Scotsman Ice Machine C0322 Service Manual

Prodigy Series Modular Cuber
Technical Service Manual
Models C0322, C0522, C0722, C0330, C0530, C0630, C0830, C1030, C1448, C1848 and C2148
also includes CB0522, CB0330, CB0530, CB0630, CB0830 and CB1030
Introduction
Table of Contents
Model Number Description ......... page 2
Water ....................page 3
General Installation - Air or Water Cooled . page 4
Water purge setting ............ page 8
General Installation - Remote ....... page 9
Pre-Charged Tubing Coupling Connections page 17
General Installation - Remote ....... page 18
Adjustments ................ page 20
Prodigy Cuber System Information..... page 21
Controller Information ........... page 22
How It Works - Air Cooled ......... page 24
How It Works - Water Cooled ....... page 25
How It Works - Remote........... page 26
Electrical Sequence - Air or Water Cooled. page 27
Electrical Sequence - Remote Cooled . . . page 29
Diagnostics - Water Cooled ........ page 47
Low ice Making Capacity - Water Cooled . page 50
Makes Excessive Noise - Water Cooled . . page 51
Diagnostics - Remote Air Cooled ..... page 52
Low Ice Making Capacity - Remote .... page 55
Makes Excessive Noise - Remote ..... page 56
Test Procedures - Sensors......... page 57
Ice Thickness Sensor ........... page 58
Water Level Sensor ............ page 59
Temperature Sensors ........... page 60
Test Procedures - Loads .......... page 61
Compressor Electrical Chart ........ page 62
Refrigerant Charges ............ page 63
Test Procedures - Loads
Technical Information ........... page 72
.......... page 64
Remote Schematics ............ page 31
Electrical Component Details ....... page 32
Refrigeration ................page 35
Water System ............... page 36
Control Operation ............. page 37
Control Safeties .............. page 38
Restarts................... page 39
Control Button Use (from standby) ..... page 40
Control Button Use - continued ...... page 41
Diagnostics – Air Cooled .......... page 42
Low Ice Making Capacity - Air Cooled . . . page 45
Makes Excessive Noise - Air Cooled.... page 46
May 2011 Page 1
Heat Load & Condenser Water GPM . . . page 73
Controller Differences ........... page 74
Thermistor Values ............. page 75
Performance Data ............. page 76
Performance Data - Remotes ....... page 87
Wiring Diagrams .............. page 95
Wiring Diagram ............... page 103
Repair Procedures ............. page 108
Refrigeration Removal and Replacement Procedures
.......................page 116
Optional add-on control information .... page 121
Selected Prodigy Cuber Suction Graphs. . page 126
Wiring Diagram - 50 Hz .......... page 129
Model Number Description
Example:
C0530SA-1C
C= cuber. CB = Prodigy Advanced Sustainability Cuber
05= nominal ice capacity in 100s of pounds
30= nominal width of cabinet. Other sizes are 22 and 48.
S= Cube size. S=small or half dice cube. M=medium or full dice cube
A=Condenser type. A=air cooled. W=water cooled. R = Remote
-1=Electrical code. -1=115 volts. -32=208-230 single phase. -3=208-230 three phase.
-6=230 50 Hz C=Series revision code. C=third series
Note: In some areas of this manual model numbers may include only the first five characters of the model number, meaning that the cube size, condenser type and voltage differences are not critical to the information listed there.
Scotsman reserves the right to make design changes and/or improvements at any time. Specifications and design are subject to change without notice.
September 2011 Page 2
Water
The quality of the water supplied to the ice machine will have an impact on the time between cleanings and ultimately on the life of the product. There are two ways water can contain impurities: in suspension or in solution. Suspended solids can be filtered out. In solution or dissolved solids cannot be filtered, they must be diluted or treated. Water filters are recommended to remove suspended solids. Some filters have treatment in them for suspended solids. Check with a water treatment service for a recommendation.
RO water. This machine can be supplied with Reverse Osmosis water, but the water conductivity must be no less than 10 microSiemens/cm.
Potential for Airborne Contamination
Installing an ice machine near a source of yeast or similar material can result in the need for more frequent sanitation cleanings due to the tendency of these materials to contaminate the machine. Most water filters remove chlorine from the water supply to the machine which contributes to this situation. Testing has shown that using a filter that does not remove chlorine, such as the Scotsman Aqua Patrol, will greatly improve this situation, while the ice making process itself will remove the chlorine from the ice, resulting in no taste or odor impact. Additionally, devices intended to enhance ice machine sanitation, such as the Scotsman Aqua Bullet, can be placed in the machine to keep it cleaner between manual cleanings.
Water Purge
Cube ice machines use more water than what ends up in the bin as ice. While most water is used during ice making, a portion is designed to be drained out every cycle to reduce the amount of hard water scale in the machine. That’s known as water purge, and an effective purge can increase the time between needed water system cleaning.
