Scotsman UF424A-1A, UF424W-1A, UN324A-1A, UN324W-1A, UN324A-6A Technical Manual

...
Page 1
Technical Manual for
Model UF424 and UN324
Page 2
UF424 / UN324 Technical Manual
Introduction
To the owner or user: the service manual is intended to provide you and the maintenance or service technician with the information needed to install, startup, clean, maintain and repair this product. Observe any caution or warning notices. They are important and provide notice of potential hazards.
Keep this manual for future reference.
If additional technical information is needed, go to Scotsman’s website, www.scotsman-ice.com.
Note: This is a commercial product. If service is needed on a unit in a residence, warranty may be limited. Use a commercial service company. Locate one from the Scotsman website: www.Scotsman-ice. com
Table of Contents
Specications .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 3
Cabinet Drawing . .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 4
Plan and Front Views .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 5
Side and Back Views.. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 6
Operational Data .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 7
Placement.. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 8
Installation . .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 9
Initial Start up .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 10
Maintenance and Cleaning .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 11
Condensers and Air Filter Cleaning.. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 13
Operation .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 14
Basic Troubleshooting . .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 15
Controller Functions . .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 16
Controller Details .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 17
Controller Diagnostics . .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 18
Electrical Sequence.. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 19
Testing Compressor.. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 20
Replace Compressor .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 21
Replace Fan Motor .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 22
Testing Sensors .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 23
Panel Removal .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 24
Remove Ice Storage Bin. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 25
Remove Gear Reducer .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 26
Remove Auger . .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 27
Replace Evaporator.. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 28
Replace Auger Motor .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 29
Prep to Replace Water Seal or Bearings .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 30
Replace Water Seal and Auger Bearings .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 31
Replace Electrical Components . .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 32
Schematic Diagram .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 33
Wiring Diagram .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 34
September 2017
Page 2
Page 3
UF424 / UN324 Technical Manual
Specications
This ice maker is designed to be installed indoors, in a controlled environment. Although it can operate in a wide range of air and water temperatures, it will provide the best performance if not subject to extremes.
Air Temperature Limitations
o
Maximum: 100
Minimum: 50o F or 10o C
Water Temperature Limitations
Maximum: 100o F or 38o C
Minimum: 40o F or 4.4o C
Water Pressure, Potable
Maximum: 80 PSI or 5.5 BAR
Minimum: 20 PSI or 1.3 BAR
Water Pressure, Condenser inlet
Maximum: 145 PSI or 10 BAR
Minimum: 20 PSI or 1.3 BAR; can be as low as 5 PSI or 0.3 BAR if clean and supplied with 45o F water.
F or 38o C
Operating the machine outside of any of the above limitations is considered abuse and any resulting damage is not covered by warranty and could cause a complete loss of warranty coverage.
Warranty Information
The warranty statement for this product is provided separately from this manual. Refer to it for applicable coverage. In general warranty covers defects in material or workmanship. It does not cover maintenance, corrections to installations, or situations when the machine is operated in circumstances that exceed the limitations printed above.
Product Information:
The UF424 produces aked ice and the UN324
produces nugget ice. The ice is stored in an insulated bin with ice level automatically maintained by the control system.
A back ow preventer may be required by local
plumbing codes.
Condenser GPM
70oF or 21oC water: 0.25 GPM or 0.95 LPM
50o F or 10oC water: 0.15 GPM or 0.57 LPM
Voltage 115 volt models
Maximum 126 VAC
Minimum 104 VAC
Water Conductivity:
Minimum:10 micro Siemens/CM
RO water may be supplied to the potable water system, but if it has less than the above conductivity, the water level sensor will not detect water and the unit will not make ice.
Deionized water is not recommended due to its potential corrosive nature and any damage caused by DI water will not be covered by warranty.
Has a 5.5 ft. power cord with NEMA 5-15P plug.
Air cooled models ows in the right front and out the left front and include a cleanable air lter.
Legs are provided, thread size is 5/8-11. Replacement leg kit number is KLP7.
Machine may be installed without legs.
For available options and kits, see sales literature.
Scotsman Ice Systems are designed and manufactured with the highest regard for safety and
performance. They meet or exceed UL563, veried by
Intertek, ETL.
September 2017
Page 3
Page 4
UF424 / UN324 Technical Manual
Cabinet Drawing
WATER INLET
ACCESS
POWER CORD
DRAIN
September 2017
Page 4
Page 5
UF424 / UN324 Technical Manual
Plan and Front Views
72.3cm
28.4in
99cm
39.0in
61cm
24.0in
84.7cm
33.4in
AIR EXHAUST
50.8cm
20.0in
AIR INLET
September 2017
Page 5
Page 6
UF424 / UN324 Technical Manual
Side and Back Views
72.8cm
28.7in
5.3cm
2.08in
UTILITY
CLEARANCE
WATER INLET
3/8 FLARE
CONDENSOR WATER DRAIN CONNECTION 1/2-14 NPT
POWER CORD
15.1cm
6.0in
51.4cm
20.3in
UNIT DRAIN 3/4" FPT
CONDENSER WATER INLET 3/8-18NPT
11.9cm
4.7in
13.6cm
5.4in
16.8cm
6.6in
WATER REGULATOR
ADJUSTMENT ACCESS
7.8cm
3.1in
17.5cm
6.9in
24.5cm
9.7in
September 2017
Page 6
Page 7
UF424 / UN324 Technical Manual
Operational Data
High Pressure
Electrical
Model
(Volts/Hz/Phase)
UF424A-1A / UN324A-1A 115/60/1 Air 260 190 12 15
UF424W-1A / UN324W-1A 115/60/1 Water 260 190 12 15
UF424A-6A / UN324A-6A 230/50/1 Air 260 190
Model Typical Watts Typical Amps Auger Motor Amps Compressor Amps
UF424A-1A / UN324A-1A
UF424W-1A / UN324W-1A
UF424A-6A / UN324A-6A
560 - 690 6.3 - 7 1.1 - 1.4 5 - 5.8
540 - 575 6.1 - 6.7 1.1 - 1.4 5 - 5.8
Condenser
Switch (PSIG)
Cut Out Cut In
Refrigerant
Charge
(R-134a)
Ounces
Maximum Fuse Size
or Breaker (Amps)
Model Condenser 70/50 Suction
Pressure (PSIG)
UF424A-1A / UN324A-1A
UF424W-1A / UN324W-1A
Note: 70/50 and 90/70 refer to the air and water temperatures (in degrees F) the machine was tested in. All
eld conditions are unique, but at temperatures near those listed a eld machine will have similar results.
