Seametrics FT500 Operating Manual

d
C
FT500
Batch Flow Processor
Instructions
o
m
e
i
p
f
PROUDLY MADE IN THE
USA
t
r
e
C
ISO
9001:2008
a
n
y
TABLE OF CONTENTS
General Information
General Information ...................................................................................................................................................Page 4
Features ...........................................................................................................................................................................Page 4
Dimensions ....................................................................................................................................................................Page 4
Specications ................................................................................................................................................................Page 4
Installation
Mounting ........................................................................................................................................................................Page 5
Connections ...................................................................................................................................................................Page 5
Settings and Operation
FT520 Batch Controller ..............................................................................................................................................Page 6
FT520-84 Filter Regeneration .................................................................................................................................Page 7
FT520-86 Flowrate Alarm .........................................................................................................................................Page 8
FT522 Usage Monitor ................................................................................................................................................Page 9
Repair/Troubleshooting
Repair ...............................................................................................................................................................................Page 10
Troubleshooting ...........................................................................................................................................................Page 10
Warranty
Seametrics Limited Warranty ..................................................................................................................................Page 11
FT500 INSTRUCTIONS
Seametrics • 253.872.0284 Page 3 seametrics.com
GENERAL INFORMATION
6.42"
16.31 cm
1/2" NPT
5.67"
14.40 cm
11.81 cm
14.40 cm
FT500 INSTRUCTIONS
The FT500-Series is a batching ow processor with additional output controls. It is designed for use with
Seametrics ow meters and ow sensors, as well as other
manufacturer’s products which have frequency output
proportional to ow. In addition to batch functions, the FT500-Series indicates ow rate, and other data in large 3/8” (9.66 mm) digits on an easily-read, backlit display. Units of measure are user selectable, and range from
milliliters per second to millions of gallons per day. The unit can be 110 Vac powered with a standard 3-wire cord
(included), 220 Vac powered (optional), or DC powered
through an internal terminal strip (battery not included).
Features
Cover Screws
(Can be ordered cross­drilled for seal wire)
Display
An analog output of 4-20 mA is available both in active
and passive loop conguration, and in 0-5 Vdc or 0-10 Vdc outputs, and can be used in applications such as ow
rate logging. Two programmable pulse scaled outputs are
also standard, and can be used, for example, to provide
proportional chemical feed with a pulse-responsive metering pump.
The housing is supplied with two brackets for wall-mount applications, or the top/bottom housings can be easily
separated and reassembled for panel-mount.
Dimensions
16.31 cm
6.42"
Setting Keys
Indicator Lights
1/2" NPT
5.67"
4.65"
Specications*
Power 115 Vac, 50/60 Hz @ 125 mA, 12 Vdc @ 750 mA or 10–16 Vdc (220 Vac optional)
Temperature 32˚ - 130˚ F (0˚ - 55˚ C)
Enclosure Precision cast aluminum, NEMA 4X, panel or wall mount conguration
Batch Outputs Two form C (SPDT) relays, 115 Vac 6 A max
Max Pulse Output 100 mA at 60 Vac/Vdc, opto-isolated, open-collector
Memory Type Non-volatile EEPROM with auto-backup
Sensor Power 12 Vdc, 10 mA
Display Totalizer = 8 digit, Rate = 5 digit, backlit
Units Volume = Gallons, cubic feet, cubic meters, millions of gallons, milliliters, uid ounces, pounds, liters
Analog Output 4-20 mA passive opto-isolated; 4-20 mA active; 0–5 Vdc, or 0–10 Vdc
Sensor Input 1–1000 Hz, ESD protected, interfaces to current sinking sensor output
Environmental NEMA 4X, IP66
Setup Memory Non-volatile EEPROM, auto-backup
*Specications subject to change. Please consult our web site for current data (seametrics.com)
Seametrics • 253.872.0284 Page 4 seametrics.com
Time = Seconds, minutes, hours, days
SEN1
–G
SEN2
Alternate
DC power
Customer Supplies 1A Fuse
Pulse 1
Pulse 2
Pulse Outputs
(for metering pumps)
Regeneration Outputs
AC Power
Relay 1
Relay 2
Main power fuse
250mA
Line Neutral Ground
Ribbon connector
from display board
Resume
Start/Stop
Remote Controls
NO COM NC NO COM NC
Resume
COM
BATCH
+12
Power Signal Ground
RED
WHITE
BLACK
Meter
Dry contact
0-5 V or 0-10 V or 4-20 mA
Analog Switch*
Analog Header
A +
-
B
Active
Passive
Jumpers
A
P
5V
10V
4-20mA
An Output
110 Vac Jumpers
220 Vac Jumper
*Consult Seametrics before changing from factory pr eset
INSTALLATION
5.50"
gasket
PANEL CUTOUT
5.50"
6.03"
6.03"
1/4" holes (4 required)
.375"
FT500 INSTRUCTIONS
Mounting
Wall Mounting. Using the four screws provided, attach
the two foot brackets to the sides of the enclosure. Then
attach the unit to any secure surface by inserting screws
through the mounting holes in the foot brackets.