In addition, this product has the capability to automatically vary the amount of water purgeed based on the purity of the water supplied to it. The water purge rate can also be set manually. Adjustments of purge due to local water conditions are not covered by warranty.
October 2012 Page 3
General Installation - Air or Water Cooled
Location Limitations:
The product is designed to be installed indoors, in a controlled environment. Air cooled models discharge very warm air into the room out the back. Space must be allowed at the left side and back for air intake and discharge. Water cooled models discharge warm water into the building’s drain. Space needs to be provided on both sides and above for service access.
Space Limitations
Note: Although the machine will function, ice capacity of air cooled machines will be significantly reduced with minimal clearance at the sides, back and top. Some space is recommended for service and maintenance purposes on all models.
6" of space at the sides and back are required for adequate operation. To get the most capacity, locate the machine away from heat producing appliances and heating ducts.
22 and 30 inch wide models: Airflow is in the left side, out the back (as viewed from the front).
48 inch wide models: Air flow is in the front and left side and out the back.
Environmental Limitations
Minimum Maximum
Air temperature 50
Water temperature 40
o
F. 100oF.
o
F. 100oF.
Water pressure 20 psi 80 psi
Power supply – acceptable voltage ranges
Minimum Maximum
115 volt model 104 volts 126 volts
208-230 volt model 198 volts 253 volts
Warranty Information
The warranty statement for this product is provided separately from this manual. Refer to it for applicable coverage. In general warranty covers defects in material or workmanship. It does not cover maintenance, corrections to installations, or situations when the machine is operated in circumstances that exceed the limitations printed above.
October 2012 Page 4
General Installation - Air or Water Cooled
Plumbing Requirements
All models require connection to cold, potable water. A hand actuated valve within site of the machine is required. Air cooled models have a single 3/8” FPT inlet water connection.
Water cooled models have the same inlet fitting plus an additional 3/8” FPT condenser inlet water connection.
Water Filters
If connecting to water filtration, filter only the water to the reservoir, not to the condenser. Install a new cartridge if the filters were used with a prior machine.
All models require drain tubing to be attached to them. Air cooled models have a single ¾” FPT drain fitting in the back of the cabinet. Water cooled models have the same fitting plus an additional ½” FPT drain fitting in the back of the cabinet.
Install new tubing when replacing a prior ice machine, as the tubing will have been sized for the old model and might not be correct for this one.
Note: This NSF listed model has a 1" anti-back flow air gap between the water inlet tube end and the highest possible reservoir water level, no back flow device is required for the potable water inlet.
Drain Tubing:
Use rigid drain tubes and route them separately – do not Tee into the bin’s drain and, if water cooled, do not Tee the condenser drain into the reservoir or bin drain.
Vent the reservoir drain. A vertical vent at the back of the drain, extended about 8 – 10” will allow the gravity drain to empty and also keep any surges during draining from discharging water out the vent..
Horizontal runs of drain tubing need a ¼” fall per foot of run for proper draining.
Follow all applicable codes.
August 2013 Page 5
General Installation - Air or Water Cooled
Electrical
See the spec sheet or User's Manual for Minimum Circuit Ampacity or Maximum Fuse Size ratings.
The machine is not supplied with a power cord, one must either be field installed or the machine hard-wired.
The dataplate on the back of the cabinet details the power requirements, including voltage, phase, minimum circuit ampacity and maximum fuse size. HACR type circuit breakers may be used in place of fuses. Extension cords are not permitted. Use of a licensed electrician is recommended.
Electrical connections are made inside the junction box in the back panel of the ice machine.
Follow all applicable local, state and national codes.
October 2012 Page 6
General Installation - Air or Water Cooled
Note: Indentations may be deeper on C0322 and C0330
Adjustments
Ice Bridge Thickness
Caution: Do not make the bridge too thin or the machine will not harvest properly. Bridge thickness adjustments are not covered by warranty.
Shut machine off.
Access the ice thickness sensor.
Too Big
Check gap between metal tip and evaporator grid. Small cube standard gap is 3/16 inch, medium cube standard gap is 7/32 inch. To set, place a 3/16" (small cube) or 7/32" (medium cube) drill bit between sensor tip and evaporator to check. Adjust gap using adjustment screw.
Ice Bridge Thickness Measurement
Adjustment Screw
1/8" indentation
1/8-3/16"
bridge
Just Right
Too Small
Restart unit and check ice bridge. Repeat as needed.
Evaporator
Ice Thickness Sensor
Gap
Ice Thickness Sensor Adjustment
Gap
Side View of Evaporator and Ice Thickness
Sensor
October 2012 Page 7
Water purge setting
The water purge is factory set to the Automatic setting. The setting can be changed to one of 5 manual settings or placed on automatic. The purge setting shows in the Code Display.
purge setting
Water Type
To set:
Switch the machine OFF by holding the Off button in until a number or the letter A shows on the display.
Press and release the On button repeatedly until the number on the display corresponds to the desired setting.
Press and release the Off switch again to return to the normal control state.
