This product manual contains the information
needed for the setup, installation, initial start up,
sanitation and maintenance of this ice machine.
Keep it for future reference.
There are 2 models covered in this manual:
• CME1356R, (5 evaporators)
• CME1656R, (6 evaporators)
TABLE OF CONTENTS
Specifications .................PAGE2
Condenser and Ice Machine Layouts .....PAGE3
Pre-Installation .................PAGE4
Location & Assembly .............PAGE5
Bin Control: Installation ............PAGE6
Bin Control ...................PAGE7
Be certain that the information applies to the model
in question. If no model is listed, the information
applies to all models.
This manual is organized in the same way as the
expected use of the machine, it begins with
specifications, goes thru unpacking and setup,
shows where everything is; continues with initial
start up, then describes how it works. After that is
the sanitation section, followed by service diagnosis
and repair.
Sanitation and Cleaning ........... PAGE 26
Additional Maintenance ........... PAGE 27
Additional Maintenance: Water Distributors . PAGE 28
Both of these ice machines are designed to be
installed indoors, in a controlled environment.
They can operate satisfactorily under a wide
variety of conditions. However, Do NOT operate
the machine in temperatures it has not been
designed for. Do NOT operate the machine above
or below the voltage limits for the particular model.
Do NOT operate the machine with too little or too
much water pressure.
Operational Limits
MinimumMaximum
Air Temperature50oF.100oF.
Water Temperature40oF.100oF.
Water Pressure20 psi80 psi
Voltage (60 Hz)197253
Voltage (50 Hz)207253
Scotsman reserves the right to make design
changes and/or improvements at any time.
Specifications and designs are subject to change
without notice.
Scotsman assumes no liability or responsibility
of any kind for products manufactured by
Scotsman that have been altered in any way,
including the use of any parts and/or other
components not specifically approved by
Scotsman.
BASIC INFORMATION
Bins:
All models will fit a standard, 48" wide or wider
open top Scotsman Ice Storage Bin. Some
examples are:
BH900
·
BH1366
·
BH1666
·
In addition, there may be other bins that can be
used, check Scotsman’s sales literature for
application information.
Note: Slope-front bins must have an internal baffle.
Scotsman’s BH900 has the required baffle. Baffle
must be approximately in the position shown in the
diagram below.
* The remote condenser is designed to work in temperatures from -20oF. to 120oF.
Use precharged tubing kits, RTE25 (25’) or RTE40 (40’) or RTE75 (75’). Select the length closest to the
needs of the particular installation.
The stacking kit required to place two like model cubers together is: KSCME6-LG-B. The kit required to
connect this ice machine to a central condenser is: RCKCME6GX
Basic Electrical
(volts/Hz/phase)
Use
Condenser
Refrigerant
Charge
R-404A
Minimum
Circuit
Ampacity
Max
Fuse
Size
March 2010
Page 2
Condenser and Ice Machine Layouts
2
.88 DIA. ELECTRICAL
INLET
DISCHARGE LINE
1/2" MALE CPLG.
CME1356R and CME1656R
29.50 in
74.9 cm
ERC411
.562 DIA.
MOUNTING
HOLES (4)
6.00 in
15.2 cm
CONDENSER FINS
23.54 in
59.7 cm
29.15 in
74.0 cm
MINIMUM FOR
UTILITY CONNECTIONS
2.75
38.47 in
97.7 cm
32.32 in
35.72 in
90.7 cm
15-0782-01CANCAUSEINJURYOR DEATH:DISCONNECT ALL REMOTE ELECTRICPOWERSUPPLIESBEFORESERVICING.RISKOFELECTRICSHOCK^MWARNING
2.84 in
7.2 cm
82.1 cm
28.07 in
71.2 cm
7.60 in
19.3 cm
6.10in
66.3 cm
MINIMUM BIN
TOP OPENING
24.71 in
62.7 cm
11.50 in
29.2 cm
14.56 in
36.9 cm
27.56 in
70.0 cm
29.19 in
74.1 cm
.65 in
1.7 cm
LIQUID LINE
3/8" MALE CPLG.
AIR FLOW
PLAN VIEW
18.75 in
47.6 cm
ICE
OPENING
6.00 in
15.2 cm
MINIMUM FOR
AIR VENTILATION
REMOTE CONDENSER
LIQUID LINE
3/8" MALE CPLG.
23.30 in
59.2 cm
22.65 in
57.5 cm
BACK VIEW
DUMP
VALVE
DRAIN
3/4" F.P.T.
REMOTE CONDENSER
DISCHARGE LINE
1/2" MALE CPLG.
WATER INLET
3/8" FLARE
May 2001
4.20 in
10.7 cm
ICE
OPENING
18.67 in
47.4 cm
Page 3
.88 DIA. KNOCKOUT
ELECTRICAL INLET
15.77 in
40.1 cm
21.77 in
55.3 cm
10.15 in
25.8 cm
2.50 in
6.4 cm
5.87 in
14.9 cm
17.87 in
45.4 cm
2.46 in
6.2 cm
3.81 in
9.7 cm
.88 DIA. KNOCKOUT
REMOTE CONDENSER FAN
23.87 in
60.6 cm
CME1356R and CME1656R
Pre-Installation
Other Applications:
Check sales literature for additional information.
Electrical:
Check the nameplate for electrical requirements.
The nameplate is located on the back of the ice
machine. If the information on the nameplate is
different from other published information, go by
the nameplate data.
While the model and
serial number are on
the nameplate, a
serial number plate is
located at the front of
the machine, behind
the left front panel
and to the right of the
purge valve.
Nameplate
Serial Number Plate
Water:
There is no such thing as pure water. All water
contains some impurities. There are two ways
water carries the impurities: suspended and
dissolved. Suspended solids can be filtered out.
Dissolved solids must be diluted or treated. Water
filters are recommended to remove suspended
solids. Some filters have treatment in them for
suspended solids. Check with a water treatment
service for a recommendation.
Cube Ice machines use more water than what
ends up in the bin as ice. While most water is used
during ice making, a portion is designed to “rinse"
out the water system to keep hard water scale
from clogging up the machine. That water rinse,
combined with water filters, prolongs the times
between needed water system cleaning.
Service Technicians: All models covered here
come set from the factory with at a “Standard”
water rinse. Standard water rinse is designed to be
compatible with typical water conditions. The
machine may be adjusted to a different water rinse
after start up. If the prior ice machine worked
acceptably well with the local water conditions,
leave the machine at the factory setting. If severe
water conditions are present, and water filters do
not solve the problem acceptably, adjust the
machine to use more water. If water conditions are
excellent, adjust the machine to use less water.
See the Adjustments section.
Note: Water use adjustments are customer
convenience adjustments; they are NOT factory
defects and are NOT covered by warranty.
May 2001
Page 4
Location & Assembly
CME1356R and CME1656R
Locate the ice machine indoors. A 6 inch minimum
clearance on the back and left sides is required for
the proper operation and service of this machine.
Locate the remote condenser as close as possible
to the ice machine. See page 11 for details.
Unpacking and Assembly:
Begin with unpacking the ice storage bin. Remove
the carton, and using part of the carton as a
cushion, tip the bin on its back to remove the skid
and attach the legs or casters. Note: Stacked
applications may not use casters.
Return the bin to an upright position. Check the bin
top gasket for gaps and tears, fill any in with food
grade sealant prior to placing the ice machine on
the bin.
Note: If recycling a prior bin, be sure that the bin
top gasket is in good condition or seal the ice
machine to the bin with food grade sealant.
Level the top edge of the bin front to back and left
to right.
If the ice machine has not been unpacked, do so
now. Remove the carton from the skid. Remove
shipping straps.
Remove the front panels and all packaging
materials.
After all packing materials have been removed
from the ice machine, lift or hoist the machine onto
the bin. Align the sides and back of the machine
with the sides and back of the bin.
Secure the ice machine to the bin with the two
metal straps and 4 bolts provided.
Cabinet Panel Removal:
1. Remove the front panel by removing the two
screws connecting the front panel to the machine.
2. Lift up at the front edge and push the top panel
back until it releases from the tabs connecting it to
the back panel.
3. Remove two screws at the front of each side
panel, and pull them forward until they release
from the tabs connecting them to the back panel.
Evaporator Cover:
To Remove
Evaporator Cover:
Push Up and Tilt Out
May 2001
Page 5
CME1356R and CME1656R
Bin Control: Installation
The bin control is a thermostat. It must be field
installed after the ice machine has been placed on
the bin.
Before starting, remove the left front panel and any
baffle in the bin.
1. Locate bin thermostat bulb.
2. Route bulb thru routing tube (located between
the compressor and the reservoir).
3. Locate bin thermostat bracket.
4. Carefully position the thermostat bulb on the
bracket (see the diagram on the next page).
5. Fasten the bracket to the bottom of the ice
machine with the two 3-pronged knobs supplied
with the unit.
6. Pull back into the ice machine any excess
capillary tubing.
7. Return the baffle to the bin and continue with
the installation.
Note: If the machine is located at an altitude higher
than 2,000 ft., adjust the thermostat by removing
the plastic cover and rotating the adjustment screw
per the table.
Thermostat Bulb Routing Tube
Bin Thermostat Altitude Correction Table
CW Turns of Range Screw (under plastic cover)
FeetTurnsFeetTurns
200055
4000160
6000250
o
o
o
8000340
9000385
10000405
o
o
o
Use This Table to Adjust Thermostat
Bin
Thermostat
Body
Thermostat Bulb
Routing Tube
Bin Thermostat Bulb
Route Bin Thermostat Bulb Into Bin
May 2001
Page 6
Bin Control
Bin Thermostat
Bracket
Mount Bulb
Tip Here
CME1356R and CME1656R
Bin Thermostat
Capillary Tube
Mount Thermostat
Capillary Tube Here
Attach Thermostat Bulb to Bracket
Minimize Excess
Tube in Bin
Three-Pronged Knob
Thermostat and
Bracket
Attach Bracket to Bottom of Ice Machine
May 2001
Page 7
CME1356R and CME1656R
Stacking - Kit KSCME6-LG-B
Only like models may be stacked. Begin after the
bottom unit has been placed on the ice storage bin
and secured. Stacking requires heavy duty leg kits.