Panel Mounting. Follow the dimensions below for “Panel Cutout”. Be sure to include the four corner screw
holes. After cutting and drilling, place the front plate on the front side of the panel with its gasket against the panel, and the remainder of the square housing on the back side. Slide the screws through the four holes drilled in the panel, and into the threaded holes in the housing. Tighten until the gasket is rmly compressed against the
panel.
Connections
Expose Terminals. Remove the four screws which hold
the front plate to the lower housing ange. Remove front
plate. The display board is attached to this front plate. It is also connected to the power board by a ribbon cable.
This cable can be disconnected while making connections. Connections can be made inside the enclosure, or the
terminals can be unplugged by gentle tugging for easier access.
Batch Control Connection (if used). Connect the valve or other device(s) to be controlled for starting and stopping
the batch to the appropriate relay terminals. Note: if the staged shutoff (“prewarn”) will not be used, connect to relay one only. Relay 1 remains energized for the entire batch cycle. If a staged shutoff is desired, connect the main valve to Relay 2 (early shutoff) and the low-ow
valve to Relay 1.
Monitor Alarm Connection (if used). Connect the alarm
devices to the appropriate relay terminals. Note that the relays have both normally-open (NO) and normally-closed (NC) contacts.
Analog Connection (if used). This output can be
congured 4-20 mA, 0-5 V or 0-10 V by placing a jumper
in the correct position on the analog header. The analog
switch next to the header selects active (powered) or passive (unpowered) output. NOTE: Consult factory to change internal rmware when changing switch position.
When using the 12 Vdc powered input you may only select passive output.
Caution: Always disconnect power to the unit before opening the terminal cover. Do not reconnect power until all connections have been made and the terminal cover has been replaced.
Power Connection. Connect AC or DC power as desired
to the appropriate terminals. For safety, if using AC power,
be sure to connect the ground terminal provided to a
good earth ground. If using 12 Vdc, use a 12 Vdc 500 mA power supply. Replace the front panel, taking care to
reconnect the ribbon cable if it has been disconnected.
When power is switched on, the display should light up
immediately with meaningful letters or digits.
Connections
Seametrics • 253.872.0284 Page 5 seametrics.com
SETTINGS AND OPERATION
TX Flow Sensor
High-Flow
Valve
Low- Flow
Valve
Tank
FT520
Staged shut-off at end of batch
High-Flow Valve
Low-Flow Valve
Relay 1
Relay 2
NC
COM
NO
NC
NO
COM
Power Source
+
-
FT500 INSTRUCTIONS
FT520 Batch Controller
In Batch Processing Mode, the display indicates a ow rate on the top line, and one of three user-selectable congurations on the bottom line: an accumulated total ow (resettable), accumulated batch ow, or batch process
bar graph. The batch output is controlled via two relays.
The main relay starts and stops the batch as a set, or the auxiliary “prewarn” relay can be used to operate a second
valve. This allows increased accuracy by engaging a staged shut off at the end of the batch.
Settings
Use left arrow and up arrow keys to change settings. Press SET to advance to next menu.
- SET Batch Size
Set the batch size for the desired number of units. If the staged shut-off feature is not being used, this is the only setting
required for the batch.
