Page 5
FT520-84
> FT520-84 Filter Regeneration
In Filter Regeneration Mode, the display indicates a flow rate
on the top line, and one of two configurations on the bottom
line: an accumulated total flow (resettable), or batch process
remainder. The regeneration process is initiated by setting a
target volume, a value for regeneration time as well. A single
relay or alternate relay setting allows control of either single
tank or alternating dual tank systems.
On the input side, this model can be used with Seametrics
flow sensors and meters, as well as with water meters from
other manufacturers. The output can be used to initiate regeneration in a variety of one-tank and two-tank water treatment systems. In addition to the regeneration functions, this
unit features displays of flow rate and accumulated flow, as
well as programmable pulse output and a 4-20 mA analog
output, for use with remote recorders. There are two regeneration relays, which can be used for alternating regeneration of
two tanks. The outputs remain on for a duration programmed
by the user, depending on the requirements of the regeneration valve being used. A programmable pulse output can be
used as needed to control a chemical metering pump, for
controlled chemical addition to the water stream.
Settings
Use Left Arrow and UP Arrow keys to change settings. Press
SET to advance to next menu.
- SET Flow/Rate
Select the par ticular volume unit desired (gallons, liters, etc.).
Then switch to time units and select the time unit desired
(minutes, hours, etc.).
- SET Decimal
Select none, one, or two decimal places on the flow units.
- SET K-Factor
The unit will not function properly until this number is entered.
The K-factor is simply the number of pulses which the flow
meter or flow sensor puts out per gallon of liquid. It is marked
on the Model/Serial tag of Seametrics flow meters and flow
sensor fittings. On adjustable depth flow sensors, the K-factor
must be taken from the chart in the flow sensor instructions,
based on pipe size.
- SET Pulse (scaled) Output 1
An output pulse is activated at the selected volume intervals
if this feature is in use. If a pulse output is not needed, pulse
out does not need to be set.
- SET Pulse (scaled) Output 2
An output pulse is activated at the selected volume intervals
if this feature is in use. If a pulse output is not needed, pulse
out does not need to be set.
- SET 20 mA Rate
The “SET 20mA RATE” programs the maximum flow rate at
which the output is 20 mA full scale, at 5 V or 10 V.
- Clear Total
This function resets the accumulated total back to zero. It is
unrelated to the regeneration function, and can be ignored
unless it is needed.
- SET Regeneration Volume
This is the volume (in the units you have selected; typically
gallons) at which the relay energizes to initiate a regeneration
cycle.
- SET Regeneration Time in seconds (3 digits)
This is the length of time in seconds, the relay remains energized to initiate regeneration. Enter a value slightly over the
minimum time required by the regeneration valve to begin a
cycle.
- SET Relay Mode to one or alternate relays
Choose between single relay (Relay No. 1) and dual relay (Alternate Relays) operation. In alternate relay mode, the first
regeneration will use Relay 1, the next will use Relay 2, and
successive regenerations will switch between the two.
- Clear Total
This function resets the accumulated total back to zero. It is
unrelated to the regeneration function, and can be ignored
unless it is needed.
Operation
Choice of Displays. When all of the settings have been en-
tered, the next press of the SET Key puts the unit in operation. If a T appears at the left side of the display, the values
shown are flow rate and running total. If there is no T, the
values shown are flow rate and units remaining until regeneration. The total increases with flow, and the regeneration quantity counts down. Use the UP Arrow to choose the preferred
display, usually regeneration quantity.
Regeneration Initiation. When the regeneration quantity number first reaches 0, Relay No. 1 energizes for the length of
time which has been set. The regeneration quantity immediately resets and begins counting down again. If alternating
mode has been selected, the next time it reaches 0, Relay
No. 2 will energize, and the cycle after that, will return to Relay No. 1. An output can be manually forced at any time by
pressing the Start/Stop key. The relay will energize for the set
time, and regeneration volume will return to its original setting
to begin counting down again.