four Position Furnace
Models
Single Pipe
N9MP1050B12A4
N9MP1075B12A4
N9MP1080F16A4
N9MP1100F14A4
N9MP1100J 20A4
N9MP1125 J20A4
Two Pipe
N9MP2050B12A4
N9MP2075B12A4
N9MP2080F16A4
N9MP2100F14A4
N9MP2100J20A4
N9MP2125J20A4
or
or
Dual Certified
*9MPD050F12A4
*9MPD075F12A4
*9M PD080J 16A4
25-23-30
*9MPD100J14A4
*9MPD100J20A4
*9MPD125L20A4
_Denotes Brand
Manufactured by:
International Comfort Products Corporation (USA)
Lewisburg, TN USA 37097
Save This Manual For Future Reference
44001 111400 [_

ManufacturersNumber (Mfr No -See Rating Plate) ALL Models
Specifications (N9MP1)
NgMP1050B12A N9MP1075B12A
General
GasType Nat./LP Nat./LP Nat./LP Nat./LP
Input(Btuh) 80,000 100,000 100,000 125,000
Output(Btuh) 72,000 91,000 96,500 113,750
Transformer Size (VA) 40 40 40 40
T'stat HeatAnticipator .10 .10 .10 .10
Temp.Rise(F) 35-65 40-70 40-70 40-70
Electrical(Volts/Hz/FLA) 11516019.0 115/60/9.0 115/60110.5 115/60/11.2
Gas& Ignition
GasType Nat. L.P. Nat. L.E Nat. LP. Nat. L.E
GasValve HWSV9541M HWSV9541M HW SV9541M HWSV9541M
RegulationType SNAP SNAP SNAP SNAP
IgnitionTypeISeries HWHSP HWHSP HW HSP HWHSP
ManifoldPress.(Inch'sWC) 3.5 I0.0 3.5 I0.0 3.5 10.0 3.5 I0.0
Std.MainOrifices (NoISize) 4144 4155 4146 4154 4142 4154 5142 5154
PilotOrificeSize .018 .011 .018 .011 .018 .011 .018 .011
Nat./LP Nat./LP
50,000 75,000
45,500 68,000
40 40
.10 .10
35-65 40-70
11516019.8 11516018.9
Nat. L.P. Nat. LE
HWSV9541M HWSVg541M
SNAP SNAP
HWHSP HWHSP
3.5 10.0 3.5 10.0
2142 2154 3142 3154
.018 .011 .018 .011
FanControls
FanControl(Type) HWST9160 HWST9160 HW ST9160 HWST9160
FanControl On 30 30 30 30
(Timed-secs) Off 60,100,140,180 60,100,140,180 60,100,140,180 60,100,140,180
HWST9160 HWST9160
30 30
60,100,140,180 60,100,140,180
Combustion
Flue Outlet Size (Inches) 2 3 3 3
Std. Outlet Temp (°5' No Elbows) <140 <140 <140 <140
2 2
<140 <140
BlowerPressure 5' No Elbows (" WC)
BlowerPressure40' +5-90 ° DWV Elbows (" WC)
Transition Bx Pressure 5' No Elbows (" WC)
TransitionBx Pressure 40' +5-90 ° DWV Elbows (" WC)
Limits & Controls
Rollout Switch (F)
Limit Control Setting (F)
Standard Pressure Sw. (Part No)
Blower Switch Pressure (Close) (" WC)
Blower Switch Pressure (Open) (" WC)
Transition Switch Pressure (Close) (" WC)
Transition Switch Pressure (Open) (" WC)
High Altitude Pressure Sw. (Part No)
Blower Switch Pressure (Close) (" WC)
Blower Switch Pressure (Open) (" WC)
Transition Switch Pressure (Close) (" WC)
Transition Switch Pressure (Open) (" WC)
-2.6 -2.6
-2.3 -2.3
300 300
240 210
1013802 1013802
-2.2 -2.2
-2.0 -2.0
1013803 1013803
-2.0 -2.0
-1.8 -1.8
Long Vent Kit (Part No)
Pressure Switch (Part No)
Blower Switch Pressure (Close) (" WC)
Blower Switch Pressure (Open) (" WC)
Transition Switch Pressure (Close) (" WC)
Transition Switch Pressure (Open) (" WC)
High Altitude Long Vent Kit (Part No)
Pressure Switch (Part No)
Blower Switch Pressure (Close) (" WC)
Blower Switch Pressure (Open) (" WC)
Transition Switch Pressure (Close) (" WC)
Transition Switch Pressure (Open) (" WC)
Blower Data
Type& Size
MotorAmpsIRpm
MotorTypelH.p.