Air 6 - 8 8 - 9 130-135 180 - 185
Water 6 - 8 6 - 8 135 135
90/70 Suction Pressure (PSIG)
70/50 Discharge Pressure (PSIG)
90/70 Discharge Pressure (PSIG)
September 2017
Page 7
Page 8
UF424 / UN324 Technical Manual
Placement
The location of the equipment should be selected with care. Consideration should be given to allow adequate space for air cooled models to breathe.
The ice machine is not designed for outdoor use. It must be installed indoors, in a controlled environment. The air and water temperatures must not exceed rated limits.
Scotsman assumes no liability or responsibility of any kind from products manufactured by Scotsman that have been altered in any way, including the use
of any part and/or other components not specically
approved by Scotsman.
Scotsman reserves the right to make design changes and/or improvements at any time.
Specications and design are subject to change
without notice.
Airow on air cooled models:
Intake from the right grill
Exhaust from the left grill
Do not install where this air ow is blocked.
The power outlet should be located within the length of the supplied power cord. If legs will be used, allow space for the total cabinet height.
Air cooled models in a small room will require ventilation to exhaust heat from the condenser. The condenser fan and motor will generate some noise while the machine is running. Noise sensitive areas should consider water cooled equipment or locate the machine where the noise from ice making will not objectionable.
Unpack
1. Separate the carton from the shipping pallet
2. Inspect for any hidden shipping damage. If any is found, retain carton and notify carrier for potential claim. Shipping damage is not covered by warranty.
Caution: Tip Over hazard to prevent injury or damage to the machine please use caution when lifting the unit. It will easily tips to the rear.
3. Remove bolts holding machine to pallet.
4. Install the legs. The legs are to be screwed into the same holes the shipping bolts were removed.
5. Remove the protective plastic covering the panels.
The longer it is left on the panel, the more di󰀩cult it
will be to remove it.
Airow
Spacing:
No additional spacing is required at the top or sides. However, suggested minimum side clearance for the installation is 1/8’’ or 3.2 mm and suggested minimum top clearance is 1/4” or 6.4 mm.
The machine may be installed with 0 clearance at the back. Do not block louvers at the front of the cabinet.
Pre Installation:
Water supplied to the ice machine should be ltered. Install a lter system that lters out suspended solids. It may be necessary to add a coarse pre-lter ahead of the ne lter.
Inspect the place where the ice machine is to be installed. Check for:
Space for the cabinet
Water Supply
Drain Availability
Electrical Power Supply
September 2017
Page 8
Page 9
UF424 / UN324 Technical Manual
Installation
Note: The building drain inlet must be lower than the drain outlets at the back of the ice machine.
The water supply must have a hand shut o󰀨 valve
accessible when the unit is installed.
For the Plumber
1. Connect cold potable water to the 3/8’’ male
are behind the lower back panel. A water lter is recommended. Flush the water line
prior to connecting to the ice machine.
A loop of copper tubing may be used between the ice machine and the water supply. This will allow the ice machine to be pulled out from its installed location
without disconnecting water. No back ow preventer is
required in the potable water line. This is provided by the reservoir seat, which is above the reservoir water level and cannot be siphoned
2. Connect a drain tube to the drain tting. Drain
tubes for a water cooled machine should be
run separately. The bin drain tting is 3/4’’
FPT. And it is plastic. Do not overheat.
• Drain tube material must be rigid and meet local code.
• Traps in the bin drain line without vents ahead of them will cause poor draining
• The bin drain must be vented if there is a long horizontal run 5 feet or more. All drains are gravity and must have a minimum fall of 1/4’’ per foot of horizontal run.
• Maintain the air gap required by local code between the end of the drain to, and the building drain receptacle.
• Drain tubing should be insulated to prevent condensation from forming on the tubing.
For the Electrician
This is a cord-connected unit and must be on a separate single phase power supply. Check the name plate for the correct voltage. The maximum fuse size for this circuit should be 15 A, per the nameplate use fuses or HACR circuit breaker.
Follow all local codes. This unit must be
grounded. Do not use extension cords and
do not disable or bypass the ground pin on electrical plug.
After utility connections
1. Level the cabinet, use the leg levelers on the end of the legs to adjust to cabinet height. Legs should have been installed when the unit was unpacked.
2. Wash the bin and hood. If desired, the interior of the bin could be sanitized.
3. Locate the scoop, wash it and have it available for use when needed.
Water Inlet
3. Water cooled models have a separate 3/8”
FPT tting for condenser water inlet. DO
NOT FILTER water to this connection. The condenser drain is1/2’’ FPT and does not need a vent.
Drain
Utility Connections
September 2017
Page 9
Page 10
UF424 / UN324 Technical Manual
Initial Start up
Final check list:
Ice machine is installed indoors with air and water temperature controlled within the limitations detailed in this manual
Ice machine is level in its nal position
Electrical disconnect (switch or plug as required) is within sight of the installed machine
Electrical circuit is dedicated to this ice maker
Voltage has been conrmed within the specications in this manual and the name
plate on the ice maker Plumbing connections are complete and
tested for leaks Ice maker is installed with proper
clearance, allowing for service and utility connections
Water shut o󰀨 valve installed near the ice
maker
Start up:
7. Create a solution of sanitizer. Mix 4oz/118ml of NuCalgon IMS III and 2.5gal/9.5L of (900F/320C to 1100F/430C) potable water to create a 200 ppm solution.
8. Sanitize bin by wiping all surface areas with the sanitizer solution. Allow to air dry.
9. Turn the ice maker on by pressing the on button.
10. Replace inner panel, front cover and louvered panel.
11. Give the owner/user this manual, instruct him/her in the operation and maintenance requirements of the unit. Make sure they know who to call for service.
