To the owner or user: The service manual you are
reading is intended to provide you, and the
maintenance or service technician, with the
information needed to install, start up, clean,
maintain, and service this ice system.
Table of Contents
FOR THE INSTALLER ······································ Page 2
FOR THE INSTALLER: Remote Condenser ··························· Page 3
FOR THE INSTALLER ······································ Page 4
Remote Condenser Location ··································· Page 5
FOR THE INSTALLER: Remote Condenser Installation ····················· Page 6
FOR THE INSTALLER ······································ Page 7
FOR THE PLUMBER ······································· Page 8
FOR THE ELECTRICIAN ····································· Page 9
FOR THE INSTALLER: Completed Installation ·························· Page 10
FOR THE INSTALLER: Final Check List ····························· Page 11
START UP ············································ Page 12
COMPONENT DESCRIPTION ·································· Page 13
COMPONENT DESCRIPTION: Control Box Components ···················· Page 14
ELECTRICAL SEQUENCE:··································· Page 15
OPERATION: Water ······································· Page 16
OPERATION: Refrigeration ···································· Page 17
OPERATION: Refrigeration ···································· Page 18
OPERATION: Refrigeration ···································· Page 19
CLEANING and SANITATION ·································· Page 20
SENSOR MAINTENANCE: ···································· Page 21
BEARING MAINTENANCE ···································· Page 22
AUGER MAINTENANCE ····································· Page 23
SERVICE DIAGNOSIS:····································· Page 24
SERVICE DIAGNOSIS:····································· Page 25
CONTROL SYSTEM DIAGNOSTICS······························ Page 26
REMOVAL AND REPLACEMENT: Reservoir·························· Page 27
REMOVAL AND REPLACEMENT: Bearing And Breaker···················· Page 28
REMOVAL AND REPLACEMENT: Auger ···························· Page 29
REMOVAL AND REPLACEMENT: Evaporator & Water Seal ·················· Page 30
REMOVAL AND REPLACEMENT: Evaporator ·························· Page 31
REMOVAL AND REPLACEMENT: Gearmotor························· Page 32
REFRIGERATION SYSTEM SERVICE····························· Page 33
What to Do Before Calling for Service ······························ Page 34
Note this symbol
when it appears.
January 2000
Page 1
It marks a possible hazard.
NME954R & FME1204R
FOR THE INSTALLER
Either the FME1204R or the NME954R is
designed to fit the following Scotsman storage
bins:
SB480 and extensions (with bin top KBT18)
·
BH800 using bin top KBT15 (one unit) or KBT25
·
(two units).
BH801 using bin top KBT28
·
BH900 with KBT24 (one unit)
·
BH900 with KBT25 (two units side by side)
·
Allow 6" above machine
for service.
NME954 Dispenser Applications
The NME954 can be placed on and used with
certain ice and ice-beverage dispensers. Kits are
required for proper operation:
Back View
ID150 use adapter KBT42 and KNUGDIV
·
ID200 or ID250, use adapter KBT46 and
·
KDIL-N-ID2
Cornelius ED/DF200 beverage dispensers, use
·
KBT46 and KDIL-N-200
Cornelius ED/DF250 beverage dispensers, use
·
KBT46 and KDIL-N-250
Lancer nugget IBD, use KDIL-N-L & Lancer kit.
·
Liquid Line Connection
Discharge Line Connection
Remote Condenser
Junction Box
Electrical Inlet
20.84"
2.96"
Drain
3/4" FPT
SPECIFICATIONS: ICE MAKER
Model NumberDimensions
(w/o bin)
H”xW”xD”
FME1204RS-32A 27 x 21 x 24 208-230/60/1FLAKERemote Air 14.120208 ounces
FME1204RS-3A same203-230/60/1FLAKERemote Air 11.215208 ounces
NME954RS-32A same208-230/60/1NUGGETRemote Air 14.120208 ounces
NME954RS-3Asame208-230/60/3NUGGETRemote Air 11.215208 ounces
Minimum Circuit Ampacity is used to determine wire size and type per National Electric Code.
Basic Electrical Ice TypeCond. Type Minimum
Water Inlet
3/8" Flare
5.25"
3"
Circuit
Ampacity
Maximum
Fuse Size
Refrigerant
Charge
(R-404A)
January 2005
Page 2
NME1254R & FME1504R
FOR THE INSTALLER: Remote Condenser
Installation Limitations:
This ice system is designed to be installed indoors,
in a controlled environment:
Min.Max.
