Scotsman NME1250R Installation Manual

INTRODUCTION
NME1250R
To the owner or user: The service manual you are reading is intended to provide you, and the maintenance or service technician, with the information needed to install, start up, clean, maintain, and service this ice system.
The NME1250R is a remote condenser modular ice system that features: front service for the freezer, gearmotor, control box, water reservoir, and bin control; an electronic circuit for monitoring ice and water level; a thermostatic expansion valve; and HP62 as the refrigerant.
Table of Contents
FOR THE INSTALLER: Remote Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
FOR THE PLUMBER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
FOR THE ELECTRICIAN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
FOR THE INSTALLER: Completed Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
FOR THE INSTALLER: Final Check List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
START UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
COMPONENT DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
ELECTRICAL SEQUENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
MAINTENANCE AND CLEANING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
ICEMAKER MAINTENANCE: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
SERVICE DIAGNOSIS: Condition - No Ice Being Produced . . . . . . . . . . . . . . . . . . . . . . . . 22
SERVICE DIAGNOSIS: Condition - Low Ice Production . . . . . . . . . . . . . . . . . . . . . . . . . . 26
REMOVAL AND REPLACEMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
REMOVAL AND REPLACEMENT: Bearing And Breaker . . . . . . . . . . . . . . . . . . . . . . . . . 28
REMOVAL AND REPLACEMENT: Auger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
REMOVAL AND REPLACEMENT: Evaporator & Water Seal . . . . . . . . . . . . . . . . . . . . . . . 30
REMOVAL AND REPLACEMENT: Evaporator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
REMOVAL AND REPLACEMENT: Gearmotor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
REFRIGERATION SERVICE: HP62 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
ELECTRONIC CONTROL TESTER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Parts Lists and Wiring Diagrams are located in the center of this manual, printed on yellow paper.
This manual was printed on recycled paper. Keep it for future reference.
August 1993
Page 1
Note this symbol when it appears.
It marks a possible hazard.
10(5
)257+(,167$//(5
7KHVHPDFKLQHVDUHGHVLJQHGWRILWWKHIROORZLQJ
6FRWVPDQVWRUDJHELQV
%DQGH[WHQVLRQV
ZLWKELQWRS.%7
+7%RU%+
%+XVLQJELQWRS
.%7
%+XVLQJELQWRS
.%7
:KHQLQVWDOOLQJDQHZ
V\VWHPFKHFNWREH
VXUHWKDW\RXKDYH
HYHU\WKLQJ\RXQHHG
EHIRUHEHJLQQLQJ
&RUUHFW&RQGHQVHU
&RUUHFW%LQ%LQ7RSLI
UHTXLUHG
&RUUHFW,FH0DFKLQH
&RUUHFW3UHFKDUJHGOLQH
VHW
$OONLWVOHJVDQG
LQIRUPDWLRQUHTXLUHGIRU
WKHVSHFLILFMRE
63(&,),&$7,216,&(0$.(5
02'(/ ',0(16,216
ZLWKRXWELQ
10(5($ [[
&21'
7<3(
5(027(
5HIULJHUDQW
&KDUJH
+3
RXQFHV
,&(
7<3(
18**(7
%$6,&
(/(&75,&$/

0,1,080
&,5&8,7

0$;,080
)86(
6,=(

0LQLPXP&LUFXLW$PSDFLW\LVXVHGWRGHWHUPLQHZLUHVL]HSHU1DWLRQDO(OHFWULF&RGH
7KHVWDQGDUGILQLVKLVHQDPHO$VWDLQOHVVVWHHOSDQHONLW63.&0'PD\EHILHOGLQVWDOOHGWRFRQYHUWWKH
XQLWWRDVWDLQOHVVVWHHOILQLVK
$XJXVW
3DJH
FOR THE INSTALLER: Remote Condenser
19 7⁄8"
ERC DIMENSIONS
Model A B F G ERC201
33 3⁄8" 10 3⁄4" 16 3⁄4" 11 5⁄8"
ERC402
43 3⁄8" 10 3⁄4" 21 3⁄4" 16 5⁄8"
Installation Limi tations:
This ice system is desig ned to be ins talled indo ors, in a controlled env iron men t:
Min. Max. Air Temperature 50 Water Temperature 40 Water Pressure 20 psi 80 psi Voltage 5% +10%
(Compared to the nameplate) The temperature limita tio ns do not apply to the
remote condenser. It will work betwe en -20 degrees F, and 120 degrees F.
