Scotsman F0522 Prodigy Plus, F1222 Prodigy Plus, F1522 Prodigy Plus, N0922 Prodigy Plus, N1322 Prodigy Plus User Manual

Page 1
Installation and User’s Manual for
Modular Flaked and Nugget Ice Machines
Prodigy Plus D Series Models
F0522, F0822, F1222, F1522, N0422, N0622,
N0922 and N1322
Air Cooled, Water Cooled and Remote Air Cooled
Page 2
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522
D Series Air, Water or Remote User Manual Introduction
This ice machine is the result of years of experience
with aked and nugget ice machines. The latest in
electronics has been coupled with the time tested
Scotsman aked ice system to provide reliable ice making and the features needed by customers. The features include easily accessible air lters, simple conductivity water level sensing, evaporator clearing
at shut down, photo-eye sensing bin control and the
ability to add options.
Contents
Installation:
Location:
N0422, F0522, N0622, F0822 Cabinet Layout
N0922, F1222, N1322, F1522 Cabinet Layout
Unpacking & Install Prep
Water - Air or Water Cooled
Electrical - All Models
Refrigeration - Remote Condenser Models
Remote Condenser Location - Limits
For The Installer: Remote Condenser
Precharged Line Routing - Remote Only. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Coupling Instructions - Remote Only
Water - Remote Models
Final Check List
..................................................................... 2
....................................................................... 3
.......................................... 4
.......................................... 5
........................................................... 6
......................................................... 7
............................................................. 8
............................................. 9
................................................. 10
................................................. 11
.................................................. 13
............................................................ 14
.................................................................. 15
Initial Start Up and Maintenance
Maintenance: Scale Removal and Sanitation
Maintenance: Check Top Bearing
Bearing Service
Maintenance: Sensors
Options
What to do before calling for service
........................................................................ 21
.................................................................. 19
............................................................. 20
..................................................... 16
.................................................... 18
.................................................. 22
........................................... 17
Page 1
Page 3
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522
D Series Air, Water or Remote User Manual Installation:
This machine is designed to be used indoors, in a
controlled environment. Operation outside the limits listed here will void the warranty.
Air temperature limits
Minimum Maximum Ice maker 50 Remote
o
F. 100oF.
-20oF. 120oF.
condenser
Water temperature limits
Minimum Maximum All models 40
o
F. 100oF.
Water pressure limits (potable)
Minimum
Maximum All models 20 psi 80 psi
Water pressure limit to water cooled condenser is 150 PSI
Voltage limits
Minimum Maximum 115 volt 104 126 208-230 60 Hz 198 253
Minimum conductivity (RO water)
10 microSiemens / CM
Water Quality (ice making circuit)
Potable
The quality of the water supplied to the ice machine
will have an impact on the time between cleanings and ultimately on the life of the product. Water can contain impurities either in suspension or in solution. Suspended solids can be ltered out. In solution or dissolved solids cannot be ltered, they must be diluted or treated. Water lters are recommended to remove suspended solids. Some lters have treatment in them for dissolved solids.
Check with a water treatment service for a recommendation.
RO water. This machine can be supplied with Reverse Osmosis water, but the water conductivity must be no less than 10 microSiemens/cm.
Potential for Airborne Contamination
Installing an ice machine near a source of yeast or similar material can result in the need for more frequent sanitation cleanings due to the tendency of
these materials to contaminate the machine.
Most water lters remove chlorine from the water
supply to the machine which contributes to this
situation. Testing has shown that using a lter that does not remove chlorine, such as the Scotsman Aqua Patrol, will greatly improve this situation.
Warranty Information
The warranty statement for this product is provided separately from this manual. Refer to it for applicable coverage. In general warranty covers defects in material or workmanship. It does not cover
maintenance, corrections to installations, or situations when the machine is operated in circumstances that
exceed the limitations printed above.
Page 2
Page 4
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522
D Series Air, Water or Remote User Manual Location:
While the machine will operate satisfactorily within the listed air and water temperature limits, it will produce more ice when those temperatures are nearer the
lower limits. Avoid locations that are hot, dusty, greasy or conned. Air cooled models need plenty of room air to breathe. Air cooled models must have at least
six inches of space at the back for air discharge;
however, more space will allow better performance.
Airow
Air ows into the front of the cabinet and out the back. The air lters are on the outside of the front panel and are easily removed for cleaning.
Bin compatibility
All models have the same footprint: 22 inches wide by 24 inches deep. Conrm available space when replacing a prior model.
Bin & adapter list:
B322S – no adapter needed
• B330P or B530P or B530S – Use KBT27
• B842S – KBT39
• B948S – KBT38 for single unit
• B948S – KBT38-2X for two units side by side
BH1100, BH1300 and BH1600 upright bins include ller panels to accommodate a single 22 inch wide ice machine. No adapter is needed.
