Scotsman NH0422A-1, NH0422W-1, NS0422A-1, NS0422W-1, FS0522A-1 Owners Manual

...
Page 1
Installation and User’s Manual for
Modular Flake and Nugget Ice Machines
Prodigy Plus A Series Models
NH0422, NS0422, FS0522, NH0622, NS0622, FS0822,
NH0922, NS0922, FS1222, NH1322, NS1322, FS1522
Air Cooled, Water Cooled, and Remote Air Cooled
Page 2
NH0422, NS0422, FS0522, NH0622, NS0622, FS0822, NH0922, NS0922, FS1222, NH1322, NS1322, FS1522
A Series Air, Water, or Remote User Manual
Introduction
This ice machine is the result of years of experience
with aked and nugget ice machines. The latest in
electronics has been coupled with the time tested
Scotsman aked ice system to provide reliable ice making and the features needed by customers. The features include easily accessible air lters, simple conductivity water level sensing, evaporator clearing
at shut down, photo-eye sensing bin control and the
ability to add options.
Contents
Installation: .....................................................................2
Location: ....................................................................... 3
NH0422, NS0422, FS0522, NH0622, NS0622, F0822 Cabinet Layout ....................... 4
NH0922, NS0922, FS1222, NH1322, NS1322, FS1522 Cabinet Layout ...................... 5
Unpacking & Install Prep ........................................................... 6
Water - Air or Water Cooled ......................................................... 7
Electrical - All Models ............................................................. 8
Electrical - All Models Continued ..................................................... 9
Refrigeration - Remote Condenser Models ............................................. 10
Remote Condenser Location - Limits ................................................. 11
For The Installer: Remote Condenser ................................................. 12
Line Set Routing and Brazing (applies to remote units only) ............................... 13
Line Set Routing and Brazing ....................................................... 14
Water - Remote Models ............................................................ 15
Final Check List .................................................................. 16
Initial Start Up and Maintenance .....................................................17
Maintenance: Scale Removal and Sanitation ........................................... 18
Maintenance: Sensors ............................................................. 19
Options ........................................................................ 20
What to do before calling for service .................................................. 21
Page 1
Page 3
NH0422, NS0422, FS0522, NH0622, NS0622, FS0822, NH0922, NS0922, FS1222, NH1322, NS1322, FS1522
A Series Air, Water, or Remote User Manual

Installation:

This machine is designed to be used indoors, in a
controlled environment. Operation outside the limits listed here will void the warranty.
Air temperature limits
Minimum Maximum Ice maker 50 Remote
o
F. 100oF.
-20oF. 120oF.
condenser
Water temperature limits
Minimum Maximum All models 40
o
F. 100oF.
Water pressure limits (potable)
Maximum Minimum All models 20 psi 80 psi
Water pressure limit to water cooled condenser is 150 PSI
The quality of the water supplied to the ice machine
will have an impact on the time between cleanings and ultimately on the life of the product. Water can contain impurities either in suspension or in solution. Suspended solids can be ltered out. In solution or dissolved solids cannot be ltered, they must be diluted or treated. Water lters are recommended to remove suspended solids. Some lters have treatment in them for dissolved solids.
Check with a water treatment service for a recommendation.
RO water. This machine can be supplied with Reverse Osmosis water, but the water conductivity must be no less than 10 microSiemens/cm.
Potential for Airborne Contamination
Installing an ice machine near a source of yeast or similar material can result in the need for more frequent sanitation cleanings due to the tendency of
these materials to contaminate the machine.
Voltage limits
Minimum Maximum 115 volt 104 126 208-230 60 Hz 198 253
Minimum conductivity (RO water)
• 10 microSiemens / CM
Water Quality (ice making circuit)
• Potable
Most water lters remove chlorine from the water
supply to the machine which contributes to this
situation. Testing has shown that using a lter that does not remove chlorine, such as the Scotsman Aqua Patrol, will greatly improve this situation.
Warranty Information
The warranty statement for this product is provided separately from this manual. Refer to it for applicable coverage. In general warranty covers defects in material or workmanship. It does not cover
maintenance, corrections to installations, or situations when the machine is operated in circumstances that
exceed the limitations printed above.
Page 2
Page 4
NH0422, NS0422, FS0522, NH0622, NS0622, FS0822, NH0922, NS0922, FS1222, NH1322, NS1322, FS1522
A Series Air, Water, or Remote User Manual

Location:

While the machine will operate satisfactorily within the listed air and water temperature limits, it will produce more ice when those temperatures are nearer the
lower limits. Avoid locations that are hot, dusty, greasy or conned. Air cooled models need plenty of room air to breathe. Air cooled models must have at least
six inches of space at the back for air discharge;
however, more space will allow better performance.
Airow
Air ows into the front of the cabinet and out the back. The air lters are on the outside of the front panel and are easily removed for cleaning.
Bin compatibility
All models have the same footprint: 22 inches wide by 24 inches deep. Conrm available space when replacing a prior model.
Bin & adapter list:
• B322S – no adapter needed
B330P or B530P or B530S – Use KBT27
B842S – KBT39
B948S – KBT38 for single unit
B948S – KBT38-2X for two units side by side
• BH1100, BH1300 and BH1600 upright bins include
ller panels to accommodate a single 22 inch wide ice machine. No adapter is needed.
Dispenser compatibility
Only nugget ice models may be used with ice
dispensers. Flaked ice is not dispensable.
Airow
Options
Ice is made until it lls the bin enough to block an infrared light beam inside the base of the machine. A eld installed kit is available to adjust the maintained ice level lower. The kit number is KVS.
The standard controller has excellent diagnostic capabilities and communicates to the user through the
AutoAlert light panel, seen through the front panel. Field installed kits are available that can log data and provide additional information when the front panel is removed. The kit numbers are KSBU and KSB-NU. See page 21.
ID150 – use KBT42 and KDIL-PN-150, includes KVS, KNUGDIV and R629088514
ID200 – use KBT43 and KNUGDIV and KVS
ID250 – use KBT43 and KNUGDIV and KVS
See sales literature for other brand model ice and
beverage dispenser applications.
Other Bins & Applications:
Note the drop zone and ultrasonic sensor locations in
the illustrations on the next pages.
Scotsman ice systems are designed and manufactured with the highest regard for safety
and performance. Scotsman assumes no liability of
responsibility of any kind for products manufactured
by Scotsman that have been altered in any way,
including the use of any part and/or other components
not specically approved by Scotsman.
Scotsman reserves the right to make design changes and/or improvements at any time. Specications and design are subject to change without notice.
Page 3
Page 5
NH0422, NS0422, FS0522, NH0622, NS0622, FS0822, NH0922, NS0922, FS1222, NH1322, NS1322, FS1522
A Series Air, Water, or Remote User Manual

NH0422, NS0422, FS0522, NH0622, NS0622, F0822 Cabinet Layout

Note: Bin Top
Cut-outs for
drop zone
31.8
12.50
55.9
22.00 REF.
should include
ultrasonic
sensor location
REMOTE COND.
DISCHARGE LINE
1/2" COPPER
BRAZE JOINT
OPENING
7.1
10.9
2.81
4.30
16.5
6.48
A/C UNITS ONLY
LOUVER AND
REMOVABLE FILTER
7.4
2.92
ICE DROP
PLAN VIEW
57.7
22.70
41.9
16.50
61
REF.
24.00
58.4
23.00
48.9
19.24
3/8" FLARE
MACHINE
WATER
INLET
55.9
2.3
22.00
FRONT VIEW
.90
REMOTE COND.
LIQUID LINE
3/8" COPPER
3/8" FPT
CONDENSER
WATER
.88 DIA.
ELECTRICAL
CONNECTION
61
1.85
24.00
LEFT SIDE VIEW
BACK VIEW
AIR COOLED
4
1.59
5.5
2.17
3/4" FPT
DRAIN
BACK VIEW
23.6
17.2
6.78
2.17
CONDENSER
DRAIN
49.1
19.31
2.17
9.28
BACK VIEW
WATER COOLED
REMOTE COOLED
.88 DIA.
ELECTRICAL
ACCESS
3/8" FLARE
MACHINE
WATER
INLET
37.2
14.65
23.1
4.7
9.1
4
1.59
4.7
1.85
4
3/4" FPT
DRAIN
44.6
1.59
3/4" FPT
5.5
1/2" FPT
17.55
5.5
DRAIN
BRAZE JOINT.
.88 DIA.
ELECTRICAL
CONNECTION
INLET
3/8" FLARE
MACHINE
WATER
INLET
39.2
15.45
37.1
37.1
14.60
14.60
23.1
9.1
23.1
9.1
8.6
3.38
4.7
1.85
Page 4
Page 6
NH0422, NS0422, FS0522, NH0622, NS0622, FS0822, NH0922, NS0922, FS1222, NH1322, NS1322, FS1522
A Series Air, Water, or Remote User Manual

NH0922, NS0922, FS1222, NH1322, NS1322, FS1522 Cabinet Layout

55.9
22.00
Note: Bin Top Cut-outs
for drop zone should
include ultrasonic
sensor location
REMOTE COND.
DISCHARGE LINE
1/2" COPPER
BRAZE JOINT
7.4
2.92
ULTRA SONIC
BIN LEVEL
SENSOR
OPTIONAL
31.8
12.50
ICE DROP
OPENING
REF.
PLAN VIEW
10.9
4.30
7.1
2.81
A/C UNITS ONLY
LOUVER AND
REMOVABLE FILTER
16.5
6.48
55.9
57.7
22.70
22.00
FRONT VIEW
61
REF.
24.00
68.6
27.00
53.9
21.24 3/8" FLARE
MACHINE
WATER
INLET
REMOTE COND.
LIQUID LINE
3/8" COPPER
.88 DIA.
.88 DIA.
ELECTRICAL
CONNECTION
BRAZE JOINT.
ELECTRICAL
CONNECTION
3/8" FPT
3/8" FLARE
MACHINE
WATER
CONDENSER
WATER
INLET
INLET
47.2
47.2
18.60
18.60
39.2
30.7
15.45
30.7
12.10
12.10
12.6
4.7
4.7
4.95
38.3
15.09
32
12.59
4
1.59
BACK VIEW
REMOTE COOLED
61
24.00
LEFT SIDE VIEW
1.85
5.5
2.17
1/2" FPT
CONDENSER
DRAIN
48.3
19.00 .88 DIA.
ELECTRICAL
ACCESS
44.6
17.56
4
1.59
BACK VIEW
WATER COOLED
1.85
3/4" FPT
DRAIN
5.5
2.17
3/8" FLARE
MACHINE
WATER
INLET
47.4
18.65
30.7
12.10
4
1.59
BACK VIEW
AIR COOLED
4.7
1.85
3/4" FPT
DRAIN
Page 5
Page 7
NH0422, NS0422, FS0522, NH0622, NS0622, FS0822, NH0922, NS0922, FS1222, NH1322, NS1322, FS1522
A Series Air, Water, or Remote User Manual

