Seametrics FT522 Instructions Manual

FT522 Usage Monitor Instructions rev. b
General Information
The FT522 is a flowmeter monitor with added output and alarm features. It is designed for use with SeaMetrics flow meters and sensors, as well as other units which have a pulse or frequency output. It displays flow rate and total in large digits on an easily-read backlit display. Units are user selectable between gallons, cubic feet, and cubic meters.
The primary output of this unit is a user-set alarm relay which signals excessive total flow within a given time period (up to 48 hours). This is typically used to detect an elevated usage level in a cooling tower or potable water application. The dual relays can be connected to an alarm, autodialer, or any other switch-controllable device.
In addition to the usage alarm, the FT522 has analog output (4-20 mA, 0-5 VDC or 0-10 VDC) and programmable pulse output. These can be used for data logging or to provide proportional chemical feed, using an externally-controlled metering pump.
Specifications
Power 115 VAC (220 VAC optional),
50/60 Hz; 12 VDC
Temperature 32° -130° F (0° - 55° C) Enclosure Precision cast aluminum,
NEMA 4X
Alarm Outputs Two Form C SPDT relay,
115 VAC 5A max
Max Pulse Output 100 mA at 60 VDC Memory Type Non-volatile EEPROM
auto-backup
Sensor Power 12 VDC, 10 mA Totalizer 8 digit Rate Display 5 digit Volume Units Gallons, cubic feet, cubic
meters, liters, million gallons
Time Units Minutes, hours Analog Output 4-20 mA, 0-5 VDC, 0-10 VDC,
opto-isolated
Sensor Input Open collector current sink,
ESD protected
Max Input Frequency 1,000 Hz Shipping Weight 7 lbs
Features
Easy-read
backlit display
Remote control terminals
(inside housing)
Rugged cast aluminum
housing
(wall or panel mount)
ELAPSED
Stop
Set
0:00:00
0 GAL
Resume
Relay 1 Relay 2
Pulse
Output
Choice of
rate/volume units
Alarm output
indicator LED
Accessible
control
buttons
LT-10829-A Page 1 of 4
Installation
Wall Mounting. Using the four screws provided, attach
the two foot brackets to the sides of the enclosure. Then attach the unit to any secure surface by inserting screws through the mounting holes in the foot brackets.
Displays
SETTINGSOPERATION MODE
Panel Mounting. Follow the dimensions given for
“Panel Cutout”. Be sure to include the four corner screw holes. After cutting and drilling, place the front plate on the front side of the panel with its gasket against the panel, and the remainder of the square housing on the back side. Slide the screws through the four holes drilled in the panel, and into the threaded holes in the housing. Tighten until the gasket is firmly compressed against the panel.
Expose T erminals. Remove the four screws which hold the front plate to its flange. Remove the front plate. The display board is attached to this front plate. It is also connected to the power board by a ribbon cable. For convenience, this cable can be disconnected while making connections. Connections can be made inside the enclosure, or the terminals can be unplugged for easier access, by gently tugging on them.
Caution: When the control is powered up, relay or analog outputs may be present. If this could be a hazard, wait to make external
!
connections until program­ming is complete.
ELAPSED
Flow Monitor
0 GPM 0 GAL
0:00:00
0 GAL
Flow
SET
Rate
SET
Set Decimal
0.00
SET
SET
SET
SET
SET
SET
SET
1234 GAL
SET
SET
Set K-factor
Set Pulse Out
1.00 Gal
SET 20 mA RATE
123456 GPM
Time Period: 12 HOURS
Alarm Point:
TO CLEAR TOTAL
PRESS UP & LEFT
return to operation mode
60.00
GAL
MINUTE
Settings
Set Units. Press . Use to select volume
units. Use to select the particular unit desired (gallons, liters, etc.). Then use to switch to time units. Again, select the unit desired. Press for
next menu item.
Sensor Connection. Follow the “Connections” diagram to connect either two or three wires from the flow meter or flow sensor.
Monitor Alarm Connection. Connect the alarm devices to the appropriate relay terminals. Note that the relays have both normally-open (NO) and normally-closed (NC) contacts.