Fill out the Customer Evaluation and Warranty Registration form, and mail it in to Scotsman or register the unit at Scotsman’s website (www. scotsman-ice.com).
Once started, the ice machine will automatically make ice until the bin level sensors are blocked. This will happen once the ice piles up to the sensors.
The typical ice level when the machine is o󰀨 will be
several inches below the door. When ice level drops from use or meltage, the ice machine will resume making ice.
1. Remove louvered front panel.
2. Open bin door and remove the inner panel, held in place by 4 thumb screws.
3. Open the water valve. Observe that water enters
the water reservoir, lls and then shuts o󰀨. Check
for leaks. Repair any leaks before going further.
4. Switch electrical supply on. Lights on controller
will ash and then the power light will remain on.
The code display will show O.
5. Push and release the On/O󰀨 button. The machine will start the ice making process. The code display will show F. Air cooled models will discharge warm air Water cooled models will discharge warm (about 1200F/480C) water out of the condenser drain. In a few minutes, ice will begin to fall into the bin.
6. Push the on/o󰀨 button to switch the machine o󰀨. Scoop out any ice in the bin.
out the left side of the front panel.
Tip: To maximize ice storage scoop the ice to the sides of the bin.
Noise:
This is a commercial ice machine. It contains a powerful compressor, heavy duty gear reducer and, if air cooled, a fan motor. It will produce some noise
when it is making ice. Every e󰀨ort was made during
its design to minimize the sound level but some is unavoidable.
September 2017
Page 10
Page 11
UF424 / UN324 Technical Manual
Maintenance and Cleaning
There are 4 areas of maintenance
1. Ice making system
2. Photo eye ice level control system
3. Bin
4. Air cooled condenser and lters
Ice making System:
Remove Scale
1. Remove front panel.
2. Turn the machine o󰀨 by pressing the on / o󰀨 button.
Reservoir
5. Remove the top cover from the reservoir.
6. Shut water supply o󰀨 at the reservoir by turning the knob counterclockwise.
Knob
3. Empty the ice from the storage bin
4. Remove the inner panel using the 4 thumb screws.
Inner Panel
7. Locate the evaporator drain in the ice machine compartment. Unplug it and drain the evaporator.
8. Replug the drain.
9. Mix a solution of 1.5qt/1.4L of warm water (900F/320C to 1100F/430C) and 4 ounces of Scotsman Clear 1 Ice Machine Scale Remover.
Ice machine cleaner contains acids. Acids can cause burns.
If concentrated cleaner comes
in contact with skin, ush with
water. If swallowed, do NOT induce vomiting. Give large amounts of water or milk. Call physician immediately. Keep out of the reach of children.
September 2017
Page 11
Page 12
UF424 / UN324 Technical Manual
10. Pour the cleaning solution into the reservoir until
it is full (a squirt bottle may be necessary to ll
reservoir with cleaning solution).
11. Push the clean button. The machine will operate the auger motor for approximately 20 minutes. Then it will start making ice with the cleaning solution.
12. Add remaining cleaning solution to the reservoir as ice is being made for the next 20 minutes. After
the full 40 minutes (steps 11 & 12) the unit turn o󰀨.
13. Drain the solution from the reservoir by removing the plug. Once drained, replace the plug.
Sanitize Water System
1. Create a solution of sanitizer. Mix 4oz/118ml of NuCalgon IMS III and 2.5gal/9.5L of (900F/320C to 1100F/430C ) potable water to create a 200 ppm solution.
2. Pour the sanitizing solution into the reservoir until it is full and wait 2 minutes.
3. Turn on the water supply and press the ON /O󰀨 button to turn the ice machine on
4. Operate the machine for at least 15 minutes.
5. Drain the solution from the system by pulling the reservoir plug from the drain hose. Return plug when drained.
Photo Eye ice level control
1. Mix solution of 4 ounces of Clear 1 Ice Machine Scale Remover and 1.5qt/1.4L of 900F/320C to 1100F/430C water.
2. Remove sensors from inner cover by removing the white c-clip .
3. Use cotton swab and cleaning solution to thoroughly clean photo sensors.
4. Rinse sensors with clean water.
5. Reinstall sensors in inner panel.
14. Pour clean water into the bin to melt any ice produced during the cleaning cycle.
15. Mix a solution of 4oz/118ml of Scotsman Clear 1 ice machine scale remover and 16oz/473ml of potable water. Use this scale remover solution for the water reservoir cover, ice discharge chutes, the storage bin and the inner front cover.
Bin
1. Use the same cleaning mixture to thoroughly clean bin surfaces.
2. Rinse with clean water.
3. Use sanitizer mix on all bin surface areas and areas that may contact the ice.
4. Rinse with clean water.
September 2017
Page 12
Page 13
UF424 / UN324 Technical Manual
Condensers and Air Filter Cleaning
Filters and Air Cooled Condenser
The air lter located on the lower front grill will capture
airborne dust during operation. As the dirt builds up, it
begins to restrict air ow and causes the refrigeration system to work less e󰀩ciently. Clean the air lter
regularly.
1. Remove the lter by sliding it to the right until it is clear of the ice machine.
Note: It is a snap t and the snaps may be very tight.
Pull hard with two thumbs.
2. Remove dust and dirt by washing the lter in a utility sink.
3. Reinstall lter in the ice machine.
Condenser
The condenser ns require semi annual cleaning. Use caution to prevent damage to the condenser ns.
1. Lightly brush dust from the condenser.
2. Use a vacuum to thoroughly clean the condenser.
Water cooled equipment may be connected to a closed loop recirculating system or to a regular water supply. See the pressure limits on page 3.
The included water regulating valve will vary the amount of water or coolant needed to maintain a constant discharge pressure. Higher coolant
temperatures will result in increased coolant ow to
maintain the discharge pressure set point.
That pressure is factory set to 135 PSIG. If needed, it
may be eld adjusted to that set point. An access port
to the adjustment stem is available on the lower back panel.
In areas with highly mineralized water, the inside of the condenser may become coated with scale. When that occurs the amount of water used by the condenser will increase, as the water regulating valve opens further to keep the discharge pressure at the set point.