Unpacking & Install Prep

Remove the carton from the skid. Check for hidden
freight damage, notify the carrier immediately if any is
found. Retain the carton for the carrier’s inspection.
The machine is not bolted to the skid. If strapped remove the strap.
Place on Bin or Dispenser
If reusing an existing bin, be sure that the bin is in good shape and that the gasket tape on the
top is not torn up. Water leaks, not covered by warranty, could result from a poor sealing surface. If
installing a remote or a remote low side, a new bin is recommended due to the high cost to the user of
replacing an old bin when a remote system is on top.
Install the correct adapter, following the directions
supplied with that adapter.
Hoist the machine onto the adapter.
Note: The machine is heavy! Use of a mechanical lift is recommended.
Panel Removal
Position the machine on the bin or adapter. Secure
with straps from the hardware bag packed with the
machine, or those supplied with the adapter.
Remove any plastic covering the stainless steel panels.
Remove any packaging, such as tape or foam blocks, that may be near the gear reducer or ice chute.
Level the bin and ice machine front to back and left to right by using the bin leg levelers.
1. Locate and loosen the two screws at the bottom of the front panel.
2. Pull the front panel out at the bottom until it clears.
3. Lower the front panel down and o󰀨 the machine.
4. Remove two screws at the front of the top panel.
Lift up the front of the top panel, push the top panel
back an inch, then lift to remove.
5. Locate and loosen the screw holding each side panel to the base. Left side panel also has a screw holding it to the control box.
6. Pull the side panel forward to release it from the back panel.
Control Panel Door
The door can be moved to allow access to the on and o󰀨 switches.
Page 6
Page 8
NH0422, NS0422, FS0522, NH0622, NS0622, FS0822, NH0922, NS0922, FS1222, NH1322, NS1322, FS1522
A Series Air, Water, or Remote User Manual

Water - Air or Water Cooled

The water supply for ice making must be cold, potable
water. There is a single 3/8” male are potable water connection on the back panel. Water cooled models also have a 3/8” FPT inlet connection for the water cooled condenser. Chilled water can also be used for this connection.
Backow
Water Inlet
Connection
The design of the oat valve and reservoir prevents potable water backow by means of a 1" air gap between the reservoir's maximum water level and the oat valve water inlet orice.
Drain
There is one 3/4” FPT condensate drain tting at the back of the cabinet. Water cooled models also have a 1/2” FPT discharge drain connection on the back panel.
Attach Tubing
Connect the potable water supply to the potable water
tting, 3/8” OD copper tubing or the equivalent is recommended.
Water ltration is recommended. If there is an existing lter, change the cartridge.
Connect the water cooled water supply to the
condenser inlet.
Note: Do NOT lter water to the water cooled condenser circuit.
Drain
Connection
Condensate
Drain Tube
Building Drain
Air Cooled or Remote Plumbing
Condenser Inlet
Connection
Drains - use rigid tubing: Connect the drain tube to the
condensate drain tting. Vent the drain.
Connect the water cooled condenser drain tube to the
condenser outlet. Do not vent this drain.
Do not Tee ice machine drains into the drain tube
from the ice storage bin or dispenser. Back ups
could contaminate and / or melt the ice in the bin or
dispenser. Be sure to vent the bin drain.
Follow all local and national codes for tubing, traps
and air gaps.
Page 7
Water Inlet
Connection
Drain
Connection
Condensate
Drain Tube
Condenser Drain Tube
Water Cooled Plumbing
Page 9
NH0422, NS0422, FS0522, NH0622, NS0622, FS0822, NH0922, NS0922, FS1222, NH1322, NS1322, FS1522
A Series Air, Water, or Remote User Manual

Electrical - All Models

The machine does not include a power cord, one
must be eld supplied or the machine hard wired to the electrical power supply.
The junction box for the power cord is on the back panel. See the next page.
Refer to the dataplate on the machine for minimum circuit ampacity and determine the proper wire size
for the application. The dataplate (on the back of the cabinet) also includes the maximum fuse size.
Model Series Dimensions
w” x d” x h”
NH0422A-1 A 22 x 24 x 23 115/60/1 Air 12.9 15 NH0422W-1 A 22 x 24 x 23 115/60/1 Water 12.1 15 NS0422A-1 A 22 x 24 x 23 115/60/1 Air 12.9 15 NS0422W-1 A 22 x 24 x 23 115/60/1 Water 12.1 15 FS0522A-1 A 22 x 24 x 23 115/60/1 Air 12.9 15 FS0522W-1 A 22 x 24 x 23 115/60/1 Water 12.1 15 NH0622A-1 A 22 x 24 x 23 115/60/1 Air 16.0 20 NH0622W-1 A 22 x 24 x 23 115/60/1 Water 14.4 20 NH0622R-1 A 22 x 24 x 23 115/60/1 Remote 17.1 20 NS0622A-1 A 22 x 24 x 23 115/60/1 Air 16.0 20 NS0622W-1 A 22 x 24 x 23 115/60/1 Water 14.4 20 NS0622R-1 A 22 x 24 x 23 115/60/1 Remote 17.1 20 FS0822A-1 A 22 x 24 x 23 115/60/1 Air 16.0 20 FS0822W-1 A 22 x 24 x 23 115/60/1 Water 14.4 20 FS0822R-1 A 22 x 24 x 23 115/60/1 Remote 17.1 20 NH0622A-32 A 22 x 24 x 23 208-230/60/1 Air 8.8 15 NS0622A-32 A 22 x 24 x 23 208-230/60/1 Air 8.8 15 FS0822W-32 A 22 x 24 x 23 208-230/60/1 Water 7.6 15 NS0622A-6 A 22 x 24 x 23 230/50/1 Air 7.9 15
Voltage
Volts/Hz/Phase
Connect electrical power to wires inside the junction box in the back of the cabinet. Use a strain relief and connect a ground wire to the ground screw.
Remote models power the condenser fan motor from
marked leads in the junction box.
Do not use an extension cord. Follow all local and national codes.
Condenser
Type
Min Circuit
Ampacity
Max Fuse Size or HACR
Type Circuit Breaker
Page 8
Table continued on following page
Page 10
NH0422, NS0422, FS0522, NH0622, NS0622, FS0822, NH0922, NS0922, FS1222, NH1322, NS1322, FS1522
A Series Air, Water, or Remote User Manual