Cap.MfdNolts
FilterType&Size (Permanent- notsupplied)
CoolCap. (Tons)@ .5" W.C. L, ML,MHi& Hi
11-8 11-8
10/850 8.0/1050
PSC/1/2 PSC/112
7.51370 7.51370
16x25x1 16x25x1
1112,2,21/2,3 11/2,2,2112,3
GasConversion Kits
Natto LP
LPto Nat
NAHF002LP(*1009509)
NAHF002NG(*1009510)
_Order from Service Parts
N9MP1080F16A N9MP1100F14A NgMP110OJ20A N9MP1125J20A
-2.6
-2.5
300
230
1013811
-1.8
-1.7
-2.6
-2.5
300
230
1013801
-1.8
-1.7
-2.6
-2.5
300
220
1013802
-1.8
-1.7
-2.6
-2.5
300
190
1013166
-1.3
-1.1
-1.8
-1.6
1013812
-2.3
-2.1
1013803
-2.2
-2.0
1013803
-1.8
-1.6
1013157
-0.9
-0.7
-1.5
-1.3
-2.0
-1.8
NAHAO01LV
1013518
-1.0
-0.8
-2.0
-1.8
-2.0
-1.8
NAHA002LV
1013515
-1.0
-0.8
-1.7
-1.5
-1.7
-1.5
NAHA003LV
1013165
-0.7
-0.6
-1.4
-1.2
11-10
10/1050
PSC/112
101370
16x25x1
21/2,3,3112,4
NAHF003LP
C1013815)
11-10
10/1050
PSC/1/2
10/370
16x25x1
1112,2,3,3112,
11-10
131900
PSC/314
40/370
16x25x1
31/2,4,4112,5
NAHF002LP(*1009509)
NAHF002NG(*1009510)
11-10
13/900
PSC/314
40/370
16x25x1
31/2,4,4112,5
NAHF003NG
C1013816)
44001 111400

Manufacturers Number (Mfr No -See Rating Plate) ALL Models
Specifications (N9MP2)
N9MP2050B12A N9MP2075B12A
General
GasType Nat./LP Nat./LP Nat./LP Nat./LP
Input(Btuh) 80,000 100,000 100,000 125,000
Output(Btuh) 72,000 91,000 96,500 113,750
Transformer Size (VA) 40 40 40 40
T'stat HeatAnticipator .10 .10 .10 .10
Temp.Rise(F) 35-65 40-70 40-70 40-70
Electrical(Volts/Hz/FLA) 115/6019.0 115/60/9.0 115/60110.5 115/60/11.2
Gas& Ignition
GasType Nat. L.P. Nat. L.E Nat. LP. Nat. L.E
GasValve HWSV9541M HWSV9541M HW SV9541M HWSV9541M
RegulationType SNAP SNAP SNAP SNAP
IgnitionTypelSeries HWHSP HWHSP HWHSP HWHSP
ManifoldPress.(Inch'sWC) 3.5 I0.0 3.5 I0.0 3.5 10.0 3.5 I0.0
Std.MainOrifices (NolSize) 4144 4155 4142 4154 4142 4154 5142 5154
PilotOrificeSize .018 .011 .018 .011 .018 .011 .018 .011
Nat./LP Nat./LP
50,000 75,000
45,500 68,000
40 40
.10 .10
35-65 40-70
11516019.8 11516018.9
Nat. L.P. Nat. LE
HWSV9541M HWSVg541M
SNAP SNAP
HWHSP HWHSP
3.5 10.0 3.5 10.0
2142 2154 3142 3154
.018 .011 .018 .011
FanControls
FanControl(Type) HWST9160 HWST9160 HW ST9160 HWST9160
FanControl On 30 30 30 30
(Timed-secs) Off 60,100,140,180 60,100,140,180 60,100,140,180 60,100,140,180
HWST9160 HWST9160
30 30
60,100,140,180 60,100,140,180
Combustion
Flue Outlet Size (Inches) 2 3 3 3
Std. Outlet Temp (°5' No Elbows) <140 <140 <140 <140
BlowerPressure 5' No Elbows (" WC)
BlowerPressure40' +5-90 ° DWV Elbows (" WC)
Transition Bx Pressure 5' No Elbows (" WC)
TransitionBx Pressure40' +5-90 ° DWV Elbows (" WC)
Limits & Controls
Rollout Switch (F)
Limit Control Setting (F)
Standard Pressure Sw. (Part No)
Blower Switch Pressure (Close) (" WC)
Blower Switch Pressure (Open) (" WC)
Transition Switch Pressure (Close) (" WC)
Transition Switch Pressure (Open) (" WC)
High Altitude Pressure Sw. (Part No)
Blower Switch Pressure (Close) (" WC)
Blower Switch Pressure (Open) (" WC)
Transition Switch Pressure (Close) (" WC)
Transition Switch Pressure (Open) (" WC)
Long Vent Kit (Part No)
Pressure Switch (Part No)
Blower Switch Pressure (Close) (" WC)
Blower Switch Pressure (Open) (" WC)
Transition Switch Pressure (Close) (" WC)
Transition Switch Pressure (Open) (" WC)
High Altitude Long Vent Kit (Part No)
Pressure Switch (Part No)
Blower Switch Pressure (Close) (" WC)
Blower Switch Pressure (Open) (" WC)
Transition Switch Pressure (Close) (" WC)
Transition Switch Pressure (Open) (" WC)
2 2
<140 <140
-- -I .8
-- -1.3
-2.6 -2.6
-2.3 -2.3
300 300
240 210
1013802 1013801
-2.2 -2.3
-2.0 -2.1
1013803 1013803
-2.0 -2.0
-1.8 -1.8
-- NAHA001LV
-- 1013518
-- -1.0
-- -0.8
-- -2.0
-- -1.8
-- NAHA003LV
-- 1013165
-- -0.7
-- -0.6
-- -I .4
-- -I .2
Blower Data
Type& Size
MotorAmpslRpm
MotorTypelH.p.
