INSTALLATION
INSTRUCTIONS
Models
EF08B1500A3
EF12F1900A2
EF16J2200A2
EF20N2600A2
With
AMF001NHA
//
Use ONLY factor' listed electric heaters.
ELECTRIC
FURNACE
Safety Labeling and Signal Words
Danger, Warning and Caution
The signal words DANGER, WARNING and CAUTION
are used to identify levels of hazard seriousness. The
signal word DANGER is only used on product labels to
signify an immediate hazard. The signal words WARN-
ING and CAUTION will be used on product labels and
throughout this manual and other manuals that may ap-
ply to the product.
DANGER - Immediate hazards which WILL result in se-
vere personal injury or death,
WARNING - Hazards or unsafe practices which
COULD result in severe personal injury or death.
CAUTION - Hazards or unsafe practices which COULD
result in minor personal injury or product or property
damage.
Accessory No Heat Kit
Safety Labeling and Signal Words Cov
General Information / Installation ............ 2
Vertical Installations ........................ 2
Horizontal Installations ..................... 3
Condensate Drain .......................... 5
Refrigerant Orifice and Lines ................ 5
Electrical Wiring ............................ 6
Checks and Maintenance ................... 7
Blower Performance ........................ 8
Signal Words in Manuals
The signal word WARNING is used throughout this
manual in the following manner:
The signal word CAUTION is used throughout this
manual in the following manner:
CAUTION
Product Labeling
Signal words are used in combination with colors and/or
pictures on product labels.
Printed in U.S.A. 442 01 2204 01
Aug 2001
_ Installation Instructions Electric Furnace]
Figure 1 Dimensions and Clearances
14-3/8 '' (EF08)
17-7/8 '' (EF12)
21-1/2" (EF16)
25-1/8" (EF20)
LowVoltage
PilotHole
CLEARANCES
Alternate
LineVoltage
Pilot Hole
DrainConnections
For Horizontal
Main3/4 Fpt
Overflow 3/4 FPT
Main/OverflowDrains
3/4FPT
LineVoltage
Pilot Hole
45" (EF08-12)
54" (EF16-20)
Suction-
Liquid
21 1/2"
NO HEATERS
All Sides .................................. O"
From Supply Duct .......................... O"
Recommended Service From Front .......... 20"
(Service for blower, filter if installed)
WITH HEATERS
All Sides .................................. O"
From First Three
Feet of Supply Duct to Combustibles ........ 1"
From Duct after Three Feet ................. O"
Recommended Service From Front .......... 20"
(Service for blower, filter, heaters if installed)
W
FilterDoor
16-3/8'' (EF08)
19-7/e'' (EF12)
23-1/2'' (EF16)
27-1/e'' (EF20)
38-20-17
General Information
Installation or repairs made by unqualified persons can
result in hazards to you and others. Installation MUST
conform with local building codes and with the
National Electrical Code NFPA70 current edition.
The information contained in this manual is intended
for use by a qualified service technician familiar with
safety procedures and equipped with the proper tools
and test instruments.
Failure to carefully read and follow all instructions in
this manual can result in equipment malfunction,
property damage, personal injury and/or death.
THESE INSTRUCTIONS ASSUME THAT A TYPICAL INSTAL-
LATION WILL INCLUDE ELECTRIC HEAT AND A COIL. BA-
SIC INSTRUCTIONS ARE PROVIDED BUT THE INSTALLER
WILL HAVE TO REFER TO INSTRUCTIONS FOR OTHER AC-
CESSORIES FOR MORE COMPLETE INFORMATION.
The blower cabinet may be used as an electric furnace or for cool-
ing or heat pump operation with orwithout electric heat. The cabi-
net can be installed in an upfiow, downflow or horizontal position
(Figure 2). Horizontal installations require a horizontal kit for prop-
Fire Hazard
When heaters are installed maintain clear-
ances from combustible materials as speci-
fied on unit rating plate.
Failure to do so can result in fire, property
damage, personal injury or death.
er coil support and drain pan. Downflow installations require a
subbase kit which provides proper clearances and a support to
install a coil.These units are not shipped with air filters installed.
Filter must be field supplied, either washable or disposal type.
Washable filters are available as an accessory.
Location
Select the best position wi_ich suits timeinstallation site conditions.
The location should provide adequate structural support, space in
the front ofthe unit for service access, clearance for return air and
supply duct connections, space for refrigerant piping connections
and condensate drain line connections, and clearance forfilter re-
moval.
NOTE: Internal filter can be accessed from separate filter door. If
the filter can NOT be easily accessed, a remote filter is recom-
mended. Refer to ACCA Manual D for remote filter sizing.
Ifthe unit is located in an area of high humidity, nuisance sweating
of casing may occur. On these installations a wrap of 2"fiberglass
insulation with a vapor barrier should be used.
Upflow Installations
The unit is ready to install in the upflow position without modifica-
tions.
The unit MUST be supported on the bottom ONLY and set on a
supporting frame or shelf. Use screws through the bottom to an-
chor to supporting frame.
Downflow Installations
Refer to instructions with Subbase Kit.