1­Minimum
RO water or equivalent, TDS less than 35
2­Moderate3-Standard
Low TDS non-RO water
Setting for typical water
4­Heavy
High TDS water
5­Maximum
Very high TDS water, greater than 256
A - Automatic
Any with conductivity not less than 10 microSiemens/ cm
October 2012 Page 8
General Installation - Remote
Location Limitations
This ice system is made up of three parts, the ice making machine, or head; the remote condenser; and the interconnecting tubing. The ice making machine must be installed indoors, in a controlled environment. Space must be provided near the machine for service access. The remote condenser may be installed above or below the ice machine, per the limits stated later in this manual. The remote condenser may be installed outdoors within the temperature limits listed below. The interconnecting tubing must be installed per the directions stated in this manual, and the amount of tubing exposed to uncontrolled temperatures must be minimized.
Space Limitations
Although the machine will function with no clearance to the top and sides, some space must be allowed for service access. Building the machine in with no access will cause higher service cost, in many cases this extra cost may not be covered by warranty.
Environmental Limitations, ice machine:
Minimum Maximum
Air temperature 50
Water temperature 40
o
F. 100oF.
o
F. 100oF.
Water Pressure 20 psi 80 psi
Environmental Limitations, remote condenser
Minimum Maximum
Air temperature -20
o
F. 120oF.
Power Supply
Minimum Maximum
115 volt model 104 volts 126 volts
208-230 volt model 198 volts 253 volts
Warranty Information
The warranty statement for this product is provided separately from this manual. Refer to it for applicable coverage. In general warranty covers defects in material and workmanship. It does not cover maintenance, corrections to installations, or situations when the ice machine is operated in circumstances that exceed the limitations printed above.
October 2012 Page 9
General Installation - Remote
Product Description and Electrical Requirements
- See spec sheet or User's Manual for Minimum Circuit Ampacity or Maximum Fuse SIze
Dimensions w”xd”xh”
22 x 24 x 23 C0522SR-1 115/60/1 ERC111-1
same same same ERC211-1**
30 x 24 x 23 C0530SR-1 115/60/1 ERC111-1
same same same ERC211-1**
same C0630SR-32 208-230/60/1 ERC311-32
30 x 24 x 29 C0830SR-32 208-230/60/1 ERC311-32
same C0830SR-3 208-230/60/3 ERC311-32
same C1030SR-32 208-230/60/1 ERC311-32
same C1030SR-3 208-230/60/3 ERC311-32
48 x 24 x 29 C1448SR-32 208-230/60/1 ERC311-32
same C1448SR-3 208-230/60/3 ERC311-32
same C1848SR-32 208-230/60/1 ERC611-32
Model Electrical Use condenser
same C1848SR-3 208-230/60/3 ERC611-32
same C2148SR-32 208-230/60/1 ERC611-32
same C2148SR-3 208-230/60/3 ERC611-32
** ERC211 has two circuits, when two C0522s or C0530s are connected to it, fan motor relay kit KCMR120 must be used to control the fan motor.
Ratings include the remote condenser motor, as it is designed to be powered by the ice machine. If connecting remote condenser independently of the ice machine, use the information on the condenser's dataplate for fuse and wire sizes.
Table notes: Medium cube models have the same electrical characteristics as Small. Series revision code omitted. All the listed condensers include a headmaster valve.
October 2012 Page 10
General Installation - Remote
Central Condenser Coils
The ice machine may be connected to a central condenser coil. The requirements are:
Coil – not previously used with mineral oil system. Virgin coil preferred.
Correct size (internal volume) and capacity (BTUH).
Includes a headmaster valve for discharge pressure control. Headmaster kit available for
certain MAC condensers, kit number is Fan motor on all the time or controlled to be on whenever the ice machine is operating.
Non-Scotsman condensers must have prior Scotsman Engineering approval for warranty
coverage to be in effect.
Precharged tubing kits:
The ice making head’s and the remote condenser’s refrigeration circuits must be connected. They are designed to be connected using precharged refrigerant tubing, supplied in kits of liquid and discharge tubes. Several lengths are available, order the one that just exceeds the length needed for the site.
RCKCME6GX.
10” 25’ 40’ 75’
RTE10 RTE25 RTE40 RTE75
No additional refrigerant is required. Note: Refrigerant charge is supplied with the ice machine.
January 2009 Page 11
General Installation - Remote
Water
The quality of the water supplied to the ice machine will have an impact on the time between cleanings and ultimately on the life of the product. There are two ways water can contain impurities: in suspension or in solution. Suspended solids can be filtered out. In solution or dissolved solids cannot be filtered, they must be diluted or treated. Water filters are recommended to remove suspended solids. Some filters have treatment in them for suspended solids. Check with a water treatment service for a recommendation.
RO water. This machine can be supplied with Reverse Osmosis water, but the
conductivity must be no less than 10 microSiemens/cm.
