Scotsman NME1854R Operator’s Manual

INTRODUCTION
NME1854R & FME2404R
To the owner or user: The service manual you are reading is intended to provide you, and the maintenance or service technician, with the information needed to install, start up, clean, maintain, and service either ice system.
The product is a remote condenser modular ice system. Its features include: front service for the freezer, gear motor, control box, water reservoir, and bin control; an electronic circuit for monitoring ice and water level; and R-404A as the refrigerant.
Table of Contents
FOR THE INSTALLER ···································· Page 2 REMOTE CONDENSER SPECIFICATIONS ························· Page 3 FOR THE INSTALLER ···································· Page 4 Remote Condenser Location ································· Page 5 FOR THE INSTALLER: Remote Condenser ························· Page 6 FOR THE INSTALLER: Precharged Lines ·························· Page 7 FOR THE INSTALLER: Location ······························· Page 8 FOR THE PLUMBER ····································· Page 9 FOR THE ELECTRICIAN ·································· Page 10 FOR THE INSTALLER: Completed Installation ······················· Page 11 FOR THE INSTALLER: Final Check List ··························· Page 12 START UP ·········································· Page 13 COMPONENT DESCRIPTION ································ Page 14 OPERATION: Water ····································· Page 15 COMPONENT DESCRIPTION: Control Box ························· Page 16 ELECTRICAL SEQUENCE ·································· Page 17 SYSTEM INFORMATION ·································· Page 18 OPERATION: Refrigeration ································· Page 19 OPERATION: Refrigeration ································· Page 20 CLEANING and SANITATION ································ Page 21 SENSOR MAINTENANCE ·································· Page 22 BEARING MAINTENANCE ·································· Page 23 AUGER MAINTENANCE ··································· Page 24 SERVICE DIAGNOSIS: Condition ······························ Page 25 SERVICE DIAGNOSIS: ··································· Page 26 CONTROL SYSTEM DIAGNOSTICS ···························· Page 27 REMOVAL AND REPLACEMENT: Water Reservoir & Bin Controls ············· Page 28 REMOVAL AND REPLACEMENT: Bearing And Breaker ·················· Page 29 REMOVAL AND REPLACEMENT: Auger ·························· Page 30 REMOVAL AND REPLACEMENT: Water Seal ······················· Page 31 REMOVAL AND REPLACEMENT: Evaporator ······················· Page 32 REMOVAL AND REPLACEMENT: Gear motor Assembly ·················· Page 33 REFRIGERATION SYSTEM SERVICE ··························· Page 34 What to Do Before Calling for Service ···························· Page 35
The manual was printed on recycled paper. Keep it for future reference.
Note the Warning symbol where it appears. It marks a possible hazard.
January 2000
Page 1
NME1854R & FME2404R
FOR THE INSTALLER
These machines are designed to fit the following Scotsman storage bins:
B90 and extensions, with bin top
·
KBT18.
BH800 no bin top needed.
·
BH900 using bin top KBT14.
·
When installing a new system, check to be sure that you have everything you need before beginning:
Correct Bin
·
Correct Ice Machine
·
Correct Bin Top
·
All kits, legs, and information
·
required for the specific job.
There are two separate ice making
and refrigeration systems in this
model. The liquid and discharge
lines from each system must go to
separate circuits in one remote
condenser (ERC302).
Ice Chute
6.7" x 6.2"
TOP VIEW
Allow 6" of space behind the machine
for utility connections.
34.84"
BACK VIEW Liquid Line
15.53"
3.1"
21"
3.1"
18.28"
13.84"
Discharge Line
Connection
(left system)
Allow 6"
above
machine for
service.
20.84"
5.25"
3"
17.8"
18.8"
SPECIFICATIONS: Ice Machine
Model Number Dimensions
(w/o bin)
HXWXD
FME2404RS-32A 27" x 42" x 24" 208-230/60/1 FLAKE R-Air 22.8 30 208
FME2404RS-3A 27" x 42" x 24" 208-230/60/3 FLAKE R-Air 17.6 20 208
NME1854RS-32A 27" x 42" x 24" 208-230/60/1 Nugget R-Air 22.8 30 208
NME1854RS-3A 27" x 42" x 24" 208-230/60/3 Nugget R-Air
Basic
Electrical
21.66"
Ice Type Cond.