- SET Prewarn Size
This is only used for a staged shut-off. The number set is the number of units early (before the end of the batch) that Relay 2 will shut off.
- SET Flow/Rate
Select the particular volume unit desired (gallons, liters, etc.).
Then switch to time units and select the time unit desired
(minutes, hours, etc.).
- SET Decimal
Select none, one, or two decimal places on the ow units.
- SET K-Factor
The unit will not function properly until this number is entered.
The K-factor is simply the number of pulses which the ow meter or ow sensor puts out per gallon of liquid. It is marked on the Model/Serial tag of Seametrics ow meters and ow sensor ttings. On adjustable depth ow sensors, the K-factor must be taken from the chart in the ow sensor instructions, based on pipe size.
- SET Pulse (scaled) Output 1
An output pulse is activated at the selected volume intervals if
this feature is in use. If a pulse output is not needed, pulse out
does not need to be set.
- SET Pulse (scaled) Output 2
An output pulse is activated at the selected volume intervals if
this feature is in use. If a pulse output is not needed, pulse out
does not need to be set.
- SET 20 mA Rate
The “SET 20 mA RATE” programs the maximum ow rate at which the output is 20 mA full scale, at 5 V or 10 V.
- Clear Total
This function resets the accumulated total back to zero. It is unrelated to the regeneration function, and can be ignored
unless it is needed.
Operation
Start Batch. Pressing the Start/Stop key starts the batch
by energizing Relay 1. The indicator for Relay 1 will light,
also light, depending on the prewarn setting. If staged shut-off is being used, the Relay 2 indicator light should go out before the end of the batch, at the prewarn set point.
The batch will continue on to the set amount unless it is halted in the middle of the process by pressing the Start/
Stop key again.
Stop Batch/Resume Batch. Pressing the Start/Stop key
anywhere in the batch will stop it. It will remain stopped
until the Resume key is pressed. Pressing the Start/Stop key again allows the batch to restart from zero.
Choice of Displays for Batching. When in Operation Mode, press the UP Arrow to change the type of display. Running Totalizer (“T”) accumulates a Total Flow until it is reset. Batch (“B”) accumulates the ow of the present batch only, then resets. Bar Graph (“❚”) graphically indicates from left to right, how much of the batch has already
accumulated.
Staged Shut-Off Application
indicating normal operation. The indicator for Relay 2 may
Seametrics • 253.872.0284 Page 6 seametrics.com
Connection for Staged Shut-Off
SETTINGS AND OPERATION
FT500 INSTRUCTIONS
FT520-84 Filter Regeneration
In Filter Regeneration Mode, the display indicates a ow rate on the top line, and one of two congurations on the bottom line: an accumulated total ow (resettable), or batch
process remainder. The regeneration process is initiated by
setting a target volume, a value for regeneration time as
well. A single relay or alternate relay setting allows control
of either single tank or alternating dual tank systems.
On the input side, this model can be used with Seametrics ow sensors and meters, as well as with water meters
from other manufacturers. The output can be used to
initiate regeneration in a variety of one-tank and two-tank
water treatment systems. In addition to the regeneration
functions, this unit features displays of ow rate and accumulated ow, as well as programmable pulse output and a 4-20 mA analog output, for use with remote recorders. There are two regeneration relays, which can be used for alternating regeneration of two tanks. The outputs remain on for a duration programmed by the user, depending on
the requirements of the regeneration valve being used. A programmable pulse output can be used as needed to
control a chemical metering pump, for controlled chemical
addition to the water stream.
Settings
Use Left Arrow and UP Arrow keys to change settings. Press SET to advance to next menu.
- SET Flow/Rate
Select the particular volume unit desired (gallons, liters, etc.).
Then switch to time units and select the time unit desired
(minutes, hours, etc.).
- SET Decimal
Select none, one, or two decimal places on the ow units.
- SET K-Factor
The unit will not function properly until this number is entered.
The K-factor is simply the number of pulses which the ow meter or ow sensor puts out per gallon of liquid. It is marked on the Model/Serial tag of Seametrics ow meters and ow sensor ttings. On adjustable depth ow sensors, the K-factor must be taken from the chart in the ow sensor instructions, based on pipe size.