Casters are NOT recommended.
Note: Instructions are for either model.
Bottom Machine:
1. Remove front panel, left side panel, and top
panel.
2. Remove & discard top cover from over the
freezing compartment.
3. Install gasket materials to freezing
compartment:
Cut about 22" of gasket material from the roll in the
kit. Apply it to the back side top edge of the
freezing compartment.
Cut two lengths of gasket material to fit the right
side top edge of the freezing compartment and
apply them.
4. Place a bead of food grade sealant to the top of
the back wall’s gasket.
5. Place the shield bracket (has a large hole in the
center) from the kit over the center of the freezing
compartment.
Insert the tabs of the bracket into slots on the back
of the unit.
6. Secure bracket at the front with screws from the
kit.
7. Hang the plastic shields from the bracket
installed in the prior step. Use the slots in the
shields to hang them from the stainless steel
hooks.
Note: The notch in the bottom of the shield goes to
the front.
Note: The tabs on the shields must fit inside the
ice outlet port.
8. Check the position of the shields. They must
move freely and be vertical.
Note: The suction line may need to be moved
slightly so the tubing clears the bracket & shields.
9. Place a bead of food grade sealant onto the top
left edge of the freezing compartment.
10. Install the front-to-back support bracket over
the left edge of the freezing compartment.
11. Remove two existing screws and secure the
bracket to the: freezing compartment, back panel
and front channel with the 2 existing screws and 1
large and 4 small screws from the kit.
Both Machines:
12. Place the top ice machine onto the bottom one.
Secure together with hardware from the top
machine. Remove left front and left side panels.
13. At the back of the ice machines, on the
compressor end, remove the upper knock-out from
the bottom machine and the lower knock out from
the upper machine.
14. Place a strain relief (from the kit) into each
hole.
15. Insert wire harness from kit thru strain-relief
and hole in upper corner of the lower ice
machine’s back panel.
NOTE: Harness is marked which end goes to
which machine.
Bottom Machine:
16. Remove harness from controller terminal 7 and
bin thermostat.
17. Route wire harness in lower ice machine to the
controller. Connect to terminal #7. Plug the two
free wires onto the thermostat terminals #1 and #2.
18. Return left side panel to its original position on
the lower ice machine.
Top Machine:
19. Remove harness from controller terminal 7.
20. Route wire harness thru upper unit’s lower
knock-out hole and strain relief and continue
internally to the controller. Plug wire onto terminal
7 of the controller.
21. Return all panels and covers to their normal
positions.
22. Complete the balance of the installation.
Service Notes:
A. The shields must be positioned so they hang
vertically and move freely left to right. Their
purpose is to guide the ice past the bottom
machine’s evaporators and into its cube port.
B. The drain lines from each ice machine must be
kept separate.
May 2001
Page 8
Stacking
CME1356R and CME1656R
Gasket on
Plastic Walls of
Lower Unit
Gasket for Metal
Edges of Bottom
Unit
Front-to-Back
Support Bracket
Mounting Straps
and Hardware
Shield Hanger
Bracket
Shield
May 2001
Page 9
CME1356R and CME1656R
For The Installer: Remote Condenser
Locate the condenser as near as possible to the
interior location of the ice maker.
Note: The location of the condenser relative to the
ice machine is LIMITED by the specification on the
following page.
Select the best available location, one that protects
the condenser from extremes of dust, grease and
sun.
Meet all applicable building codes.
Roof Attachment
Install and attach the remote condenser to the roof
of the building, using the methods and practices of
construction that conform to the local building
codes, including having a roofing contractor secure
the condenser to the roof.
Note: If using any other condenser besides the
ERC411, its use must be approved by
Scotsman, and a head pressure control
valve must be connected to the
condenser coil. The head pressure
valve kit number is: RCKCME6
Precharged Line Routing
Do not connect the precharged tubing
until all routing and forming of the tubing
is complete. See the Coupling
Instructions for final connections.
1. Each set of pre-charged tubing lines contains a
3
“ diameter liquid line, and a
8
1
” diameter
2
discharge line. Both ends of each line have quick
connect couplings, the end without access valves
goes to the ice maker.
Note: The openings in the building ceiling or wall,
listed in the next step, are the minimum sizes
recommended for passing the refrigerant lines
through.
2. Have the roofing contractor cut a minimum hole
for the refrigerant lines of 2“. Check local codes, a
separate hole may be required for the electrical
power supply to the condenser.
Caution: Do NOT kink the refrigerant tubing while
routing it.
3. Route the refrigerant tubes thru the roof
opening. Follow straight line routing whenever
possible.
Note: Excess tubing may EITHER be coiled up
INSIDE the building OR cut out prior to connection
to the ice maker and condenser.
If the excess tubing is cut out, after re-brazing the
tubing must be evacuated prior to connection to
the ice maker or condenser.
If the excess tubing is to be coiled, spiral it
horizontally to avoid excess trapping in the lines.
Note: A 36" service loop may be placed behind the
ice machine.
5. Have the roofing contractor seal the holes in the
roof per local codes.
ERC411 Remote
Condenser
Electrical
Power Supply
Coil Excess
Tubing
Horizontally
Within the
Building
Typical Installation
May 2001
Page 10
Remote Condenser Location
22.87"
17.15"
40.35"
CME1356R and CME1656R
Use the following for planning the placement of
the condenser relative to the ice machine
Location Limits - condenser location must not
exceed ANY of the following limits:
• Maximum rise from the ice machine to the
condenser is 35 physical feet
• Maximum drop from the ice machine to the
condenser is 15 physical feet
• Physical line set maximum length is 100 feet.
• Calculated line set length maximum is 150.
Calculation Formula:
• Drop = dd x 6.6 (dd = distance in feet)
• Rise = rd x 1.7 (rd = distance in feet)
• Horizontal Run = hd x 1 (hd = distance in
feet)
• Calculation: Drop(s) + Rise(s) + Horizontal
Run = dd+rd+hd = Calculated Line Length
Configurations that do NOT meet these
requirements must receive prior written
authorization from Scotsman.
Do NOT:
• Route a line set that rises, then falls, then
rises.
• Route a line set that falls, then rises, then
falls.
Calculation Example 1:
The condenser is to be located 5 feet below the ice
machine and then 20 feet away horizontally.
5 feet x 6.6 = 33. 33 + 20 = 53. This location would
be acceptable
Calculation Example 2:
The condenser is to be located 35 feet above and
then 100 feet away horizontally.
35 x 1.7 = 59.5. 59.5 +100 = 159.5. 159.5 is
greater than the 150 maximum and is NOT
acceptable.
Operating a machine with an unacceptable
configuration will void the refrigeration system
warranty.
rd
dd
Max 35’
Max 15’
Remote
Condenser
Located ABOVE
Ice Machine
hd
Condenser Distance &
Location Schematic
Remote
Condenser
Located BELOW
Ice Machine
May 2001
Page 11
CME1356R and CME1656R
Coupling Instructions
The couplings on the ends of the pre-charged line
sets are self-sealing when installed properly.
Follow these instructions carefully.
These steps must be performed by an EPA
Certified Type II or higher technician.
Initial Connections
1. Remove the protector caps and plugs. Wipe the
seats and threaded surfaces with a clean cloth to
remove any possible foreign matter.
2. Thoroughly lubricate the threads, o-rings,
diaphragms and all internal coupling surfaces with
polyolester refrigerant oil.
Clean and Lubricate Couplings
3. Position the fittings on the correct connections
on the condenser and ice machine.
1
·
The
“ discharge line (schrader valve end)
2
goes to the remote condenser fitting marked
“discharge line”.
3
·
The
“ liquid line (schrader valve end) goes to
8
the remote condenser fitting marked “liquid
line”.
·
The “ discharge line goes to the ice maker
fitting marked “discharge line”.
·
The “ liquid line goes to the ice maker fitting
marked “liquid line”.
Final Connections:
4a. Begin to tighten the couplings together by
hand. Continue to turn the swivel nuts by hand
until it is certain that the threads are properly
engaged.
4b. Using two wrenches, one to rotate the swivel
nut and one to hold the tubing in place, tighten
each coupling.
Tighten Swivel Nut
It is CRITICAL that ONLY the NUT on the
pre-charged tube be turned, or the diaphragms will
be torn by the piercing knives and become loose in
the refrigeration system causing severe
operational problems.
Note: As the coupling is tightened, the diaphragms
in the quick connect couplings will begin to be
pierced. As that happens, there will be increased
resistance to tightening the swivel nut.
4c. Continue tightening the swivel nut until it
bottoms out or a very definite increase in
resistance is felt (no threads should be showing).
Do NOT overtighten.
5. Use a marker or pen to mark a line on the
coupling nut and unit panel. Then tighten the
coupling nut an additional one-quarter turn. The
line will show the amount that the nut turns.
Note: The system charge is contained in the
receiver tank of the ice machine. Only
“holding" charges are present in the
“pre-charged" tubing or the condenser.
Rotate Swivel Nut ¼ Turn More
6. After all connections have been made, and after
the liquid line valve has been opened (do not open
yet), check the couplings for leaks.
May 2001
Page 12
Head Pressure Control Add-On Kit
CME1356R and CME1656R
Kit: RCKCME6GX
Required when a CME1656R or CME1356R is to
be connected to a Remote Condenser that is not
equipped with a Head Pressure Control Valve
2. Locate correct position on condenser: The
RCKCME6GX can fit either a Mac G series or a
Mac X series condenser.
3. Use metal box as a template, mark the positions
of 4 holes to be drilled to mount the box to the
condenser.
4. Drill four .157" (#22 or 5/32" bit) dia. holes.
5. Remove plastic covers from the condenser’s
quick connects and those to be used to connect to
the condenser.
6. Thoroughly clean and lubricate the threads and
diaphragms of both the condenser’s and the kit’s
quick connects. Use Polyolester oil.