Electrical - All Models Continued

Model Series Dimensions
w” x d” x h”
Voltage Volts/
Hz/Phase
Condenser
Type
Min Circuit
Ampacity
Max Fuse Size or HACR
NH0922A-1 A 22 x 24 x 27 115/60/1 Air 24.0 30 NH0922R-1 A 22 x 24 x 27 115/60/1 Remote 25.0 30 NS0922A-1 A 22 x 24 x 27 115/60/1 Air 24.0 30 NS0922R-1 A 22 x 24 x 27 115/60/1 Remote 25.0 30 NH0922A-32 A 22 x 24 x 27 208-230/60/1 Air 11.9 15 NH0922W-32 A 22 x 24 x 27 208-230/60/1 Water 10.7 15 NH0922R-32 A 22 x 24 x 27 208-230/60/1 Remote 11.7 15 NS0922A-32 A 22 x 24 x 27 208-230/60/1 Air 11.9 15 NS0922W-32 A 22 x 24 x 27 208-230/60/1 Water 10.7 15 NS0922R-32 A 22 x 24 x 27 208-230/60/1 Remote 11.7 15 FS1222A-32 A 22 x 24 x 27 208-230/60/1 Air 11.9 15 FS1222W-32 A 22 x 24 x 27 208-230/60/1 Water 10.7 15 FS1222R-32 A 22 x 24 x 27 208-230/60/1 Remote 11.7 15 NS0922W-3 A 22 x 24 x 27 208-230/60/3 Water 8.0 15 FS1222A-3 A 22 x 24 x 27 208-230/60/3 Air 9.2 15 FS1222R-3 A 22 x 24 x 27 208-230/60/3 Remote 9.0 15 NH1322A-32 A 22 x 24 x 27 208-230/60/1 Air 17.8 20 NH1322W-32 A 22 x 24 x 27 208-230/60/1 Water 16.6 20 NH1322R-32 A 22 x 24 x 27 208-230/60/1 Remote 17.6 20 NS1322A-32 A 22 x 24 x 27 208-230/60/1 Air 17.8 20 NS1322W-32 A 22 x 24 x 27 208-230/60/1 Water 16.6 20 NS1322R-32 A 22 x 24 x 27 208-230/60/1 Remote 17.6 20 FS1522A-32 A 22 x 24 x 27 208-230/60/1 Air 17.8 20 FS1522R-32 A 22 x 24 x 27 208-230/60/1 Air 17.6 20 NS1322W-3 A 22 x 24 x 27 208-230/60/3 Water 9.9 15 NH1322W-3 A 22 x 24 x 27 208-230/60/3 Water 9.9 15
Type Circuit Breaker
Page 9
Page 11
NH0422, NS0422, FS0522, NH0622, NS0622, FS0822, NH0922, NS0922, FS1222, NH1322, NS1322, FS1522
Ground
To Remote
Ground
A Series Air, Water, or Remote User Manual

Refrigeration - Remote Condenser Models

Remote condenser models have additional installation needs.
The correct remote condenser fan and coil must
be connected to the ice making head. Liquid and
discharge tubing connections are on the back of
the ice machine cabinet. Tubing kits are available in several lengths to accommodate most installations. Order the one that just exceeds the length needed for the installation.
The kit numbers are:
BRTE10, BRTE25, BRTE40, BRTE75
There are limits as to how far away from the ice machine and where the remote condenser can be
located. See page 10 for those limits.
The correct condenser must be used:
Wire
Connection
Install Strain Relief
Junction
Box
Cover
Black
White
Ground
Power Supply
Wires
Install Strain Relief
Wire
Connection
Install Strain Relief
Junction
Cover
Condenser
Fan Motor
Blue
Box
Black
White Ground
Power
Supply
Wires
Ice Machine Model
NH0622R-1
Voltage Condenser
Model
115 ERC111-1 NS0622R-1 FS0822R-1 NH0922R-1 NS0922R-1
NH0922R-32
208-230 ERC311-32 NS0922R-32 FS1222R-32 FS1222R-3
NH1322R-32
208-230 ERC311-32 NS1322R-32
Do not reuse condenser coils contaminated with
mineral oil (used with R-502 for example). They will cause compressor failure and will void the warranty.
A headmaster is required for all remote condenser
systems. Installation of headmaster kit KPFHM will be
required if any of the following condensers are being used:
ERC101-1, ERC151-32, ERC201-32, ERC301-32, ERC402-32
Use of non-Scotsman condensers requires
pre-approval from Scotsman Engineering.
Page 10
Page 12
NH0422, NS0422, FS0522, NH0622, NS0622, FS0822, NH0922, NS0922, FS1222, NH1322, NS1322, FS1522
22.87"
17.15"
40.35"
A Series Air, Water, or Remote User Manual