Dispenser compatibility
Only nugget ice models may be used with ice
dispensers. Flaked ice is not dispensable.
Airow
Options
Side air ow kits KPFSA223 or KPFSA227 are available for air cooled models. A lter kit for the remote condenser is KERCF
Ice is made until it lls the bin enough to block an infrared light beam inside the base of the machine. A eld installed kit is available to adjust the maintained ice level lower. The kit number is KVS.
The standard controller has excellent diagnostic capabilities and communicates to the user through the
AutoAlert light panel, seen through the front panel. Field installed kits are available that can log data and provide additional information when the front panel is removed. The kit numbers are KSBU and KSB-NU. See page 21.
• ID150 – use KBT42 and KDIL-PN-150, includes KVS, KNUGDIV and R629088514
• ID200 – use KBT43 and KNUGDIV and KVS
• ID250 – use KBT43 and KNUGDIV and KVS
See sales literature for other brand model ice and
beverage dispenser applications.
Other Bins & Applications:
Note the drop zone and ultrasonic sensor locations in
the illustrations on the next pages.
Scotsman ice systems are designed and manufactured with the highest regard for safety
and performance. Scotsman assumes no liability of
responsibility of any kind for products manufactured
by Scotsman that have been altered in any way,
including the use of any part and/or other components
not specically approved by Scotsman.
Scotsman reserves the right to make design changes and/or improvements at any time. Specications and design are subject to change without notice.
Page 3
Page 5
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522
D Series Air, Water or Remote User Manual N0422, F0522, N0622, F0822 Cabinet Layout
7.1
7.1
2.81
2.81
7.4
7.4
2.92
41.9
41.9
ICE DROP
16.50
16.50
2.92
OPENING
16.5
16.5
6.48
6.48
10.9
10.9
4.30
4.30
57.7
22.70
55.9
55.9
REF.
REF.
22.00
22.00
31.8
31.8
12.50
12.50
ULTRA SONIC
BIN LEVEL
SENSOR
OPTIONAL
PLAN VIEW
61
61
REF.
REF.
24.00
24.00
LOUVER AND
REMOVABLE FILTER
A/C UNITS ONLY
55.9
22.00
FRONT VIEW
Note: Bin Top
Cut-outs for
drop zone
should include
ultrasonic
sensor location
REMOTE COND.
DISCHARGE LINE
1/2" MALE CPLG.
REMOTE COND.
LIQUID LINE
3/8" MALE CPLG.
3/8" FPT
CONDENSER
WATER
.88 DIA.
ELECTRICAL
CONNECTION
.88 DIA.
ELECTRICAL
INLET
CONNECTION
48
37.1
18.88
39.1
14.60
15.40
31.5
12.40
[58.5]
23.00
.92
[2.4]
BACK VIEW
REMOTE COOLED
27.8
4
1.59
5.5
3/4" FPT
DRAIN
CONDENSER
DRAIN
1/2" FPT
49
17.55
19.31
2.17
WATER COOLED
6.8
2.68
8.5
3.33
44.6
7.40
18.8
BACK VIEW
5.5
2.17
10.94
.88 DIA.
ELECTRICAL
ACCESS
61
24.00
LEFT SIDE VIEW
BACK VIEW
AIR COOLED
5.5
2.17
3/8" FLARE
MACHINE
WATER
INLET
3/4" FPT
DRAIN
4
1.59
3/8" FLARE
MACHINE
WATER
INLET
37.2
14.65
6.7
2.63
31.4
12.35
37
14.55
31.5
12.40
6.8
2.68
3/4" FPT
DRAIN
4
1.59
Page 4
Page 6
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522
D Series Air, Water or Remote User Manual N0922, F1222, N1322, F1522 Cabinet Layout
7.1
7.1
2.81
2.81
ULTRA SONIC
BIN LEVEL
SENSOR
55.9
55.9
REF.
REF.
22.00
22.00
31.8
31.8
12.50
12.50
OPTIONAL
7.4
7.4
ICE DROP
PLAN VIEW
2.92
2.92
OPENING
16.5
16.5
6.48
6.48
10.9
10.9
4.30
4.30
LOUVER AND
REMOVABLE FILTER
A/C UNITS ONLY
Note: Bin Top Cut-outs
for drop zone should
include ultrasonic
sensor location
REMOTE COND.
DISCHARGE LINE
1/2" CPLG
REMOTE COND.
LIQUID LINE
3/8" CPLG
.88 DIA.
ELECTRICAL
ACCESS
3/8" FLARE
MACHINE
WATER
INLET
55.5
21.84
47.2
61
61
18.59
24.00
24.00
REF.
REF.