7. Mount the box to the condenser with the screws
from the kit.
8. Start the swivel nuts by hand.
Use a back up wrench to be certain that the
·
tubing is NOT ROTATING. Only the SWIVEL
NUTS should be rotating!
Then use an adjustable wrench to tighten them
·
until no threads are seen AND a very definite
resistance is felt.
9. Mark the positions of the swivel nuts to the
condenser panel.
10. Rotate the swivel nuts additional one-quarter
turn.
11. Place cover on metal box & secure with screws.
12. Finish the balance of the installation. Ice
machine’s precharged line sets will now connect to
the quick connect fittings on the metal box instead
of the condenser’s.
Connections to
Central Condenser
Central
RCKCME6GX
G series
Pre-Charged
Lines from
Ice Machine
X Series
May 2001
Page 13
CME1356R and CME1656R
Electrical
All models must be installed with the correct wire
size and type per the National Electric Code.
Locate the nameplate on the back of the cabinet
and find the numbers for Voltage, Phase, Minimum
Circuit Ampacity and Maximum Fuse Size. Either
fuses or HACR type circuit breakers may be used.
The ice maker is designed to operate on its own
electrical circuit and must be individually fused.
Voltage variation must not exceed the limits listed
on page 2.
The remote condenser is designed to be powered
from the ice machine. A separate knockout hole
has been provided in the ice maker electrical
junction box.
Remote Condenser
Power Connection
Note: Central Condensers connected to more than
one refrigeration system will likely have a wiring
scheme to control the fan motor. Follow those
directions for condenser wiring.
Electrical connections are made in the junction box
in the back of the cabinet.
1. Remove the junction box cover.
2. Knock out both holes for a field supplied strain
relief.
3. Install wires and strain reliefs per code. Note:
Condenser fan motor wires are tagged.
4. Connect to wires and secure ground wire to
ground screw inside junction box.
All external wiring should conform to the national,
state and local electrical code requirements.
Usually an electrical permit and the services of a
licensed electrician will be required.
Interconnecting
Wire
Power Supply
May 2001
Page 14
Plumbing
CME1356R and CME1656R
All models require an adequate potable water
supply and a gravity drain. The recommendations
for tubing are:
Water supply to be
·
Drain to be
·
3
" OD.
4
3
" OD.
8
Note: When replacing a prior ice machine, do not
take a short cut and reuse the old inlet and drain
system. INSTALL A NEW SYSTEM.
Supply:
3
All models have 1 water supply connection, a
"
8
male flare at the back of the cabinet. Connect to
cold potable water that has adequate pressure.
Note: Using water supply tubing smaller than
3
"
8
will cause severe operational issues.
Water Filters:
The water filters must flow at least 2.7 GPM or they
will cause severe operational issues. Check with
the filter manufacturer. When replacing a prior ice
machine, do NOT assume that the water flow
capacity of the filter will be adequate.
All Drain Tubing Material must be RIGID.
Flexible tubing will eventually cause a restricted
drain.
Drain:
3
All models have 1 gravity drain connection, a
"
4
FPT fitting at the back of the cabinet. Use only
RIGID TUBING. Flexible tubing may be easily
kinked or become cracked.
The drain tube must be vented at the back of the
cabinet. Use an 18" high vent.
The ice storage bin will have a drain out the back or
base, depending upon the model.
The drain for the ice machine and the ice storage
bin must be SEPARATE or the ice machine’s drain
water may run into the bin and MELT THE ICE.
Insulation is recommended for the ice machine
reservoir and bin drains.
Follow all applicable codes
Refrigerant and
Electrical Lines
to Condenser
Potable
Water Inlet
- 3/8" Male
Flare
Supplied
Water Filter
Potable
Water
Source
Field
Vented
Drain
Ice
Machine
Drain
Bin Drain
Floor Drain
May 2001
Page 15
CME1356R and CME1656R
After Utility Connections
1. Wash out the bin. If desired, the interior of the
bin could be sanitized.
2. Locate the ice scoop (if supplied) and have it
available for use when needed.
3. Switch on the electrical power. Do not start the
machine for 4 hours.
4. Go thru the final check list (below).
Final Check List:
___ 1.Is the unit located indoors in a controlled
environment?
___ 2.Has the correct remote condenser been
properly located and mounted?
___ 3.Has the correct electrical power (voltage
and phase) been supplied to the
machine?
___ 4.Have all the water supply connections
been properly made with the correct size
tubing?
___ 5.Have all the drain connections been
properly made?
___ 6.Has the unit been leveled? Level the unit
at the bin.
___ 7.Have all unpacking materials been
removed?
___ 8.Is the water pressure adequate?
___ 9.Is the machine secured to the ice storage
bin?
___ 10. Is the bin control system been properly
installed?
___ 11. Have the drain connections been checked
for leaks?
___ 12. Has the bin interior been wiped clean or
sanitized?
___ 13. Have any water filter cartridges been
replaced?
___ 14. Check all refrigerant lines and conduit
lines, for vibration or rubbing and possible
failure. Adjust as needed.
___ 15. After 4 hours of electrical power, proceed
to Initial Start Up.
May 2001
Page 16
Component Location and Function
CME1356R and CME1656R
Reservoir: Contains the water used to make ice.
Water Inlet Valve: Opens to allow water into the
reservoir.
Evaporators/Freezing Compartment: Location of
the evaporators. Ice forms on the evaporators, and
is released when warmed up during the harvest
cycle. The freezing compartment is fully insulated
for maximum efficiency.
Head Pressure
Control Valve
Cube Deflectors: The slots in the inclined
deflectors let the water falling from the evaporators
back into the reservoir, but when ice falls during
harvest, the ice slides off into the bin.
Harvest Bypass Valve: Injects additional refrigerant
into the harvest system.
Water Pump: Forces the water from the reservoir
to the top of the evaporator(s). The motor is kept
separate from the water to minimize contact with
moisture.
Hot Gas Valve: Closed during freeze, it opens
during harvest to divert hot discharge refrigerant
gas into the inlet of the evaporators.
Purge Valve: Opens during the first part of harvest,
when the water pump restarts the water in the
reservoir is diverted to the drain.
Check Valves: Liquid and Discharge lines contain
check valves. These control refrigerant migration
during the Harvest and Off cycles.
Liquid Check
Valve
Filter-Dryer
Receiver
Harvest
Bypass
Valve
Compressor
Discharge
Check
Valve
Hot Gas
Valve
Water
Pump
Evaporators
Inlet Water
Valve
Thermostatic
Expansion
Valve
Accumulator
with Heat
Exchange
May 2001
Page 17
Purge Valve
CME1356R and CME1656R
AutoIQ Controller
Indicator Lights:
Bin Full: On when bin is full, goes on and off as
·
ice falls during a harvest cycle.
Freeze: On when the unit is in the Freeze
·
cycle, blinks when a freeze cycle is pending.
Harvest: On when the unit is in the Harvest
·
cycle.
Clean: On when the unit is in the Clean cycle.
·
Off: On when the unit has been switched off,
·
blinks when the machine is preparing to shut
off.
Water: On when the controller has identified a
·
problem with the water system.
Refrigeration: On when the controller has
·
identified a problem with the refrigeration
system.
LOW VOLTAGE IN/OUT
WATER VALVE
HOT GAS VALVE
PURGE VALVE TIMER
CONTACTOR COIL
Cycle Definitions:
Freeze: The refrigeration system is operating to
·
remove heat from the evaporators. The
compressor, remote fan motor and water pump
are ON.
Harvest: The refrigeration and water systems
·
are operating to harvest the ice cubes. While
the compressor and fan motors are on for the
full cycle, the water pump will be off at the
beginning and the inlet water valve will switch
off before the end.
Clean: Water valve opens to fill the reservoir.
·
The Water pump starts. The Clean indicator
light is switched ON. A manually initiated rinse
cycle flushes the system.
HI VOLTAGE IN/OUT
WATER PUMP
89
STACKING and/or
THERMOSTAT
FUTURE USE
RESERVOIR & DISCHARGE
LINE THERMISTORS
ICE SENSOR
ICE SENSOR
RESERVOIR WATER
LEVEL SENSOR
FACTORY USE
7
6
5
4
3
2
1
PUSH BUTTON
CONTROL SWITCHES
INDICATOR LIGHTS:
BIN FULL
FREEZE
HARVEST
CLEAN
OFF
DIAGNOSTIC LIGHTS:
WATER
REFRIGERATION
May 2001
Page 18
Initial Start Up
CME1356R and CME1656R
1. Remove the left front panel.
2. Locate and open the liquid line valve.
Open By Turning
Stem Fully Out (Up)
Service
Port
3. Double check quick-connect couplings for leaks.
4. Locate the AutoIQ Controller.
5. Connect electrical power. All lights will blink on
and off together then, for blue controllers, the two
red lights will blink while the Freeze light is on.
After 20 seconds the Freeze light will go out and
the Bin Full and Off lights will be on. After a few
seconds only the Off light will be glowing.
6. Open the water supply valve.
7. Push and release the Freeze cycle push button
(the Freeze indicator light will blink until the
compressor starts).
Initial Start (30 seconds)
·
The Freeze light will begin to blink.
·
The hot gas solenoid valve will be open.
·
The purge valve will be open
·
The water pump will be on
·
After 30 seconds, the hot gas valve closes
·
The purge valve will shut and the inlet water
valve will open to fill the reservoir. The inlet
water valve shuts off when the reservoir is full.
·
The compressor & remote fan motor start.
Freeze Cycle
The Freeze indicator light will come on. The unit
will be in a Freeze cycle for many minutes. Slush
may appear in the reservoir, it is temporary and
normal.
·
The pump will stop for a few seconds a few
minutes into the freeze cycle
·
The freeze cycle will continue until the water
level in the reservoir drops to its factory set
point, the first time that happens the water valve
will re-fill the reservoir. The second time it
happens in a freeze cycle starts the Harvest
Cycle.
Harvest Cycle:
The Harvest indicator light will be ON,
·
The hot gas valve will open.
·
The purge valve will be open for 74 seconds.
