Seametrics AO55 Operating Manual

AO55
BLIND ANALOG TRANSMITTER INSTRUCTIONS
A O 5 5 B L I N D A N A L O G T R A N S M I T T E R I N S T R U C T I O N S
GENERAL INFORMATION, SPECIFICATIONS and INSTALLATION
Loop Power (Vdc)
Load Resistance (Ohms)
700 900 1100 1300
Load vs. Supply Voltage
Ope r a t i n g
Reg i o n
36
34
32
30
28
26
24
1500
GENERAL INFORMATION INSTALLATION
The Seametrics AO55 is a blind (non-indicating) 4-20 mA transmitter, designed for use with almost all Seametrics flow sensors. It accepts a pulse frequency input from the flow sensor, and conver ts this input into a continuous analog output signal. Power for the transmitter is taken from the current loop itself, so only two wires are required. The digital design makes it possible to span the unit in the field without tools. The frequency at which 20 mA is desired is entered on a set of rotary switches, and an internal microcontroller automatically scales all other values accordingly. An additional benefit of the microcontroller is its ability to average inputs, for smoothing of the output signal. The degree of averaging can be selected in the field, from 2 to 16 seconds.
For maximum environmental protection, the electronic components are encased in a special semi-flexible urethane potting material. The housing is cast from aluminum and fuse-coated. The clamshell housing is connected directly to the flow sensor or, in the wall mount version, provided with mounting feet.
The AO55 will operate on a relatively wide range of current loop voltages, 24 to 36 Vdc. Lower voltages limit the load that can be applied to the loop without distortion of the signal. (See Load/Supply chart if there is a question regarding voltage vs. load.) A built-in power regulator supplies the appropriate power to the flow sensor.
Mounting. The AO55M comes mounted on the flow sensor. The AO55W wall mount comes with mounting feet and requires four screws to attach it to any stable surface.
Connection. On either style of housing, the upper portion must be removed to make connections. Use a standard hex wrench (5/32” or 4 mm) to loosen the screws, then remove the upper half. The connections are made to terminal blocks in the upper half, which contains the potted electronics.
Consult the Connections diagram before connecting to the current loop. The only connections required on an AO55M are the positive and negative loop connections. On an AO55W, the sensor must also be connected, since it is remote from the transmitter. Be careful to follow the color coding of the flow sensor wires in order to establish the correct polarity. Incorrect polarity can damage the sensor.
Typical applications for this transmitter are telemetr y (or SCADA), distributed control systems, programmable controllers, data logging, and chart recording.
SPECIFICATIONS*
Power
Temperature
Input
Input Averaging
Response Time
Frequency Minimum
Maximum
Setting
Output
*Specifications subject to change • Please consult our website for current data (www.seametrics.com).
24 - 36 Vdc
32˚ - 130˚ F (0˚ - 55˚ C)
Open-collector solid state sensor
2 - 16 seconds (switch selectable)
2-60 seconds; 90% of full scale (dependent on input averaging)
10 Hz (@20 mA)
999.9 Hz
4 Rotary DIP switches
Proportional 4-20 mA
0
9
8 7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
8 7
6
5
4
3
2
1
0
9
8 7
6
5
4
3
2
1
Power
Sensor
4-20 mA
AO55
Frequency
SETTINGS, CALIBRATION and FREQUENCY
0
9
8
7
6
5
4
3
2
1
0
9
8 7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
8 7
6
5
4
3
2
1
AO55
Frequency
Power
Sensor
4-20 mA
UP DOWN
L R
0
9
8 7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
8 7
6
5
4
3
2
1
0
9
8 7
6
5
4
3
2
1
AO55
Frequency
Power
Sensor
4-20 mA
4mA Adjust
Force 4 mA
Force 20 mA
20 mA Adjust
S
SETTINGS
Setting Frequency. The AO55 conver ts a train of off/on
pulses from the flow sensor into a continuous milliAmp signal that ranges from 4 mA at zero flow to 20 mA at the desired maximum flow. The desired maximum is determined by the user and entered as a frequency as follows:
1)
Decide what flow rate should represent the top of the scale. This is ordinarily the maximum expected flow, or a value just above it, in gallons per minute.