Cap.MfdNolts
FilterType&Size (Permanent- notsupplied)
CoolCap. (Tons)@ .5" W.C. L, ML,MHi& Hi
11-8 11-8
101850 8.0/I 050
PSC/I/2 PSC/II2
7.51370 7.51370
16x25x1 16x25x1
1112,2,21/2,3 11/2,2,2112,3
GasConversion Kits
Natto LP
LPto Nat
NAHF002LP(*1009509)
NAHF002NG(*1009510)
_Order from Service Parts
N9MP2080F16A N9MP2100F14A N9MP2100J20A N9MP2125J20A
-2.6
-2.5
300
230
1013811
-1.8
-1.7
-2.6
-2.5
300
230
1013801
-1.8
-1.7
-2.6
-2.5
300
220
1013802
-1.8
-1.7
-2.6
-2.5
300
190
1013166
-1.3
-1.1
-1.8
-1.6
1013812
-2.3
-2.1
1013803
-2.2
-2.0
1013803
-1.8
-1.6
1013157
-0.9
-0.7
-1.5
-1.3
-2.0
-1.8
NAHAO01LV
1013518
-1.0
-0.8
-2.0
-1.8
-2.0
-1.8
NAHA002LV
1013515
-1.0
-0.8
-1.7
-1.5
-1.7
-1.5
NAHA003LV
1013165
-0.7
-0.6
-1.4
-1.2
11-10
10/1050
PSC/II2
101370
16x25x1
21/2,3,3112,4
NAHF003LP
C1013815)
11-10
10/1050
PSC/I/2
10/370
16x25x1
1112,2,3,3112,
11-10
131900
PSC/314
40/370
16x25x1
31/2,4,4112,5
NAHF002LP(*1009509)
NAHF002NG(*1009510)
11-10
13/900
PSC/314
40/370
16x25x1
31/2,4,4112,5
NAHF003NG
C1013816)
44001 1114O0 [_

Manufacturers Number (Mfr No -See Rating Plate) ALL Models
Specifications ('_9MPD)
*gMPD05OF12A *gMPDO75F12A
General
GasType Nat./LP Nat./LP Nat./LP Nat./LP
Input(Btuh) 80,000 100,000 100,000 125,000
Output(Btuh) 73,600 92,000 92,000 115,000
Transformer Size (VA) 40 40 40 40
T'stat HeatAnticipator .10 .10 .10 .10
Temp.Rise(F) 35-65 40-70 40-70 40-70
Electrical(Volts/Hz/FLA) 11516019.0 115/60/9.0 115/60110.5 115/60/11.2
Gas& Ignition
GasType Nat. L.P. Nat. L.E Nat. LP. Nat. L.E
GasValve HWSV9541M HWSV9541M HW SV9541M HWSV9541M
RegulationType SNAP SNAP SNAP SNAP
IgnitionTypeISeries HWHSP HWHSP HW HSP HWHSP
ManifoldPress.(Inch'sWC) 3.5 I0.0 3.5 I0.0 3.5 10.0 3.5 I0.0
Std.MainOrifices (NoISize) 4144 4155 4142 4154 4142 4154 5142 5154
PilotOrificeSize .018 .011 .018 .011 .018 .011 .018 .011
Nat./LP Nat./LP
50,000 75,000
46,000 69,000
40 40
.10 .10
35-65 40-70
115/60/9.8 11516018.9
Nat. L.P. Nat. LE
HWSV9541M HWSV9541M
SNAP SNAP
HWHSP HWHSP
3.5 10.0 3.5 10.0
2142 2154 3142 3154
.018 .011 .018 .011
FanControls
FanControl(Type) HWST9160 HWST9160 HW ST9160 HWST9160
FanControl On 30 30 30 30
(Timed-secs) Off 60,100,140,180 60,100,140,180 60,100,140,180 60,100,140,180
HWST9160 HWST9160
30 30
60,100,140,180 60,100,140,180
Combustion
Flue Outlet Size (Inches) 2 3 3 3
Std. Outlet Temp (°5' No Elbows) <140 <140 <140 <140
2 2
<140 <140
BlowerPressure 5' No Elbows (" WC)
BlowerPressure40' +5-90 ° DWV Elbows (" WC)
Transition Bx Pressure 5' No Elbows (" WC)
TransitionBx Pressure40' +5-90 ° DWV Elbows (" WC)
Limits & Controls
Rollout Switch (F)
Limit Control Setting (F)
Standard Pressure Sw. (Part No)
Blower Switch Pressure (Close) (" WC)
Blower Switch Pressure (Open) (" WC)
Transition Switch Pressure (Close) (" WC)
Transition Switch Pressure (Open) (" WC)
High Altitude Pressure Sw. (Part No)
Blower Switch Pressure (Close) (" WC)
Blower Switch Pressure (Open) (" WC)
Transition Switch Pressure (Close) (" WC)
Transition Switch Pressure (Open) (" WC)
-2.6 -2.6
-2.3 -2.3
300 300
260 240
1013802 1013802
-2.2 -2.2
-2.0 -2.0
1013803 1013803
-2.0 -2.0
-1.8 -1.8
Long Vent Kit (Part No)
Pressure Switch (Part No)
Blower Switch Pressure (Close) (" WC)
Blower Switch Pressure (Open) (" WC)
Transition Switch Pressure (Close) (" WC)
Transition Switch Pressure (Open) (" WC)
High Altitude Long Vent Kit (Part No)
Pressure Switch (Part No)
Blower Switch Pressure (Close) (" WC)
Blower Switch Pressure (Open) (" WC)
Transition Switch Pressure (Close) (" WC)
Transition Switch Pressure (Open) (" WC)
Blower Data
Type& Size
MotorAmpsIRpm
MotorTypelH.p.
