Installation Instructions
PIN CPCRKHTR003A00, CPCRKHTR004A00
CPCRKHTR005A00, CPCRKHTR007A00
NOTE: Read the entire instruction manual before starting the
SAFETY CONSIDERATIONS
Installing and servicing air conditioning equipment can be hazard- ous due to system pressures, electrical components, and fuel gases. Only trained and qualified personnel should install, service, or repair air conditioning equipment.
Untrained personnel can perform basic maintenance functions such as cleaning coils, or cleaning and replacing filters. All other operations should be performed by trained service personnel. When working on air conditioning equipment, observe precautions
in the literature, on tags, and on labels attached to the unit. Recognize safety information. This is the safety-alert symbol z_ -
When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAU
TION. These words are used with the safety alert symbol DAN- GER identifies the most serious hazards which will result in severe
personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to
identify unsafe practices which would result in minor personal injury or product and property danlage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
Follow all safety codes. Wear safety glasses and work gloves. Have a fire extinguisher available.
INTRODUCTION
These instructions cover the installation of an Accessory Crank- case Heater on Electric Cooling, Heat Pump and Electric
Cooling/Gas Ideating units.
_) DESCRIPTION AND USAGE
The accessory crankcase heater warms the compressor crankcase
oil to reduce refrigerant migration in the crankcase and ensure proper compressor lubrication. Refer to Tables 1, 2 and 3.
INSTALLATION
Small Packaged Products
Accessory Crankcase Heaters
Cancels: IlK 582A-18-4 IlK 582A-18-12
Table 1--Accessory Crankcase Heater Usage
See Below for Units Applicable
48GXJ583A/PY2P-S 50GX/702A/PA2P-S
50JZ/602B (FACTORY INSTALLED ON 042-_0)
UNIT SIZE 240 V 460 V
024 CPCRKHTR004A00 NA 030 CPCRKHTR004A00 NA 036 CPCRKHTROO4AO0 CPCRKHTROO5AO0 042 CPCRKHTROO4AO0 CPCRKHTROOSAO0
048 CPCRKHTR004A00 CPCRKHTR005A00 060 CPCRKHTROO4AO0 CPCRKHTROO5AO0
50JXJ602A/PH2P-B
48GP/583B 50GL/702B
Table 2--Accessory Crankcase Heater Usage
See Below for Units Applicable
48GS/582A/PY1 P-S 50GS/701 A/PAt P-B
UNIT SIZE
018 024 030
036 O42
O48 060
240 V
CPCRKHTR007A00 CPCRKHTR007A00
CPCRKHTR007A00 CPCRKHTR007A00 CPCRKHTR007A00
CPCRKHTROCAA00 CPCRKHTR007A00
460 V
CPCRKHTROO3AO0 CPCRKHTROO3AO0
CPCRKHTROO5AO0 CPCRKHTR003A00
Table 3--Accessory Crankcase Heater Usage
See Below for Units Applicable
50JSi601A/PHIP-B (FACTORY INSTALLED ON 036)
UNIT SIZE 240 V 460V
018 CPCRKRTR007A00 HA
024 CPCRKHTR007A00 NA 030 CPCRKHTR007A00 NA
036 CPCRKHTR007A00 CPCRKHTR003A00 042 CPCRKHTR004A00 CPCRKHTR005A00
048 CPCRKHTR004A00 CPCRKHTR005A00 060 CPCRKHTR004A00 CPCRKHTR005A00
5-01
NA NA NA
4. Spread crankcase heater arms and wrap heater around com-
pressor base approximately 2-in. above compressor mounting
1. Turn off gas supply (if applicable) first, then disconnect
electric power supply.
2. Install Lockout Tag,
3. Remove access panel for compressor and control box. (See Fig. 1.)
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice andwithout incurring obligations.
Book 1 4 PC 101 Catalog No. 534-80055 PrintedinU.S.A. Form48/50-102SI Pg 1 501 Replaces: 48GS,GX-3SI
plate. (See Fig. l.I
5. Fasten heater firmly in place with fastening clip provided with the crankcase heater. (See Fig. 1.1
6. Route crankcase heater leads into unit control box, following the path of the compressor leads. (See Fig. 1.)
( NOTE: TOP CONDENSER SECTION NOT SHOWN )
COMPRESSOR ROUTE WIRES INDOOR FANMOTOR
CRANKCASE HEATER
AS SHC_'N
CONTROL BOX
/_HEATER CLIP
Fig. l_Typical Crankcase Heater Installation
c
LEGEND
C -- Compressor Contactor CH -- Crankcase Heater
<_) Marked Terminal
Fig. 2--Crankcase Heater Wiring
7. Connect one black lead to the compressor contactor terminal 11, and connect other black lead to compressor contactor
terminal 21. (See Fig. 2.)
8. Attach green crankcase heater ground lead to ground screw in control box.
C01015
CH
c
-- BLK---_
C01014
9. Replace access panel.
10. Turn on main power, then (if applicable) gas supply.
Copyright 2001 Carder Corporation 582a1812