0
F1000F
0
F1000F
Operating the mach ine outside of the limitations is misuse and can void the warran ty.
Scotsman Ice Syste ms are desig ne d an d manufact ure d with the highest regard for saf et y and performan ce. They meet or exc ee d the standard s of UL, NSF, and CSA.
Scotsman assumes no liabilit y or resp on sib ility of any kind for products manufactured by Scotsman that have been alt ere d in any way, includin g th e use of any part and/or other components not specifically approved by Scotsman.
Scotsman reserves the right to make design changes and/or improvements at any time.
NME1250R
SPECIFICATIONS: REMOTE CONDENSER
Model Use with Basic Electrical RCE651-32 1 NME1250R 208-230/6 0/1 ERC201-32 SAME 208-230/6 0/1 RCE652-32 1 or 2 NME1250Rs* 208-230/60/ 1 ERC402-32 SAME 208-230/6 0/1
23 13⁄16"
RTE25 Precharged line set, 25’. R-404A RTE40 Precharged line set, 40’. R-404A * Two units on one condenser requires a fan relay kit.
Icemaker Nameplate Located On Back Panel
Serial Plate Located Behind Front Panel
December 1995
Page 3
LEVEL THE ASSEMBLY
NME1250R
FOR THE INSTALLER
Location:
After uncrating and inspection, the unit is ready for installation. It is important that the machine be installed in a location where it has enough space around it to be accessible for service, usually a minimum of 6 inches. Try to avoid hot, dirty and crowded locations. Be sure that the location for the machine is within the limitations described on page 3.
Storage Bin:
Tip the storage bin on its back, using parts of the carton to protect the exterior finish. Install the legs into the threaded holes in the bottom of the bin. Turn the leg levelers all the way in preparation for leveling later. Return the bin to the upright position, remove paper covering the bin gasket.
Install bin top if required, follow the directions included with the bin top.
Note: Do not push bin into position, but lift it there. Pushing a bin, especially one with ice in it, can cause damage to the legs and the leg mounts.
GASKET
Ice Maker:
The machine is heavy, so the use of a mechanical lift is recommended for lifting the machine high enough to install on top of the bin. After the unit is placed on the bin, line it up so it is even with the back, left, and right sides. Secure the machine to the bin with the hardware provided with the machine.
Remove the front panel and remove the styrofoam shipping blocks from under the gearmotor, the top of the ice chute, and from between the gearmotor and the right side panel.
FASTEN THE MACHINE
TO THE BIN WITH THE
HARDWARE SUPPLIED
WITH THE ICEMAKER
June 1994
Page 4
FOR THE INSTALLER: Remote Condenser Installation
LOCATE REMOTE
CONDENSER
ABOVE ICEMAKER
NME1250R
Location:
Limited to a 40 foot or a 25 foot length of precharged refrigerant tubing connecting the icemaker to the remote condenser. The condenser must be above or level with the icemaker.
Select the best available location, protecting the condenser from extremes of dirt, dust, and sun.
Meet all applicable building codes. Usually the services of a licensed electrician are required.
Roof Attachment:
1. Install and attach the remote condenser to the roof of the building, using the methods and practices of construction that conform to the local building codes, including having a roofing contractor secure the condenser to the roof.
2. Have an electrician connect the remote condenser fan motor to the icemaker, using the junction box at the back of the icemaker.
PRECHARGED LINE ROUTING
///////////////////////////////CAUTION//////////////////////////////// Do not connect precharged tubing until all routing
and forming of the tubing is complete. See the coupling instructions, next page for connecting instructions.
////////////////////////////////////////////////////////////////////////////
1. Each set of precharged refrigerant lines (either 25 foot or 40 foot) consists of a 3/8 inch diameter liquid line and a 1/2 inch diameter discharge line. Both ends of each line have quick connect couplings, one end has a schrader valve connection, that end goes to the condenser.
Note: The openings in the building ceiling or wall, listed in the next step, are the minimum sizes recommended for passing the refrigerant lines through.
2. Have the roofing contractor cut a minimum hole for the refrigerant lines of 1 3/4 inch. Check local codes, a separate hole may be required for the electrical power to the condenser.