Cap.MfdNolts
FilterType&Size (Permanent- notsupplied)
CoolCap. (Tons)@ .5" W.C. L, ML,MHi& Hi
11-8 11-10
10/850 8.0/1050
PSC/1/2 PSC/112
7.51370 7.51370
16x25x1 16x25x1
1112,2,21/2,3 11/2,2,2112,3
GasConversion Kits
Natto LP
LPto Nat
NAHF002LP(*1009509)
NAHF002NG(*1009510)
_Order from Service Parts
*9MPDO80J16A *gMPD100J14A *9MPD100J20A *gMPD125L20A
-2.6
-2.5
3OO
22O
1013812
-1.8
-1.7
-2.6
-2.5
300
220
1013802
-1.8
-1.7
-2.6
-2.5
300
220
1013802
-1.8
-1.7
-2.6
-2.5
300
190
1013166
-1.3
-1.1
-1.5
-1.3
1013813
-2.2
-2.0
1013803
-2.2
-2.0
1013803
-1.8
-1.6
1013157
-0.9
-0.7
-1.2
-1.0
-2.0
-1.8
-2.0
-1.8
-1.7
-1.5
NAHA002LV
1013518
-1.0
-0.8
-2.0
-1.8
NAHA00SLV
1013165
-0.7
-0.6
-1.4
-1.2
11-10
10/1050
PSC/112
101370
16x25x1
21/2,3,3112,4
NAHF003LP
C1013815)
11-10
10/1050
PSC/1/2
10/370
16x25x1
1112,2,3,31/2
11-10
131900
PSC/314
40/370
16x25x1
31/2,4,4112,5
NAHF002LP(*1009509)
NAHF002NG(*1009510)
11-10
13/900
PSC/314
40/370
16x25x1
31/2,4,4112,5
NAHF003NG
C1013816)
44001 111400

CIRCULATION AIR BLOWER DATA
For 050 Models 3 Ton Units
For 080 Models 4 Ton 19" & 223/4 " Units
Speed Low Med L Med H Hi
Tap
0.1 826 1083 1301 1408
0.2 804 1050 1242 1347
m
_d
0.3 770 1028 1195 1295
0.4 735 985 1153 1237
0.5 698 952 1093 1183
0.6 657 909 1040 1118
0.7 --- 863 935 1053
lJJ
1.. m
X
0.8 .... 812 865 976
0.9 ...... 802 887
1.0 ...... 720 787
For 075 Models 3 Ton Units
Speed Low Med L Med H Hi
Tap
0.1 706 917 1163 1368
0.2 677 875 1120 1319
m
$
_d
X
0.3 636 840 1076 1263
0.4 595 812 1031 1202
0.5 546 766 987 1148
0.6 490 702 889 1077
0.7 --- 630 821 989
0.8 --- 550 750 914
0.9 --- 462 676 833
1.0 ...... 601 747
Speed Low Med L Med H Hi
Tap
0.1 823 1109 1527 1850
0.2 795 1087 1482 1791
: 0.3 747 1056 1426 1720
_ 0.4 677 1016 1382 1648
,-9 0.5 617 970 1317 1575
0.6 544 854 1245 1485
"_ 0.7 --- 763 1154 1401
X
uJ
0.8 --- 652 1043 1284
0.9 ...... 905 1161
1.0 ...... 737 1028
For 100 Models 5 Ton 223/4" Units
Speed Low Med L Med H Hi
Tap
0.1 1682 1870 2081 2263
0.2 1654 1826 2031 2193
= 0.3 1597 1775 1963 2165
_J 0.4 1547 1719 1899 2056
,£ 0.5 1498 1653 1825 1978
0.6 1428 1583 1737 1854
_ 0.7 1355 1503 1650 1757
x
uJ 0.9 --- 1266 1428 1515
0.8 1267 1392 1548 1644
1.0 ......... 1351
For 100 Models 3.5 Ton 19" & 22314" Units
Speed Low Med L Med H Hi
Tap
0.1 700 912 1209 1550
0.2 660 884 1171 1492
0.3 616 843 1139 1434
0.4 575 790 1088 1378
0.5 528 735 1040 1317
0.6 472 677 979 1247
0.7 --- 608 909 1161
0.8 --- 528 827 1058
0.9 ...... 733 932
1.0 ...... 624 778
m
o
_J
_d
X
For 125 Models 5 Ton Units
Speed Low Med L Med H Hi
Tap
0.1 1720 1910 2127 2315
'_ 0.2 1686 1881 2087 2268
_ 0.3 1644 1833 2024 2201
,£ 0.4 1600 1777 1961 2131
_ 0.5 1533 1720 1891 2029
"_ 0.6 1494 1647 1804 1948
0.7 1413 1571 1708 1820
uJ 0.8 1306 1470 1604 1730
0.9 .... 1349 1484 1614
1.0 ........ 1328 1430
44001 111400 [_

0
CONNECTION DIAGRAM
DANGER: ELECTRICAL SHOCK HAZARD
DISCONNECT BEFORE SERVICING
LADDER DIAGRAM
HOT 115V*60HZ NEUTRAL
SWITCH GND.