Scale on the inside of the condenser may be cleaned by circulating an acid solution with an auxiliary pump.
Air Filter
Remove and Clean the Air Filter
September 2017
Page 13
Page 14
UF424 / UN324 Technical Manual
Operation
At initial start up there is no ice in the ice storage bin, so there is nothing blocking the infrared sensors that are
used to control the on or o󰀨 mode of the machine. A push of the on o󰀨 button triggers the controller to begin ice
making.
The controller checks for water using the continuity sensor in the reservoir. If that sensor indicates there is water, and the refrigeration pressure switch is closed, the controller connects power to the compressor, fan motor (if air cooled) and auger drive motor.
The compressor forces refrigerant to circulate causing the evaporator to become very cold, which takes heat from the water inside the evaporator’s tube. That refrigerated space also contains the slowly rotating auger. Eventually enough heat is removed from the water to cause ice crystals to form. When enough ice crystals have formed the auger moves them vertically up the tube and the soft, wet ice is forced through the slots in
the ice breaker. The limited area of the slots causes the soft ice to be forced together, forming either aked or nugget ice, depending upon the design of the breaker. As ice exits the breaker or extruder, more water ows
from the reservoir into the bottom of the evaporator tube.
Water replenishment by the gravity fed water is the key element in this ice making process. It provides a continuous heat load to the refrigeration system so that, as ice is made, an equal amount of water re-enters the
system, keeping the system in balance. A aker then, is a unique refrigeration system in that it is steady-state.
Once the machine has begun to make ice the evaporator’s temperature does not change as the replenished water keeps adding heat.
The ice slides down a chute into the insulated bin. The bin is not refrigerated. There is a drain at the bin’s oor
to let melt water out. As it is made, ice will pyramid under the chute and form a pile that gradually increases to the point that the top of the pile enters the chute, blocking the infrared light between the ice sensor’s emitter
and receiver, which signals the controller to stop making ice. The ice level at the rst shut o󰀨 may be less than
later when the bin temperature has stabilized. Ice storage bin capacities are calculated by the bin’s internal volume, so the amount of available ice may not equal the calculated quantity unless ice is distributed to the sides during use.
The shut o󰀨 process begins when the controller opens the compressor relay, cutting the power to the
compressor. The auger motor continues to operate to clear the evaporator tube of any ice that was in it. Then it
is shut o󰀨. In normal operation when the ice is used or melts enough to expose the emitted infrared light to the sensor’s receiver, and the compressor has been o󰀨 for the preset amount of time, ice making will restart.
Sound
The normal sounds of this machine are the compressor, fan blade if air cooled, and auger drive motor. Occasionally there may be a slight crunching sound as ice is forced thru the extruder or breaker. A loud moaning noise could occur if ice is not sliding vertically up the evaporator tube. If it revolves with the auger, it will remain under refrigeration too long, and could even freeze to the evaporator wall. Then it becomes like chipped ice, which causes the gear reducer to be overloaded as it pushes the extra hard ice thru the extruder. That is known as a rotating freeze. The most likely cause of a rotating freeze is internal scale build up, especially on the auger.
September 2017
Page 14
Page 15
UF424 / UN324 Technical Manual
Basic Troubleshooting
Symptom Possible Cause Probable Correction
No ice in bin Unit in o󰀨 mode or o󰀨 on
error code.
False bin full
No power to unit Check for the power light on the controller. If not
Auger motor not operating Open windings. Check motor windings and replace
Compressor not operating Contactor coil is open, check and replace if needed.
Compressor operating, auger turning, no ice is made
Excessive noise Tubing contact Check for tubes rattling and panels not tight
Fan blade out of balance Replace fan blade Compressor noisy Replace compressor
Moaning noise when making ice
Slow or Low production Air lter is dirty Clean air lter
Unit cycles o󰀨 and
restarts
Water seal being compressed
Condenser is dirty Check and clean condenser Room and/or Water
Temperature too high
Restricted air ow to unit Check and remove air ow restrictions
Loose electrical connection Check power cord and outlet. Outlet may be worn,
Remove front panel and check controller code display. Push ON/OFF button to reset. See pages 16 and 17 for further details.
b is showing in the display but the bin is not full. Check that there is good connection from the controller to the photo eye set. Replace photo eye set if no other cause can be found.
illuminated restore power.
if open. Gear reducer seized, replace gear reducer. Auger bearings seized, replace bearings and seal No power to auger motor, Auger light is ON.
Replace controller. Code 2 in controller. Check that sensor rotates with
motor and isn’t loose. Tighten screw if loose. Code 1 in controller, replace auger motor.
Compressor hot and overheated, check start relay and start capacitor. Check system charge. Check TXV for high superheat.
No power to compressor or contactor coil. Compressor light is ON. Replace controller.
Compressor at room temperature, will not start. Check windings. If open, replace compressor. If not open, check/replace start relay and start capacitor.
Check refrigeration system, TXV may be set to too much superheat or the system is low on refrigerant.
Gear reducer bearing failure, replace gear reducer
Maximum production will be achieved at 70°F / 21°C air and 50° / 10°C water
replace worn outlet.
Note: A damaged power cord must be replaced by the identical, OEM service part.
September 2017
Page 15
Page 16
UF424 / UN324 Technical Manual
Controller Functions
All models use the same control system.
The electronic controller operates the compressor (with fan motor), and auger drive motor, It monitors:
• Reservoir water availability
• Storage bin ice level
• Refrigeration pressure
• Auger motor speed
• Auger motor rotation
Many of these are used to insure that the machine does not damage itself during use. For example, it is critical that it not attempt to make ice without water, so if the water sensor is dry, the machine will not make ice.
Switches - there are two switches:
• On/O󰀨 - to switch the machine on or o󰀨. Holding it
in to shut o󰀨 will stop ice making immediately.
• Clean - to engage the clean mode
Indicators - there are ve LEDs:
• Power - Glows when controller has power
• Status - Glows when in ice making mode
• Time to Clean - Glows when it is time to clean the machine
• Auger - glows when the auger motor is on
There is also a code display, the codes are: O - - - for o󰀨 F - - - for ice making b - - - for bin full E - - - for controller error C - - - for clean mode d - - - for test mode 1 - - - for auger rotation direction wrong 2 - - - for auger speed too slow 3 - - - for no water sensed 4 - - - for high refrigerant pressure
If a number code is triggered, the controller will stop ice making. A blinking code means it is a temporary condition. Example: A blinking F occurs during the ice making restart process; it stops blinking when the compressor starts.