57.7
22.70
41.9
41.9
16.50
16.50
[68.6]
27.00
BACK VIEW
3/4" FPT
DRAIN
REMOTE COOLED
4
1.59
6.8
34
2.67
13.39
27.8
10.93
7.39
18.8
5.5
2.17
2.3
61
55.9
22.00
.91
24.00
FRONT VIEW
LEFT SIDE VIEW
.88 DIA.
ELECTRICAL
ACCESS
3/8" FPT
3/8" FLARE
MACHINE
WATER
INLET
CONDENSER
WATER INLET
47.2
18.59
39.2
15.44
34
13.39
8.6
3.37 1/2" FPT
50.3
45.8
18.05
6.8
2.67
3/4" FPT
CONDENSER
DRAIN
BACK VIEW
19.80
WATER COOLED
5.5
4
1.59
DRAIN
Page 5
2.17
.88 DIA.
ELECTRICAL
ACCESS
3/8" FLARE
MACHINE
WATER
INLET
47.3
18.64
BACK VIEW
AIR COOLED
3/4" FPT
DRAIN
2.67
4
1.59
6.8
34
13.39
Page 7
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522
D Series Air, Water or Remote User Manual Unpacking & Install Prep
Remove the carton from the skid. Check for hidden
freight damage, notify the carrier immediately if any is
found. Retain the carton for the carrier’s inspection.
The machine is not bolted to the skid. If strapped remove the strap.
Place on Bin or Dispenser
If reusing an existing bin, be sure that the bin is in good shape and that the gasket tape on the
top is not torn up. Water leaks, not covered by warranty, could result from a poor sealing surface. If
installing a remote or a remote low side, a new bin is recommended due to the high cost to the user of
replacing an old bin when a remote system is on top.
Install the correct adapter, following the directions
supplied with that adapter.
Hoist the machine onto the adapter.
Note: The machine is heavy! Use of a mechanical lift is recommended.
Panel Removal
Position the machine on the bin or adapter. Secure
with straps from the hardware bag packed with the
machine, or those supplied with the adapter.
Remove any plastic covering the stainless steel panels.
Remove any packaging, such as tape or foam blocks, that may be near the gear reducer or ice chute.
Level the bin and ice machine front to back and left to right by using the bin leg levelers.
1. Locate and loosen the two screws at the bottom of the front panel.
2. Pull the front panel out at the bottom until it clears.
3. Lower the front panel down and off the machine.
4. Remove two screws at the front of the top panel.
Lift up the front of the top panel, push the top panel
back an inch, then lift to remove.
5. Locate and loosen the screw holding each side panel to the base. Left side panel also has a screw holding it to the control box.
6. Pull the side panel forward to release it from the back panel.
Control Panel Door
The door can be moved to allow access to the on and off switches. To better limit switch access, a different door may be installed.
Page 6
Page 8
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522
D Series Air, Water or Remote User Manual Water - Air or Water Cooled
The water supply for ice making must be cold, potable
water. There is a single 3 8” male are potable water connection on the back panel. Water cooled models also have a 3/8” FPT inlet connection for the water cooled condenser. Chilled water can also be used for this connection.
Backow
Water Inlet
Connection
The design of the oat valve and reservoir prevents potable water backow by means of a 1" air gap between the reservoir's maximum water level and the oat valve water inlet orice.
Drain
There is one ¾” FPT condensate drain tting at the back of the cabinet. Water cooled models also have a ½” FPT discharge drain connection on the back panel.
Attach Tubing
Connect the potable water supply to the potable water
tting, 3/8” OD copper tubing or the equivalent is recommended.
Water ltration is recommended. If there is an existing lter, change the cartridge.
Connect the water cooled water supply to the
condenser inlet.
Note: Do NOT lter water to the water cooled condenser circuit.
Drain
Connection
Condensate
Drain Tube
Building Drain
Air Cooled or Remote Plumbing
Condenser Inlet
Connection
Drains - use rigid tubing: Connect the drain tube to the
condensate drain tting. Vent the drain.
Connect the water cooled condenser drain tube to the
condenser outlet. Do not vent this drain.
Do not Tee ice machine drains into the drain tube
from the ice storage bin or dispenser. Back ups
could contaminate and / or melt the ice in the bin or
dispenser. Be sure to vent the bin drain.
Follow all local and national codes for tubing, traps
and air gaps.
Page 7
Water Inlet
Connection
Drain
Connection
Condensate
Drain Tube
Condenser Drain Tube
Water Cooled Plumbing
Page 9
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522
D Series Air, Water or Remote User Manual Electrical - All Models
The machine does not include a power cord, one
must be eld supplied or the machine hard wired to the electrical power supply.
The junction box for the power cord is on the back panel. See the next page.