Type
Drain 3/4" FPT
Minimum
Circuit
Ampacity
Remote Condenser
Electrical Inlet
Water Inlet 3/8" Flare
Maximum Fuse Size
4.5"
9.43"
Junction Box
Refrigerant
Minimum circuit ampacity is used to determine wire size and type per National Electrical Code.
January 2000
Page 2
Charge
NME1854R & FME2404R
REMOTE CONDENSER SPECIFICATIONS
Model Use with Basic Electrical ERC302-32 1 FME2404R or NME1854R 208-230/60/1
ERC DIMENSIONS
Model A B F G ERC302 43
13
23
3
"10
8
"
16
3
4
3
21
"16
4
5
"
8
Other Required Items: RTE25 Precharged line set, 25’, R-404A - 2 required. Or: RTE40. Precharged line set, 40’, R-404A - 2 required.
7
19
"
8
Ice Machine NAMEPLATE
LOCATED ON BACK PANEL
SERIAL PLATE LOCATED
BEHIND FRONT PANEL
REMOTE CONDENSERS AND BINS ALSO
HAVE MODEL AND SERIAL NUMBERS
January 2000
Page 3
NME1854R & FME2404R
FOR THE INSTALLER
Installation Limitations:
This ice system is designed to be installed indoors, in a controlled environment:
Min Max
0
Air Temperature 50 (Not including the remote condenser) Water Temperature 40 Water Pressure (psi) 20 80 Voltage 198 253 (Compared to the nameplate)
Operating the machine outside of the limitations is misuse and can void the warranty.
Water Limitations:
An ice machine is a food manufacturing plant; it takes a raw material, water, and turns it into a food product, ice. The purity of the water is very important in obtaining pure ice and in maximizing product life. This is not intended as a complete resource for water related questions, but it does offer these general recommendations:
1. Check with a water treatment specialist for a water test, and recommendations regarding filters and treatment.
2. In most cases, the water used to make ice should be filtered or treated, depending upon the water. There is no one type of water filter that will be effective in all situations. That is why a water test is important.
Scotsman Ice Systems are designed and manufactured with the highest regard for safety and performance. They meet or exceed the standards of UL, NSF, and CUL.
Scotsman assumes no liability or responsibility of any kind for products manufactured by Scotsman that have been altered in any way, including the use of any part and/or other components not specifically approved by Scotsman.
Scotsman reserves the right to make design changes and/or improvements at any time. Specifications and design are subject to change without notice.
F 1000F
0
F 1000F
Location
Install the machine a location where it has enough space around it to be accessible for service, usually a minimum of 6 inches. Avoid hot, dirty and crowded locations. Be sure that the location for the machine is within its limitations for air and water temperatures.
Storage Bin
Tip the storage bin on its back, using parts of the carton to protect the exterior finish. Install the legs into the threaded holes in the bottom of the bin. Turn the leg levelers all the way in preparation for leveling later. Return the bin to the upright position, remove paper covering the bin gasket.
Install the bin top according to the directions with the bin top.
Note: Do not push bin into position, instead lift it there. Pushing a bin, especially one with ice in it, can cause damage to the legs and the leg mounts.
Ice Machine
The machine is heavy, so the use of a mechanical lift is recommended for lifting the machine high enough to install on top of the bin. After the unit is placed on the bin, line it up so it is even with the back side. Secure the machine to the bin with the hardware provided with the machine.
Remove the front panel and remove any shipping blocks.
Note: Be sure to allow a 6" minimum space above the top of the machine for service.
January 2000
Page 4
Remote Condenser Location
NME1854R & FME2404R
Use the following for planning the placement of the condenser relative to the ice machine
Location Limits - condenser location must not exceed ANY of the following limits:
Maximum rise from the ice machine to the
·
condenser is 35 physical feet
Maximum drop from the ice machine to the
·
condenser is 15 physical feet
Physical line set maximum length is 100 feet.
·
Calculated line set length maximum is 150.