Potential for Airborne Contamination
Installing an ice machine near a source of yeast or similar material can result in the need for more frequent sanitation cleanings due to the tendency of these materials to contaminate the machine. Most water filters remove chlorine from the water supply to the machine which contributes to this situation. Testing has shown that using a filter that does not remove chlorine, such as the Scotsman Aqua Patrol, will greatly improve this situation, while the ice making process itself will remove the chlorine from the ice, resulting in no taste or odor impact. Additionally, devices intended to enhance ice machine sanitation, such as the Scotsman Aqua Bullet, can be placed in the machine to keep it cleaner between manual cleanings.
Water purge
Cube ice machines use more water than what ends up in the bin as ice. While most water is used during ice making, a portion is designed to be drained out every cycle to reduce the amount of hard water scale in the machine. That’s known as water purge, and an effective purge can increase the time between needed water system cleaning.
water
In addition, this product is designed to automatically vary the amount of water purged based on the purity of the water supplied to it. The water purge rate can also be set manually. Adjustments of purge due to local water conditions are not covered by warranty.
October 2012 Page 12
General Installation - Remote
Remote Condenser Location
Use the following for planning the placement of the condenser relative to the ice machine - see illustration on the following page.
Location Limits - condenser location must not exceed ANY of the following limits:
Maximum rise from the ice machine to the condenser is 35 physical feet
Maximum drop from the ice machine to the condenser is 15 physical feet
Physical line set maximum length is 100 feet.
Calculated line set length maximum is 150.
Calculation Formula:
Drop = dd x 6.6 (dd = distance in feet)
Rise = rd x 1.7 (rd = distance in feet)
Horizontal Run = hd x 1 (hd = distance in feet)
Calculation: Drop(s) + Rise(s) + Horizontal Run = dd+rd+hd = Calculated Line Length
Configurations that do NOT meet these requirements must receive prior written authorization from Scotsman.
Do NOT:
Route a line set that rises, then falls, then rises.
Route a line set that falls, then rises, then falls.
Calculation Example 1:
The condenser is to be located 5 feet below the ice machine and then 20 feet away horizontally.
5 feet x 6.6 = 33. 33 + 20 = 53. This location would be acceptable
Calculation Example 2:
The condenser is to be located 35 feet above and then 100 feet away horizontally. 35 x 1.7 =
59.5. 59.5 +100 = 159.5. 159.5 is greater than the 150 maximum and is NOT acceptable.
Operating a machine with an unacceptable configuration is misuse and will void the warranty.
October 2012 Page 13
General Installation - Remote
22.87"
17.15"
40.35"
For The Installer: Remote Condenser
Locate the condenser as near as possible to the interior location of the ice machine.
Note: The location of the condenser is relative to the ice machine is LIMITED by the specification on the prior page.
Meet all applicable building codes.
Roof Attachment
Install and attach the remote condenser to the roof of the building, using the methods and practices of construction that conform to the local building codes, including having a roofing contractor secure the condenser to the roof.
rd
dd
Max
35'
Max
15'
Remote Condenser Locate ABOVE
Remote Condenser Locate BELOW
hd
Condenser Distance & Location
October 2012 Page 14
General Installation - Remote
Precharged Line Routing
Do not connect the precharged tubing until all routing and forming of the tubing is complete. See the Coupling Instructions for final connections.
1. Each set of pre-charged tubing lines contains a 3/8” diameter liquid line, and a 1/2” diameter discharge line. Both ends of each line have quick connect couplings, the end without access valves goes to the ice maker.
Note: The openings in the building ceiling or wall, listed in the next step, are the minimum sizes recommended for passing the refrigerant lines through.
2. Have the roofing contractor cut a minimum hole for the refrigerant lines of 1 3/4”. Check local codes, a separate hole may be required for the electrical power supply to the condenser.
Caution: Do NOT kink the refrigerant tubing while routing it.
3. Route the refrigerant tubes thru the roof opening. Follow straight line routing whenever possible. Excess tubing may EITHER be coiled up INSIDE the building OR cut out prior to connection to the ice maker and condenser.
If the excess tubing is cut out, after re-brazing the tubing must be evacuated prior to connection to the ice maker or condenser.
Note brazing requires a nitrogen purge.
If the excess tubing is to be coiled, spiral it horizontally to avoid excess trapping in the lines.
5. Have the roofing contractor seal the holes in the roof per local codes
October 2012 Page 15
General Installation - Remote
Coupling Instructions
The couplings on the ends of the pre-charged line sets are self-sealing when installed properly. Follow these instructions carefully.
These steps must be performed by an EPA Certified Type II or higher technician.
Initial Connections
1. Remove the protector caps and plugs. Wipe the seats and threaded surfaces with a clean cloth to remove any possible foreign matter.
2. Lubricate the inside of the couplings, especially the O-rings, with refrigerant oil.
3. Position the fittings on the correct connections on the condenser and ice machine.
The 1/2" discharge line (schrader valve end) goes to the remote condenser fitting marked “discharge line”.
The 3/8" liquid line (schrader valve end) goes to the remote condenser fitting marked “liquid line”.