·
The water pump will switch off. The pump will
·
restart part way thru the harvest cycle.
The purge valve closes.
·
The Inlet water valve will open for a short time
·
The Bin Full indicator light will go on and off as
·
ice falls from the evaporators.
8. Machines are shipped from the factory with the
purge level set to accommodate average water
conditions. To achieve optimal machine
performance, set the purge level to the minimum
setting.
Note: While the amount of water purge is
adjustable, only those installations with a water
supply known to be excellent (very low TDS)
should adjust to the minimum setting. See the next
page for purge adjustment procedures.
9. After about 6 minutes (first cycle after any
restart) the machine will return to a freeze cycle.
Note: After the first harvest, the controller will
adjusts harvest time as needed to release all ice.
10. The reservoir refills at the beginning of Freeze.
11. Fill out the Customer Evaluation and Warranty
Registration. Send it to Scotsman.
12. Return all panels to their normal positions.
13. Inform the user of the location and telephone
number of the local service company. Inform the
user of the required maintenance of the machine.
Operational Notes:
1. The machine will only shut off on Bin Full at the
end of the Harvest Cycle after the bin fills. That
last harvest cycle will be about 6 minutes long.
2. After switching off on Bin Full, if ice is removed
from the bin, the machine will not restart until it has
been off for 4 minutes. If the Freeze button is
pushed, the machine will restart immediately.
3. If the bin controls sense a bin full signal before
any water is used (float stem up), the machine will
shut off on bin full.
4. When shutting off, the compressor will run for 30
seconds (everything else will be off) and then
switch off.
March 2003
Page 19
CME1356R and CME1656R
Adjustments
If there was a problem during Initial Start Up:
If a diagnostic light came on, check the following.
1. Water.
A water error could have been determined by the
AutoIQ Controller if the inlet water valve does not
fill the reservoir or if the water pump does not start
and lower the water level in the reservoir. If either
condition is found, the water error light will be
switched on and the machine will Shut Down.
2. Refrigeration.
A refrigeration error could have been determined
by the AutoIQ Controller if the water temperature
did not drop during the freeze cycle. The
Controller will next check the compressor
discharge temperature. If the discharge
temperature is too low, the refrigerant error light
will be switched on, and the machine will Shut
Down.
Note: The machine can be reset and restarted by
pushing and releasing the Off push button switch,
and then pushing and releasing the freeze push
button switch.
Thermostatic Expansion Valve:
The TXV is not adjustable, do not attempt to adjust
it.
How to Adjust the Amount of Water Purge
Adjustment is done by use of the control buttons
on the AutoIQ Controller. Examine the next section
to become familiar with the AutoIQ Controller
before beginning.
1. If the machine is on, push and hold the OFF
button for more than 3 seconds, then release it.
This switches the machine Off.
2. Push and hold the OFF button for more than 3
seconds (just until all Lights flash on) then release
it. Do not hold it in it too long.
3. Examine the green Lights. They should have all
flashed once, then certain ones will have turned on
to indicate which purge level the machine is set at.
There are 5 levels of purge available:
1. Maximum Purge is when All 5 lights are ON.
·
Use for extreme water conditions. Note: This
setting may extend the Harvest cycle and
reduce capacity.
2. Heavy Purge is when these 4 lights are ON:
·
Freeze
to severe water conditions. This setting may
extend the Harvest cycle and reduce capacity.
·
3. Standard Purge (factory setting) is when
these 3 lights are ON: Harvest
for typical water conditions.
, Harvest, Clean,Off. Use for moderate
, Clean,Off.Use
Typical Ice Level When Unit Shuts Off
·
4. Moderate Purge is when these 2 lights are
ON: Clean
conditions.
·
5. Minimum Purge is when this light is ON: Off.
For excellent water conditions.
Adjust by pushing and releasing the Freeze button.
Pushing and releasing the Freeze button increases
the purge one level up to the maximum, then it
goes to the minimum.
4. The machine will automatically restart after 60
seconds of no switch inputs, or restart the machine
by pushing in and holding the Off button for more
than 3 seconds, then releasing it. The unit will then
be Off. From there the machine may be placed in a
freeze cycle by pushing and releasing the Freeze
button.
,Off. This is for good water
May 2001
Page 20
How To Operate The AutoIQ Controller
The AutoIQ Controller is a
microprocessor based device that
receives input from several sources
and switches various components
on and off.
Its manual control is thru the use of
the Push Button Control Switches
1. Freeze Button. Pushing and
releasing this button starts or
restarts the machine. The AutoIQ
Controller remembers what cycle it
was last in and returns to that cycle.
2. Harvest Button: Pushing and
releasing this button will cause the
machine to go directly to a Harvest
Cycle. Can be done from Freeze or
Off. The machine will switch Off at
the end of the Harvest cycle.
3. Clean Button: Pushing and
releasing this button will cause the
machine to empty the reservoir, refill
and leave only the water pump on
for circulation of ice machine
cleaner. After the ice machine
cleaner has circulated for about 10
minutes a second push of this button
will switch on the rinsing system to
flush out the dissolved scale and ice
machine cleaner.
4. Off Button: Pushing and
releasing this button will switch the
machine OFF at the end of the next
cycle. If the button is pushed and
HELD for more than 3 seconds, the
unit will switch off immediately.
To Reset Errors: First push and
release the Off button, then push
and release the Freeze button.
7
6
5
4
3
2
1
CME1356R and CME1656R
89
PUSH BUTTON
CONTROL SWITCHES
INDICATOR LIGHTS:
BIN FULL
FREEZE
HARVEST
CLEAN
OFF
DIAGNOSTIC LIGHTS:
WATER
REFRIGERATION
May 2001
Page 21
CME1356R and CME1656R
How The Electronic Cuber Works
This section is intended for the technician. It is not necessary for the normal operation and maintenance
of the machine.
Refrigeration System:
The refrigeration system is similar to that of most
commercial cube ice machines. Heat is removed
from the water and discharged out the condenser
during the freeze cycle. As liquid refrigerant
passes thru the Thermostatic Expansion Valve, it
enters the top of the evaporators, and ice will form
at the top first.
Remote Condenser
Head
Pressure
Control
Val ve
When cubes need to be released (Harvest) the Hot
Gas Valve is opened and Hot discharge gas flows
directly from the compressor to the evaporator
inlets. At the same time, a Harvest Bypass Valve
opens for a few seconds to add the refrigerant
needed for harvest. After that the Harvest Bypass
Valve and the closed Discharge Check Valve
keeps the refrigerant in the condenser out of the
Hot Gas Circuit.
This warms up the evaporators and the surface of
the ice frozen to the evaporator surface melts. Ice
then falls into the bin.
The Check Valves also prevent liquid migration
during the Off cycle.
Harvest
Bypass
Val ve
Process
Port
Discharge Line
Receiver
Check
Val ve
Check
Val ve
Heat
Exchange
Accumulator
Hot Gas
Valve
Thermostatic
Expansion
Valve
Refrigerant
Distributor
Evaporator
Suction
Evaporator
Evaporator
Compressor
Refrigeration Schematic
May 2001
Page 22
How The Electronic Cuber Works
CME1356R and CME1656R
Water System:
Freeze:
The water pump forces water to the top of the
evaporators. The un-frozen water falls thru the
cube deflectors and back into the reservoir. As
water is turned into ice, the water level in the
reservoir falls, and the machine will re-fill the
reservoir once during the freeze cycle.
At the point where the cubes are fully formed, the
water level sensor indicates to the AutoIQ
Controller that it is time to begin the Harvest cycle.
Harvest:
At the beginning of Harvest, the water pump shuts
off and the purge valve opens. The purge valve
remains open for 74 seconds. No water will drain
until the water pump restarts. The water pump will
start at a variable time depending upon the amount
of water rinse that has been set.
After the purge valve has closed, the inlet water
valve opens and water flows into the ice machine.
The water valve will NOT be open the complete
length of the harvest cycle.
The inlet water valve will “top off” the reservoir at
the beginning of the next freeze cycle.
The AutoIQ Controller operates the ice machine by
monitoring several input measures and switching
various loads on and off.
Controller Inputs:
1. Reservoir water temperature. This is
measured by a thermistor located in the water
pump outlet.
2. Discharge line temperature. This is measured
by a thermistor located on the compressor
discharge line.
3. Water level. This is measured by an infrared
sensor and float. The float rises and falls with the
water level, and switches the sensor on and off as
it moves.
4. Bin fill level. This is measured by a set of
electric eyes in the cube outlet port. If ice fills the
bin, it will block the “eyes".
Some units are equipped with a bin thermostat,
those units use the thermostat to switch the
machine on and off. The electric eyes in the cube
outlet port will also control the machine if the bin
thermostat sticks in an ON position.
5. Time. The controller measures and compares
how long it takes for various events to happen. It
stores that data for future reference.
Controller Outputs:
A. 24 volt:
·
1. Lights
·
·
·
·
B. High Voltage
·
·
May 2001
Page 23
2. Inlet water valve
3. Hot Gas Valve
4. Contactor Coil
5. Harvest Bypass Valve Coil
1. Water Pump
2. Purge Valve
CME1356R and CME1656R
Technicians Only: Freeze Cycle Sequence
Assuming the machine has been operational, the
Freeze cycle begins with the end of the Harvest
Cycle:
Water Inlet Valve is Closed
·
Water Pump is ON
·
Compressor is ON
·
Hot Gas Valve is Open
·
AutoIQ Controller Operation, Beginning freeze:
1. Switches on Freeze indicator light and shuts off
the hot gas valve.
2. Opens the water valve to top off the reservoir.
The controller checks that water fills the reservoir,
if it does not fill up within 250 seconds, the
controller shuts the machine down. It will
automatically try to restart in 20 minutes.
3. Measures and stores the discharge
temperature.
4. If the discharge temperature exceeds the design
maximum, shuts the machine down on a
Refrigeration Error.
5. Checks for a “bin full" signal throughout the
cycle.