Refer to the dataplate on the machine for minimum circuit ampacity and determine the proper wire size
for the application. The dataplate (on the back of the cabinet) also includes the maximum fuse size.
Model Series Dimensions
w" x d" x h"
N0422A-1 D 22 x 24 x 23 115/60/1 Air 15.2 20 N0422W-1 D same 115/60/1 Water 14.4 20 F0522A-1 D same 115/60/1 Air 15.2 20 F0522W-1 D same 115/60/1 Water 14.4 20 N0622A-1 D same 115/60/1 Air 18.3 25 N0622W-1 D same 115/60/1 Water 16.7 25 N0622R-1 D same 115/60/1 Remote 19.4 25 N0622A-32 D same 208-230/60/1 Air 9.8 15 F0822A-1 D same 115/60/1 Air 18.3 25 F0822W-1 D same 115/60/1 Water 16.7 25 F0822R-1 D same 115/60/1 Remote 19.4 25 F0822W-32 D same 208-230/60/1 Water 8.9 15 N0922A-32 D 22 x 24 x 27 208-230/60/1 Air 13.2 20 N0922W-32 D same 208-230/60/1 Water 12 15 N0922R-32 D same 208-230/60/1 Remote 13 20 F1222A-32 D same 208-230/60/1 Air 13.2 20 F1222W-32 D same 208-230/60/1 Water 12 15 F1222R-32 D same 208-230/60/1 Remote 13 20 F1222A-3 D same 208-230/60/3 Air 10.5 15 F1222R-3
N1322A-32 D same 208-230/60/1 Air 19.1 30 N1322W-32 D same 208-230/60/1 Water 17.9 30 N1322R-32 D same 208-230/60/1 Remote 18.9 30 F1522A-32 D same 208-230/60/1 Air 19.1 30
D same 208-230/60/3 Remote 10.3 15
Voltage Volts/
Hz/Phase
Connect electrical power to wires inside the junction box in the back of the cabinet. Use a strain relief and connect a ground wire to the ground screw.
Remote models power the condenser fan motor from
marked leads in the junction box.
Do not use an extension cord. Follow all local and national codes.
Condenser Type
Min Circ Ampacity
Max Fuse Size or HACR Type Circuit Breaker
Page 8
Page 10
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522
Ground
To Remote
D Series Air, Water or Remote User Manual Refrigeration - Remote Condenser Models
Remote condenser models have additional installation needs.
The correct remote condenser fan and coil must
be connected to the ice making head. Liquid and
discharge tubing connections are on the back of the
ice machine cabinet. Pre-charged tubing kits are available in several lengths to accommodate most installations. Order the one that just exceeds the length needed for the installation.
The kit numbers are:
RTE10
RTE25
RTE40
RTE75
Wire
Connection
Install Strain Relief
Junction
Box
Cover
Black
White Ground
Power Supply
Wires
Install Strain Relief
Ground
Wire
Connection
Install Strain Relief
Junction
Cover
Condenser
Fan Motor
Blue
Box
Black
White Ground
Power
Supply
Wires
There are limits as to how far away from the ice machine and where the remote condenser can be
located. See page 10 for those limits.
The correct condenser must be used.
Ice Machine Model
F0822R,
Voltage Condenser
Model
115 ERC111-1
N0622R F1222R,
208-230 ERC311-32
N0922R N1322R 208-230 ERC311-32
Do not reuse condenser coils contaminated with
mineral oil (used with R-502 for example). They will cause compressor failure and will void the warranty.
A headmaster is required for all remote condenser
systems. Prior condensers did not have a headmaster. New head / prior condenser retrots can use headmaster kit KPFHM.
Use of non-Scotsman condensers requires pre-
approval from Scotsman Engineering.
Page 9
Page 11
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522
D Series Air, Water or Remote User Manual Remote Condenser Location - Limits
Use the following for planning the placement of the
condenser relative to the ice machine
Location Limits - condenser location must not exceed ANY of the following limits:
Maximum rise from the ice machine to the condenser is 35 physical feet
Maximum drop from the ice machine to the condenser is 15 physical feet
• Physical line set maximum length is 100 feet.
• Calculated line set length maximum is 150.
Calculation Formula:
• Drop = dd x 6.6 (dd = distance in feet)
• Rise = rd x 1.7 (rd = distance in feet)
• Horizontal Run = hd x 1 (hd = distance in feet)
• Calculation: Drop(s) + Rise(s) + Horizontal
Congurations that do NOT meet these requirements must receive prior written authorization from Scotsman to maintain warranty.
Do NOT:
• Route a line set that rises, then falls, then rises.
• Route a line set that falls, then rises, then falls.
Calculation Example 1:
The condenser is to be located 5 feet below the ice
machine and then 20 feet away horizontally.