The 1/2" discharge line goes to the ice maker fitting marked “discharge line”.
The 3/8" liquid line goes to the ice maker fitting marked “liquid line”.
Final Connections:
4a. Begin by tightening the couplings together by hand until it is certain that the threads are properly engaged.
4b. Then using two wrenches tighten the coupling until it bottoms out or a definite increase in resistance is felt.
It is important that ONLY the nut on the pre-charged tube be turned, or the diaphragms will be torn out by the piercing knives and they will be loose in the refrigeration system. Note: As the couplings are tightened, the diaphragms in the quick connect couplings will begin to be pierced. As that happens, there will be some resistance to tightening the swivel nut.
4c. Continue tightening the swivel nut until it bottoms out or a very definite increase in resistance is felt (no threads should be showing).
5. Use a marker or pen to mark a line on the coupling nut and unit panel. Then tighten the coupling nut an additional one-quarter turn. The line will show the amount that the nut turns. Do NOT over tighten.
6. After all connections have been made, and after the receiver valve has been opened (open at Initial Start Up), check the couplings for leaks.
October 2012 Page 16
Pre-Charged Tubing Coupling Connections
Inspect couplings, wipe clean and lubricate both parts with polyolester refrigerant oil.
Hand tighten to be sure threads are properly engaged.
Use two wrenches and continue tightening the couplings. As the diaphragms being to pierce, the couplings will be harder to turn. Be sure only the swivel nut is rotated.
Continue tightening until the swivel nut feels like it is tight, then go to the next step. No threads will be seen when the couplings are tight.
After the swivel nut feels like it is tight, mark the nut and the panel. Then tighten one quarter turn more. That ensures that there is a brass-to-brass joint inside the coupling.
October 2012 Page 17
General Installation - Remote
Plumbing Requirements
All models require connection to cold, potable water. A hand actuated valve within site of the machine is required.
Water Filters
Install a new cartridge if the filters were used with a prior machine.
All models require drain tubing to be attached to them. There is a single ¾” FPT drain fitting in the back of the cabinet.
Install new tubing when replacing a prior ice machine, as the tubing will have been sized for the old model and might not be correct for this one.
Connect water supply to water inlet fitting.
Note: This NSF listed model has a 1" anti-back flow air gap between the potable water inlet tube end and the highest possible reservoir water level, no back flow device is required.
Connect drain tubing to drain fitting.
Route the drain tubing to building drain. Follow local codes for drain air gap.
Use rigid drain tubes and route them separately – do not Tee into the bin’s drain.
Vent the reservoir drain. A vertical vent at the back of the drain, extended about 8 – 10” will allow the gravity drain to empty and also keep any surges during draining from discharging water.
Horizontal runs of drain tubing need a ¼” per fall per foot of run for proper draining.
Follow all applicable codes.
August 2013 Page 18
General Installation - Remote
Electrical
The machine is not supplied with a power cord, one must either be field installed or the machine hard-wired.
The dataplate on the back of the cabinet details the power requirements, including voltage, phase, minimum circuit ampacity and maximum fuse size. HACR type circuit breakers may be used in place of fuses. Extension cords are not permitted. Use of a licensed electrician is recommended.
The ice maker is designed to operate on its own electrical circuit and must be individually fused. Voltage variation must not exceed the limits listed earlier.
The remote condenser is designed to be powered from the ice machine. A separate knockout hole has been provided in the ice maker electrical junction box.
Electrical connections are made inside the junction box in the back panel of the ice machine.
Remove the junction box cover and route the power cord through the access hole and properly attach the power supply wires to the leads in the junction box.
Attach the remote condenser fan motor wires to the wires in the junction box tagged “fan motor leads”.
Install field supplied strain reliefs per code. Attach a ground wire to the ground connection in the junction box.
Check voltage when complete.
Return the junction box cover to its original position and secure with the original screws.
Follow all applicable local, state and national codes.
October 2012 Page 19
Adjustments
Bridge Thickness - For the Service Tech Only
Adjustment
Push and hold Off till the machine stops.
Access ice thickness sensor.
Check gap between metal tip and evaporator grid. Small cube standard gap is 3/16 inch, medium cube standard gap is 7/32 inch. To set, place a 3/16" (small cube) or 7/32" (medium cube) drill bit between sensor tip and evaporator to check. Adjust gap using adjustment screw.
Restart unit and check ice bridge. Repeat as needed
Caution: Do not make the bridge too thin or the machine will not harvest properly. Bridge thickness adjustments are not covered by warranty.
Screw
Gap
Water purge setting
The water purge is factory set to Automatic. The setting can be changed to one of 5 manual settings or left on automatic.
purge setting
Water Type
To set:
Switch the machine OFF by holding the Off button in until a number or the letter A shows on the display.
Press and release the On button repeatedly until the number on the display corresponds to the desired setting.