6. Measures the reservoir water temperature. If the
machine is operating correctly, the reservoir water
temperature will fall at a standard rate. The AutoIQ
Controller will be checking to see if the water
temperature fall matches that rate.
If not, it re-checks the discharge line temperature.
If too low, it Shuts Down on a Refrigeration Error. If
the discharge temperature is acceptable, the water
system is checked by shutting off the water pump
and determining if the water level goes up enough.
If it does not, the inlet water valve will open again
to fill it. If, after restarting, the water level does not
drop, it is assumed that there is a water pump
problem and the machine Shuts Down on a Water
Error.
If the water level does “measure up" the water
pump is restarted and the AutoIQ Controller then
measures how long it takes to lower the water
level. If the water level does not fall, the machine
Shuts Down on a Water Error.
7. Once per freeze cycle the machine will shut off
the water pump. It only does this when the water
temperature reaches a preset minimum. The pump
will only be off for a few seconds.
8. As the machine makes ice, the water level in the
reservoir will ultimately fall to the Harvest Level.
The first time that happens per freeze cycle the
inlet water valve is re-opened and the reservoir is
refilled. The next time it happens, the unit will go
into a harvest cycle.
Note: If the freeze cycle exceeds the preset
Maximum (36 minutes), the Controller will Shut
Down the machine and switch on the Refrigeration
Light.
9. The end of Freeze cycle will see the machine in
this state:
Water level = below harvest position
·
Water inlet valve will be off
·
Water pump will be ON
·
Compressor will be ON
·
Hot gas valve will be off
·
At this point Harvest begins and the AutoIQ
Controller switches the Harvest indicator light ON.
Restarts:
If the machine is restarting after it has shut off
because the bin was full, the first freeze cycle
sequence is like this:
1. Purge valve is open.
2. Pump starts.
3. Purge valve closes.
4. Water valve opens to fill the reservoir.
5. Compressor starts.
Note: If there is a power interruption, after power is
restored the machine will restart, go thru a brief
Freeze cycle and go thrua6minute Harvest cycle.
Error Restarts:
The machine automatically attempts to restart 50
minutes after a shut down. If another problem
occurs in the next cycle, the machine will attempt
one more restart. If another problem occurs in the
next cycle, the machine will shut off and must be
manually reset.
May 2001
Page 24
CME1356R and CME1656R
Technicians Only: Harvest Cycle Sequence & Other Notes
Harvest
The Purge Valve will be open for 74 seconds.
The water pump shuts off, it will restart before 74
seconds, the restart time is based on the Purge
Level Setting.
The pump restarts and pumps water out of the
reservoir until the purge valve closes.
The inlet water valve will stay on for about 30
seconds to add enough water to assist with
harvest.
The Hot Gas Valve will be open for the entire
length of the Harvest Cycle.
The Harvest Bypass Valve will be open for a few
seconds at the beginning of the Harvest Cycle.
During the Harvest Cycle, ice will be falling from
the evaporators and between the ice sensor’s
electric eyes. The AutoIQ Controller monitors the
ice falling and uses that information to determine
the next harvest cycle length.
The first Harvest after a restart will take about 6
minutes to establish a base line, then the time it
took to release that ice is used to determine the
next harvest cycle’s length.
The maximum harvest time is 14 minutes.
If no cubes fall (or are sensed) by the end of the
Maximum Harvest Time, the machine senses a
Refrigeration error. If the next cycle also produces
a Refrigeration error, the machine will shut down.
Note: The last Harvest cycle before shutting off on
Bin Full will be about 6 minutes long.
Note: The machine will not restart for 4 minutes
after switching off on Bin Full, unless the Freeze
button is pressed.
Bin Full: The controller will switch on the
compressor for 30 seconds after 12 hours of off
time to keep refrigerant out of the compressor oil.
Continuous Run Time
A unit that operates 24 hours a day 7 days a week
is too small for the user’s needs. To maintain
harvest integrity, the controller will extend the
harvest time to 6 minutes every 15th consecutive
harvest cycle.
Bin Thermostat (for those units so equipped):
In normal ambients the thermostat will react to ice
on the bulb in a few seconds. Reaction after
removal will take about a minute under normal
conditions, and longer in colder rooms.
Stacked Units:
If the bottom unit is in harvest and receives a
signal from the top unit that it is also in Harvest,
the bottom unit will stay in harvest for about 6
minutes.
If the bottom unit is shut off, but its controller still
has power, the top unit may continue to operate. If
the bottom unit’s power is shut off, the top unit will
shut down on bin full at the end of the next cycle. If
the top unit’s power is shut off, it does not impact
the bottom unit.
An error shut down on one unit does not affect the
other.
Either one may be switched off at the controller
without impacting the other.
Diagnostic Light Code Table
If a Diagnostic
Light
Blinks once
and repeats
Blinks twice
and repeats
Blinks three
times and
repeats
Is ON all the
time
Both ON all the
time
Water LightRefrigeration
Light
Water pump
will not start
Lack of water
fill
not usedHigh Discharge
Water valve
leaking thru
rapidly
Check for thermistor set
unplugged or failed
Very long ice
harvest
No harvest of
ice
Temperature
Check for low
discharge
temperature or
long freeze
cycle
May 2001
Page 25
CME1356R and CME1656R
Sanitation and Cleaning
It is the User’s responsibility to keep the ice machine and ice storage bin in a sanitary condition.
Without human intervention, sanitation will not be maintained. Ice machines also require occasional
cleaning of their water systems with a specifically designed chemical. This chemical dissolves mineral
build up that forms during the ice making process.
Sanitize the ice storage bin as frequently as local health codes require, and every time the ice machine
is cleaned and sanitized.
The ice machine’s water system should be cleaned and sanitized a minimum of twice per year.
In Place Cleaning of the Ice Machine Water
System:
1. Remove all ice from the bin.
2. Remove the front panels.
3. Push and release the Harvest button (this releases
any ice that may be on the evaporators and warms
them up).
4. Wait for the machine to finish the Harvest cycle
(the machine will stop).
5. Remove the the insulated plastic evaporator cover,
the two inner splash panels (part number 02-3680-01
and the one above it), both cube deflectors, and the
ice sensors. Place the splash panels and the cube
deflectors in a separate container. Place the ice
sensors in the reservoir, but be sure that the ends of
the connecting wires are not in the water.
6. Push and release the Clean button. The Clean
indicator light will be blinking, and the pump will
restart.
7. Pour 24 ounces of Scotsman Ice Machine Cleaner
into the reservoir water. Return the evaporator cover
to its normal position.
8. Mix a solution of 8 ounces of Scotsman ice
machine cleaner and 1 gallon of warm (95-115oF.)
water. Use the solution to scrub the splash panels
and cube deflectors in the separate container.
Scotsman Ice Machine
Cleaner contains acids.
Acids may cause burns.
If concentrated cleaner
comes in contact with skin,
flush with water.
If swallowed, do NOT
induce vomiting. Give large
amounts of water or Milk.
Call Physician immediately.
Keep out of the reach of
children.
9. After the ice machine cleaner has circulated for 10
minutes, push and release the Clean button. This
starts the rinsing process. The Clean indicator light
will be ON. Note: The rinse process flushes any
residual cleaner out of the ice machine’s water
system.
10. Continue the rinsing process for 20 minutes, then
push the off button to switch the machine off.
11. Go to the next step to sanitize the machine or go
to step 19 to finish the cleaning process.
12. Mix 2 gallons of Sanitizer solution. Follow local
codes for Sanitizer.
Note: A possible sanitizing solution may be made by
mixing 1 ounce of liquid household bleach with 2
gallons of warm (95-115oF.) potable water.
13. Push and release the Clean button again.
14. Pour 24 ounces of Sanitizer solution into the
reservoir water.
15. After the solution has circulated for 10 minutes
push and release the Clean button. This starts the
rinse process. Sanitize the ice storage bin while
waiting.
16. Continue the rinsing process for 20 minutes, then
push the off button to switch the machine off.
17. Remove the evaporator cover and spray or wash
all interior surfaces of the freezing compartment
including the evaporator cover with sanitizer solution.
18. Thoroughly immerse the splash panels and cube
deflectors in the sanitizing solution.
19. Return the ice sensors, splash panels and cube
deflectors to their original positions.
20. Return the evaporator cover to its original
position. Push and release the Freeze button.
21. Return the front panels to their normal positions
and secure them to the machine with the original
screws.
May 2001
Page 26
Additional Maintenance
CME1356R and CME1656R
To Properly Place the Evaporator Covers
Removal:
1. Remove right front panel.
2. Push up on evaporator cover and swing out the
base.
3. Use the finger holes to pull the lower inside
cover down and swing it out from the machine.
4. Pull upper inside cover out from behind the
pump hose.
Note: ALL COVERS MUST BE PROPERLY IN
PLACE or the MACHINE WILL MALFUNCTION.
Replacement:
Insert Bottom Tabs in 5th
Slot of Cube Deflectors
To drain reservoir (if desired):
1. Remove front panel.
2. Push and hold the Off button.
3. Push and Hold the Clean Button for 3 Seconds
to Activate Purge Valve.
4. Push and release Freeze button.
5. Return the front panel to its original position.
To Sanitize the Ice Storage Bin
1. Remove all ice.
2. Remove baffle.
3. Switch ice machine OFF or wait for it to be in a
cleaning cycle.
1
4. Mix a 1 gallon solution of warm (95-115oF. )
.
water and sanitizer. Follow local codes for
sanitizer.
5. Wash or spray the entire interior of the ice
storage bin with the sanitizer solution. This
includes the bottom of the ice machine and the
inside of the door, the door gaskets (if any) and
door frame.
6. Pour excess sanitizer into the bin to flush the
drain system.
7. If the approved sanitizer requires a rinse, rinse
all interior surfaces with potable water.
Return upper inside cover to its original position.
2. Using finger holes to control the part, insert the
two tabs on the bottom of the lower inside cover
into the 5th slot of each cube deflector.
3. Push down and insert upper edge of the lower
inside cover into the slot on the bottom of the
evaporator bracket.
4. Insert evaporator cover into plastic slot at the
top of the compartment and then place the lower
end onto the reservoir wall.