·
Calculation Formula:
Drop = dd x 6.6 (dd = distance in feet)
·
Rise = rd x 1.7 (rd = distance in feet)
·
Horizontal Run = hd x 1 (hd = distance in feet)
·
Calculation: Drop(s) + Rise(s) + Horizontal Run
·
= dd+rd+hd = Calculated Line Length
Configurations that do NOT meet these requirements must receive prior written authorization from Scotsman.
Do NOT:
Route a line set that rises, then falls, then rises.
·
Route a line set that falls, then rises, then falls.
·
Calculation Example 1:
The condenser is to be located 5 feet below the ice machine and then 20 feet away horizontally.
5 feet x 6.6 = 33. 33 + 20 = 53. This location would
be acceptable
Calculation Example 2:
The condenser is to be located 35 feet above and then 100 feet away horizontally.
35 x 1.7 = 59.5. 59.5 +100 = 159.5. 159.5 is
greater than the 150 maximum and is NOT acceptable.
rd
22.87"
dd
17.15"
Remote
Condenser
Located ABOVE
Ice Machine
Remote
Condenser
Located BELOW
Ice Machine
hd
40.35"
January 2000
Page 5
NME1854R & FME2404R
FOR THE INSTALLER: Remote Condenser
Location
Select the best available location, protecting the condenser from extremes of dirt, dust, and sun.
Meet all applicable building codes. Usually the services of a licensed electrician are required.
Roof Attachment
1. Install and attach the remote condenser to the roof of the building, using the methods and practices of construction that conform to the local building codes, including having a roofing contractor secure the condenser to the roof.
2. Have an electrician connect the remote condenser fan motor to the Ice Machine, using the junction box at the back of the Ice Machine.
PRECHARGED LINE ROUTING
CAUTION
Do not connect precharged tubing until all routing and forming of the tubing is complete. See the coupling instructions for connecting information.
1. Each set of precharged refrigerant lines (either 25 foot or 40 foot) consists of a 3/8 inch diameter liquid line and a 1/2 inch diameter discharge line. Both ends of each line have quick connect couplings, one end has a schrader valve connection, that end goes to the condenser.
Note: The openings in the building ceiling or wall, listed in the next step, are the minimum sizes recommended for passing the refrigerant lines through.
2. Have the roofing contractor cut a minimum hole for the refrigerant lines of 1 3/4 inch. Check local codes, a separate hole may be required for the electrical power to the condenser.
CAUTION
DO NOT KINK OR CRIMP REFRIGERANT TUBING WHEN INSTALLING IT.
Note: Precharged tubing contains a R-404A holding charge. The entire refrigerant charge required for the system is contained in the ice machine.
Tubing illustration shows tight spiral; a spiral in the field depends on tubing limitations. Tight spiral not required.
REMOTE CONDENSER
SPIRAL
EXCESS
TUBING
INSIDE
BUILDING
LOCATE REMOTE
CONDENSER ABOVE
Ice Machine
3. Route the refrigerant lines through the roof opening.
Follow straight line routing whenever possible. Any excess tubing MUST be retained within the
building.
4. Spiral the excess length of pre charged tubing inside the building. Use a horizontal spiral (as illustrated) to avoid any traps in the lines.
5. Have the roofing contractor seal the holes in the roof per local codes.
January 2000
Page 6
FOR THE INSTALLER: Precharged Lines
NME1854R & FME2404R
Note: The couplings on the sets of precharged lines must be installed properly to prevent leaking. Carefully follow the instructions:
Initial Connections:
1. Remove the protector caps and plugs. Wipe the seats and threaded surfaces with a clean cloth to be certain that no foreign matter remains on them.
2. Lubricate the inside of the couplings, especially the O-Rings with refrigerant oil.
Clean and Lubricate Couplings
3. Position the fittings on the correct connections on the condenser and ice machine.
· The ½ inch discharge line (schrader valve end)
goes to the remote condenser fitting marked “discharge line.”
3
·
The to the remote condenser fitting marked “liquid
line.”
·
The ½ inch discharge line goes to the Ice Machine fitting marked “discharge line.”
·
The fitting marked “liquid line.”
Final Connections:
4a. Begin by tightening the couplings together by hand. Continue to turn the swivel nuts by hand until is is certain that the threads are properly engaged.
inch liquid line (schrader valve end) goes
8
3
inch liquid line goes to the Ice Machine
8
4b. Using two wrenches, one to rotate the swivel nut and one to hold the tubing, tighten each coupling.