5 feet x 6.6 = 33. 33 + 20 = 53. This location would be
acceptable
Calculation Example 2:
The condenser is to be located 35 feet above and then 100 feet away horizontally. 35 x 1.7 = 59.5.
59.5 +100 = 159.5. 159.5 is greater than the 150 maximum and is NOT acceptable.
• Run = dd+rd+hd = Calculated Line Length
rd Max 35 feet
22.87"
dd Max 15 feet
Operating a machine with an unacceptable
conguration is misuse and will void the warranty.
40.35"
hd
Remote Condenser located
above ice machine.
Condenser Distance &
Location Schematic
17.15"
Remote Condenser located
below ice machine.
Page 10
Page 12
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522
D Series Air, Water or Remote User Manual For The Installer: Remote Condenser
Locate the condenser as near as possible to the
interior location of the ice machine. Allow it plenty of
space for air and cleaning: keep it a minimum of two
feet away from a wall or other rooftop unit.
Note: The location of the condenser relative to the ice machine is LIMITED by the specication on the prior page.
Roof penetration. In many cases a roong contractor
will need to make and seal the hole in the roof for the
line sets. The suggested hole diameter is 2 inches.
Meet all applicable building codes.
Roof Attachment
Install and attach the remote condenser to the roof of the building, using the methods and practices of construction that conform to the local building codes,
including having a roong contractor secure the
condenser to the roof
Power Supply from
Ice Machine
Remote Condenser
Pre-Charged Refrigeration
Tubing
To Remote Condenser
Refrigeration Quick
Connects
Page 11
Page 13
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522
D Series Air, Water or Remote User Manual Precharged Line Routing - Remote Only
Do not connect the precharged tubing until all routing
and forming of the tubing is complete. See the Coupling Instructions for nal connections.
1. Each set of pre-charged tubing lines contains
a 3/8” diameter liquid line, and a 1/2” diameter discharge line. Both ends of each line have quick connect couplings.
Note: The openings in the building ceiling or wall, listed in the next step, are the minimum sizes recommended for passing the refrigerant lines
through.
2. Have the roong contractor cut a minimum hole
for the refrigerant lines of 2”. Check local codes,
a separate hole may be required for the electrical
power supply to the condenser.
Caution: Do NOT kink the refrigerant tubing while
routing it.
3. Route the refrigerant tubes thru the roof opening. Follow straight line routing whenever possible.
4. Excess tubing may EITHER be coiled up INSIDE
the building OR cut out prior to connection to the
ice maker and condenser.
If the excess tubing is cut out, after re-brazing the
tubing must be evacuated prior to connection to the ice maker or condenser.
If the excess tubing is to be coiled, spiral it
horizontally to avoid excess trapping in the lines.
5. Have the roong contractor seal the holes in the
roof per local codes
Potable Water
Supply
Condensate Drain
To Remote
Fan Motor
Condenser
Power Supply to Condenser
Pre-Charged Tubing Line Set
Page 12
Page 14
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522
D Series Air, Water or Remote User Manual Coupling Instructions - Remote Only
The couplings on the ends of the pre-charged line
sets are self-sealing when installed properly.
Follow these instructions carefully.
These steps must be performed by an EPA Certied Type II or higher technician.
Initial Connections
1. Remove the protector caps and plugs. Wipe the
seats and threaded surfaces with a clean cloth to
remove any possible foreign matter.
2. Lubricate the inside of the couplings, especially the O-rings, with refrigerant oil. Oil packets are supplied with Scotsman line sets.
3. Position the ttings on the correct connections on the condenser and ice machine.
Final Connections:
4. Tighten the couplings together by hand until it is certain that the threads are properly engaged.
6. Continue tightening the swivel nut until it bottoms out or a very denite increase in resistance is felt (no threads should be showing).
Critical Step!!!!!
7. Mark a line on the coupling nut and unit panel.
Then tighten the coupling nut an additional one-
quarter turn. The line will show the amount that the nut turns. Do NOT over tighten.
5. Use two wrenches tighten the coupling until it bottoms out or a denite increase in resistance is felt. It is important that ONLY the nut on the pre-
charged tube be turned, or the diaphragms will
be torn out by the piercing knives and they will be loose in the refrigeration system.
Note: As the couplings are tightened, the diaphragms in the quick connect couplings will begin to be
pierced. As that happens, there will be some resistance to tightening the swivel nut.
Page 13
8. After all connections have been made, and after the receiver outlet valve has been opened (do not open yet), check the couplings for leaks.
Page 15
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522
To Remote Condenser
D Series Air, Water or Remote User Manual Water - Remote Models
The water supply for ice making must be cold, potable
water. There is a single 3 8” male are potable water connection on the back panel.
Backow
The design of the oat valve and reservoir prevents potable water backow by means of a 1" air gap between the reservoir's maximum water level and the oat valve water inlet orice.