May 2001
Page 27
CME1356R and CME1656R
Additional Maintenance: Water Distributors
It may become necessary to remove the water
distributors from the top of the evaporator and
clean (de-mineralize) them outside of the ice
machine.
1. Remove front panels.
2. Push and release the OFF button.
3. Remove the evaporator covers.
4. Pull the tab at the front of the evaporators
forward and lift the water distributors up until they
clear the tab.
Water
Distributors
distributors in or with a solution of Scotsman Ice
Machine Cleaner and warm potable water.
10. Return the water distributors to their normal
installed position.
11. Push and release the clean button to flush the
water system.
12. After the machine stops, push and release the
Freeze button.
13. Replace the evaporator covers.
Check That Water Channels
Are Clear
5. Repeat for all evaporators and distributors..
6. Slide the left and right groups of distributors
forward until the center manifold is accessible.
7. Remove the distributors from the manifolds.
Manifold
8. Examine the top of the evaporators. The Water
Distribution Channels must be free from mineral
build up. If build up is evident, scrub the channels
with Scotsman Ice Machine Cleaner and a plastic
bristle brush.
9. Examine the water distributors. Although they
are made of a material that is resistant to mineral
build up, some may be present. Soak or scrub the
14. Replace the front panel.
Insert Bottom Tabs in 5th Slot
of Cube Deflectors
May 2001
Page 28
Additional Maintenance: Inlet Water Valve Screen
The inlet water valve has a screen on its inlet side
to keep debris from flowing into the valve. In some
cases, this screen may become clogged or
restricted by debris build up. Check for the proper
water flow:
Flow rate is 2.7 G.P.M.
1. Remove front panel.
2. Obtain a 16 ounce cup and a watch.
3. Pull the water discharge tube out of the
reservoir and place it in the cup.
4. Push and release the Harvest button.
5. If working properly, the water valve will fill an 16
oz cup in about 3 seconds. Be prepared to push
the Off button! If it does not, the water valve inlet
or other water device is restricted.
To Check the Inlet Water Valve Screen.
1. Disconnect the electrical power.
2. Shut off the water supply.
3. Remove the left front panel.
4. Unplug the electrical connection of the inlet
water valve.
5. Remove the screws holding the inlet water valve
to the cabinet.
6. Remove outlet tube from inlet water valve.
7. Rotate inlet water valve from inlet fitting and
remove valve from machine.
8. Examine the inlet screen, if dirty, brush off
screen. Note: Screen is not replaceable, and may
only be removed by taking off the covering
bracket. The bracket forms part of the inlet water
system, and must be water tight to the valve body,
removal is not recommended.
9. Reverse to reassemble.
CME1356R and CME1656R
May 2001
Page 29
CME1356R and CME1656R
Additional Maintenance: Ice Sensors, Condenser
The ice sensors use a system of infrared emitting
and receiving components to sense the build up of
ice in the bin. They are located at the bottom of the
ice outlet port. They must be free of mineral build
up to function properly. To check:
1. Remove front panels.
2. Push and release the harvest button.
3. Wait for the machine to stop.
4. Remove the evaporator cover.
5. Locate the front ice sensor.
Push the sensor from the front (at the wire area) to
the back until it releases from the holder.
6. Locate the back ice sensor Pull on the
rectangular tab to release it from its mounted
position.
7. Examine the bottom of the brackets, there are
two sensors in each bracket, check that they are
clear of mineral build up. They may be wiped clean
with ice machine cleaner to assist in removal of the
build up.
Note: Do NOT use abrasive materials or cleaner
on the ice sensor lenses. A soft toothbrush works
well to get into the hard to reach spots.
8. Reverse steps 1-6 to reassemble.
To Clean the Remote Air Cooled Condenser
1. Disconnect and lock out the electrical power.
2. At the remote condenser, check for loose debris
on the roof, remove any near the condenser.
3. Check the fan blade and condenser for grease
or dust build up. Brush the intake surfaces
(outside) of the condenser coils with a nylon brush
to remove surface dirt. Use a fin comb to
straighten any bent fins.
Note: Air flow is UP, towards the fan.
If grease is present, use coil cleaner on the
condenser. Be sure to wipe up any excess coil
cleaner.
4. Reconnect the electrical power.
May 2001
Page 30
CME1356R and CME1656R
Service Diagnosis: Diagnostic Light Analysis
Problem or SymptomPossible CauseProbable Correction
Bin is fullUse some ice
Bin thermostat is closedCheck thermostat
Machine is off
Unit is off on a Water
Error
Power is off, check
Lights.
Transformer is open
Unit has been switched
off or has finished a
Clean cycle, Off Light is
glowing
Unit has Shut DownCheck for Refrigeration or Water Error
Water supply inadequate
Water pump malfunction
Water level sensor may
have failed.
Low discharge or long
freeze cycle
If all Lights are out, check power supply,
restore power if off
If all Lights are out and there is power, check
transformer output for 24 vac
Push and release Freeze button
Check water Light, if the Light blinks 2 times
and repeats, check the water inlet valve for
proper water flow.**
Check that pump hose is attached and if
pump is plugged in and working.
Check float stem, reset machine. If it will not
reset or gives another water error and
everything else is OK, replace the water level
sensor.
Check refrigeration Light. If the Light is
glowing, there is a probable refrigeration
problem - fan motor could have failed.
Check refrigeration Light. If the Light blinks
once and repeats, look for a harvest problem.
Harvest problem
Unit is off on a
Refrigeration Error
High Discharge Temp
Unit does not go into
harvest - exceeds
maximum freeze time
Exceeds maximum
harvest time
Unit runs and both
Diagnostic lites are ON
Same, only 1 light onReservoir temp. wrongCheck water temp. and sensor.
Temperature sensors out
of range
where some cubes were sensed.**
Check refrigeration Light. If the Light blinks
two times and repeats, look for a harvest
problem. - no cubes sensed**
Check refrigeration Light. If the Light blinks 3
times and then repeats, check for a reason for
high discharge temperatures - fan motor hot
ambient.
Push and release Off button. Push and
release Freeze button. Check operation.
Push cube size float down and check
operation.
Check for cause of long harvest cycle**
Replace the temperature sensor set (water
and discharge).
* Machine may be reset by pushing and releasing the Off button, then pushing and releasing the
Freeze button. ** See following pages
May 2001
Page 31
CME1356R and CME1656R
Service Diagnosis
Problem or SymptomPossible CauseProbable Correction
Check bin controls. If the bin full light is on or
blinking the bin controls may be dirty. Clean if
dirty. The board and bin controls may also
Unit is off because of a
“Harvest Problem”
Bin controls did not sense
ice falling, unit stayed in
harvest until the maximum
harvest time ran out.
need to be checked.
Check evaporators for lime scale build up.
Clean evaporators and bin controls if dirty.
Push and release Off button. Push and
release Freeze button. Check machine
operation. Check if ice is made and harvests.
Bin controls or AutoIQ
Controller may have failed.
Other components may
have failed
Cube size control float is
Cubes are too large
Cubes are too smallNot enough water
Low ice capacity
Unit does not shut off
sticking.
Inlet water valve leaking
thru (slowly)
Dirty condenserClean condenser
Recirculation of airBlock air re-circulation or move condenser
Low refrigerant charge
Too much waterCheck for inlet water valve leak thru
Ice sensing system may
have failed.
See “Unit does not shut off” below..
Check the next page
Check/clean
Check hose from water valve for slow drip.
Replace valve if dripping.
Check for leak in reservoir
Check for a leak thru the purge valve
Check system. If there is a low charge, find
the leak, recover the refrigerant, repair the
leak, replace the dryer, evacuate and weigh in
the nameplate charge.
Check controls. Unplug thermostat and check
bin full light, if off, place something between
the electric eyes. The bin full light should
begin to blink (after 20 seconds of continuous
blockage it will glow steadily). If not, check
operation of electric eyes by unplugging #4
and jumping out the two pins on the controller
(touch the tool to the cabinet to discharge
static electricity before contacting the
controller). If the bin full light blinks, replace
the bin controls. If it does not blink, replace
the controller. Note: Leaving #4 unplugged
and jumped for 20 seconds will shut the
machine down on a bin full (at the end of the
harvest cycle). It will restart after 4 minutes or
may be reset by pushing the Freeze button.
May 2001
Page 32
CME1356R and CME1656R
Service Diagnosis: Components
Problem or SymptomPossible CauseProbable Correction
Fan motor does not
turn.
Pump motor does not
turn
Hot Gas Valve does
not open.
Hot Gas Valve leaks
thru (warm tube
temperatures on both
sides of valve during
freeze)
Water Inlet Valve does
not open
Open motor windings, or
seized bearings
No power to fan motorContactor may not close.
Open motor windings, or
seized bearings
No power to pump
Open solenoid coil.Replace hot gas valve
Stuck valveReplace hot gas valve
No power to coil in Harvest
Mechanical problem in
valve
Open solenoid coilReplace valve
Stuck valveReplace valve
No power to valve (best
checked at the beginning
of Freeze)
Replace fan motor
Replace pump
Check electrical connections. In Freeze, the
pump should have power to it. If not, replace
the AutoIQ Controller.
Check wire connections, if ok, replace AutoIQ
Controller
Replace valve
Check wire connections, if ok, replace AutoIQ
Controller
Water Inlet Valve does
not flow enough water
Water Inlet Valve
leaks thru
Compressor does not
work
Restriction in water supplyCheck water filters and/or inlet screen.
Mechanical problem in
valve
Unit in Clean cyclePush and release Freeze button.
Contactor coil openReplace contactor
Open starting componentsCheck and replace
Open windingsCheck and replace compressor
Internal valve failureReplace compressor
Replace valve
May 2001
Page 33
CME1356R and CME1656R
Service Diagnosis
Problem or SymptomPossible CauseProbable Correction
Scale in water system.Clean water system.
Poor Harvest
Low capacity
Water or Air Temperatures too
cold
Low system chargeRecover and weigh charge.