Remote Condenser Location - Limits

Use the following for planning the placement of the
condenser relative to the ice machine
Location Limits - condenser location must not exceed ANY of the following limits:
• Maximum rise from the ice machine to the condenser is 35 physical feet
• Maximum drop from the ice machine to the condenser is 15 physical feet
Physical line set maximum length is 100 feet.
Calculated line set length maximum is 150.
Calculation Formula:
Drop = dd x 6.6 (dd = distance in feet)
Rise = rd x 1.7 (rd = distance in feet)
• Horizontal Run = hd x 1 (hd = distance in feet)
• Calculation: Drop(s) + Rise(s) + Horizontal
Congurations that do NOT meet these requirements must receive prior written authorization from Scotsman to maintain warranty.
Do NOT:
Route a line set that rises, then falls, then rises.
Route a line set that falls, then rises, then falls.
Calculation Example 1:
The condenser is to be located 5 feet below the ice
machine and then 20 feet away horizontally.
5 feet x 6.6 = 33. 33 + 20 = 53. This location would be
acceptable
Calculation Example 2:
The condenser is to be located 35 feet above and then 100 feet away horizontally. 35 x 1.7 = 59.5.
59.5 +100 = 159.5. 159.5 is greater than the 150 maximum and is NOT acceptable.
• Run = dd+rd+hd = Calculated Line Length
rd Max 35 feet
dd Max 15 feet
Operating a machine with an unacceptable
conguration is misuse and will void the warranty.
hd
Remote Condenser located
above ice machine.
Condenser Distance &
Location Schematic
Remote Condenser located
below ice machine.
Page 11
Page 13
NH0422, NS0422, FS0522, NH0622, NS0622, FS0822, NH0922, NS0922, FS1222, NH1322, NS1322, FS1522
A Series Air, Water, or Remote User Manual

For The Installer: Remote Condenser

Locate the condenser as near as possible to the
interior location of the ice machine. Allow it plenty of
space for air and cleaning: keep it a minimum of two
feet away from a wall or other rooftop unit.
Note: The location of the condenser relative to the ice machine is LIMITED by the specication on the prior page.
Roof penetration. In many cases a roong contractor
will need to make and seal the hole in the roof for the
line sets. The suggested hole diameter is 2 inches.
Meet all applicable building codes.
Roof Attachment
Install and attach the remote condenser to the roof of the building, using the methods and practices of construction that conform to the local building codes,
including having a roong contractor secure the
condenser to the roof
To Remote Condenser
Refrigeration
Tubing
Remote Condenser
Power Supply from
Ice Machine
Refrigeration
connections
Brazing required
Page 12
Page 14
NH0422, NS0422, FS0522, NH0622, NS0622, FS0822, NH0922, NS0922, FS1222, NH1322, NS1322, FS1522
A Series Air, Water, or Remote User Manual

Line Set Routing and Brazing (applies to remote units only)

Do not connect the refrigeration tubing until all routing
and forming of the tubing is complete. See the Coupling Instructions for nal connections.
1. Each set of tubing lines contains a 3/8” diameter
liquid line, and a 1/2” diameter discharge line. Both ends of each line are designed for eld brazed connections.
Note: The openings in the building ceiling or wall, listed in the next step, are the minimum sizes recommended for passing the refrigerant lines
through.
2. Have the roong contractor cut a minimum hole
for the refrigerant lines of 2”. Check local codes,
a separate hole may be required for the electrical
power supply to the condenser.
Caution: Do NOT kink the refrigerant tubing while
routing it.
3. Route the refrigerant tubes thru the roof opening. Follow straight line routing whenever possible.
Excess tubing must be cut to proper length prior to
connecting to the ice maker and condenser.
4. The tubing must be evacuated after connection
to the ice maker or condenser before opening the
ball valve.
5. Have the roong contractor seal the holes in the
roof per local codes
Potable Water
Supply
Condensate Drain
To Remote
Fan Motor
Condenser
Power Supply to Condenser
Refrigeration Tubing
Page 13
Page 15
NH0422, NS0422, FS0522, NH0622, NS0622, FS0822, NH0922, NS0922, FS1222, NH1322, NS1322, FS1522
A Series Air, Water, or Remote User Manual