I_NTERLOCK O--111 t i
L P _(_ _ COOL HI (BK) NI'
lL _ 10 HEAT MHI (O)
: iF"_,,.,, _W- _) _x/,.-.._ II
LO,R,
II II
II
5
&= = =@O_,c
_= -----:4)O HuM
L1
&o--d22,
"J----" TRANSFORMER
r- -"r72'7'Lf
5AO,.S"_
FUSE
FURNACE
CONTROL
li I TO 2 IN SER,ES
N
EACOI:= _ :_
N
HUM_= _ :_
N
o= --_ :_
ROLLOUT SWITCH
1 TO 3 IN SERIES
DEPENDING ON MODEL
PRESSURE SWITCH
DEPENDING ON MODEL
:£
m c) c)
>
-_ O0
O0
ON---_
r_m m_ _Z
--t -t
p z
r- r-
oo
_. cJ1
n _R
o
II
o0 ;;13
-- O
3: I--
©
o
z
.-4
!
£
_ o O
m C
m ITi
-<
NOTE:
MOST VOLT METERS WILL READ 13-16 VOLTS TO
CHASSIS ON BOTH SIDES OF AN OPEN LIMIT OR
PRESSURE SWITCH IN THE RECTIFIED AC
VOLTAGE CIRCUIT
o
2
-e
4_
o
SEE MANUALS FOR ADJUSTING SPEED TAPS FOR PROPER HEATING, COOLING & CIRCULATING SPEEDS.
I SPEED TAP CODE BLACK BK
BLACK HI BLUE-MLO BLUE BL
-- LINE VOLTAGE FACTORY
LINE VOLTAGE FIELD
-- -- -- LOW VOLTAGE FACTORY
-- -- -- LOW VOLTAGE FIELD
-- i = INTERNAL CIRCUIT BOARD WIRING
-- • -- RECTIFIED AC VOLTAGE FACTORY
ORANGE-MHI REDLO BROWN BR
COLOR CODE
GREEN G
ORANGE O
RED R
WHITE W
YELLOW Y
PURPLE P
IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE
MUST BE REPLACED, iT MUST BE REPLACED WITH TYPE
AWM _ 105°C WIRE OR ITS EQUIVALENT
©
t012910-E

AA-
EE
15
2
O
z
E
C¢
FF
18
2
KK
T
K
25-23-95
Representative 0kawing only, some models may vary in appearance.
oo
o

I Replacement Parts - NgMP1 & NgMP2
Models - N9MP1050B12A4, N9MP1075B12A4, N9MP1080F16A4, N9MP1100F14A4, N9MP1100J20A4 &
N9MP1125J20A4 - N9MP2050B12A4, N9MP2075B12A4, N9MP2080F16A4, N9MP2100F14A4, N9MP2100J20A4 &
N9MP2125J20A4 (Natural Gas)
Replacement part supplied will be current active part. For parts not listed, consult place of purchase.
Key Description Part
No, Functional Number 050B 075B 080F 100F 100J 125J 050B 075B 080F 100F 100J 125J
1 HeatExchanger,Primary 1012847 1 1
2 HeatExchanger,Secondary 1013760 1 1
3 Motor, Blower 1009052 1 1 1 1
4 Mount, Motorkit 1013379 1 1 1 1
5 Wheel, Blower 1013011 1 1 1 1
6 Transformer 1012722 1 1 1 1 1 1 1 1 1 1 1 1
7 Capacitor, 10Mfd, 370V 1094956 1 1 1 1
7.5Mfd.,370V 1094239 1 1 1 1
40Mfd.,370V 1012176 1 1 1 1
8 Control,Fan Timer 1012358 1 1 1 1 1 1 1 1 1 1 1 1
9 Switch, Interlock 1012351 1 1 1 1 1 1 1 1 1 1 1 1
10 Switch, Pressure 1013802 1 1 1 1 1
11 Blower,Exhaust(Jakel) 1014338 1 1 1 1 1 1 1 1 1 1
12 Valve,GasHSP Nat. 1013350 1 1 1 1 1 1 1 1 1 1 1 1
13 Burner,PilotHSP 1008731 1 1 1 1 1 1 1 1 1 1 1 1
14 Igniter/SensorHSP 1009524 1 1 1 1 1 1 1 1 1 1 1 1
15 Orifice,Burner#42 Nat. 1011351 2 3 4 4 5 2 3 4 4 5
#44Nat. 1011352 4 4
16 Switch, Limit(Reneut) 1013102 2 2 2 2 2 2 2 2 2 2 2 2
17 BurnerAssembly 1008723 1 1
18 Switch, Limit(Main) 34335001 1 1
19 Orifice,Pilot .018 503211 1 1 1 1 1 1 1 1 1 1 1 1
1012851 1 1
1012855 1 1 1 1
1012856 1 1
1012859 1 1
1013761 1 1
1013764 1 1 1 1
1013765 1 1
1013766 1 1
1013341 1 1 1 1
1011906 1 1 1 1
522020024 1 1 1 1 1 1 1 1
1011420 1 1 1 1 1 1 1 1
1013811 1 1
1013801 1 1 1
1013166 1 1
1014341 1 1
1008724 1 1
1008725 1 1 1 1 1 1
1008726 1 1
34335002 1 1
1320361 1 1 1 1
1008445 1 1
1320367 1 1
12A 12A 16A 14A 20A 20A 12A 12A 16A 14A 20A 20A
N9MP1 N9MP2
_] 44001 1114O0

I Replacement Parts - NgMP1 & NgMP2
Models - N9MP1050B12A4, N9MP1075B12A4, N9MP1080F16A4, N9MP1100F14A4, N9MP1100J20A4 &
N9MP1125J20A4 - N9MP2050B12A4, N9MP2075B12A4, N9MP2080F16A4, N9MP2100F14A4, N9MP2100J20A4 &
N9MP2125J20A4 (Natural Gas)
Replacement part supplied will be current active part. For parts not listed, consult place of purchase.