The controller will automatically restart from a water interruption or power interruption or when a refrigerant pressure switch has automatically reset.
To reset the control when it has been manually locked
out, Push and release the On/O󰀨 button to shut it O󰀨
and then Push and release it again to switch it On.
Note: The compressor will not restart for 2 minutes
from the time it was shut o󰀨.
• Compressor - glows when the compressor is on
September 2017
Page 16
Page 17
UF424 / UN324 Technical Manual
Controller Details
The controller has features for the service technician. Some details:
• Any auger motor failure is an immediate shut down. Because of the critical nature of that failure there is no
auto restart from an auger error.
• An open Water Sensor (dry probes) will stop the machine. Because water can be restored at any time,
whenever both Water Sensor probes are wet again AND the compressor has been o󰀨 for at least two minutes,
ice making will restart.
• An open High Pressure switch will stop the machine. Because the pressure switch is an automatic reset,
when it closes AND the compressor has been o󰀨 for at least two minutes, ice making will restart.
• Fault Code View: Push and HOLD the clean button (auger motor starts) AND then push and release the
on/o󰀨 button 3 times (auger motor stops) or until Status light is on. Release both. Pushing Clean will cycle
thru the available codes, the total number of codes stored is 30.
Note: An existing error cause will not allow the fault codes to be read. Example: No water in the reservoir will trigger an immediate code 3 and any other codes cannot be read. Either correct the cause or jump out the sensor signaling the error and then go thru the Fault Codes View process.
• Clear codes: Only from Fault Code View: Push and HOLD the Clean button for about 3 seconds. The
display code will blink 3 times. Release.
The compressor will not restart until it has been o󰀨 for at least 2 minutes.
There is a Test Mode. The Test Mode operates each load in sequence to conrm that it is being powered
by the controller.
To start Test Mode: Push and HOLD the ON/OFF button; at the same time, push and HOLD the CLEAN button. When a “d” appears in the code display, release the buttons, the test mode will begin.
Time (seconds) On O󰀨 0 Compressor Auger Gear Motor 10 Compressor and Auger Gear Motor 20 Auger Gear Motor Compressor 20 None Auger Gear Motor, Compressor 40 None All – Test Complete
• The Time to Clean indicator light glows when 6 months of power up time have elapsed. When it is on it
does NOT stop ice making. It is cleared and reset when the Cleaning process has been completed.
• The Cleaning process, described in detail in the Maintenance section, is initiated by a press of the Clean button. The auger motor will be operating during the entire Clean mode, the compressor starts automatically to make ice with the scale remover solution. The scale is dissolved by the action of the scale remover solution and the auger’s motion.
USB rmware updates may become available. To update the unit must be in Test Mode and then a USB stick with ONLY the update on it is inserted into the USB connector. L will be displayed during the Loading process. After a few seconds the LEDs begin scrolling up for about 75 seconds then the LEDs start scrolling down for about 20 seconds. At the end “0” is displayed. Unplug the USB drive.
Note: If during the update process the display ashes between “L” and “F” that means that the Load Failed. If
that happens, unplug the USB drive, then power cycle the control board. If “0” is not displayed, press the On/
O󰀨 button. The controller will revert to the original rmware.
September 2017
Page 17
Page 18
UF424 / UN324 Technical Manual
Controller Diagnostics
Code or Light Action Probable Cause Suggested Action
O F b E C d
1
2
3
4
Status light is on Unit is in ice making mode Normal, may not be making ice if
Time to Clean light is on Unit has not been cleaned for at
Unit manually switched o󰀨 If desired, switch unit on.
Freeze mode None, unit is making ice.
Bin sensors sense bin full Check if bin is full.
Corrupted memory Replace controller
Clean mode Continue clean mode
Test mode None, allow unit to nish test
mode.
Auger motor rotated auger backwards.
Auger motor stalled or operating slowly
No water in reservoir Restore water. If there is water,
High pressure cut out open Check fan motor on air cooled or
least 6 months
Replace auger motor. Check water seal area for leaks, replace seal if leaking.
Clean ice making system and retry.
If unit shuts o󰀨 again right after a
reset, magnet rotor on motor shaft may be loose.
is it too pure? Are sensor wires connected?
water supply on water cooled.
bin is full Clean unit
Auger light is on Auger motor is active Normal when making ice
Compressor light is on Compressor is active Normal when making ice
Code E cannot be corrected in the eld. Replace controller.
September 2017
Page 18
Page 19
UF424 / UN324 Technical Manual
Electrical Sequence
When electrical power is connected, and the prior
mode was O󰀨, the controller veries the voltage and performs a self check. If the self check conrms the
controller is working and that water is sensed in the reservoir, it will display an O and blink the Status light. If the prior mode was ice making, the controller will also perform a self check, when it is successful it will begin a restart process and display F.
If no water is sensed, the controller will not allow ice making, but instead a 3 will show in the display, indicating that no water has been sensed. When water is sensed, and the bin control is calling for ice and at least two minutes have passed, the controller will automatically start ice making.
Note: A failure of the self check will result in the controller displaying an E and no other action will occur.
After a successful restart, the controller will switch on the compressor and auger motor to begin ice making. The controller’s compressor relay supplies power to the contactor coil while the auger motor’s power is supplied directly from the controller’s auger relay. If the unit is air cooled, the fan motor will also start, as it is electrically tied to the compressor contactor.
Timings
Status changes from Bin Full to Bin Empty: 10 second delay.
Status changes from Bin Empty to Bin Full. 6 second delay
Auger motor on after bin full or timed shut down: 60 seconds.
Compressor restart after o󰀨: 2 minutes.
Hi pressure control reset time: Varies by ambient and cabinet temperature. Longer in high temperatures.
Clean mode: 20 minutes of auger only operation and then 20 minutes of auger and compressor operation. 40 minutes total.