////////////////////////////////CAUTION//////////////////////////////// DO NOT KINK OR CRIMP REFRIGERANT
TUBING WHEN INSTALLING IT. /////////////////////////////////////////////////////////////////////////////
3. Route the refrigerant lines through the roof opening.
Follow straight line routing whenever possible.
Any excess tubing MUST be retained within the building.
4. Spiral the excess length of pre charged tubing inside the building. Use a horizontal spiral (as illustrated) to avoid any traps in the lines.
Note: spiral need not be as tight as illustrated.
5. Have the roofing contractor seal the holes in the roof per local codes.
REMOTE CONDENSER
SPIRAL
EXCESS
TUBING
INSIDE
BUILDING
August 1993
Page 5
SERVICE PORTS
REMOTE
CONDENSER
NME1250R
FOR THE INSTALLER
COUPLING INSTRUCTIONS
////////////////////////////////CAUTION////////////////////////////////// The couplings on the sets of precharged lines are
self sealing when installed properly. Carefully follow the instructions:
//////////////////////////////////////////////////////////////////////////////////
1. Remove the protector caps and plugs. Wipe the seats and threaded surfaces with a clean cloth to be certain that no foreign matter remains on them.
2. Lubricate the inside of the couplings, especially the O-Rings with refrigerant oil.
3. Connect the couplings to the fittings:
••The 3/8 inch liquid line (schrader valve end) to
the remote condenser fitting marked "liquid line".
••Connect the other end of the liquid line to the
icemaker fitting marked "liquid line."
••Connect the 1/2 inch discharge line (schrader
valve end) to the remote condenser fitting marked "discharge line".
••Connect the other end of the liquid line to the
icemaker fitting marked "liquid line".
4. Begin tightening the couplings together by hand, then using two wrenches (it is important that ONLY the nut on the precharged lines be turned, the other parts of the couplings must NOT be allowed to turn or the process will tear out the diaphragms and they will be loose in the refrigeration system) tighten the coupling until it bottoms out or a definite increase in resistance is felt.
5. Using a marker or pen, mark a line lengthwise from the coupling union nut to the bulkhead. Then tighten the coupling and additional 1/4 turn. As the nut turns, the line will show when 1/4 turn is made.
6. After all connections are made, and after the king valve has been opened, check the couplings for leaks.
Note: The system charge is contained in the machine’s receiver. Holding charges of the same refrigerant are present in the remote condenser and pre-charged line sets.
SCHRADER VALVE
TO REMOTE
CONDENSER
NO SHRADER
VALVE
TO ICEMAKER
3/8" LIQUID LINE
1/2" DISCHARGE LINE
June 1994
Page 6
FOR THE PLUMBER
ICEMAKER DRAIN
3/4" FPT
CONFORM TO ALL APPLICABLE CODES
NME1250R
Water Inlet
The recommended water supply is cold water. Use 3/8" O.D. copper tubing, connect to the 3/8" male flare at the back of the cabinet. Install a hand valve near the machine to control the water supply.
WATER
INLET
3/8" FLARE
HAND
SHUT OFF
VALVE
Drains
There is one 3/4" FPT drain at the back of the cabinet, the drain line is of the gravity type, and 1/4 inch per foot fall is an acceptable pitch for the drain tubing. There should be a vent at the highest point of the drain line, and the ideal drain receptacle would be a trapped and vented floor drain. Use only 3/4" rigid tubing.
Storage Bin: A separate gravity type drain needs to be run. Insulation of this drain line is recommended.
CONNECT TO
COLD WATER
FIELD INSTALLED
BIN DRAIN
3/4" FPT
FILTER
(OPTIONAL)
August 1993
Page 7
NME1250R
FOR THE ELECTRICIAN
CONFORM TO ALL APPLICABLE CODES
The electrical power to the unit is supplied through the junction box at the rear of the machine.
Check the nameplate (located on the back panel) for the voltage requirements, and for the minimum circuit ampacity. The machine requires a solid chassis to earth ground wire.
The ice maker should be connected to its own electrical circuit so it would be individually fused. Voltage variation must remain within design limitations, even under starting conditions.
Electrically the remote condenser fan motor is connected to the icemaker at the contactor terminals for the compressor and the fan motor operates whenever the compressor operates.
Electrical connections are made at the junction box at the back of the icemaker and at the junction box on the remote condenser.