Air Temperature50
Water Temperature40
0
F1000F
0
F1000F
Water Pressure20 psi 80 psi
Voltage5%+10%
(Compared to the nameplate)
The temperature limitations do not apply to the
remote condenser. It will work between -20
degrees F, and 120 degrees F.
Operating the machine outside of the limitations is
misuse and can void the warranty.
ERC DIMENSIONS
ModelABFG
ERC20133
ERC40243
Scotsman Ice Systems are designed and
manufactured with the highest regard for safety
and performance. They meet or exceed the
standards of UL, NSF, and CUL.
Scotsman assumes no liability or responsibility of
any kind for products manufactured by Scotsman
that have been altered in any way, including the
use of any part and/or other components not
specifically approved by Scotsman.
Scotsman reserves the right to make design
changes and/or improvements at any time.
Specifications and design are subject to change
without notice.
3
"10
8
3
"10
8
3
"16
4
3
"21
4
3
4
3
4
"11
"16
5
"
8
5
"
8
SPECIFICATIONS: REMOTE CONDENSER
ModelUse withBasic Electrical
ERC201-32 1 FME1504R or 1
208-230/60/1
NME1254R
ERC402-32 1 or 2
208-230/60/1
FME1504Rs/NME1254Rs
RTE25 Precharged line set, 25’. R-404A
RTE40 Precharged line set, 40’. R-404A
* Two machines on one condenser require a fan relay kit.
23
19
13
"
16
7
"
8
Icemaker Nameplate Located On Back Panel
Serial Plate Located Behind Front Panel
January 2000
Page 3
NME1254R & FME1504R
FOR THE INSTALLER
Location:
After uncrating and inspection, the unit is
ready for installation. It is important that the
machine be installed in a location where it
has enough space around it to be
accessible for service, usually a minimum of
6 inches. Try to avoid hot, dirty and
crowded locations. Be sure that the location
for the machine is within the limitations
described on page 3.
Storage Bin:
LEVEL THE ASSEMBLY
Tip the storage bin on its back, using parts
of the carton to protect the exterior finish.
Install the legs into the threaded holes in the
bottom of the bin. Turn the leg levelers all
the way in preparation for leveling later.
Return the bin to the upright position,
remove paper covering the bin gasket.
Install bin top if required, follow the
directions included with the bin top.
Note: Do not push bin into position, but lift it
there. Pushing a bin, especially one with ice
in it, can cause damage to the legs and the
leg mounts.
Ice Maker:
The machine is heavy, so the use of a
mechanical lift is recommended for lifting
the machine high enough to install on top of
the bin. After the unit is placed on the bin,
line it up so it is even with the back, left, and
right sides. Secure the machine to the bin
with the hardware provided with the
machine.
Remove the front panel and remove the
styrofoam shipping blocks from under the
gearmotor, the top of the ice chute, and
from between the gearmotor and the right
side panel.
GASKET
FASTEN THE MACHINE
TO THE BIN WITH THE
HARDWARE SUPPLIED
WITH THE ICEMAKER
January 2000
Page 4
Remote Condenser Location
Use the following for planning the placement of
the condenser relative to the ice machine
Location Limits - condenser location must not
exceed ANY of the following limits:
Maximum rise from the ice machine to the
·
condenser is 35 physical feet
Maximum drop from the ice machine to the
·
condenser is 15 physical feet
Physical line set maximum length is 100 feet.
·
Calculated line set length maximum is 150.
·
Calculation Formula:
Drop = dd x 6.6 (dd = distance in feet)
·
Rise = rd x 1.7 (rd = distance in feet)
·
Horizontal Run = hd x 1 (hd = distance in feet)
·
Calculation: Drop(s) + Rise(s) + Horizontal Run
·
= dd+rd+hd = Calculated Line Length
Configurations that do NOT meet these
requirements must receive prior written
authorization from Scotsman.
NME1254R & FME1504R
Do NOT:
Route a line set that rises, then falls, then rises.
·
Route a line set that falls, then rises, then falls.
·
Calculation Example 1:
The condenser is to be located 5 feet below the ice
machine and then 20 feet away horizontally.
5 feet x 6.6 = 33. 33 + 20 = 53. This location would
be acceptable
Calculation Example 2:
The condenser is to be located 35 feet above and
then 100 feet away horizontally.