Ice making continues until the infrared light is blocked and the unit shuts down on bin full. It can also stop from any of these safeties:
1. Hi pressure cut out: 230 PSIG, automatic reset when the pressure drops to 190 PSIG. If triggered, it signals a severe condition where there was either no fan blade rotation on air cooled models or no water supplied to water cooled models.
2. Auger motor overload. Immediate shut down, manual reset. This signals a condition where the auger motor could not rotate the auger at the correct current.
3. Auger motor reversal. Immediate shut down, manual reset. Auger motor failure.
Manual reset - restart process: Push and release the
On/O󰀨 button, unit will display O. To restart: push and release the On/O󰀨 button again.
Manually shut down either by pushing and releasing
the On/O󰀨 button (compressor shuts o󰀨, auger motor continues for a minute) or by holding in the On/O󰀨
button until the machine completely stops.
September 2017
Page 19
Page 20
UF424 / UN324 Technical Manual
Testing Compressor
The refrigeration system is steady-state. When in operation and stabilized, it will maintain nearly constant discharge and suction pressures.
Items that can a󰀨ect that are:
Irregular water ow
Erratic thermostatic expansion valve
Changes in room air temperature
Normally use of refrigeration gauges is unnecessary. If the unit is making ice properly, it is highly likely that all is normal. Refrain from attaching gauges, and then only use very short hoses to avoid changing the amount of refrigerant charge. See pressure information on page 7.
Electrical Shock Hazard
Disconnect electrical power before beginning
Capacitor Testing
Capacitors may be tested using a multimeter, but begin with a visual test. A good indication of a failed capacitor is one that is bulging or leaking.
If the capacitor looks ok, check it with a multimeter.
1. Discharge the capacitor.
2. Set a digital meter to a high resistance scale of at least 4k.
3. Put the probes on the capacitor terminals and observe the display. It should provide a reading and then show Open Line. If no reading, the capacitor has failed and should be replaced.
If the meter has a Capacitance setting, use it to measure the capacitance, replace if not near to the mfd listed on it.
Compressor Testing
Because the compressor is the hermetic type, the available testing methods are limited. Some items that can be measured are winding resistance and amp draw.
The compressor gets its power from the contactor, which is operated by the controller. It must be working
or the compressor will be o󰀨.
Compressor Starting
The compressor uses a potential relay and start capacitor to provide starting power.
Potential relay: The contacts of this relay are normally closed and open when the compressor starts.
Compressor starts but current too high, overheats. If the relay contacts do not open, there will be current from the start capacitor. Replace the relay.
Compressor does not start. Relay contacts open, check for continuity. Replace relay if open. Start capacitor may have failed.
If the compressor does not start and a check with an amp meter shows it does not draw any current, it is likely it has an open winding or overload. Those can be checked using a multimeter.
If the compressor is hot the overload may be open. An open overload is an indication of a worn compressor, defective starting components or high superheat.
Note: Normal operating temperature of the compressor dome is 85 - 95 degrees F. - warm to the touch.
If the overload is open and the compressor is not hot, the overload itself could be the problem. Overloads also open due to high current and a shorted winding could cause that. Check for shorted or grounded windings with a multimeter.
High superheat is caused by lack of refrigeration, possibly from low charge or a TXV starving the evaporator.
September 2017
Page 20
Page 21
UF424 / UN324 Technical Manual
Replace Compressor
The compressor can be replaced from the back.
Note: Always check electrical information on new compressor to be sure it is the correct voltage and phase.
1. Disconnect electrical power.
Electrical Shock Hazard
Disconnect electrical power before beginning
2. Remove lower back panel.
3. Disconnect wires from compressor terminals.
4. Recover refrigerant from the unit.
5. Remove hair pins holding compressor to chassis.
6. Disconnect suction, discharge and process tubes from compressor.
7. Remove compressor from unit.
8. Install new compressor in unit.
9. Reconnect suction, discharge and process tubes using the proper techniques of the refrigeration trade.
10. Remove and replace the dryer.
11. Attach a vacuum pump with micron gage to the system and evacuate it to 300 microns.
12. Reattach electrical wires to compressor terminals.
13. Replace the relay and capacitors with those from the kit.
14. Weigh in the nameplate charge.
September 2017
Page 21
Page 22
UF424 / UN324 Technical Manual
Replace Fan Motor
Suggested tools include 1/4 inch drive ratchet set.
The fan motor is located behind the front panel.
1. Remove the front panel.
Electrical Shock Hazard
Disconnect electrical power before beginning
2. Disconnect electrical power.
3. Unplug motor from power harness.
4. Remove bolts (3/8 inch head) holding fan motor brackets to condenser.
5. Remove screws (1/4” head) holding fan motor to brackets.
Note: Fan blade is marked “Nut Side” for correct
positioning on motor. Air ow direction is pull thru the
condenser.
Replace condenser
The deck cover cannot be removed without disconnecting ice making system from the refrigeration system. The condenser must be replaced from the front.
Begin by taking the fan motor, blade and brackets o󰀨
the condenser.
Then, from the front, remove the screw holding the condenser to the base.
Next, locate an access hole in the deck above the back condenser fastener. Remove that screw.
September 2017
Page 22
Page 23
UF424 / UN324 Technical Manual
Testing Sensors
Photo-Eye Bin Control
The sensors consist of an emitter and a receiver. The emitter shines infrared light in a certain pattern at the receiver. The receiver’s signal is checked by the
controller to conrm proper reception. If conrmed,
the controller starts or continues the ice making process.
Remove front panel.
Check controller code display. If the unit is in ice making mode (status light on) there will normally either be an F or a b displayed.
If the bin is full, b is displayed.
If the bin is not full and the unit is in ice making mode, F is displayed.
if the bin is not full and the unit is o󰀨, O is displayed.