Drain
There is one ¾” FPT condensate drain tting at the back of the cabinet.
Attach Tubing
1. Connect the potable water supply to the potable water tting, 3 / 8” OD copper tubing or the equivalent is recommended.
2. Change the cartridge on the existing water lter (if any present).
Do not Tee ice machine drains into the drain tube
from the ice storage bin or dispenser. Back ups
could contaminate and / or melt the ice in the bin or
dispenser. Be sure to vent the bin drain.
Follow all local and national codes for tubing, traps
and air gaps.
3. Connect the drain tube to the condensate drain tting. Use rigid tubing.
4. Vent the drain tubing
between the ice machine
and the building drain.
Potable Water
Connection
Drain Vent
Condensate Drain
Page 14
Page 16
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522
D Series Air, Water or Remote User Manual Final Check List
After connections:
1. Wash out the bin. If desired, the interior of the bin could be sanitized.
2. Locate the ice scoop (if supplied) and have it available for use when needed.
3. Remote only: Switch on the electrical power to warm up the compressor. Do not start the machine for 4 hours.
Final Check List:
1. Is the unit located indoors in a controlled environment?
2. Is the unit located where it can receive adequate cooling air?
3. Has the correct electrical power been supplied to the machine?
4. Have all the water supply connections been made?
5. Have all the drain connections been made?
6. Has the unit been leveled?
7. Have all unpacking materials and tape been removed?
8. Has the protective covering on the exterior panels been removed?
9. Is the water pressure adequate?
10. Have the drain connections been checked for leaks?
11. Has the bin interior been wiped clean or sanitized?
12. Have any water lter cartridges been replaced?
Caution: Do not place anything on top of the ice
machine, including the ice scoop. Debris and moisture from objects on top of the machine can work their way into the cabinet and cause serious damage. Damage caused by foreign material is not covered by warranty.
There are four indicator lights at the front of the
machine that provide information on the condition
of the machine: Power, Status, Water, De-scale &
Sanitize.
Power
Note: If the De-Scale & Sanitize light is ON, following the cleaning process will clear the light for another
cleaning time internal.
Two button switches are at the front – On and Off. To
switch the machine OFF, push and release the Off
button. The machine will shut off at the end of the next cycle. To switch the machine ON, push and release the On button. The machine will go through a start up process and then resume ice making.
This user accessible panel provides important
operational information and duplicates the lights and
switches on the controller. It also allows access to the On and Off buttons that operate the ice machine.
Sometimes access to the switches should be limited
to prevent unauthorized operation. For that purpose a xed panel is shipped in the hardware package. The xed panel cannot be opened.
No Water
Status
Lower Light and Switch Panel
Time to Clean
On
Off
13. Have all required kits and adapters been properly installed?
Control and Machine Operation
Once started, the ice machine will automatically make
ice until the bin or dispenser is full of ice. When ice level drops, the ice machine will resume making ice.
Page 15
To install the xed panel:
1. Remove the front panel and remove the bezel.
2. Spread the bezel frame open and remove original door, insert xed panel into bezel. Be sure it is in the closed position.
3. Return bezel to panel and install panel on unit.
Page 17
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522
D Series Air, Water or Remote User Manual Initial Start Up and Maintenance
1. Turn the water supply on. Remote models also open the liquid line valve.
2. Switch the electrical power on. Conrm voltage is correct for the model.
3. Push and release the On button. The machine will start in about two minutes.
4. Soon after starting, air cooled models will begin
to blow warm air out the back of the cabinet and water cooled models will drain warm water from
the condenser drain tube. Remote models will be discharging warm air from the remote condenser.
After about 5 minutes, ice will begin to drop into
the bin or dispenser.
5. Check the machine for unusual rattles. Tighten
any loose screws, be sure no wires are rubbing
moving parts. Check for tubes that rub. Remote
models check quick connects for leaks, retighten
as needed.
6. Fill out the warranty registration form and either le it on line or mail it.
7. Notify the user of the maintenance requirements and whom to call for service.
Maintenance
This ice machine needs ve types of maintenance:
Sanitizing: Every time the scale is removed or as often as needed to maintain a sanitary unit.
Sensor Cleaning: Every time the scale is removed.
Top bearing check: At least twice a year or every time
the scale is removed.
Maintenance: Air lters
1. Pull air lter(s) from panel.
2. Wash the dust and grease off the lter(s).
3. Return it(them) to their original position(s).
Do not operate the machine without the lter in place except during cleaning.
Maintenance: Air cooled condenser
If the machine has been operated without a lter the air cooled condenser ns will need to be cleaned.
They are located under the fan blades. The services
of a refrigeration technician will be required to clean
the condenser.