35 x 1.7 = 59.5. 59.5 +100 = 159.5. 159.5 is
greater than the 150 maximum and is NOT
acceptable.
rd
22.87"
dd
17.15"
Remote
Condenser
Located ABOVE
Ice Machine
Remote
Condenser
Located BELOW
Ice Machine
hd
40.35"
January 2000
Page 5
NME1254R & FME1504R
FOR THE INSTALLER: Remote Condenser Installation
Location:
Limited to a 40 foot or a 25 foot length of
precharged refrigerant tubing connecting the
icemaker to the remote condenser. The condenser
must be above or level with the icemaker.
Select the best available location, protecting the
condenser from extremes of dirt, dust, and sun.
Meet all applicable building codes. Usually the
services of a licensed electrician are required.
Roof Attachment:
1. Install and attach the remote condenser to the
roof of the building, using the methods and
practices of construction that conform to the local
building codes, including having a roofing
contractor secure the condenser to the roof.
2. Have an electrician connect the remote
condenser fan motor to the icemaker, using the
junction box at the back of the icemaker.
PRECHARGED LINE ROUTING
CAUTION
Do not connect precharged tubing until all routing
and forming of the tubing is complete. See the
coupling instructions, next page for connecting
instructions.
4. Spiral the excess length of pre charged tubing
inside the building. Use a horizontal spiral (as
illustrated) to avoid any traps in the lines.
Note: spiral need not be as tight as illustrated.
5. Have the roofing contractor seal the holes in the
roof per local codes.
REMOTE CONDENSER
1. Each set of precharged refrigerant lines (either
25 foot or 40 foot) consists of a 3/8 inch diameter
liquid line and a 1/2 inch diameter discharge line.
Both ends of each line have quick connect
couplings, one end has a schrader valve
connection, that end goes to the condenser.
Note: The openings in the building ceiling or wall,
listed in the next step, are the minimum sizes
recommended for passing the refrigerant lines
through.
2. Have the roofing contractor cut a minimum hole
for the refrigerant lines of 1 3/4 inch. Check local
codes, a separate hole may be required for the
electrical power to the condenser.
CAUTION
DO NOT KINK OR CRIMP REFRIGERANT
TUBING WHEN INSTALLING IT.
3. Route the refrigerant lines through the roof
opening.
Follow straight line routing whenever possible.
Any excess tubing MUST be retained within the
building.
January 2000
Page 6
LOCATE REMOTE
CONDENSER
ABOVE ICEMAKER
SPIRAL
EXCESS
TUBING
INSIDE
BUILDING
FOR THE INSTALLER
NME1254R & FME1504R
Note: The couplings on the sets of precharged
lines must be installed properly to prevent leaking.
Carefully follow the instructions:
Initial Connections:
1. Remove the protector caps and plugs. Wipe the
seats and threaded surfaces with a clean cloth to
be certain that no foreign matter remains on them.
2. Lubricate the inside of the couplings, especially
the O-Rings with refrigerant oil.
3. Position the fittings on the correct connections
on the condenser and ice machine.
Clean and Lubricate Couplings
·
The ½ inch discharge line (schrader valve end)
goes to the remote condenser fitting marked
“discharge line.”
3
·
The
to the remote condenser fitting marked “liquid
line.”
inch liquid line (schrader valve end) goes
8
4b. Using two wrenches, one to rotate the swivel
nut and one to hold the tubing, tighten each
coupling.
Tighten Swivel Nut
It is CRITICAL that ONLY the NUT on the
pre-charged tube be turned or the diaphragms will
be torn loose by the piercing knives and be loose
in the refrigeration system causing severe
operational problems.
Note: As the coupling is tightened, the
diaphragms in the quick connect couplings will
begin to be pierced. As that happens, there will
be increased resistance to tightening the
swivel nut.
4c. Continue tightening the swivel nut until it
bottoms out or a very definate increase in
resistance is felt (no threads should be showing).
Do NOT overtighten.
·
The ½ inch discharge line goes to the ice
maker fitting marked “discharge line.”
3
·
The
fitting marked “liquid line.”
Final Connections:
4a. Begin by tightening the couplings together by
hand. Continue to turn the swivel nuts by hand until
is is certain that the threads are properly engaged.