Line Set Routing and Brazing

Do not connect the refrigerant tubing until all
routing and forming of the tubing is complete.
Final connections requires brazing, steps must
be performed by an EPA certied type II or higher technician.
The Lineset of tubing contains a 3/8” diameter liquid line, and a 1/2” diameter discharge line.
Note: The openings in the building ceiling or wall, listed in the next step, are the minimum sizes recommended for passing the refrigerant lines
through.
Have the roong contractor cut a minimum hole for the refrigerant lines of 1 3/4”. Check local codes,
a separate hole may be required for the electrical
power supply to the condenser.
Caution: Do NOT kink the refrigerant tubing while
routing it.
At Condenser:
1. Remove protective plugs from both connections and vent the nitrogen from the condenser.
Note: Be sure tube and stubs are round, dress with
swage tool if needed.
9. Add heat sink material to ball valve body.
10. Open nitrogen and ow 1 psi nitrogen into
liquid line tube and braze the liquid line and
suction line tubes to the valve stubs.
11. With nitrogen owing braze the liquid and suction line connections.
At Condenser:
1. Braze the liquid and suction line connections.
At Head:
1. Remove nitrogen source.
2. Return valve cores to access valves.
3. Connect vacuum pump to both access valves and evacuate the tubing and head to at least a 300 micron level.
4. Remove vacuum pump and add R-404A to all three tubes to provide a positive pressure.
5. Leak check the all braze connections and repair any leaks.
6. Open both valves to full open.
2. Remove the tubing access bracket to allow more room for brazing.
3. Route the lineset tubes to there connection.
4. Clean tubing ends and position into stubs.
Note: Be sure tube and stubs are round, dress with
swage tool if needed.
At Head:
1. Remove the tubing access bracket to allow more room for brazing.
2. Conrm connection ball valves are fully closed.
3. Remove protective plugs from both connec­tions.
4. Remove caps from access valve connec­tions.
5. Remove cores from access valves.
6. Connect refrigeration hoses to access valves.
7. Connect dry nitrogen source to liquid line connection.
8. Shorten tubing to correct length, clean ends and insert them into valve stubs.
Note: The full refrigerant charge is contained in the
receiver of the ice machine.
Page 14
Page 16
NH0422, NS0422, FS0522, NH0622, NS0622, FS0822, NH0922, NS0922, FS1222, NH1322, NS1322, FS1522
To Remote Condenser
A Series Air, Water, or Remote User Manual

Water - Remote Models

The water supply for ice making must be cold, potable
water. There is a single 3/8” male are potable water connection on the back panel.
Backow
The design of the oat valve and reservoir prevents potable water backow by means of a 1" air gap between the reservoir's maximum water level and the oat valve water inlet orice.
Drain
There is one 3/4” FPT condensate drain tting at the back of the cabinet.
Attach Tubing
1. Connect the potable water supply to the potable
water tting, 3/8” OD copper tubing or the equivalent is recommended.
2. Change the cartridge on the existing water lter (if
any present).
Do not Tee ice machine drains into the drain tube
from the ice storage bin or dispenser. Back ups
could contaminate and / or melt the ice in the bin or
dispenser. Be sure to vent the bin drain.
Follow all local and national codes for tubing, traps
and air gaps.
3. Connect the drain tube to
the condensate drain tting. Use rigid tubing.
4. Vent the drain tubing
between the ice machine
and the building drain.
Potable Water
Connection
Drain Vent
Condensate Drain
Page 15
Page 17
NH0422, NS0422, FS0522, NH0622, NS0622, FS0822, NH0922, NS0922, FS1222, NH1322, NS1322, FS1522
A Series Air, Water, or Remote User Manual

Final Check List

After connections:
1. Wash out the bin. If desired, the interior of the bin
could be sanitized.
2. Locate the ice scoop (if supplied) and have it
available for use when needed.
3. Remote only: Switch on the electrical power to
warm up the compressor. Do not start the machine for 4 hours.
Final Check List:
1. Is the unit located indoors in a controlled
environment?
2. Is the unit located where it can receive adequate
cooling air?
3. Has the correct electrical power been supplied to
the machine?
4. Have all the water supply connections been
made?
5. Have all the drain connections been made?
6. Has the unit been leveled?
7. Have all unpacking materials and tape been
removed?
8. Has the protective covering on the exterior panels
been removed?
9. Is the water pressure adequate?
10. Have the drain connections been checked for
leaks?
11. Has the bin interior been wiped clean or sanitized?
12. Have any water lter cartridges been replaced?
Caution: Do not place anything on top of the ice
machine, including the ice scoop. Debris and moisture from objects on top of the machine can work their way into the cabinet and cause serious damage. Damage caused by foreign material is not covered by warranty.
There are four indicator lights at the front of the
machine that provide information on the condition
of the machine: Power, Status, Water, De-scale &
Sanitize.
Power
Status
No Water
Time to Clean
On
O󰀨
Note: If the De-Scale & Sanitize light is ON, following the cleaning process will clear the light for another
cleaning time internal.
Two button switches are at the front – On and O󰀨. To switch the machine OFF, push and release the O󰀨 button. The machine will shut o󰀨 at the end of the next cycle. To switch the machine ON, push and release the On button. The machine will go through a start up process and then resume ice making.
Lower Light and Switch Panel
This user accessible panel provides important
operational information and duplicates the lights and
switches on the controller. It also allows access to the On and O󰀨 buttons that operate the ice machine.
Sometimes access to the switches should be limited
to prevent unauthorized operation. For that purpose a xed panel is shipped in the hardware package. The xed panel cannot be opened.
13. Have all required kits and adapters been properly
installed?
Control and Machine Operation
Once started, the ice machine will automatically make
ice until the bin or dispenser is full of ice. When ice level drops, the ice machine will resume making ice.
Page 16
To install the xed panel:
1. Remove the front panel and remove the bezel.
2. Spread the bezel frame open and remove original door, insert xed panel into bezel. Be sure it is in the closed position.
3. Return bezel to panel and install panel on unit.
Page 18
NH0422, NS0422, FS0522, NH0622, NS0622, FS0822, NH0922, NS0922, FS1222, NH1322, NS1322, FS1522
A Series Air, Water, or Remote User Manual