Maintenance: Remote air cooled condenser
The condenser ns will occasionally need to be cleaned of leaves, grease or other dirt. Check the coil every time the ice machine is cleaned.
Air cooled and remote models need their air lters or condenser coils cleaned regularly.
All models need scale removed from the water system.
All models require regular sanitization.
All models require sensor cleaning.
All models require a top bearing check.
Maintenance Frequency:
Air lters: At least twice a year, but in dusty or greasy air, monthly.
Scale removal. At least twice a year, in some water conditions it might be every 3 months. The yellow De-
Scale & Sanitize light will switch on after a set period
of time as a reminder. The default time period is 6 months of power up time.
Page 16
Maintenance: Exterior Panels
The front and side panels are durable stainless steel.
Fingerprints, dust and grease will require cleaning with a good quality stainless steel cleaner
Note: If using a sanitizer or a cleaner that contains chlorine on the panels, after use be sure to wash the
panels with clean water to remove chlorine residue.
Maintenance: Water lters
If the machine has been connected to water lters,
check the cartridges for the date they were replaced
or for the pressure on the gauge. Change cartridges if they’ve been installed more than 6 months or if the pressure drops too much during ice making.
Page 18
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522
D Series Air, Water or Remote User Manual Maintenance: Scale Removal and Sanitation
Note: Following this procedure will reset the de-scale
and sanitize light.
1. Remove front panel.
2. Push and release the Off button.
3. Remove ice from bin or dispenser.
4. Turn the water supply to the oat valve OFF.
5. Drain the water and evaporator by disconnecting
the leg of the hose connected to the water sensor
and draining it into the bin. Return the hose to its original position.
6. Remove the water reservoir cover.
Drain Water
7. Mix a solution of 8 ounces of Scotsman Clear One Scale Remover and 3 quarts of 95-115 degree F. potable water.
Ice machine scale remover contains acids. Acids can cause burns.
If concentrated cleaner comes in contact with
skin, ush with water. if
swallowed, do NOT induce
vomiting. Give large amounts of water or milk. Call Physician immediately. Keep out of the reach of children.
8. Pour the scale remover solution into the reservoir. Use a small cup for pouring.
9. Push and release the Clean button: the auger drive motor and light are on, C is displayed and the De-scale light blinks. After 20 minutes the compressor will start.
10. Operate the machine and pour the scale remover into the reservoir until it is all gone. Keep the reservoir full. When all the scale remover solution has been used, turn the water supply back on.
After 20 minutes of ice making the compressor
and auger motor will shut off.
11. Turn the water supply to the ice machine OFF
Discard or melt all ice made during the previous step.
13. To sanitize the water system, mix a locally approved sanitizing solution. An example of a
sanitizing solution is mixing one ounce of liquid household bleach and two gallons of 95 – 115
degree F. water.
14. Pour the sanitizing solution into the reservoir.
15. Push and release the On button.
16. Switch the water supply to the ice machine on.
17. Operate the machine for 20 minutes.
18. Push and release the Off button.
19. Wash the reservoir cover in the remaining sanitizing solution.
20. Return the reservoir cover to its normal position.
21. Melt or discard all ice made during the sanitizing process.
22. Wash the inside of the ice storage bin with the sanitizing solution.
23. Push and release the On button.
24. Return the front panel to its original position and
secure with the original screws
12. Drain the water reservoir and evaporator by
disconnecting the leg of the hose connected to the water sensor and draining it into the bin or a
bucket. Return the hose to its original position.
Page 17
Page 19
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522
D Series Air, Water or Remote User Manual Maintenance: Check Top Bearing
This task should only be done by a qualied service
technician
The bearing in the breaker should be checked at least
two times per year.
Check the bearing by:
1. Removing the bail clamp and ice chute cover
Bail Clamp
Breaker
Cover
2. Unscrewing the ice sweep
3. Removing the water shed & unscrewing the breaker cover (left hand threads).
Inspect the top of the bearing. When new the grease is white, over time some gray will appear over the rollers, that is normal. Add grease to replace the gray grease or if gaps between rollers are visible. If grease is watery, all gray or rust is visible, have the bearing replaced. See the next page for more information.
Note: When checking the top bearing, always inspect
the drip pan for water seal leaks. If water is present in the drip pan, service the water seal and check the gear reducer's lubricant. See the next page.
Page 18
Page 20
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522
D Series Air, Water or Remote User Manual Bearing Service
This task should only be done by a qualied service
technician
If the grease is uniformly white, no further action is
needed. If very gray, rusty, wet or has any embedded metal, have the bearing replaced.
Grease
Drip Pan
If the bearing only needs grease, or to conrm the quality of the grease low in the bearing, inject grease
into the lower part of the bearing using Scotsman grease needle pn 02-3559-01 and Scotsman bearing
grease cartridge, pn A36808-001. Be sure to inject grease evenly and thoroughly.