Tighten Swivel Nut
It is CRITICAL that ONLY the NUT on the pre-charged tube be turned or the diaphragms will be torn loose by the piercing knives and be loose in the refrigeration system causing severe operational problems.
Note: As the coupling is tightened, the diaphragms in the quick connect couplings will begin to be pierced. As that happens, there will be increased resistance to tightening the swivel nut.
4c. Continue tightening the swivel nut until it bottoms out or a very definite increase in resistance is felt (no threads should be showing). Do NOT overtighten.
5. Using a marker or pen, mark a line lengthwise from the coupling union nut to the bulkhead. Then tighten the coupling and additional 1/4 turn. As the nut turns, the line will show when 1/4 turn is made.
6. After all connections are made, and after the king valve has been opened (do not open at this time), check the couplings for leaks.
SCHRADER
TO REMOTE
CONDENSER
NO SCHRADER
VALVE
Rotate Swivel Nut ¼ Turn More
TO Ice Machine
January 2000
Page 7
NME1854R & FME2404R
FOR THE INSTALLER: Location
CONTACT ROOFING
CONTRACTOR
EXCESS
PRECHARGED
TUBING INSIDE
BUILDING
REMOTE
CONDENSER
ROOF
CUTAWAY
ICE MACHINE
SERVICE
ACCESS
SERVICE ACCESS
SIDE AND BACK
WALL
CUTAWAY
January 2000
Page 8
FOR THE PLUMBER
CONFORM TO ALL APPLICABLE CODES
NME1854R & FME2404R
Water Inlet
HAND SHUT
OFF VALVE
CONNECT TO
COLD WATER
WATER INLET
3/8" MALE
FLARE
FIELD SUPPLIED
WATER FILTER
VENT ICE MACHINE
DRAIN,
3/4" FPT
Connect the ice machine to cold potable water. Use 3/8" O.D. copper tubing, and connect to the 3/8" male flare at the back of the cabinet. Install a hand valve near the machine to control the water supply.
Drains
There is one 3/4" FPT drain at the back of the cabinet, the drain line is of the gravity type, and 1/4 inch per foot fall is an acceptable pitch for the drain tubing. Install a vent at the highest point of the drain line, and the ideal drain receptacle would be a trapped and vented floor drain.
Use only 3/4" rigid tubing. Storage Bin: Install a separate
gravity type drain. Insulation of this drain line is recommended.
VENT BIN DRAIN
3/4" FPT
FLOOR DRAIN
January 2000
Page 9
NME1854R & FME2404R
FOR THE ELECTRICIAN
CONFORM TO ALL APPLICABLE CODES
Connect electrical power to the wires in the junction box at the rear of the machine.
Check the nameplate (located on the back panel) for the voltage requirements, and for the minimum circuit ampacity. The machine requires a solid chassis to earth ground wire.
The Ice Machine should be connected to its own electrical circuit so it would be individually fused. Voltage variation must remain within design limitations, even under starting conditions.
Electrically the remote condenser fan motor is connected to the Ice Machine at the contactor terminals for the compressor and the fan motor operates whenever the compressor operates.
TERMINAL STRIP
FOR REMOTE
CONDENSER
ICE MACHINE
JUNCTION BOX
POWER
SUPPLY
Electrical connections are made at the junction box at the back of the Ice Machine and at the junction box on the remote condenser.
The remote condenser must be wired to the Ice Machine in accordance with local and national electrical codes with a minimum of 18 Awg. wire with an ground bonding wire connected to the ground screws provided in both the condenser and machine field wiring boxes. All outdoor wiring must be in rain proof conduit.
All external wiring must conform to national, state, and local electrical codes. The use of a licensed electrician is required to perform the electrical installation.
GROUND
THE
CHASSIS
RAIN PROOF
CONDUIT
January 2000
Page 10
NME1854R & FME2404R
FOR THE INSTALLER: Completed Installation
A typical installation should generally appear as illustrated below. The remote condenser must be located above the Ice Machine and the precharged lines installed per the instructions on page 6.
INSULATED PRECHARGED REFRIGERANT
TUBING
January 2000
Page 11
Loading...
+ 24 hidden pages