1­Minimum
RO water or equivalent, TDS less than 35
2­Moderate3-Standard
Low TDS non-RO water
Setting for typical water
4­Heavy
High TDS water
5­Maximum
Very hHigh TDS water, greater than 256
A - Automatic
Any with conductivity not less than 10 microSiemens/ cm
Press and release the Off switch again to return to the normal control state.
October 2012 Page 20
Prodigy Cuber System Information
Overall System Type:
Refrigeration: Mechanical, either air cooled, water cooled or remote cooled.
Water System: Inlet water solenoid valve fills reservoir once per cycle. Purge solenoid
valve opens to discharge some reservoir water once per cycle. Control System: Electronic
Harvest cycle sensor: Conductivity probe
Water full/empty sensor: Conductivity probe
Bin Control: Curtain Switch
Ice type: Unified
Harvest system: Hot gas defrost with mechanical assist
Electrical Components:
Compressor
Contactor
Water Pump
Inlet Water Solenoid Valve
Purge or purge Valve
Fan Motor(s)
Fan motor pressure control
High pressure cut out – certain AC models only
Harvest Assist Solenoid(s)
Hot Gas Valve(s)
Controller
Transformer – 12v AC for the controller only
Water Level Sensor
Ice Thickness Sensor
Curtain Switch(es)
October 2012 Page 21
Controller Information
Machine Indicator Lights
Power
Status
Water
Clean
Code Display
Main codes - automatically displayed
F .......Freeze Cycle
F flashes . . Freeze Cycle is Pending
H .......Harvest Cycle
H flashes . . Manual Harvest
b .......BinisFull
C .......Clean Cycle
L .......Board Locked
d .......Test Mode
O .......Off
E .......Self Test Failed
1 flashes . . Max Freeze - Retrying
1 .......MaxFreeze Time Shut Down
2 flashes . . Max Harvest - Retrying
2 .......MaxHarvest Time Shut Down
3 .......Slow Water Fill
4 .......High Discharge Temp
5 .......Sump Temp Sensor Failure
7 .......Discharge Temp Sensor Failure
8 flashes . . Short Freeze - Retrying
8 .......Short Freeze - Thin ice
Change De-Scale Notification Interval ­This feature is accessible only from standby (Status Light Off).
1. Press and hold harvest button for 3 seconds.
This starts the Time to Clean Adjustment Mode and displays the current time to clean setting.
Setting Codes - requires push button sequence
Water Purge Settings
A, 1, 2, 3, 4, 5
De-Scale notification
- see table to the right
November 2008 Page 22
2. Press the clean button repeatedly to cycle through the 4 settings:
Prior Effective 11/6/08
3 months 1 year
4 months 0 or disabled
5 months 4 months
6 months (default) 6 months (default)
3. Push Off to confirm the selection.
Controller Information
Component Indicator Lights
Condenser Fan / Aux (Aux = liquid line solenoid when a remote condenser model)
Water Pump
Purge Valve
Water Solenoid
Hot Gas
Compressor
Ready to Harvest
Sump Empty
Sump Full
Curtain SW1
Curtain SW2
Component Indicator Lights
October 2012 Page 23
How It Works - Air Cooled
Freeze Cycle. At start up the controller drains and refills the reservoir. The reservoir refills
when the mid length water level sensor probe is uncovered and continues to fill until the top probe is in contact with water. When the reservoir has filled, the compressor and water pump start. After the discharge pressure has increased past the cut in point of the fan pressure control, the fan motor(s) will begin to operate and warm air will be discharged out the back of the cabinet. The fan motor will switch on and off as the discharge pressure rises and falls. Water flows over the evaporator as the refrigeration system begins to remove heat. When the water temperature falls to a preset point, as measured by the water temperature sensor, the controller shuts off the water pump for 30 seconds. The freeze cycle resumes when the pump restarts and ice begins to form on the evaporator. As it forms, the water flowing over the ice moves closer and closer to the metal tip of the ice thickness sensor. When it comes into contact with the sensor for a few continuous seconds, that signals the controller that the freeze cycle is complete.
The controller may shut the air cooled fan motor off for a variable period of time to build up heat for harvest. This is dependant upon the temperature of the discharge line sensor.
Harvest Cycle. When the harvest cycle begins, the controller shuts off the fan motor, switches on the hot gas valve, and through a parallel circuit, the harvest assist solenoid. After a few seconds the purge valve opens and water is drained from the reservoir. Based on either the automatic purge or manual purge setting, the pump and purge valve will be switched off at a time determined to have drained enough water for that setting. The inlet water valve will open to fill the reservoir anytime the mid length probe is uncovered, which occurs during the reservoir drain cycle. Harvest continues as the hot discharge gas flows into the evaporator serpentine, heating up the evaporator. At the same time the harvest assist solenoid is pushing against the back of the ice slab. When the ice releases from the evaporator, it harvests as a unit, and the harvest assist probe provides some additional force to push it off. When the ice falls off it will force the curtain(s) open. An open curtain during the harvest cycle signals the controller that the evaporator has released its ice. If this is a single evaporator machine the controller will terminate harvest. If it is a two evaporator machine, the controller will continue harvest until both curtains have opened. If one curtain remains open, the controller will shut the machine down on bin full. Anytime harvest is complete the hot gas valve and harvest assist solenoid are shut off. The harvest assist solenoid pin returns to its normal position by spring pressure.