- SET Pulse (scaled) Output 1
An output pulse is activated at the selected volume intervals if
this feature is in use. If a pulse output is not needed, pulse out
does not need to be set.
- SET Pulse (scaled) Output 2
An output pulse is activated at the selected volume intervals if
this feature is in use. If a pulse output is not needed, pulse out
does not need to be set.
- SET 20 mA Rate
The “SET 20 mA RATE” programs the maximum ow rate at which the output is 20 mA full scale, at 5 V or 10 V.
- SET Regeneration Volume
This is the volume (in the units you have selected; typically
gallons) at which the relay energizes to initiate a regeneration
cycle.
- SET Regeneration Time in seconds (3 digits)
This is the length of time in seconds, the relay remains energized to initiate regeneration. Enter a value slightly over the minimum
time required by the regeneration valve to begin a cycle.
- SET Relay Mode to one or alternate relays
Choose between single relay (Relay No. 1) and dual relay (Alternate Relays) operation. In alternate relay mode, the rst regeneration will use Relay 1, the next will use Relay 2, and
successive regenerations will switch between the two.
- Clear Total
This function resets the accumulated total back to zero. It is unrelated to the regeneration function, and can be ignored
unless it is needed.
Operation
Choice of Displays. When all of the settings have been
entered, the next press of the SET Key puts the unit in operation. If a T appears at the left side of the display, the values shown are ow rate and running total. If there is no T, the values shown are ow rate and units remaining until regeneration. The total increases with ow, and the
regeneration quantity counts down. Use the UP Arrow to
choose the preferred display, usually regeneration quantity.
Regeneration Initiation. When the regeneration quantity
number rst reaches 0, Relay No. 1 energizes for the length
of time which has been set. The regeneration quantity immediately resets and begins counting down again.
If alternating mode has been selected, the next time it reaches 0, Relay No. 2 will energize, and the cycle after that, will return to Relay No. 1. An output can be manually forced at any time by pressing the Start/Stop key. The relay will energize for the set time, and regeneration volume will
return to its original setting to begin counting down again.
TX Flow Sensor
FT520-84
Alternating Tanks Application
Connections for Alternating Tanks
Tank 1
Tank 1
Tank 2
Relay 1
Relay 2
Tank 2
NO
COM
NC
NO
COM
NC
Seametrics • 253.872.0284 Page 7 seametrics.com
SETTINGS AND OPERATION
FT500 INSTRUCTIONS
FT520-86 Flowrate Alarm
In Flowrate Alarm Mode, the display indicates a ow rate on the top line, and on the bottom line, an accumulated total ow (resettable). The user sets a minimum and maximum ow rate, and if the ow exceeds the min/max parameter, Relay 1 or Relay 2 will close. The output relay will stay latched until the ow rate increases/decreases back between the min/max settings.
Settings
Use Left Arrow and UP Arrow keys to change settings. Press SET to advance to next menu.
- SET Flow/Rate
Select the particular volume unit desired (gallons, liters, etc.).
Then switch to time units and select the time unit desired
(minutes, hours, etc.).
- SET Decimal
Select none, one, or two decimal places on the ow units.
- SET K-Factor
The unit will not function properly until this number is entered.
The K-factor is simply the number of pulses which the ow meter or ow sensor puts out per gallon of liquid. It is marked on the Model/Serial tag of Seametrics ow meters and ow sensor ttings. On adjustable depth ow sensors, the K-factor must be taken from the chart in the ow sensor instructions, based on pipe size.
- SET Pulse (scaled) Output 1
An output pulse is activated at the selected volume intervals if
this feature is in use. If a pulse output is not needed, pulse out
does not need to be set.
- SET Pulse (scaled) Output 2
An output pulse is activated at the selected volume intervals if
this feature is in use. If a pulse output is not needed, pulse out
does not need to be set.
- SET 20 mA Rate
The “SET 20 mA RATE” programs the maximum ow rate at which the output is 20 mA full scale, at 5 V or 10 V.
- SET Low Flow Alarm
Set the desired minimum ow rate at which you want an
alarm to occur. Low alarm corresponds to alarm Relay 1 (see Connections diagram).