Bypass solenoid does not openCheck solenoid operation
Check valve leaks backReplace check valve
Hot gas valve does not open
Head pressure control valve
does not maintain enough
pressure (in freeze)
High discharge pressure, from a
dirty condenser or faulty fan
motor
Extreme hot locationRelocate the cabinet
Extremely hot condenser
location
Overcharge of refrigerant
Hot gas valve leaks thru, unit off
on refrigeration error
Check temps. Unit cannot
operate with water and air
temps below stated limits.
Check for power to the coil, if
there is power, replace the hot
gas valve
Replace the head pressure
control valve
Clean the condenser, repair the
fan motor
Move condenser or provide
shade
Recover, evacuate and weigh in
the nameplate charge
At the end of the freeze cycle,
there should be a definite
difference in temperature
between the inlet and outlet of
the Hot Gas Valve. If not,
replace the hot gas valve
Liquid and discharge lines are
in contact with each other
Compressor cycles on and offCompressor overheats
May 2001
Page 34
Separate and insulate them
Low on refrigerant, locate leak,
recover refrigerant, repair leak,
replace drier, evacuate and
weigh in the nameplate charge.
TXV superheat too high, check
charge, if charge is OK, replace
TXV
Mechanical fault with
compressor, replace
compressor
Internal relief valve opened,
check for cause of high
discharge pressure
PTCR
CME1356R and CME1656R
The “D” series cubers use a PTCR (Positive
Temperature Coefficient Resistor) in place of a
conventional start relay and start capacitor.
Power from the contactor connects to the PTCR
and to the Run Capacitor
A wire connects the other terminal of the PTCR to
the compressor’s start winding.
Another wire connects the run capacitor to the start
winding.
A parallel circuit connects power from the contactor
to the Run winding of the compressor.
A PTCR changes resistance sharply when its
temperature changes. When the PTCR is cold, it
connects full current to the compressor’s start
winding. After a very short time, the PTCR heats up
and shuts off the current flow. Under normal
conditions, the PTCR’s case is at about 180
o
F. A t
that temperature the PTCR has very high
resistance and will not allow current to flow. It must
cool down to about 120
oF. Before current will pass
through it again.
Diagnosis:
1. Disconnect electrical power.
2. Check if the PTCR is cool enough to handle
safely. If not, wait 5 minutes for it to cool off.
3. Disconnect both leads to the PTCR and measure
its resistance with an ohmmeter. If the PTCR reads
less than 21 ohms or more than 39 ohms, replace
it.
March 2003
Page 35
CME1356R and CME1656R
Operational Characteristics: CME1356R
Cycle Times (Minutes):
o
0oF. condenser air 70oF. indoor
air, 55
Freeze11 ½ - 12 ½16 - 17
Harvest32 ½
System Pressures (PSIG)
70oF. condenser air 70oF. indoor
air, 55
Suction: End of Freeze29 - 3130 - 32
Suction: Peak in Harvest70 - 8095 - 105
Discharge: 5 minutes into Freeze 230 - 250275 - 285
Discharge: Minimum in Harvest80100
o
F. water
o
F. water
90
F. condenser air 90oF. indoor
o
air, 70
90
air, 70
F. water
o
F. condenser air 90oF. indoor
o
F. water
Number of Evaporators:
5
·
Refrigerant Charge
288 ounces of R-404A
·
Typical Compressor Amps,
single phase
·
freeze 14 - 15
·
harvest 17 - 18
Typical Compressor Amps,
three phase
·
freeze 8 - 9
·
harvest 10 - 11
Typical Harvest Ice Weight
·
16.0 lb
Superheat
·
The TXV will control a nominal superheat point
that can vary unit to unit from 11oF. to 17oF.
While controlling that point the superheat can
also range + or - 4oF. without affecting
performance.
Hi Pressure Control - Automatic Reset
·
Hi Pressure Cut Out - 450 PSIG
·
Hi Pressure Cut In - 350 PSIG
Headmaster Valve
·
Setting is 240 PSIG
March 2003
Page 36
CME1356R and CME1656R
Operational Characteristics: CME1656R
Cycle Times (minutes):
o
70oF. condenser air 70oF. indoor
air, 50
Freeze15 ½ - 17 ½18 - 19
Harvest2 ½2 ½
System Pressures (PSIG):
70oF. condenser air 70oF. indoor
air, 55
Suction: End of Freeze30 - 3233 - 35
Suction: Peak in Harvest75 - 8590 - 100
Discharge: 5 minutes into Freeze 230 - 250275 - 295
Discharge: Minimum in Harvest100110
o
F. water
o
F. water
90
F. condenser air 90oF. indoor
air, 70
90
air, 70
o
o
F. condenser air 90oF. indoor
o
F. water
F. water
Number of Evaporators:
6
·
Refrigerant Charge
·
288 ounces of R-404A
Typical Compressor Amps,
single phase
·
freeze 15 - 16
·
harvest 22 - 23
Typical Compressor Amps,
three phase
·
freeze 9 - 10
·
harvest 13 - 14
Typical Harvest Ice Weight
·
19.2 lb.
Superheat
·
The TXV will control a nominal superheat point
that can vary unit to unit from 11oF. to 17oF.
While controlling that point the superheat can
also range + or - 4oF. without affecting
performance.
Hi Pressure Control - Automatic Reset
·
Hi Pressure Cut Out - 450 PSIG
·
Hi Pressure Cut In - 350 PSIG
Headmaster Valve
·
Setting is 240 PSIG
March 2003
Page 37
CME1356R and CME1656R
Removal and Replacement
Inlet Water Valve
1. Remove the left front panel.
2. Shut off the water supply.
3. Push and release the OFF button.
4. Pull the wire harness off the inlet water valve.
5. Remove screws holding the inlet water valve to
the cabinet.
6. Pull the valve away from the cabinet and
disconnect the outlet tube.
7. Unscrew the water valve from the water inlet
tubing. Hold the barbed inlet fitting and rotate the
valve.
8. Reverse to reassemble.
9. Push and release the Freeze button.
10. Replace the front panel.
Water Pump
1. Disconnect the electrical power.
2. Remove the front panel.
3. Unplug water pump from its electrical
connection.
4. Remove 1 plastic bolt and the reservoir cover.
5. Lift water pump up and disconnect outlet tube.
6. Pull float ball from float stem (it is a snap fit).
Pull stem out.
7. Locate water level sensor mounting tabs,
compress together to release sensor from bracket.
8. Remove water pump brackets from pump.
9. Reverse to replace.
10. Replace front panel.
11. Re-connect electrical power.
March 2003
Page 38
Removal and Replacement
Purge Valve
Electrical Shock Hazard.
Disconnect electrical
power before beginning
service.
1. Disconnect electrical power.
2. Remove left front panel.
3. Unplug wire harness from purge valve coil.
4. Locate and remove the two screws securing the
purge valve to the machine.
5. Pull the inlet and outlet hoses off the purge
valve and remove it from the machine.
6. Reverse to reassemble. There are no internal
parts available for this valve.
Purge Valve Timer
The purge valve timer is sensitive to electrostatic
discharge. Be certain to touch a grounded surface
before touching this component. Do the same
when handling the replacement part.
1. Touch a grounded surface.
2. Remove left front panel.
3. Disconnect electrical power.
4. Remove high voltage box cover.
5. Locate timer board at the back of the high
voltage box.
6. Unplug all the wires to the board.
7. Compress each of the four stand-off posts to
release the board from the stand-offs.
8. Remove the board from the unit.
Reverse to reassemble.
CME1356R and CME1656R
Water Level Sensor/Float Stem
1. Disconnect the electrical power.
2. Remove the front panel.
3. Remove 1 plastic bolt and the reservoir cover.
4. Pull float ball from float stem (it is a snap fit). Pull
stem out.
5. Locate water level sensor mounting tabs,
compress together to release sensor from bracket.
6. Remove harness from sensor.
7. Reverse to replace.
8. Replace front panel.
9. Reconnect electrical power.
March 2003
Page 39
CME1356R and CME1656R
Removal and Replacement: AutoIQ Controller
1. Disconnect the electrical power.
2. Remove the front panel.
3. Remove mounting screw holding controller to
cabinet.
4. Touch a metal surface to discharge any static
electricity.
5. Pull controller out slightly and unplug all
electrical connections.
Note: Do NOT touch the back of the controller.
6. Carefully remove the new controller from its
packaging. Again, do NOT touch the back of the
controller.
7. Plug all electrical connectors into the new
controller.
8. Re-attach the controller to the cabinet.
9. Switch on the electrical power. All Lights should
lite up.
10. Push and release the Freeze button.
11. Replace the front panel.
Electric Eyes (Ice Sensors)
These must be replaced as a set.
1. Remove both front panels.
2. Push and release the Off button.
3. Remove evaporator cover.
4. Remove lower inner splash panel.
5. Locate the back electric eye. Pull out on the
rectangular tab until the sensor is free of its
installed position.
6. Unplug the back sensor from its wire harness.
7. Unplug the front sensor its wire harness
8. Locate retainer clip in front sensor holder. Pull
clip up and out of the holder.
Back Sensor
9. Push in on the place where the wires enter the
sensor until it releases from the holder.
10. Twist the sensor 90 degrees and pull it up and
out of the machine.
11. Reverse to reassemble. Be sure that the color
codes of the connecting wires match.
March 2003
Page 40
Front Sensor Holder
Removal and Replacement: Water Level Sensor
CME1356R and CME1656R
1. Remove front panel.
2. Push and hold the OFF button. Release it when
the machine stops.
3. Trace wire harness from water level sensor to
the AutoIQ Controller (#2). Unplug the harness
from the controller.
4. Lift the pump and mounting plate up enough to
remove the float from the stem.
5. Remove two screws holding the sensor to the
pump bracket and lift the sensor up and out of the
machine.
6. Reverse to reassemble.
Note: 5 evaporator models have a different float
stem from the 6 evaporator machines. Do not mix
the two.
5 evaporator (CME1356) uses a tan stem
·
6 evaporator (CME1656) uses a brown stem
·
Discharge Line Temperature Sensor
1. Remove front panel, push and release the Off
button.