If the curtain(s) re-close after harvest, the freeze cycle will restart.
October 2012 Page 24
How It Works - Water Cooled
Freeze Cycle. At start up the controller drains and refills the reservoir. The reservoir refills
when the mid length water level sensor probe is uncovered and continues to fill until the top probe is in contact with water. When the reservoir has filled, the compressor and water pump start. After the discharge pressure has increased past the set point of the water regulating valve, the water regulating valve will open and warm water will be discharged out the condenser drain. The water regulating valve will modulate to maintain a relatively constant discharge pressure. Water flows over the evaporator as the refrigeration system begins to remove heat. When the water temperature falls to a preset point, as measured by the water temperature sensor, the controller shuts off the water pump for 30 seconds. The freeze cycle resumes when the pump restarts and ice begins to form on the evaporator. As it forms, the water flowing over the ice moves closer and closer to the metal tip of the ice thickness sensor. When it comes into contact with the sensor for a few continuous seconds, that signals the controller that the freeze cycle is complete.
Harvest Cycle. When the harvest cycle begins, the controller switches on the hot gas valve, and through a parallel circuit, the harvest assist solenoid. After a few seconds the purge valve opens and water is drained from the reservoir. Based on either the automatic purge or manual purge setting, the pump and purge valve will be switched off at a time determined to have drained enough water for that setting. The inlet water valve will open to fill the reservoir anytime the mid length probe is uncovered, which occurs during the reservoir drain cycle. Harvest continues as the hot discharge gas flows into the evaporator serpentine, heating up the evaporator. At the same time the harvest assist solenoid is pushing against the back of the ice slab. When the ice releases from the evaporator, it harvests as a unit, and the harvest assist probe provides some additional force to push it off. When the ice falls off it will force the curtain(s) open. An open curtain during the harvest cycle signals the controller that the evaporator has released its ice. If this is a single evaporator machine the controller will terminate harvest. If it is a two evaporator machine, the controller will continue harvest until both curtains have opened. If a curtain remains open, the controller will shut the machine down on bin full. Anytime harvest is complete the hot gas valve and harvest assist solenoid are shut off. The harvest assist solenoid pin returns to its normal position by spring pressure.
If the curtain(s) re-close after harvest, the freeze cycle will restart.
January 2010 Page 25
How It Works - Remote
Freeze Cycle. At start up the controller drains and refills the reservoir. The reservoir refills
when the mid length water level sensor probe is uncovered and continues to fill until the top probe is in contact with water. When the reservoir has filled, the liquid line valve, compressor and water pump are switched on. After the discharge pressure has increased past the set point of the headmaster in the condenser, the headmaster will direct refrigerant gas into the condenser and warm air will be discharged out of the condenser. The headmaster will modulate to maintain a minimum discharge pressure. Water flows over the evaporator as the refrigeration system begins to remove heat. When the water temperature falls to a preset point, as measured by the water temperature sensor, the controller shuts off the water pump for 30 seconds. The freeze cycle resumes when the pump restarts and ice begins to form on the evaporator. As it forms, the water flowing over the ice moves closer and closer to the metal tip of the ice thickness sensor. When it comes into contact with the sensor for a few continuous seconds, that signals the controller that the freeze cycle is complete.
Harvest Cycle. When the harvest cycle begins, the controller switches on the hot gas valve, and through a parallel circuit, the harvest assist solenoid. After a few seconds the purge valve opens and water is drained from the reservoir. Based on either the automatic purge or manual purge setting, the pump and purge valve will be switched off at a time determined to have drained enough water for that setting. The inlet water valve will open to fill the reservoir anytime the mid length probe is uncovered, which occurs during the reservoir drain cycle. Harvest continues as the hot discharge gas flows into the evaporator serpentine, heating up the evaporator. At the same time the harvest assist solenoid is pushing against the back of the ice slab. When the ice releases from the evaporator, it harvests as a unit, and the harvest assist probe provides some additional force to push it off. When the ice falls off it will force the curtain(s) open. An open curtain during the harvest cycle signals the controller that the evaporator has released its ice. If this is a single evaporator machine the controller will terminate harvest. If it is a two evaporator machine, the controller will continue harvest until both curtains have opened. If a curtain remains open, the controller will shut the machine down. Anytime harvest is complete the hot gas valve and harvest assist solenoid are shut off. The harvest assist solenoid pin returns to its normal position by spring pressure.
If the curtain(s) re-close after harvest, the freeze cycle will restart.
Shut down occurs when a curtain remains open after a harvest cycle. The controller will switch off the liquid line solenoid valve and operate the compressor for 30 seconds, then shut it off.