2)
Locate the K-factor of the flow sensor (found on the meter or fitting, or in the instruction manual, depending on meter model). The K-factor is the number of pulses the flow sensor produces per gallon of flow.
3)
Calculate frequency, using this formula:
K-Factor x Top Flow (GPM) = Frequency 60
4)
Enter the frequency using the four rotary Frequency switches. Note the decimal point between the third and fourth switches.
SETTING FREQUENCY EXAMPLE
In an installation with an estimated maximum flow
1) rate of about 150 GPM, a flow rate of 170 GPM is selected as the full-scale maximum, the flow at which the current loop will register 20 mA.
In this example, the K-factor (found on the meter
2) or fitting, or in the manual) is “K = 54.50”.
Calculate the frequency as
3)
54.50 x 170 60
4)
Rounding to one decimal point, enter 154.4 on the
= 154.42
rotary switches by turning the rotary switch pointers to the desired digits.
1 5 4
.
4
Setting Averaging Time. For most applications, this
step can be ignored, as the standard setting will work fine. However, when a particularly steady output signal is desired, or in large pipe, a larger averaging period may be desirable. Note however that the averaging period requires a tradeoff, since a longer averaging period implies a slower response time. If steady signal is more impor tant than fast response, increase the averaging time as desired. See the diagram below for the switch positions and their corresponding times.
Switch Position
Seconds L R 2 down down 4 down up 8 up down 16 up up
Checking Calibration
Normally it should not be necessar y to check calibration, since the digital design of this unit virtually eliminates drift. However, there are two types of calibration check that can be performed. Look at the diagram below to locate the 4 and 20 mA force switches. To force the 4 mA output, put its switch in the up position. Check the current output at the Power terminals, and if necessary trim to 4.00 mA using the appropriate trimpot. Return the switch to the down position, and repeat the process with the 20 mA switch.
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
AO55
Frequency
Power
Sensor
4-20 mA
-
+
4-20 mA Device
(e.g. Pump, PLC,
Chart Recorder)
24-36 Vdc
Power Supply
(may be
included in
control unit)
Mechanical
Sensor
Red
White
Black
-
+
-
+
S
+
_
S
+
+ _
_
Magmeter
Terminal Block
AO55
Terminal
Block
Power
Forward
Output
24 Vdc
-
+
Wiring AO55 to Mechanical Meter
Wiring AO55 to Magmeter
Green
White
(Either/Or)
CONNECTIONS and TROUBLESHOOTING
CONNECTIONS
The AO55 can be wired to either a mechanical meter or a magmeter. See alternative configurations below.
TROUBLESHOOTING
Problem
No analog signal at reading device
Output stuck at 4 mA
mA signal does not
match ow rate
Probable Cause Try...
Break in current loop
Dead power supply Reversed polarity
No frequency input from ow sensor
Inadequate voltage
Wrong frequency setting
Seametrics I n c o r p o r a t e d • 1 9 0 26 72nd Aven u e S o u t h • K e n t , W a shington 980 3 2 • U S A
(P) 253.87 2 . 0 2 8 4 • ( F ) 2 5 3 . 8 7 2.0285 • 1.8 0 0 . 9 7 5 . 8 1 5 3 • w w w . s eametrics.co m
Check if loop indicator light is on
Check multimeter voltage on power supply Check polarity
Check if ow sensor rotor is turning freely (mechanical meters only)
Check ow sensor connections Check ow sensor polarity Be sure terminal blocks are rmly plugged in With ow sensor disconnected, use short wire
to repeatedly short between sensor “sig” and “-” terminals. Output should rise. Verify 3-second pulse output (EX meters only)
Check load vs. supply chart Review setting procedure Check multimeter voltage on power supply
LT-65200015-B
6/24/09
Loading...