2. Remove top and left side panels.
3. Locate discharge line sensor. It is attached to
the discharge line of the compressor, 6" from the
compressor discharge port.
4. Un-snap the clip holding the sensor to the
discharge line.
5. Trace the sensor wires back to the controller,
they are plugged into #5 with the water
temperature sensor, and must be replaced with it.
6. Reverse to replace, be sure that the discharge
line sensor is 6" up from the compressor discharge
port. The discharge line sensor is marked with
yellow tape.
Note: Route wires so they do NOT contact the
discharge line.
Water Temperature Sensor
Note: This sensor is replaced as a set with the
Discharge Temperature Sensor.
1. Remove left front panel.
2. Push and release Off button.
3. Remove 1 plastic bolt and the reservoir cover.
4. Locate water temperature sensor (inserted into
pump discharge hose).
5. Pull out to remove.
6. Trace back to AutoIQ Controller, unplug from
#5.
7. Remove the Discharge Line temperature
sensor.
8. Reverse to reassemble.
Note: Do not push sensor tip in too far. There
should be about an 1/8" gap between the tip and
the inner wall of the water discharge hose.
March 2003
Page 41
CME1356R and CME1656R
Removal and Replacement
Transformer and Compressor Starting
Components
Single phase compressors use a start relay, start
capacitor and run capacitor. All are located in a
sheet metal box to the right of the AutoIQ
Controller. The compressor contactor is also
located in that box.
1. Disconnect electrical power.
2. Remove front panel.
3. Remove 2 screws at the front edge of the metal
box, and pull the cover forward and out.
4. To check components, reconnect electrical
power.
Note: The contactor coil is 24 volt.
Evaporator Support Bracket
In the unlikely event that the evaporator support
bracket needs to be replaced, two people will be
needed.
1. Remove both front panels and the top panel.
2. Push and hold the Off button until the machine
stops.
3. Remove evaporator cover.
4. Remove the interior splash panels.
5. Remove the hoses from the water distributors.
6. Use wire ties to hang the front of the
evaporators from the upper cross brace.
7. Place a clean rag under the planned cut point
and saw the old bracket in half and remove it.
8. While holding the bracket so that the right end is
higher than the left, insert the right end in the
vertical channel in the right side of the freezing
compartment.
Then, while the helper lifts the right-most
evaporator slightly, push the bracket in from below.
Keep doing this and push up on the left end of the
new bracket.
The freezing compartment walls may be pushed
apart slightly to make this easier.
9. Push up enough on the left end of the bracket
until it snaps into the vertical channel in the left
side of the freezing compartment.
10. Check that all evaporators are properly seated
front and back.
11. Remove the wire ties, and return the splash
panels, hoses, and evaporator cover to their
normal positions. Check that water distributors are
in place.
12. Push and release the Freeze button to start the
machine.
13. Check operation.
14. Return the top and front panels to their normal
positions.
Refrigeration System Components
Due to the expected level of training and
experience of a refrigeration mechanic, detailed
instructions regarding the replacement of
refrigeration components will not be presented.
However, critical items will be noted here.
Evaporators
In the unlikely event that an evaporator may need
to be replaced, do NOT braze the evaporator joints
when the evaporators are seated in the freezing
compartment, instead lift them up slightly so that
the joints to be brazed are above the top edge of
the freezing compartment.
Compressor
The compressor should not be replaced until it has
been determined that it has definitely failed. If it will
not start check the starting components first. If the
machine has low capacity, check for proper
charge, TXV operation, hot gas valve leak thru or
inlet water valve leak thru.
The metal bracket in front of the compressor must
be removed to access the compressor.
March 2003
Page 42
Refrigerant
1. This ice machine uses R-404A or HP62 as a
refrigerant. It has several unique characteristics.
A. It is a near-azeotrope, and must be liquid
charged.
B. It must use polyol ester refrigerant oil, and that
oil is very water absorbent. The system must not
be open for more than 15 minutes.
C. An electronic leak detector capable of locating
HFC-134a type refrigerant must be used to locate
refrigerant leaks.
D. A special HFC type liquid line dryer must be
used.
E. When brazing, a dry nitrogen purge is required.
F. When evacuating, use of an electronic micron
gage is recommend. Evacuate to 300 microns.
Recovering the Refrigerant
Because of the check valves, liquid refrigerant
must be recovered thru the liquid line valve, as
well as the low side access valve at the front of
the machine.
Access Valves:
1. Low Side: Remove the stem cap and insert a
3/16" allen wrench. Check that the valve is
closed.
Liquid Line: Remove the stem cap. Use a
refrigeration wrench and check that the valve
stem is fully UP or OUT. If recovering, remove
the schrader core before opening the valve.
2. Remove the port caps and attach refrigerant
manifold hoses.
3. Open the valves and purge the hoses. Note:
Open liquid line valve half way to access both
sides of the liquid line.
4. When service is complete, shut the liquid line
access valve first (fully up). Then, with the
machine running and the middle hose outlet
securely fastened to the manifold or refrigerant
tank (closed) open both manifold valves. This
allows any liquid refrigerant in the discharge hose
to flow thru the manifold and into the suction
side.
5. After the gages have equaled, shut the
manifold valves and the suction access valve.
6. Remove the gages and replace the stem and
port caps. Return the schrader core to the liquid
line valve. Make certain that all caps are on
tightly.
CME1356R and CME1656R
Allen Wrench
Torque Stem to 6-8
ft. lb.
Torque Stem Cap
to 8-12 ft. lb.
Torque Core
Cap to 7-12 ft.
Low Side Access Valve
Stem Must Be
Half-way Out
(after hose is
connected) to
Recover,
Evacuate and
Recharge
Liquid Line Access Valve
March 2003
Page 43
CME1356R and CME1656R
Liquid Charging
Because R-404A is a near-azeotrope, only liquid
refrigerant can be used to recharge the
refrigeration system. To do that may take some
special techniques:
1. Use an electronic scale to measure the charge.
2. Place a drum or cylinder of R-404A on the
scale, valve side up (most R-404A disposable
cylinders have an internal dip tube and dispense
liquid refrigerant from the valve when it is upright check yours).
3. A refrigeration manifold should be attached to
the service access valves. Attach the charging
hose to the cylinder of R-404A. Open the
cylinder’s valve and purge the hose to the
manifold.
4. Close the low side service access valve.
5. Open the discharge side manifold valve and
weigh in the name plate charge. After the charge is
weighed in, wait a few minutes and re-check the
scale.
6. If all of the refrigerant charge has not been
weighed into the discharge side, it must be
carefully added thru the low side. Close the
discharge service access valve.
7. With a sight glass or charge faster in the hose to
the low side port, start the ice machine.
8. Open the low side service access valve.
9. Crack open the low side manifold valve and
watch the scale and sight glass. Open and close
the low side manifold valve to flow liquid into the
manifold but flash off to vapor before it enters the
suction side of the refrigeration system. This
should only be a few ounces at most.
10. After the scale = the correct charge, shut off
the valve on the refrigerant cylinder.
11. With the ice machine running and the
discharge access valve closed, open both manifold
valves to allow the refrigerant in the hoses to enter
the system.
12. Shut the suction service access valve.
13. Remove the refrigeration manifold gages.
14. Replace and tighten all caps.
March 2003
Page 44
CME1356R and CME1656R
Before Calling for Service
Check the following:
1. Has the water supply to the ice machine or building been shut off? If yes, the
ice machine will automatically restart within 25 minutes after water begins to
flow to it.
2. Has power been shut off to the ice machine? If yes, the ice machine will
automatically restart when power is restored.
3. Has someone disconnected power to a central condenser (probably on the
roof - may be connected to a walk-in cooler). If yes, the ice machine may need
to be manually reset.
4. Does the bin control have ice on it? If so, remove the ice and the machine
should start in a few minutes.
To Manually Reset the machine.
1. Remove the left front panel.
2. Locate the AutoIQ Controller. If a red
diagnostic light is glowing, note which one
and its blink rate. Then push and release the
off button.
3. Push and release the Freeze button.
4. The machine should begin to operate. If
there is a lack of water it will soon shut off
again.
5. Return the front panel to its normal
position.
If the machine shuts down again, call for
service.
To Shut the Machine Off:
89
7
PUSH BUTTON
6
5
4
3
2
1
CONTROL SWITCHES
INDICATOR LIGHTS:
BIN FULL
FREEZE
HARVEST
CLEAN
OFF
DIAGNOSTIC LIGHTS:
WATER
REFRIGERATION
1. Remove the left front panel.
2. Locate the AutoIQ Controller.
3. Push and hold the Off
button for 3 seconds or until
Subject: New Ice Sensors in CME1356, CME1656 and CME2006. New Ice
Sensors, new Water Level Sensors and new Controllers in CME306 and
CME456.
Ice Sensors: Scotsman has begun production of ice machines equipped with a new style of ice
sensor. The new sensor is interchangeable with the prior sensors, which are still in use on other
Scotsman modular cubers.
Controllers: Scotsman has also added the new blue controller (see PS-3-2002) to models CME306
and CME456.
Water Level Sensor: A new water level sensor is also being used on CME306 and CME456.
Service parts for the ice sensors and water level sensor have not changed.
Ice machines built prior to this change are not affected.
The new sensors’ use will be phased in by model throughout 2002.
Additional information is on the back of this bulletin.
Ice Sensor
Photo-Eyes in New Ice Sensor
Sensor Holder
Push to Release Photo-Eye
The new ice sensor’s have a photo-eye module that
can be separated from the holder.
Once separated, the lenses of the photo-eyes can
easily be cleaned with a soft cloth or cotton swab. Ice
machine cleaner may be used if needed.
Like the other style of sensor, the photo-eye part can
be placed in the reservoir when the ice machine is
being cleaned with ice machine cleaner.
When re-assembling, be sure that the wire is not
sticking out past the edges of the sensor holder.
Module
Photo-Eye Module Separated
from Holder
Route Wire Under Clip, Push
Module Into Place
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.