The remote condenser must be wired to the icemaker in accordance with local and national electrical codes with a minimum of 18 Awg. wire with an ground bonding wire connected to the ground screws provided in both the condenser and machine field wiring boxes. All outdoor wiring must be in rainproof conduit.
All external wiring must conform to national, state, and local electrical codes. The use of a licensed electrician is required to perform the electrical installation.
REMOTE CONDENSER
WATERPROOF (LIQUID TIGHT)
CONDUIT
ICEMAKER
JUNCTION BOX
POWER SUPPLY
June 1994
Page 8
FOR THE INSTALLER: Completed Installation
A typical installation should generally appear as illustrated below. The remote condenser must be located above the icemaker and the precharged lines installed per the instructions on page 6.
NME1250R
ROOF
CUT-AWAY
INSULATED PRECHARGED
REFRIGERANT TUBING
August 1993
Page 9
LEVELED?
NME1250R
FOR THE INSTALLER: Final Check List
1. Is the ice system installed indoors in a location where the air and water temperatures are controlled, and where they do not exceed the design limitations?
2. Is there an electrical service disconnect within sight of the installed machine? Has the voltage been checked, and compared to nameplate requirements?
3. Have all the plumbing connections been made and checked for leaks?
4. Has the machine and bin been leveled?
5. Is there a minimum of 6" clearance at the rear, left, and right of the machine for proper service access and air circulation?
6. Is the water pressure a minimum of 20 psig?
7. Has the machine been secured to the bin?
8. Is there a water shut off valve installed near the machine?
9. Is the remote condenser installed per local building codes, and in a place where it has adequate ventilation and minimal solar heat gain?
10. Has all shipping material (under and next to the gearmotor, and on top of the ice chute) and literature (inside the front panel) been removed from the units?
11. Have the remote condenser and precharged lines been properly installed?
12. Has the electrical connection between the icemaker and the condenser been made?
13. Verify that the master switch is in the OFF position.
14. Switch on the electrical power.
15. Refer to Pre-Start instructions, the next page.
POWER SUPPLY?
PLUMBING?
DRAINS?
June 1994
Page 10
START UP
Pre-Start Inspection
1. Remove the front, left , an d righ t side service panels.
2. Chec k tha t the styrofoa m sh ipp ing bloc ks un de r the gearmotor, on top of the ice discharge chut e, and between the gearmotor and the right side panel have been removed.
3. Inspect the interio r of the mach ine for loos e screws or wires. Check that no refrige rant lines are rubbing ea ch oth er. Che ck th at the fan blad e turns freely (remot e conden ser).
Start Up
NME1250R
4. Check that the refrige ran t line s are properly installed .
5. Check that the electrica l powe r has been on for at least 4 hours.
6. Check that the unit is insta lled correctly according to the fin al check list on page 10.
1. Go through the pre-start inspection.
2. Open the ha nd v alve , ob serve that water enter s the water reservoir, fills the tube from the reservoir to the evaporator, and then shuts off. Check for leaks.
3. Ope n the Kin g Valve.
4. Switch the master switch on. The electrical start up sequence is now on
automatic. A. There should be a short (15 second) delay
before the gearmotor sta rts. B. After the gearmotor sta rts, the liquid line va lve
will open, the pump down control will close and the compressor will start .
5. The remote condenser fan turns, and the condenser begin s to discha rge warm air.
The low side pressure may be 25 to 28 PSIG in low condensing temperatures, and 35 to 40 PSIG when in high co nden sing tempera tu re s.
The discharge pressure will depend upon air and water temperatures, but should be between 180 ­200 psig when in low con dens ing temperat ure s; and 320 to 420 psig when in high condensing temperatures.
7. THERE ARE NO ADJUSTMENTS TO MAKE, so replace the panels.
8. Clean and/or sanitize the storage bin interior, wipe off the exterior with a clean, damp cloth.
9 Give the owner/use r the serv ice man ua l, ins truc t him/her in the operatio n of the unit , and mak e sure they know who to call for service.
10. Fill out the Customer Evalu ation and War ranty Registration form, and mail it to Scotsman.
6. The unit should so on be making ice , if de sired the low side pressure can be checked, it should be 30 psig + or - 4 psig.
April 1995
Page 11
Loading...
+ 25 hidden pages