False bin full: If the bin is not full and b is displayed:
1. Check for loose connection at the harness to the photo eye sensors.
2. Check for broken wire at sensor.
Replace Photo-Eye Bin Control
1. Remove top panel.
2. Disconnect photo eye bin control from the quick connect at the top back of the machine.
3. Lift up and remove both retaining clips holding sensor holders to evaporator cover.
4. Push sensor holders in towards the center until free of the evaporator cover.
5. Separate each photo eye sensor from its holder by pulling them apart.
6. Install new sensor into each holder. Push in until the rubber from the sensor meets the rubber sensor holder.
7. Return sensor holders to the chute and insert retaining clips.
8. Reconnect sensors to harness.
9. Return top panel to its normal position.
3. Check for something blocking the sensors, which can include scale buildup.
Note: There is no back up for the bin control. If it fails
to shut the machine o󰀨, the bin will overll.
Rotation Sensor
The sensor consists of a pick up sensor and a magnet. The pick up has a wire that connects to the controller. The magnet is in the rotating magnet holder on top of the auger motor. if the rotor is loose, it will
not rotate and the sensor will shut the machine o󰀨 for
no rotation.
1. Remove front and left side panels.
2. Remove motor cover.
3. Check that rotor has magnet and is secure to motor shaft.
Note: Special thin open end wrench may be needed
to hold motor shaft, it ts under the magnet rotor.
Electrical Shock Hazard
Disconnect electrical power before beginning
September 2017
Page 23
Page 24
UF424 / UN324 Technical Manual
Panel Removal
Top Panel
Requires back access
1. Remove three thumbscrews holding top panel to back panel.
2. Pull top panel back slightly to release it from the
top of the machine, then lift up and o󰀨 the unit.
Note: Upper brace may come with top panel, it is not attached to the unit.
Door
1. Remove top panel.
2. Push door to full open, then lift back end up and remove two bushings. Retain the bushings.
3. Pull door up thru the slot until the last two bushings appear. Remove and retain them.
4. Pull door up and out of the machine
Side Panel
1. Remove front, top and back panels.
2. Remove two screws at each side of the top edge of the unit.
Note: The front screw on the top of each side will not be tightened fully, its correct position is slightly above
the surface of the top so that the head will t into the
key hole slots in the top panel.
September 2017
Page 24
Page 25
UF424 / UN324 Technical Manual
Remove Ice Storage Bin
Replacement of these components requires removal of the ice storage bin.
Water Seal
Bottom Bearing
Evaporator
Gear Reducer
Condenser
1. Disconnect electrical power.
Electrical Shock Hazard
Disconnect electrical power before beginning
2. Shut water o󰀨 to machine.
3. Drain the reservoir and evaporator (use drain tube under control box).
4. Discard any ice.
5. Pull unit out from under any countertop.
Note: Generous space around the machine will be needed
12. Push chute cover back and remove.
13. Unscrew ice sweep and remove.
Ice Chute
Ice Sweep
Remove Ice Sweep and Ice Chute
14. Lift up and remove chute.
15. Disconnect water inlet from reservoir oat valve.
16. Disconnect evaporator water inlet from reservoir.
17. Pull water inlet tube back thru hole in bin.
6. Remove front panel.
7. Remove top panel.
8. Remove door.
9. Remove both back panels.
10. Remove both side panels.
11. Remove evaporator cover.
Evaporator Cover Removed
18. Disconnect bin drain.
19. Lift bin assembly o󰀨 chassis.
September 2017
Page 25
Page 26
UF424 / UN324 Technical Manual
Remove Gear Reducer
Removal
Note: Below steps assume the bin has been removed.
Remove or melt out all ice.
1. Disconnect electrical power to unit.
Electrical Shock Hazard
Disconnect electrical power before beginning
2. Disconnect wires to auger motor.
3. Remove 3 screws holding motor cover to motor.
Motor Cover
6. Remove four 1/2” hex head bolts securing evaporator assembly to gear reducer cover.
Remove Evaporator Bolts
7. Remove four 1/2” hex head bolts securing gear reducer condensate pan to chassis.
8. Separate gear reducer from evaporator and lift it from the machine.
4. Remove 4 screws holding rotation sensor holder to motor.
5. Use a cordless impact driver to remove the screw holding the magnet rotor. If needed use the special thin wrench to hold motor shaft.
Magnet Rotor
9. Remove three 1/4 hex socket head screws securing pan to gear reducer.
Install new gear reducer. Be sure vent plug is open
Gear Reducer
The gear reducer is a sealed component. No gears or shaft bearings are available. A gear reducer without motor is available.
A properly operating gear reducer will operate quietly and draw a consistent amount of amps. It will not leak lubricant. Oil discharge is a strong indicator of water
inltration and is cause for replacement.
High amp draw could be caused by scale build up in
the evaporator. Clean it rst, then check amp draw. Conrm the top and lower bearings are not seized or
rough.
A motor that rotates but the output shaft does not turn indicates a stripped gear and is cause for the gear reducer section to be replaced.
September 2017
Page 26
Page 27
UF424 / UN324 Technical Manual
Remove Auger
Auger
The auger must be clean and undamaged to work properly.
Remove it from the evaporator to conrm.
Note: A wet auger will appear clean - dry it to check for scale.
Damaged auger ight edges are not repairable and
the auger must be then be replaced.
A reversed motor code (1) is a strong symptom of a motor that should be replaced.
Removal
Suggested tools include a 1/4 inch drive ratchet set.
1. Disconnect electrical power.
2. Remove top panel.
3. Remove front panel.
4. Close oat valve or shut water o󰀨 to unit.
Electrical Shock Hazard
Disconnect electrical power before beginning
5. Drain reservoir and evaporator using the drain at the front of the machine.
6. Push back on chute cover, lift up and remove.
Auger Motor
The auger motor is a PSC motor with a capacitor. If
the motor will not start, check rst for voltage to the
motor.
If there is full voltage to the motor, check the capacitor and motor windings, replace the motor if the winding is open. Replace the capacitor if it is damaged, open or weak.
7. Remove ice sweep by rotating it counter clockwise.
8. Lift up and remove chute.
9. Remove the four socket head bolts at the side of the top of the evaporator.
10. Return ice sweep and attach to auger.
11. Lift up on ice sweep to remove auger. and breaker together.
Note: The replacement motor is supplied attached to a gear reducer cover. Remove the motor from the cover and attach it to the gear reducer.