- SET Hi Flow Alarm
Set the desired maximum ow rate at which you want an alrm to occur. High alarm corresponds to alarm Relay 2 (see
Connections diagram).
- Clear Total
This function resets the accumulated total back to zero. NOTE: The “Start/Stop” and “Resume” keys are not used in ow alarm
mode.
Operation
The last press of the key returns the unit to operation mode.
Flow Monitoring. The ow rate and accumulated displays
begin showing current data. The accumulated total
increases indenitely unless it is reset.
Alarms. Alarm Relay 2 activates when ow reaches the high alarm set point. Because of the built-in hysteresis, the relay does not deactivate until the ow rate has reached 10% below the high alarm set point. Similarly, alarm Relay 1 activates when ow reaches the low alarm set point, and does not deactivate until ow returns to 10% above the
low alarm set point.
NO COM
NC
NO
COM
NC
-Autodialer
-Pump
-Alarm
-Valve Shutoff
Alarm 1
Alarm 2
Seametrics • 253.872.0284 Page 8 seametrics.com
SETTINGS AND OPERATION
COM
FT500 INSTRUCTIONS
FT522 Usage Monitor
In Usage Monitor Mode, the display indicates one of two congurations: an elapsed time and elapsed ow, or a ow rate and accumulated total ow (resettable). A time period is set to monitor for a set maximum total ow. If the total ow is reached within the set time, an output relay is closed.
The output relay stays latched until the system either resets
automatically after the set time, or is reset manually via the
StartStop button. A reset condition clears the elapsed time
and ow, but not the accumulated total ow.
The FT522 is a owmeter monitor with added output and alarm features. It is designed for use with Seametrics ow meters and sensors, as well as other units which have a pulse or frequency output. It displays ow rate and total in large digits on an easily-read backlit display. Units are user selectable between gallons, cubic feet, and cubic
meters. The primary output of this unit is a user-set alarm
relay which signals excessive total ow within a given time
period (up to 48 hours). This is typically used to detect an elevated usage level in a cooling tower or potable water
application. The dual relays can be connected to an alarm, autodialer, or any other switch-controllable device. In addition to the usage alarm, the FT522 has analog output (4-20 mA, 0-5 Vdc or 0-10 Vdc) and programmable pulse output. These can be used with an external data logger or to provide proportional chemical feed, using an externally-
controlled metering pump.
Settings
Use Left Arrow and UP Arrow keys to change settings. Press SET to advance to next menu.
- SET Flow/Rate
Select the particular volume unit desired (gallons, liters, etc.).
Then switch to time units and select the time unit desired
(minutes, hours, etc.).
- SET Decimal
Select none, one, or two decimal places on the ow units.
- SET K-Factor
The unit will not function properly until this number is entered.
The K-factor is simply the number of pulses which the ow meter or ow sensor puts out per gallon of liquid. It is marked on the Model/Serial tag of Seametrics ow meters and ow sensor ttings. On adjustable depth ow sensors, the K-factor must be taken from the chart in the ow sensor instructions, based on pipe size.
- SET Pulse (scaled) Output 1
An output pulse is activated at the selected volume intervals if
this feature is in use. If a pulse output is not needed, pulse out
does not need to be set.
- SET Pulse (scaled) Output 2
An output pulse is activated at the selected volume intervals if
this feature is in use. If a pulse output is not needed, pulse out
does not need to be set.
- SET Time Period from 01–48 hours
This is the monitoring period at the end of which the unit will
alarm if total ow has exceeded its setting. Set this monitoring
period for 01–48 hours. NOTE: that if the digit to the right is set to “9”, the digit to the left will only go to “3” This is because 48 is the maximum setting allowed.
- SET Alarm Reset
Set to automatic or manual.
- SET Alarm Point in Flow (8 digits)
This is the maximum total ow allowed in the time period set above. Use the same procedure as above to set this value, up to
eight digits. The units are those previously chosen.
- SET 20 mA Rate
The “SET 20 mA RATE” programs the maximum ow rate at which the output is 20 mA full scale, at 5 V or 10 V.