Key Description Part N9MP1 N9MP2
No. Non-Functional Number 12A 12A 1GA 14A 20A 20A 12A 12A 16A 14A 20A 20A
A Panel,Top
B Gasket,TopPanel
F Partition,Blower
H Housing,Blower
J Panel,BlowerCutoff
K Hanger,Blower
L Door,Blower
M Bracket,DoorFiller
N Door,Front
O Clamp,Capacitor 1095020 1 1 1 1 1 1 1 1
P TransitionAssembly 1012280 1 1 1 1
Q Gasket,Blower 1014425 1 1 1 1 1 1 1 1 1 1 1 1
R Bear&Insulating 1012417 1 1 1 1
S Box,Collector 1012128 1 1 1 1
T Gask_,Transition 1013079 1 1 1 1
U Gask_, CollectorBox 1012593 1 1 1 1
V Partition,FrontHtExchanger 1012646 1 1
1012324 1
1012325
1012326
1012954
1012955
1012956
1012602 1
1012603
1012604
1014009 1
1014010
1014011
1014015
1014014
1014016
1012972 1
1012888
721020013 1
721020008
1012328 2
1013215 1
1013216
1013217
1013207
1013208
1013209
1014005 1
1014006
1014007
1013789 1
1013790
1013791
1013210 1 1
1013211 1 1
1013212 1 1
1095022 1 1 1 1
1012281 1 1 1 1
1012282 1 1 1 1
1012418 1 1 1 1
1012419 1 1 1 1
1012244 1 1 1 1
1012245 1 1 1 1
1013080 1 1 1 1
1013083 1 1 1 1
1012594 1 1 1 1
1012595 1 1 1 1
1012647 1 1
1012649 1 1 1 1
1012651 1 1
1012652 1 1
O50B 075B 080F lOOF lOOJ 125J O50B 075B 080F IOOF lOOJ 125J
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
2
1
1
1
1
1
2
1
1
1
1
2
1
1
1
2
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
2
1
1
1
1
1
2
1
1
1
1
1
2
1
1
44001 111400

I Replacement Parts - NPMP1 & NPMP2
Models - N9MP1050B12A4, N9MP1075B12A4, N9MP1080F16A4, N9MP1100F14A4, N9MP1100J20A4 &
N9MP1125J20A4 - N9MP2050B12A4, N9MP2075B12A4, N9MP2080F16A4, N9MP2100F14A4, N9MP2100J20A4 &
N9MP2125J20A4 (Natural Gas)
Replacement part supplied will be current active part. For parts not listed, consult place of purchase.
Key Description Part
No. Non-Functional Number 12A 12A 16A 14A 20A 20A
W Gasket,AttachmentPlate 1012542 2
X Cover,JunctionBox 1012350 1 1 1 1 1 1
Y Box,Junction 1012349 1 1 1 1 1 1
Z Tube, Pilot 1013077 1
AA Bracket,Pilot 1010901 1 1 1 1 1 1
BB Manifold 1012276 1
CC Bottom,BurnerBox 1012334 1 1
DD Baffle,BurnerBox 1012338 1 1
EE Top,BurnerBox 1013702 1 1
FF Bracket,ManifoldSupport 1012377 2 2 2 2 2 2
GG Bracket,BurnerBox Side 1012532 2 2 2 2 2 2
HH Bracket,ControlMounting 1012321 1 1 1 1 1 1
JJ Tube,Sensor 1009238 1 1 1 1 1 1
KK Trap,DrainAssembly 1013676 1 1 1 1 1 1
LL Sightglass 1012756
)( PARTNOT ILLUSTRATED
)( Clamp,Hose3/4"
)( Clamp,Hoses/8"
)( Coupling,Air Intake
)( Grommet,Vinyl
)( Drain,Vent
)( Pipe,PVC
)( Grommet,Vent
)( Gasket,Air Intake
)( Gasket,Trap
)( Harness,Wire
)( Hose,Drain1/2"
)( Hose,Drain5/8"
)( Hose,Drain3/16"
)( DoorScrews
)( DoorScrew Retainers
)( Bushing,StrainRelief
)( InstallationManual
)( User'sManual
1012543 2
1012544 2 2 2
1012545 2
1012832 1 1 1 1
1012834 1
1012277 1
1012278 1 1 1
1012279 1
1012335 1 1 1
1012336 1
1012339 1 1 1
1012340 1
1013703 1 1 1
1013704 1
1012976
1012975
1012284
1009535
1014003
1171527
1012697
1012583
1013701
1013716
1013718
1013719
1014358
1014359
1009238
1013349
1013725
1945287
44001111300
44102200300
050B 075B 080F 100F 100J 125J
2
2
1
1
1
1
1
1
4
4
1
1
1
2 2
2 2
1 1
1 1
1 1
1 1
1 1
1 1
1 1
4 4
4 4
1 1
1 1
1 1
NgMP1
2
2
I
I
I
1
1
1
4
4
1
1
1
2
2
1
1
1
1
1
1
4
4
1
1
1
050B 075B 080F 100F 100J 125J
12A 12A 16A 14A 20A 20A
2
1 1
1 1
1
1 1
1
1 1
1 1
1 1
2 2
2 2
1 1
1 1
1 1
1 1
2
2
1
1
1
1
1
1
1
4
4
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
4
4
1
1
1
2
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
4
4
1
1
1
NgMP2
2 2 2
1 1 1 1
1 1 1 1
1 1 1
1 1 1 1
1 1 1
1 1 1
1 1 1
1 1 1
2 2 2 2
2 2 2 2
1 1 1 1
1 1 1 1
1 1 1 1
1 1 1 1
2
2
1
1
1
1
1
1
1
1
1
1
1
4
4
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
4
4
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
4
4
1
1
1
2
1
1
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
4
4
1
1
1
_] 44001 1114O0

I Replacement Parts - *9MPD
Models - *9MPDO50F12A4, *9MPDO75F12A4, *9MPDO80J16A4, *9MPD100J14A4, *9MPDIOOJ2OA4 &*9MPD125L20A4
(Natural Gas)
Replacement part supplied will be current active part. For parts not listed, consult place of purchase.