_J 442 01 2204 01
JElectric Furnace Installation Instructions j
Figure 2 Airflow Positions
UPFLOW POSITION
HEATER
BLOWER
DOWNFLOW POSITION
FILLER
Coil
supop.._
Subbase
HEA'_R
\ /
FIL_ER
\,
38-20-19
Non-Ducted Return Air Closet Installation
The cabinet can be installed in acloset with a false bottom to form
a return air plenum, or mounted on an open platform inside the
closet. Platform should be high enough to provide a free (open)
area for adequate return airflow into the bottom of the cabinet.
The open area can be on the front side or a combination of front
and sides, providing there is clearance on the sides between cabi-
net and closet. Refer to ACCA Manual D for sizing and free
area recommendations.
NOTE: Local codes may limit application of systems without a
ducted return to single story dwellings.
Horizontal Left and Right Installations
No Coil
Ifa coil is not being installed, the cabinet can be placed on either
side for horizontal airflow as shipped. Refer to instructions with
electric heat for instructions on horizontal applications.
With Coil
All units must have the horizontal drain pan kit insta!led for either
left or right hand applications. For installation ofthe drain pan, re-
fer to the installation instructions included with the horizontal drain
pan kit, and the following.
Figure 3 Airflow Positions
HORIZONTAL LEFT POSITION
,,=,
m
HORIZONTAL RIGHT POSITION
38-20-19
Drain Pan Installation
1,
Position side of coil drain pan into horizontal drain pan
trough on deep end of pan.
2.
Install the coil support bracket on left or right side of the
cabinet.
3.
Install coil drip flanges on the left or right side of the coil,
(same side as horizontal drain pan).
5.
Install drain plugs as required in back side of horizontal
drain pan. Install plugs in A coil drains to prevent air leaks.
5.
Slide coil assembly into cabinet being careful not to tear in-
sulation.
NOTE: Be sure Acoil pan fits into the support bracket on the back
side of the cabinet and that pan is under the flange of the bracket
on the right side. The brackets fit over the top edge of the A coil
drain pan to hold it when it's put into the horizontal position.
6. Referto Restrictor Orifice Selection and change restrictor if
necessary, then install coil access panel.
Cabinet can now be placed on it's side for horizontal airflow.
Suspended Cabinet Installation
1. If the cabinet cannot be supported on a frame or shelf, it
may be suspended.
2. Use metal strapping or threaded rod with angle iron sup-
ports under the auxiliary drain pan to suspend cabinet.
These supports MUST run parallel with the length of the
cabinet (Figure 5 ).
3. Ensure that there is adequate room to remove service and
access panels after installing supporting brackets.
4. Place Styrofoam blocks in auxiliary drain pan to support
cabinet.
Duct Connections
Supply Duct
CAUTION
A field-fabricated auxiliary drain pan, with a seperate
drain is REQUIRED for all installations over a finished
Supply duct must be attached to the outside of flange on outlet
end of unit. Flexible connectors may be used if desired. Maintain
clearances from supply duct to combustibles when heaters are
installed. See Figure 1 and unit rating plate.
living space or in any area that may be damaged by
overflow from the main drain pan. In some localities,
local codes require an auxiliary drain pan for ANY hori-
zontal installation.
442 01 2204 01 3[._J
Return Duct
Return duct should be attached to bottom of unit using sheet met-
al screws or other fasteners.
I Installation Instructions
Electric Furnace I
Figure
Coil Access Panel
4 / Horizontal Drain Pan
\
1
Coil Support Bracket
Horizontal Drain Pan
(Left Hand Airflow)
Drip Flanges
(Left Hand Airflow)
(Right Hand Air_)
\
il Support Bracket
Coil Support Bracket
(Left Hand Airflow)
Drip Flanges
(Right Hand Airflow)
Figure 5 Horizontal Installation
Field-Fabricated
Drain Pan
Supports MUST run parallel with blower cabinet =-_
Horizontal Drain Pan
(Right Hand Airflow)
38-20-06
Filter Installation
Filters must be field supplied. The blower cabinet is set up for an
internal filter or a remote filter grille or other means may be pro-
vided. Refer to ACCA Manual D for remote filter sizing.
To install an internal filter, remove screw securing filter door and
slide filter into unit. Some filters are marked for airflow direction,
make sure arrow points towards blower if marked. Washable fil-
ters are offered as an accessory. Disposable filter sizes are listed
in Filter Static Pressure Drop Table.
Condensate Drain
The unit is provided with 3/4" National Pipe Thread (NPT) con-
densate drains. (Figure 1). Any drain can be used as a primary or
secondary drain. Condensate drain lines should be insta!led in a
manner that does not obstruct access to the filter.
There is a secondary drain fitting supplied with the unit that will
convert any of the primary condensate drain connections into a
secondary drain connection. This fitting should be insta!led in any
of the primary drain connections to convert it to a secondary drain.
1. Connect the drain lines to the appropriate drain fittings. 3/4"
PVC or other type of drain line may be used. The drain line
must not be smaller than the drain fitting.
2. Insta!l a trap in the drain line below the bottom of the drain
pan and pitch the drain lines down from the coil at least I/4"
per foot of run. Horizontal runs over 15 feet long must also
have an anti-siphon air vent (stand pipe), installed ahead
of the horizontal run. An extremely long horizontal run may
require an oversized drain line to eliminate air trapping.
_J 442 01 2204 01