SCHRADER VALVE
inch liquid line goes to the ice maker
8
NO SHRADER
TO REMOTETO ICEMAKER
January 2000
Rotate Swivel Nut ¼ Turn More
5. Using a marker or pen, mark a line lengthwise
from the coupling union nut to the bulkhead. Then
tighten the coupling and additional 1/4 turn. As the
nut turns, the line will show when 1/4 turn is made.
6. After all connections are made, and after the
king valve has been opened (do not open at this
time), check the couplings for leaks.
Page 7
NME1254R & FME1504R
FOR THE PLUMBER
CONFORM TO ALL APPLICABLE CODES
Water Inlet
The recommended water supply is cold water.
Use 3/8" O.D. copper tubing, connect to the 3/8"
male flare at the back of the cabinet. Install a hand
valve near the machine to control the water supply.
WATER
INLET
3/8" FLARE
HAND SHUT
OFF VALVE
Drains
There is one 3/4" FPT drain at the back of the
cabinet, the drain line is of the gravity type, and 1/4
inch per foot fall is an acceptable pitch for the drain
tubing. There should be a vent at the highest point
of the drain line, and the ideal drain receptacle
would be a trapped and vented floor drain. Use
only 3/4" rigid tubing.
Storage Bin: Install a separate drain line. Insulation
of this drain line is recommended.
CONNECT TO
COLD WATER
FIELD INSTALLED
ICEMAKER DRAIN
3/4" FPT
BIN DRAIN
3/4" FPT
FILTER
(OPTIONAL)
January 2000
Page 8
FOR THE ELECTRICIAN
CONFORM TO ALL APPLICABLE CODES
The electrical power to the unit is supplied
through the junction box at the rear of the
machine.
Check the nameplate (located on the back
panel) for the voltage requirements, and
for the minimum circuit ampacity. The
machine requires a solid chassis to earth
ground wire.
The ice maker should be connected to its
own electrical circuit so it would be
individually fused. Voltage variation must
remain within design limitations, even
under starting conditions.
Electrically the remote condenser fan
motor is connected to the icemaker at the
contactor terminals for the compressor
and the fan motor operates whenever the
compressor operates.
Electrical connections are made at the
junction box at the back of the icemaker
and at the junction box on the remote
condenser.
The remote condenser must be wired to
the icemaker in accordance with local and
national electrical codes with a minimum
of 18 Awg. wire with an ground bonding
wire connected to the ground screws
provided in both the condenser and
machine field wiring boxes. All outdoor
wiring must be in rainproof conduit.
All external wiring must conform to
national, state, and local electrical
codes. The use of a licensed
electrician is required to perform the
electrical installation.
NME1254R & FME1504R
REMOTE CONDENSER
WATERPROOF
(LIQUID TIGHT)
CONDUIT
ICEMAKER
JUNCTION BOX
POWER
SUPPLY
January 2000
Page 9
NME1254R & FME1504R
FOR THE INSTALLER: Completed Installation
A typical installation should generally appear as
illustrated below. The remote condenser must be
located above the icemaker and the precharged
lines installed per the instructions on page 6.
ROOF
CUT-AWAY
INSULATED PRECHARGED
REFRIGERANT TUBING
January 2000
Page 10
NME1254R & FME1504R
FOR THE INSTALLER: Final Check List
1. Is the ice system installed indoors in
a location where the air and water
temperatures are controlled, and
where they do not exceed the design
limitations?
2. Is there an electrical service
disconnect within sight of the installed
machine? Has the voltage been
checked, and compared to nameplate
requirements?
3. Have all the plumbing connections
been made and checked for leaks?
4. Has the machine and bin been
leveled?
5. Is there a minimum of 6" clearance
at the rear, left, and right of the
machine for proper service access and
air circulation?
6. Is the water pressure a minimum of
20 psig?
7. Has the machine been secured to
the bin?
8. Is there a water shut off valve
installed near the machine?
9. Is the remote condenser installed
per local building codes, and in a place
where it has adequate ventilation and
minimal solar heat gain?
10. Has all shipping material (under
and next to the gearmotor, and on top
of the ice chute) and literature (inside
the front panel) been removed from
the units?
11. Have the remote condenser and
precharged lines been properly
installed?
12. Has the electrical connection
between the icemaker and the
condenser been made?
13. Verify that the master switch is in
the OFF position.
14. Switch on the electrical power.
15. Refer to Pre-Start instructions, the
next page.
POWER SUPPLY?
PLUMBING?
DRAINS?
LEVELED?
January 2000
Page 11
Loading...
+ 23 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.