Initial Start Up and Maintenance

1. Turn the water supply on. Remote models also open the liquid line valve.
2. Conrm voltage and switch on electrical power.
3. Push and release the On button. The machine will start in about two minutes.
4. Soon after starting, air cooled models will begin
to blow warm air out the back of the cabinet and water cooled models will drain warm water from
the condenser drain tube. Remote models will be discharging warm air from the remote condenser.
After about 5 minutes, ice will begin to drop into
the bin or dispenser.
5. Check the machine for unusual rattles. Tighten
any loose screws, be sure no wires are rubbing
moving parts. Check for tubes that rub. Remote
models check brazed connections for leaks,
retighten as needed.
6. Scan the QR code found behind the front panel
door and complete the warranty registration
online or ll out and mail the included warranty
registration card
7. Notify the user of the maintenance requirements and whom to call for service.
Sanitizing: Every time the scale is removed or as often as needed to maintain a sanitary unit.
Sensor Cleaning: Every time the scale is removed.
Top bearing check: At least twice a year or every
time the scale is removed. During the course of
normal operation, some material buildup on top of the bearing is normal and should be wiped away during
maintenance.
Maintenance: Air lters
1. Pull air lter(s) from panel.
2. Wash the dust and grease o󰀨 the lter(s).
3. Return it(them) to their original position(s).
Do not operate the machine without the lter in place except during cleaning.
Maintenance: Air cooled condenser
If the machine has been operated without a lter the air cooled condenser ns will need to be cleaned.
They are located under the fan blades. The services
of a refrigeration technician will be required to clean
the condenser.
Maintenance
This ice machine needs ve types of maintenance:
Air cooled and remote models need their air lters or condenser coils cleaned regularly.
All models need scale removed from the water system.
All models require regular sanitization.
All models require sensor cleaning.
All models require a top bearing check.
Maintenance Frequency:
Air lters: At least twice a year, but in dusty or greasy air, monthly.
Scale removal. At least twice a year, in some water conditions it might be every 3 months. The yellow De-
Scale & Sanitize light will switch on after a set period
of time as a reminder. The default time period is 6 months of power up time.
Page 17
Maintenance: Remote air cooled condenser
The condenser ns will occasionally need to be cleaned of leaves, grease or other dirt. Check the coil every time the ice machine is cleaned.
Maintenance: Exterior Panels
The front and side panels are durable stainless steel.
Fingerprints, dust and grease will require cleaning with a good quality stainless steel cleaner
Note: If using a sanitizer or a cleaner that contains chlorine on the panels, after use be sure to wash the
panels with clean water to remove chlorine residue.
Maintenance: Water lters
If the machine has been connected to water lters,
check the cartridges for the date they were replaced
or for the pressure on the gauge. Change cartridges if they’ve been installed more than 6 months or if the pressure drops too much during ice making.
Page 19
NH0422, NS0422, FS0522, NH0622, NS0622, FS0822, NH0922, NS0922, FS1222, NH1322, NS1322, FS1522
A Series Air, Water, or Remote User Manual Maintenance: Scale Removal and Sanitation
Note: Following this procedure will reset the de-scale
and sanitize light.
1. Remove front panel.
2. Push and release the O󰀨 button.
3. Remove ice from bin or dispenser.
4. Turn the water supply to the oat valve OFF.
5. Drain the water and evaporator by disconnecting
the leg of the hose connected to the water sensor
and draining it into the bin. Return the hose to its original position.
6. Remove the water reservoir cover.
Drain Water
7. Mix a solution of 8 ounces of Scotsman Clear One Scale Remover and 3 quarts of 95-115 degree F. potable water.
Scotsman
Model:
NS0422, NS0622, NS0922, NS1322,
IFS0522, FS0822, FS1222, FS1522 8 oz. 3 qts.
NH0422, NH0622, NH0922, NH1322 3 oz. 3 qts.
Clear One Water
Ice machine scale remover contains acids. Acids can cause burns.
If concentrated cleaner comes in contact with
skin, ush with water. if
swallowed, do NOT induce
vomiting. Give large amounts of water or milk. Call Physician immediately. Keep out of the reach of children.
8. Pour the scale remover solution into the reservoir. Use a small cup for pouring.
11. Turn the water supply to the ice machine OFF
12. Drain the water reservoir and evaporator by
disconnecting the leg of the hose connected to the water sensor and draining it into the bin or a
bucket. Return the hose to its original position. Discard or melt all ice made during the previous step.
13. Create a solution of sanitizer. Mix 4oz/118ml of NuCalgon IMS and 2.5gal/9.5L of (90°F/32°C to 110°F/43°C) potable water to create a 200 ppm solution.
14. Pour the sanitizing solution into the reservoir.
15. Push and release the On button.
16. Switch the water supply to the ice machine on.
17. Operate the machine for 20 minutes.
18. Push and release the O󰀨 button.
19. Wash the reservoir cover in the remaining sanitizing solution.
9. Push and release the Clean button: the auger drive motor and light are on, C is displayed and the De-scale light blinks. After 20 minutes the compressor will start.
10. Operate the machine and pour the scale remover into the reservoir until it is all gone. Keep the reservoir full. When all the scale remover solution has been used, turn the water supply back on.
After 20 minutes of ice making the compressor
and auger motor will shut o󰀨.
June 2020
Page 18
20. Return the reservoir cover to its normal position.
21. Melt or discard all ice made during the sanitizing process.
22. Wash the inside of the ice storage bin with the sanitizing solution.
23. Push and release the On button.
24. Return the front panel to its original position and
secure with the original screws
Page 20
NH0422, NS0422, FS0522, NH0622, NS0622, FS0822, NH0922, NS0922, FS1222, NH1322, NS1322, FS1522
A Series Air, Water, or Remote User Manual