September 2017
Page 27
Page 28
UF424 / UN324 Technical Manual
Replace Evaporator
1. Disconnect electrical power
Electrical Shock Hazard
Disconnect electrical power before beginning
1. Go thru all steps to remove the auger.
2. Go thru all steps to remove the bin.
3. Recover the refrigerant charge.
4. Remove foam wrap from bottom of evaporator.
6. Un-braze the evaporator refrigerant inlet and outlet.
7. Lift the evaporator up and o󰀨 the bottom bearing retainer. The stationary half of the water seal will be in the bottom of the tube. The rotating half is on the auger.
5. Remove the four 1/4 inch hex socket head screws at the bottom of the evaporator.
8. Conrm auger is un-damaged.
9. Install new water seal.
10. Replace bottom and top bearings.
11. Attach new evaporator to adapter.
12. Replace the dryer and evacuate the system to at least 300 microns.
13. Weigh in the nameplate charge.
September 2017
Page 28
Page 29
UF424 / UN324 Technical Manual
Replace Auger Motor
Auger Motor
The auger motor may be replaced without removing the gear reducer. Due to manufacturing and testing reasons, the replacement auger drive motor is supplied mounted on a gear reducer cover. It is not necessary to replace the gear reducer cover.
Electrical Shock Hazard
Disconnect electrical power before beginning
1. Remove 3 screws holding motor cover to motor.
2. Remove 4 screws holding rotation sensor to motor.
3. Use a cordless impact driver to remove the screw holding the magnet rotor. If needed use the special thin 3/8 open end wrench to hold the motor shaft.
4. Remove the original drive motor.
5. Separate the replacement drive motor from the shipping casting.
6. Install the rotor of the replacement motor into the gear reducer.
7. Attach the winding of the replacement motor to the gear reducer.
8. Attach the magnet rotor to the new motor shaft.
9. Attach the sensor and its holder to the motor.
10. Attach the motor cover to the motor. Reconnect wires.
September 2017
Page 29
Page 30
UF424 / UN324 Technical Manual
Prep to Replace Water Seal or Bearings
It is the manufacturer’s recommendation that the top bearing, bottom bearing and water seal be replaced at the same time.
Extruder / Breaker
Electrical Shock Hazard
Disconnect electrical power before beginning
1. Remove top panel.
2. Slide chute cover back and remove.
3. Unscrew ice sweep.
4. Lift up and pull ice chute o󰀨 evaporator.
5. Remove four 1/4 inch hex head socket screws.
6. Lift breaker o󰀨 auger.
7. Remove four 1/4 inch hex socket head socket screws.
8. Return ice sweep to auger.
9. Lift on ice sweep to remove auger.
Auger
1. Shut water o󰀨 to machine.
2. Drain reservoir.
3. Disconnect electrical power.
4. Remove top panel.
5. Unscrew ice sweep.
6. Lift up and pull ice chute o󰀨 evaporator.
10. See Replace Water Seal and Auger Bearings
September 2017
Page 30
Page 31
UF424 / UN324 Technical Manual
Replace Water Seal and Auger Bearings
Water Seal
1. Go thru all steps to remove the auger.
2. Remove the 4 allen head screws at the bottom of the evaporator.
3. Lift the evaporator up and o󰀨 the bottom bearing retainer.
4. Push the water seal up on one side until it twists, grab it and pull it out.
5. Remove the rotating half from the bottom of the auger.
6. Clean the auger shoulder and add a very thin bead of food grade sealant to the bottom of the auger.
Top Bearing:
1. Go thru the process of removing the extruder breaker.
2. Remove the clip holding the bearing.
3. Tap out the old bearing.
4. Use the old bearing as something to tap on and drive the new bearing into the extruder.
7. Carefully push the new rotating half of the water seal up against the sealant as far as possible. It should seat tightly and straightly against the auger
shoulder. Do not put ngerprints on the sealing
surface.
8. Wet the outside edge of the stationary half of the water seal and insert it into the bottom of the evaporator.
9. Slip the evaporator onto the bottom bearing retainer, the bearing retainer will push the water seal up into the correct position.
Note: The bottom bearing should have been replaced at this time.
5. Reinstall the clip.
Bottom Bearing:
1. Go thru the process of removing the auger.
2. Remove the 4 allen head screws at the bottom of the evaporator.
3. Remove the bolts holding the bearing retainer to the gear reducer.
4. Separate the gear reducer, evaporator and bearing retainer.
5. Remove the clip.
6. Tap out the old bearing.
7. Use the old bearing as something to tap on and drive the new bearing into the extruder.
10. Secure the evaporator to the bearing retainer with the original socket head screws. Be sure they are tight.
September 2017
Page 31
Page 32
UF424 / UN324 Technical Manual
Replace Electrical Components
General Access
1. Disconnect electrical power.
Electrical Shock Hazard
Disconnect electrical power before beginning
2. Remove front panel
3. Remove one screw holding control box to chassis
(above and near the back of the control box).
4. Pull control box out until it stops.
Power Cord
1. Disconnect power
2. Remove front, top and right side panels.
3. Pull control box out all the way.
4. Remove power leads from contactor.
5. Pull cord from control box.
6. Loosen strain relief thru access hole in right side of chassis.
7. Pull cord thru back panel.
Note: It is critical that only a like OEM power cord be used as a replacement.
Controller
1. Disconnect electrical power.
2. Remove front panel.
3. Pull control box out.
4. Remove controller cover.
5. Disconnect all wires including the quick connect to the control box harness.
Note: If start capacitor needs testing or replacement, remove the thumb screw preventing the control box from being pulled further out.
Potential Relay.
1. Pull control box out.
2. Use long screwdriver from right side to remove screw holding relay to box.
6. Compress stand o󰀨s and lift controller from control box.
7. Ground yourself to the metal chassis and then install the replacement controller.
September 2017
Page 32
Page 33
UF424 / UN324 Technical Manual
Schematic Diagram
September 2017
Page 33
Page 34
UF424 / UN324 Technical Manual
Wiring Diagram
September 2017
Page 34
Page 35
SCOTSMAN ICE SYSTEMS
101 Corporate Woods Parkway
Vernon Hills, IL 60061
800-726-8762
www.scotsman-ice.com