- Clear Total
This function resets the accumulated total back to zero in the rate/total conguration. It does not affect the data in the elapsed time/ow conguration.
Operation
The last press of the key returns the unit to operation mode. In this mode, pressing either arrow key will toggle back and forth between two displays, one for ow monitoring and
the other for usage monitoring.
Usage Alarm. Pressing the Start/Stop key will start the clock and zero the total of the usage monitor. The clock
will increase and the total will accumulate (provided there
is ow) until the end of the monitoring period. At that time, the usage total and clock will zero automatically and
the cycle will start over. If the usage total ever reaches its
alarm point within the monitoring time, the usage alarm relays will energize and remain on until the Resume key is pressed. If the Resume key is pressed during a monitoring cycle, it will freeze the cycle at its current point. Pressing it
again allows the cycle to resume where it left off.
Flow Monitoring. The “Rate” indication gives the current
rate of ow. “Total” is a running total of ow which increases indenitely unless it is reset.
Autodialer
Alarm
110 Vac
Alarm 1
Alarm 2
Main
power fuse
250mA
part # 26926
Hot
Neut
Gnd
NO COM
NC
NO
NC
Seametrics • 253.872.0284 Page 9 seametrics.com
REPAIR/TROUBLESHOOTING
FT500 INSTRUCTIONS
Repair
The only eld-repairable component on the FT520 is the fuse. If failure is due to a cause other than a blown fuse, it is necessary to replace the entire board stack. Contact your distributor for information.
Troubleshooting
Problem Probable Causes Things to try…
Blank Display No power to unit Check for minimum 12 Vdc at power terminals
Short in sensor circuit Disconnect sensor, see if display returns (zero
ow rate)
Display missing segments Damaged display module Contact distributor for return/replacement
Display reading meaningless characters
Display reads normally, ow
rate incorrect
Display reads normally,
no (or wrong) pulse output
Display reads normally,
no (or wrong) 4-20 mA output
Display reads zero when there is ow
Unit's microcontroller crashed Disconnect and reconnect power. If problem
repeats, contact distributor for return/
replacement
Wrong K-factor entered Check K-factor, enter proper one if in error
Wrong pulse output setting Check "SetP" to see if it is set correctly
Polarity reversed on pulse output
Reverse leads and see if problem corrects
terminals
Wrong 20 mA setting Check "Set20" to see if it matches target top
ow rate
Inadequate loop power supply voltage
Polarity incorrect in 4-20 mA loop
Check voltage. For 4-20 mA applications 24 Vdc
recommended
Compare to Connections diagram
circuit
Flow sensor failed Consult ow sensor manual for how to test
Break in ow sensor circuit Check for continuity with multimeter
Display reads ow rate when
there is none
Long ow sensor wire, running
parallel to power lines
Reroute wire or switch to shielded wire
Flow sensor malfunction See ow sensor manual to check
Seametrics • 253.872.0284 Page 10 seametrics.com
SEAMETRICS LIMITED WARRANTY
FT500 INSTRUCTIONS
The limited warranty set forth below is given by Seametrics, with respect to Seametrics and INW brand products purchased in the
United States of America.
Seametrics warrants that products manufactured by Seametrics, when delivered to you in new condition in their original containers and properly installed, shall be free from defects in material and workmanship. Seametrics products are warranted against
defects for a period of two (2) years from date of installation, with proof of install date. If no proof of install date can be
provided, warranty period will be two (2) years from date of shipment from Seametrics, as dened on Seametrics’ invoice.
Seametrics’ obligation under this warranty shall be limited to replacing or repairing the part or parts, or, at Seametrics’ option, the products, which prove defective in material or workmanship. The following are the terms of Seametrics’ limited warranty:
a. Buyer must give Seametrics prompt notice of any defect or failure and satisfactory proof thereof. b. Any defective part or parts must be returned to Seametrics’ factory or to an authorized service center for inspection. c. Buyer will prepay all freight charges to return any products to Seametrics’ factory, or another repair facility. as designated by
Seametrics.
d. Defective products, or parts thereof, which are returned to Seametrics and proved to be defective upon inspection, will be
repaired to factory specications.