Analog Connection. This output can be configured 4­20 mA, 0-10 V or 0-5 V by placing a jumper in the cor­rect position on the analog header. The swith next to the header selects active (powered) or passive (unpowered) output. When using the 12 VDC powered input you may only select passive output.
Power Connection. Connect AC or DC power as desired to the appropriate terminals. For safety, if using AC power, be sure to connect the ground terminal provided to a good earth ground. If using DC power, be
2 of 4
Set Decimal. Use to select zero, one, or two decimal places on the flow units. Press to advance
to the next menu. Set K-Factor. The unit will not function properly
until this number is entered. It is simply the number of pulses which the flow meter or flow sensor puts out per gallon of liquid. It is marked on the Model/ Serial tag of SeaMetrics flow meters and flow sensor fittings. On adjustable flow sensors, the K­factor must be taken from the chart in the flow
sensor instructions, based on pipe size. Press for next menu item.
Set Pulse Out. An output pulse is activated at the selected volume intervals if this feature is in use.
Otherwise, it does not need to be set. Press for next menu item.
Set Time Period. This is the monitoring period at
the end of which the unit will alarm if total flow has exceeded its setting. To set this monitoring period in
hours, use the underlined is the one being set. Use the increase it. The
and keys. The digit which is
to
moves one digit to the left. Note
that if the digit to the right is set to “9”, the digit to the left will only go to “3”. This is because 48 is the
maximum setting allowed. Press
for next menu
item. Set Alarm Point. This is the maximum total flow
allowed in the time period set above. Use the same procedure as above to set this value, up to eight digits. The units are those previously chosen.
Press
for next menu item.
Operation
The last press of the key returns the unit to operation mode (see “Displays” diagram). In this
mode, pressing either arrow key will toggle back and forth between two displays, one for flow monitoring and the other for usage monitoring.
Usage Alarm. Pressing the Start/Stop key will start the clock and zero the total of the usage monitor. The clock will increase and the total will accumulate (provided there is flow) until the end of the monitoring period. At that time, the usage total and clock will zero automatically and the cycle will start over. If the usage total ever reaches its alarm point within the monitoring time, the usage alarm relays will energize and remain on until the Resume key is pressed.
Set 20 mA Out. The SET 20mA RATE programs the flow rate at which the output is 20 mA, 5 V or 10
V. Use and to set the maximum flow rate for full scale output. Press for next menu item.
Clear Total. This function resets the running total (not alarm point total) back to zero. It does not affect the alarm point total, which automatically resets itself at the end of every monitoring time period. To
reset to zero, press and simultaneously.
Connections
(for metering pumps)
AUTODIALER
ALARM
Pulse Outputs
Alternate
12 VDC power
PC1 power supply
P/N 05040
Pulse 1
Pulse 2
Alarm 1
Alarm 2
Main
power fuse
250mA
part # 26926
Customer Supplies 1A Fuse
NC COM NO NC COM NO
If the Resume key is pressed during a monitoring cycle, it will freeze the cycle at its current point. Pressing it again allows the cycle to resume where it left off.
Flow Monitoring. The “Rate indication gives the current rate of flow. “Total is a running total of flow which increases indefinitely unless it is reset (see
Ribbon connector
from display board
RESUME
COM
BATCH
+
s1
+
5V
10V
A
0m
-2
4
Jumpers
s2
Active
+
A
P
Passive
Analog Switch
Analog Jumper
A B
An Output
RED
WHITE
BLACK
Resume Start/Stop
Power signal Sensor Input
Ground
0-10 V or 4-20 mA
Remote Controls
Dry contact
Meter
Neut
Hot
Gnd
110 VAC
3 of 4
Repair
The only field-repairable component on the FT522 is the fuse. If failure is due to a cause other than a blown fuse, it is necessary to replace the entire board stack. Contact your distributor for information.
Panel Cut-out Dimension
!
Caution: Always disconnect power to the unit before opening the terminal cover. Do not reconnect power until all connections have been made and the terminal cover has been replaced.
1/4" holes (4 required)
gasket
5.50"
6.03"
5.50"
PANEL CUTOUT
6.03"
4 of 4
20419 80th Ave. So., Kent WA. 98032 USA
Phone: 253-872-0284 Fax: 253-872-0285
www.seametrics.com 1-800-975-8153
Loading...