Key Description Part *gMPD
No. Functional Number 050F12A 075F12A 080J16A 100J14A 100J20A 125L2OA
1 HeatExchanger,Primary 1
2 HeatExchanger,Secondary
Motor, Blower
4
Mount, Motor kit
5
Wheel,Blower
6
Transformer
7
Capacitor,7.SMfd.,370V
8
Control,FanTimer
9
Switch,Interlock
10
Switch,Pressure
11 Blower,Exhaust(Jakel)
12 Valve,GasHSP Nat.
13 Burner,Pilot HSP
14 Igniter/SensorHSP
15 Orifice,Burner#42 Nat.
16 Switch,Limit(Rollout)
17 BurnerAssembly
18 Switch, Limit (Main)
Orifice, Pilot .018
10Mfd.,370V
40Mfd.,370V
#44Nat
1012850
1012854
1012858
1012862
1013762
1013763
1013765
1013767
1009052
1013341
1011906
1013379
522020024
1013011
1011420
1012722
1094239
1094956
1012176
1012358
1012351
1013802
1013812
1013166
1014388
1014341
1013350
1008731
1009524
1011351
1011352
1013102
1008723
1008724
1008725
1008726
1320366
34335002
1008445
1320367
503211
1
1
1
1
I
I
I
I
I
I
I
1
1
1
2
1
1
1
1
1
1
1
1
1
3
1
1
1
1
1
1
1
1
1
1
1
4
2
1
1
I
I
I
I
I
I
1
1
1
4
1
1
1
1
1
1
1
1
1
1
1
1
4
1
1
1
1
1
1
1
1
1
1
1
1
1
5
1
1
*Denotes Brand
44001 1114O0 [_

I Replacement Parts - *9MPD
Models - *9MPDO50F12A4, *9MPDO75F12A4, *9MPDO80J16A4, *9MPD100J14A4, *9MPDIOOJ2OA4 &*9MPD125L20A4
(Natural Gas)
Replacement part supplied will be current active part. For parts not listed, consult place of purchase.
Key
No.
A
Panel,Top
B
Gasket,TopPanel
F
Partition,Blower
H
Housing,Blower
J
Panel,BlowerCutoff
K
Hanger,Blower
L
Door,Blower(Tempstaronly)
M
Bracket,DoorFiller
N
Door,Front(]-staronly)
(]-staronly)
(Tstaronly)
(Cmaker/Keepriteonly)
(Cmaker/Keepriteonly)
(Cmaker/Keepriteonly)
(Heil/Arcoonly)
(Heil/Arcoonly)
(Heil/Arcoonly)
O
Clamp,Capacitor
P
TransitionAssembly
Q
Gasket,Blower
R
Board,Insulating
S
Box,Collector
T
Gasket, Transition
U
Gasket, Collector Box
V
Partition, Frt Ht Exchanger
Non- Functional Number
Description Part *gMPD
1012342
1012343
1012344
1012603
1012604
1012605
1014018
1014014
1014016
1014017
1012972
1012888
721020013
721020008
1012328
1013151
(Tempstaronly)
(Tempstaronly)
(Comfortmaker/Keepriteonly)
(Comfortmaker/Keepriteonly)
(Comfortmaker/Keepriteonly)
(Heil/Arcoaireonly)
(Heil/Arcoaireonly)
(Heil/Arcoaireonly)
1013152
1013153
1013141
1013142
1013143
1013138
1013139
1013140
1014006
1014007
1014008
1013154
1013155
1013156
1013148
1013149
1013150
1013145
1013146
1013147
1095020
1095022
1012281
1012282
1012283
1014425
1012418
1012419
1012420
1012244
1012245
1012246
1013263
1013080
1013083
1013084
1012594
1012595
1012596
1012650
1012648
1012651
1012653
050F12A
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
075F12A
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
080J16A
I
I
1
2
1
I
I
I
I
I
I
I
I
I
100J14A
I
I
1
2
1
I
I
I
I
I
I
I
I
I
100J2OA
1
1
1
2
1
1
1
1
1
1
1
1
1
1
125L20A
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
*Denotes Brand
_]] 44001 1114O0

I Replacement Parts - *9MPD
Models - *9MPDO50F12A4, *9MPDO75F12A4, *9MPDO80J16A4, *9MPD100J14A4, *9MPDIOOJ2OA4 &*9MPD125L20A4
(Natural Gas)
Replacement part supplied will be current active part. For parts not listed, consult place of purchase.