e. Seametrics will deliver repaired products or replacements for defective products to the buyer (ground freight prepaid) to the
destination provided in the original order.
f. Products returned to Seametrics for which Seametrics provides replacement under this warranty shall become the property
of Seametrics.
g. This limited warranty covers all defects encountered in normal use of Seametrics products, and does not apply to the
following cases:
i. Loss of or damage to Seametrics product due to abuse, mishandling, or improper packaging by buyer ii. Failure to follow operating, maintenance, or environmental instructions prescribed in Seametrics’ instruction manual iii. Products not used for their intended purpose iv. Alterations to the product, purposeful or accidental v. Electrical current uctuations vi. Corrosion due to aggressive materials not approved for your specic product vii. Mishandling, or misapplication of Seametrics products viii. Products or parts that are typically consumed during normal operation
ix. Use of parts or supplies (other than those sold by Seametrics) which cause damage to the products, or cause
abnormally frequent service calls or service problems
h. A new warranty period shall not be established for repaired or replaced material, products, or supplied. Such items shall
remain under warranty only for the remainder of the warranty period on the original materials, products, or supplies.
i. In the event that equipment is altered or repaired by the buyer without prior written approval by Seametrics, all warranties
are void. Damage caused by equipment or accessories not manufactured by Seametrics may void the product’s warranty.
j. SOFTWARE: The Seller grants the user a non-exclusive license to use Seametrics’ software, according to the following
limitations and conditions:
i. The user may install the software on one or more desktop or laptop computers. ii. All title and intellectual rights to the software are owned by Seametrics. iii. No copies may be made or distributed except as described above. iv. The user may not modify or reverse-engineer the software.
THE FOREGOING WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, WHETHER ORAL, WRITTEN, EXPRESSED, IMPLIED OR STATUTORY. NO IMPLIED WARRANTY, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, APPLIED TO THE PRODUCTS AFTER THE APPLICABLE PERIOD OF THE EXPRESS LIMITED WARRANTY STATED ABOVE, AND NO OTHER EXPRESS WARRANTY OR GUARANTY, EXCEPT AS MENTIONED ABOVE, GIVEN BY ANY PERSON OR ENTITY WITH RESPECT TO THE PRODUCTS, SHALL BIND SEAMETRICS. SEAMETRICS SHALL NOT BE LIABLE FOR LOSS OF REVENUES, OR PROFITS, OR INCONVENIENCES, EXPENSE FOR SUBSTITUTE EQUIPMENT OR SERVICE, STORAGE CHARGES, LOSS OF DATA, OR ANY OTHER SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGE CAUSED BY THE USE OR MISUSE OF, OR INABILITY TO USE THE PRODUCTS, REGARDLESS OF THE LEGAL THEORY ON WHICH THE CLAIM IS BASED, AND EVEN IF SEAMETRICS HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. IN NO EVENT SHALL RECOVERY OF ANY KIND AGAINST SEAMETRICS BE GREATER IN AMOUNT THAN THE PURCHASE PRICE OF THE PRODUCT SOLD BY SEAMETRICS AND CAUSING THE ALLEGED DAMAGE. WITHOUT LIMITING THE FOREGOING, YOU ASSUME ALL RISK OF LIABILITY FOR LOSS, DAMAGE, OR INJURY TO YOU AND YOUR PROPERTY AND TO OTHERS AND THEIR PROPERTY ARISING OUT OF USE OR MISUSE OF, OR INABILITY TO USE THE PRODUCTS NOT CAUSED DIRECTLY BY THE NEGLIGENCE OF SEAMETRICS.
SOME STATES DO NOT ALLOW LIMITATIONS ON THE DURATION OF AN IMPLIED WARRANTY, SO THE ABOVE LIMITATIONS MAY NOT APPLY TO YOU. SIMILARLY, SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITATIONS OF CONSEQUENTIAL DAMAGE, SO THE ABOVE LIMITATION OR EXCLUSION MAY NOT APPLY TO YOU. THIS LIMITED WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS; HOWEVER, YOU MAY ALSO HAVE OTHER RIGHTS WHICH MAY VARY FROM STATE TO STATE.
Seametrics • 253.872.0284 Page 11 seametrics.com