Needle, part number 02-3559-01
Change De-Scale Notication Interval
This feature is accessible only from standby
(Status Light Off).
1. Press and hold Clean button for 3 seconds.
This starts the Time to Clean Adjustment State and displays the current time to clean setting.
2. Press the clean button repeatedly to cycle through
the 4 possible settings:
• 1 year
• 0 (disabled)
• 4 months
• 6 months(default)
3. Push Off to conrm the selection.
Page 19
Page 21
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522
D Series Air, Water or Remote User Manual Maintenance: Sensors
The control that senses bin full and empty is a photo­electric eye, therefore it must be kept clean so it
can “see”. At least twice a year, remove the ice level
sensors from the base of the ice chute, and wipe the
inside clean, as illustrated.
1. Remove front panel.
The ice machine senses water by a probe located
near the water reservoir. At least twice a year, the probe should be wiped clean of mineral build-up.
Probes
1. Shut off the water supply.
2. Pull photo eye holders forward to release them.
3. Wipe clean as needed. Do not scratch the photo­eye portion.
4. Return the eye holders to their normal positions and return the front panel to its original position.
Note: Eye holders must be mounted properly. They
snap into a centered position and are properly located when the wires are routed to the back and the left eye
is the one with 2 wires at the connector.
2. Remove front panel.
3. Remove the hose from the water sensor, use a hose clamp pliers for this.
4. Loosen mounting screw and release the water sensor from the frame of the unit.
5. Wipe probes clean,
Page 20
Page 22
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522
D Series Air, Water or Remote User Manual Options
Vari-Smart
Optional adjustable ice level control (KVS). When this option is present there is an adjustment post and
an additional indicator light to the right of the four
indicator lights mentioned earlier.
The ultrasonic ice level control allows the user to
control the point that the ice machine will stop making
ice before the bin or dispenser is full.
Reasons for this include:
Seasonal changes in ice used
Use of adjustable ice level control
There are several positions the ice level can be set to, including Off or Max (knob and label indicators lined up), where it lls the bin until the standard bin control shuts the machine off. See the kit’s instructions for complete details.
Planning to sanitize the bin
• Faster turnover for fresher ice
Certain dispenser applications where maximum ice level is not desired
Rotate the adjustment post to the desired ice level.
The machine will ll up to that level and when it shuts off the indicator light next to the adjustment post will be On.
Note: The maximum ll position is when the arrow on the knob points to the arrow on the label.
Dispenser applications - Nugget ice only:
Set the adjustment knob arrow to the Norm area between the green arrows. Select either the rst or second positions as a starting point and adjust as needed.
Page 21
Page 23
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522
D Series Air, Water or Remote User Manual What to do before calling for service
Normal Operation:
Ice
The machine will make either aked or nugget ice, depending upon the model. The ice will be produced continuously until the bin is full. It is normal for a few drops of water to occasionally fall with the ice.
Heat
On remote models most heat is exhausted at the remote condenser, the ice machine should not
generate signicant heat. Water cooled models
also put most of the heat from ice making into the
discharge water. Air cooled models will generate heat, and it will be discharged into the room.
Noise
The ice machine will make noise when it is in ice
making mode. The compressor and gear reducer will produce sound. Air cooled models will add fan noise. Some ice making noise could also occur. These noises are all normal for this machine.
Check the following:
1. Has the water supply to the ice machine or building been shut off? If yes, the ice machine will
automatically restart within minutes after water begins
to ow to it.
2. Has power been shut off to the ice machine? If yes,
the ice machine will automatically restart when power
is restored.
3. Has someone shut the power off to the remote condenser while the ice machine still had power? If yes, the ice machine may need to be manually reset.
To Manually Reset the machine.
Open the swtich door
• Push and release the Off button.
• Push and release the On button.
Open Switch Door
Reasons the machine might shut itself off:
• Lack of water.
• Does not make ice
• Auger motor overload
• High discharge pressure.
• Low refrigeration system pressure.
Indicator Lights & Their Meanings
Power Status Water De-Scale &
Steady Green Normal Normal - - Blinking Green Self Test Failure Switching on or
off. When Smart-
Board used, machine attention
recommended.
Blinking Red - Diagnostic shut
down
Yellow - - - Time to descale and
Blinking Yellow - - - In Cleaning Mode
Light Off No power Switched to Off Normal Normal
To Shut the Machine Off:
Push and hold the Off button for 3 seconds or until the
machine stops.
Sanitize
- -
Lack of water -
sanitize
Page 22
Page 24
SCOTSMAN ICE SYSTEMS
775 Corporate Woods Parkway
Vernon Hills, IL 60061
800-726-8762
www.scotsman-ice.com
17-3533-01
Loading...