Maintenance: Sensors

Photo Eyes
The control that senses bin full and empty is a photo­electric eye, therefore it must be kept clean so it
can “see”. At least twice a year, remove the ice level
sensors from the base of the ice chute, and wipe the
inside clean, as illustrated.
1. Remove front panel.
2. Pull photo eye holders forward to release them.
3. Wipe clean as needed. Do not scratch the photo­eye portion.
4. Return the eye holders to their normal positions and return the front panel to its original position.
Water Probe
The ice machine senses water by a probe located
near the water reservoir. At least twice a year, the probe should be wiped clean of mineral build-up.
1. Shut o󰀨 the water supply.
2. Remove front panel.
3. Remove the hose from the water sensor, use a hose clamp pliers for this.
4. Loosen mounting screw and release the water sensor from the frame of the unit.
5. Wipe probes clean.
Note: Eye holders must be mounted properly. They
snap into a centered position and are properly located when the wires are routed to the back and the left eye
is the one with 2 wires at the connector.
Probes
Change De-Scale Notication Interval
This feature is accessible only from standby
(Status Light O󰀨).
1. Press and hold Clean button for 3 seconds.
This starts the Time to Clean Adjustment State and displays the current time to clean setting.
2. Press the clean button repeatedly to cycle through
the 4 possible settings:
0 (disabled), 4 months, 6 months (default), 1 year
3. Push O󰀨 to conrm the selection.
Page 19
Page 21
NH0422, NS0422, FS0522, NH0622, NS0622, FS0822, NH0922, NS0922, FS1222, NH1322, NS1322, FS1522
A Series Air, Water, or Remote User Manual

Options

Vari-Smart
Optional adjustable ice level control (KVS). When this option is present there is an adjustment post and
an additional indicator light to the right of the four
indicator lights mentioned earlier.
The ultrasonic ice level control allows the user to
control the point that the ice machine will stop making
ice before the bin or dispenser is full.
Reasons for this include:
• Seasonal changes in ice used
Use of adjustable ice level control
There are several positions the ice level can be set to, including O󰀨 or Max (knob and label indicators lined up), where it lls the bin until the standard bin control shuts the machine o󰀨. See the kit’s instructions for
complete details including special instructions for
dispenser applications.
• Planning to sanitize the bin
Faster turnover for fresher ice
• Certain dispenser applications where maximum ice
level is not desired
Rotate the adjustment post to the desired ice level.
The machine will ll up to that level and when it shuts o󰀨 the indicator light next to the adjustment post will be On.
Note: The maximum ll position is when the arrow on the knob points to the arrow on the label.
Page 20
Page 22
NH0422, NS0422, FS0522, NH0622, NS0622, FS0822, NH0922, NS0922, FS1222, NH1322, NS1322, FS1522
A Series Air, Water, or Remote User Manual

What to do before calling for service

Normal Operation:
Ice
The machine will make either aked or nugget ice, depending upon the model. The ice will be produced continuously until the bin is full. It is normal for a few drops of water to occasionally fall with the ice.
Heat
On remote models most heat is exhausted at the remote condenser, the ice machine should not
generate signicant heat. Water cooled models
also put most of the heat from ice making into the
discharge water. Air cooled models will generate heat, and it will be discharged into the room.
Noise
The ice machine will make noise when it is in ice
making mode. The compressor and gear reducer will produce sound. Air cooled models will add fan noise. Some ice making noise could also occur. These noises are all normal for this machine.
Check the following:
1. Has the water supply to the ice machine or
building been shut o󰀨? If yes, the ice machine will
automatically restart within minutes after water begins
to ow to it.
2. Has power been shut o󰀨 to the ice machine? If yes,
the ice machine will automatically restart when power
is restored.
3. Has someone shut the power o󰀨 to the remote
condenser while the ice machine still had power? If yes, the ice machine may need to be manually reset.
To Manually Reset the machine.
• Open the switch door
• Push and release the O󰀨 button.
• Push and release the On button.
Open Switch Door
Reasons the machine might shut itself o󰀨:
• Lack of water.
• Does not make ice
• Auger motor overload
• High discharge pressure.
• Low refrigeration system pressure.
To Shut the Machine O󰀨:
Push and hold the O󰀨 button for 3 seconds or until the machine stops.
Indicator Lights & Their Meanings
Power Status Water De-Scale &
Sanitize
Steady Green Normal Normal - - Blinking Green Self Test Failure Switching on or
- -
o󰀨. When Smart-
Board used, machine attention
recommended.
Blinking Red - Diagnostic shut
Lack of water -
down
Yellow - - - Time to descale and
sanitize
Blinking Yellow - - - In Cleaning Mode Light O󰀨 No power Switched to O󰀨 Normal Normal
Page 21
Page 23
SCOTSMAN ICE SYSTEMS
101 Corporate Woods Parkway
Vernon Hills, IL 60061
800-726-8762
www.scotsman-ice.com
17-3706-01 Rev A
Loading...