Sea Breeze 24a43zcx, 24h43zcx Installation Guide

MINI-SPLIT
INSTALLATION AND MAINTENANCE
MANUAL
FOR MODELS
24A43ZCX 24H43ZCX
950-0057-revG 01-19-2007
TABLE OF CONTENTS
Installation Notes ...........................................................................................2
Installation Considerations ...........................................................................3
Unit Installation (indoor) ................................................................................4
Unit Installation (outdoor)..............................................................................5
Main Power Wiring…………………………………………………………………6
Initial Start-up..................................................................................................8
Refrigerant Charge…………………………………………………………………9
Specifications...........................................................................................10-11
Pressure Curve……………………………………………………………………12
Warranty ........................................................................................................13
Technical Support ........................................................................................13
-1-
Installation and Maintenance Manual
Report all Shipping Damage to Carrier IMMEDIATELY, Check units and box exterior for damage
NOTE TO INSTALLER
This manual is to aid the qualified HVAC contractor in the Installation and Maintenance of this Mini Split system.
Please read and understand these instructions prior to installing the unit, failure to comply with these instructions may result in improper installation, operation and maintenance, possibly resulting in fire, electrical shock, property damage, personal injury or death.
Installers please retain this manual for future reference; please pass warranty registration to end user. If Technical Assistance is required during installation or start up, please call 704-504-8590 to speak to a Technical Service Engineer. Before calling please have the Model and Serial numbers available.
Safety Instructions Read all the instructions, install and operate the system per those instructions. Use the unit only in the manner described in this manual.
1. Check Rating Plate for correct system voltage before installing the unit installing and operating a unit with the incorrect voltage may result in malfunction or other issues and will void the warranty.
2. Units must be connected to a correctly grounded Electrical Supply.
3. Do not use the units if they have been dropped or otherwise damage or installed incorrectly.
The manufacturer of the unit will not be liable for any damages caused by failure to comply with the installation and operating instructions in this manual.
The unit Rating Plate contains pertinent information to the unit operation; please refer to it as required. Completely read all Instructions prior to assembling installing, operat ing, or working on these un its. Inspect all parts for damage
prior to installation and start up. Units must be installed by a Qualified HVAC Contractor.
Sea Breeze installation kit LS3858CSB is highly recommended for all installations.
-2-
Installer Supplied Items
The following Items are necessary for the installation of the unit. An Installation Kit can be purchased that in cludes these Items. Refrigerant Line Set: Flare Connection only, suitable for R410A with both lines insulated, max length 50ft. High Voltage Interconnect wiring: 14 AWG wiring from Outdoor unit to Indoor unit for Power and Control. Condensate tubing: Per local codes to remove condensate from the indoor unit. The following Items are necessary for installation but are NOT included in the Installation Kit.
Main System Breaker: Sized per unit requirements, to be mounted adjacent to Outdoor unit. Refrigerant: R410A required for additional line set charge. Mounting Hardware: Wall Anchors, Condenser Pad etc.
Items for Consideration
Application
Check the application of the unit prior to installation, certain applications require additional components or installation parameters.
Computer or Data Server Rooms
These require ballpark sizing of approximately 12,000 Btu/h Capacity per 250 Sq Ft of room size. The units will be running 24/7, so a Low Ambient Head Pressure Controller (See accessories), a Crankcase Heater and possibly a Wind Baffle (Field Supplied for cooling below 32°F) must be installed.
Offices and Commercial Spaces, Churches etc
These require ballpark sizing of approximately 12,000 Btu/h Capacity per 400 Sq Ft of room size. The units could have the possibility of providing cooling with ambient temperatures below 65°F, so a Low Ambient Head Pressure Controller (See accessories) is required as is a Crankcase Heater (field supplied).
Residential, Bedrooms, Family Rooms etc
These require ballpark sizing of approximately 12,000 Btu/h capacity' per 600 Sq Ft of room size. Low Ambient controllers typically are not needed, unless a home office application is required.
NOTICE:
Heat Pumps are a great application, however the units do not feature any back up resistance heat, so we do not recommend their use as a primary source of heat in areas where the winter temperatures fall below 30°F.
Installation
Determine the best location for mounting the Indoor unit. It must be located a minimum of 4 ft from the floor. Paying close attention to the air circulation in the room, 9,000 &12,000 BTU units throw air approximately 15ft, 18,000 & 24,000 BTU units throw air approximately 25ft. Ensure no obstacles to airflow exist.
Locate the Indoor and Outdoor units as close together as possible, maximum line set run in cannot BE EXCEEDED, then determine how the Interconnect piping, wiring and condensate hose is to be ru n.
-3-
LINESET INFORMATION
MODEL NUMBER PART NUMBER LINE SIZES
24A43ZCX LS3858CSB 3/8” Liquid – 5/8”Suction
24H43ZCX LS3858CSB 3/8” Liquid – 5/8”Suction NOTE: All units have a Maximum Line-set Horizontal length of 50 ft and maximum vertical lift of 16 ft. Do not exceed these lengths. Ensure that all panels can be removed for service as required
Certification
AII Sea Breeze Ductless Mini Splits are certified by UL under UL standard 1995 Performance is certified by our certification under the ARI 210/240 Program.
Controls and Components
Units are supplied with a wireless remote controller, which communicates with the unit Microproce ssor controller. The return air temperature sensor mounted on the unit then controls the unit operation. Several modes of operation are available to the end user depending on the type of comfort required. AII unit operating functions are controlled via the remote controller.
Optional Controls and Components Low Ambient Controller: ICM 326H must be used in Data Room or Commercial applications
For a wiring diagram please follow general diagram supplied with ICM Controller. Probe must be located in the fin pack or on a return bend that measures approx 100°F during normal operation.
Condensate Pump: Field Installed Aspen brand of Condensate Pump (model ASP-MO-115)
Follow their wiring diagram recommendations. This pump is installed externally to the unit.
UNIT INSTALLATION
Follow Instructions, failure to follow instructions may cause possible malfunction and void any warranty.
Step 1
Remove Indoor and Outdoor units from the carton/box Indoor unit carton contains Remote Control and Batteries, ensure these are kept in a safe place during installation.
Step 2
Locate area to Install Indoor unit Indoor unit must be located a minimum of 4ft. from the floor and 6” from the ceiling. Choose an area where the wall is plumb and determine how to best to run the uni t interconnects.
Ensure no obstacles to Airflow are directly in front of the unit, for a minimum of 12ft. for 9/12,000 Btu/h units and 16ft. for 18/24,000 Btu/h units. Do not install the Indoor unit units in areas exposed to high humidity (RH of 80% plus), direct sunlight and direct heat from stoves or other devices.