Key Description *gMPD
No. Non- Functional 080J16A 100J14A 100J20A 125L20A
W Gasket, Attachment Plate
X Cover,JunctionBox
Y Box,Junction
Z Tube, Pilot
AA Bracket,Pilot
BB Manifold
CC Bottom, Burner Box
DD Baffle,BurnerBox
EE Top,BurnerBox
FF Bracket,ManifoldSupport
GG Bracket,BurnerBoxSide
HH Bracket,ControlMounting
JJ Tube,Sensor
KK Trap, DrainAssembly
LL Sightglass Comfortmaker& Hell
TempstarOnly
Part
Number
1012542
1012543
1012544
1012545
1012350
1012349
1012832
1013077
1012834
1010901
1012276
1012277
1012278
1012279
1012334
1012335
1012336
1012338
1012339
1012340
1013702
1013703
1013704
1012377
1012532
1012321
1009238
1013676
1013235
1013236
050F12A
2
1
1
1
1
1
2
2
1
1
1
1
1
075F12A
2
I
I
I
I
I
2
2
1
1
1
1
1
2
I
I
I
2
2
1
1
1
1
1
I
I
I
2
2
1
1
1
1
1
I
I
I
2
2
1
1
1
1
1
1
1
1
1
1
2
2
1
1
1
1
1
)( PART NOT ILLUSTRATED
)( DoorScrews
)( DoorScrewRetainers
)( Clamp,Hose 314"
)( Clamp,Hose518"
)( Coupling,AirIntake
)( ClampHose
)( DrainVent
)( Coupling,Discharge
)( Elbow,90°
)( Pipe,PVC
)( Gasket,AirIntake
)( Gasket,Trap
)( Grommet,Vent
)( Harness,Wire
)(
Bushing,Strain
)(
Grommet,Vinyl
)(
Hose,Drain1/2"
)(
Hose,Drain5/8"
)(
Hose,Drain 3/16"
)(
InstallationManual
User'sManual
)(
*Denotes Brand
44001 111400
1013349
1013725
1012976
1012975
1012284
1013830
1014003
1002522
1013920
1171527
1012583
1013701
1012697
1013716
1013718
1013719
1945287
1009535
1014358
1014359
1009238
44001111400
44102200300
4
4
2
2
1
4
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
4
4
2
2
1
4
1
2
1
1
1
1
1
1
I
I
I
I
I
I
I
4
4
2
2
1
4
1
2
1
1
1
1
1
I
I
I
I
I
I
I
4
4
2
2
1
4
1
2
1
1
1
1
1
I
I
I
I
I
I
I
4
4
2
2
1
4
1
2
1
1
1
1
1
I
I
I
I
I
I
I
4
4
2
2
1
4
1
2
1
1
1
1
1
I
I
I
I
I
I
I
I

I Replacement Parts - *9MPD
Models - *9MPD050F12A4, *9MPD075F12A4, *9MPD080J16A4, *9MPD100J14A4, *9MPD100J20A4 &*9MPD125L20A4
(Natural Gas)
Replacement part supplied will be current active part. For parts not listed, consult place of purchase.
Key Description
No. Non- Functional
Gas Conversion Kits
Nat to LP NAHF002LP
LP to Nat NAHF002NG
Nat to LP NAHF003LP
LP to Nat NAHF003NG
* Order from Service Parts
Part *gMPD
Number 080J16A
*1009509
*1009510
*1013815
*1013818
050F12A
1
1
075F12A
1
1
100J14A
1
1
100J20A
1
1
125L20A
1
1
I Replacement Parts - N9MP1 & N9MP2
Models - N9MP1050B12A4, N9MP1075B12A4, N9MP1080F16A4, N9MP1100F14A4, N9MP1100J20A4 &
N9MP1125J20A4 - N9MP2050B12A4, N9MP2075B12A4, N9MP2080F16A2, N9MP2100F14A4, N9MP2100J20A4 &
N9MP2125J20A4 (Natural Gas)
Replacement part supplied will be current active part. For parts not listed, consult place of purchase.
Key Description Part N9MP1 NgMP2
No. Non-Functional
Gas Conversion Kits
Nat to LP NAHF002LP
LP to Nat NAHF002NG
Nat to LP NAHF003LP
LP to Nat NAHF003NG
* Order from Service Parts
Number 12A 12A 16A 14A 20A 20A 12A 12A 16A 14A 20A 20A
*1009509 1 1 1 1 1 1 1 1 1 1
*1009510 1 1 1 1 1 1 1 1 1 1
*1013815 1 1
*1013816 1 1
O50B 075B 080F IOOF lOOJ 125J O50B 075B 080F IOOF lOOJ 125J
*Denotes Brand
44001 1114O0