November 2006 Page 26
Electrical Sequence - Air or Water Cooled
Power connected, unit previously switched Off.
Control board does a self check. If the self check fails, the unit displays an E and no further action will occur.
If the self check passes, the controller will display a 0, the curtain light(s) will be ON and the Power and Sump Empty lights will be ON.
Pushing and releasing the On button will start the ice making process.
The display will begin to blink F. The component indicator lights will switch on and off to match the following process:
The purge valve opens and the water pump starts to empty the reservoir. This is done to discharge any excess water from ice melting into the reservoir.
The hot gas valve and the harvest assist solenoid are energized.
The inlet water valve will open to fill the reservoir. The water valve can open any time the water level is low.
After a few seconds the purge valve closes and the pump shuts off.
When the reservoir is full the inlet water valve stops and the compressor switches on. Five seconds after the compressor starts the hot gas valve and the harvest assist solenoid are de-energized.
Light Information: The display shows a non-blinking F. The Power and Status Lights will be Green. The compressor, fan motor, water pump, sump full and one or two curtain switch lights will be ON.
The air cooled model's fan motor will start to turn when the discharge pressure has built up to the fan pressure control's cut in point. This is about 15 seconds after the compressor starts.
The Freeze cycle continues. The compressor, water pump, fan motor and curtain indicator lights will be ON. When the reservoir water temperature falls to a certain preset point, the water pump will shut off for 30 seconds. This is the anti-slush period. At this time the controller checks the conductivity of the water in the reservoir for the auto-purge feature. After the water pump restarts the Sump Full light will go out and neither sump lights will be on for the rest of the freeze cycle.
When the ice has built up enough so that the water flowing over the evaporator comes into continuous contact with the ice level sensor, the Ready to Harvest light will begin to blink on and off. When it has been On continuously for 5 seconds, the controller will switch the machine into a Harvest cycle.
October 2012 Page 27
Electrical Sequence - Air or Water Cooled
Indicator Information: The display shows a non-blinking H. The Power and Status Lights will be Green. The compressor, hot gas valve and one or two curtain switch lights will be ON. After a few seconds the water pump, purge valve and inlet water valve lights will come on.
The fan motor(s) shut off and remain off throughout the harvest cycle.
The harvest assist solenoid is connected in parallel with the hot gas valve. Although it is energized throughout the harvest cycle, its piston does not move until the ice has become partially loosened from the evaporator plate by the action of the hot refrigerant gas passing through the evaporator serpentine.
The water pump and purge valve will shut off when the purge level setting time has been reached, either the manual time or the automatic time. The inlet water valve will remain on until it fills the reservoir. The Ready to Harvest light will switch Off when the ice falls from the evaporator.
Harvest continues until the ice slab is ejected from the evaporator and falls, opening the curtain. When the curtain opens, the magnetic reed curtain switch opens, breaking the circuit to the controller. If the curtain re-closes within 30 seconds, the controller switches the machine back into another freeze cycle. If the curtain switch remains open, the controller shuts the machine down and puts it into a standby position.
October 2012 Page 28
Electrical Sequence - Remote Cooled
Power connected, unit previously switched Off.
Control board does a self check. If the self check fails, the unit displays an E and no further action will occur.
If the self check passes, the controller will display a 0, the curtain light(s) will be ON and the Power and Sump Empty lights will be ON.
Pushing and releasing the On button will start the ice making process.
The display will begin to blink F. The component indicator lights will switch on and off to match the following process:
The purge valve opens and the water pump starts to empty the reservoir. This is done to discharge any excess water from ice melting into the reservoir.
The hot gas valve and the harvest assist solenoid are energized.
The inlet water valve will open to fill the reservoir. The water valve can open any time the water level is low.
After a few seconds the purge valve closes and the pump shuts off.
When the reservoir is full the inlet water valve stops, the liquid line valve is opened and the compressor switches on. Five seconds after the compressor starts the hot gas valve and the harvest assist solenoid are de-energized.
Light Information: The display shows a non-blinking F. The Power and Status Lights will be Green. The compressor, fan motor, water pump, sump full and one or two curtain switch lights will be ON.
The Freeze cycle continues. When the reservoir water temperature falls to a certain preset point, the water pump will shut off for 30 seconds. This is the anti-slush period. At this time the controller checks the conductivity of the water in the reservoir for the auto-purge feature. After the water pump restarts the Sump Full light will go out and neither sump lights will be on for the rest of the freeze cycle.
When the ice has built up enough so that the water flowing over the evaporator comes into continuous contact with the ice level sensor, the Ready to Harvest light will begin to blink on and off. When it has been On continuously for 3 seconds, the controller will switch the machine into a Harvest cycle.
Indicator Information: The display shows a non-blinking H. The Power and Status Lights will be Green. The compressor, hot gas valve and one or two curtain switch lights will be ON. After a few seconds the water pump, purge valve and inlet water valve lights will come on.
October 2012 Page 29
Loading...
+ 104 hidden pages