Scotsman MV 306, MV 456, MV 426, MV 806, MV 1006 Service Manual

...
Page 1
Page 1
Page 1
SCOTSMAN EUROPE - FRIMONT SPA Via Puccini, 22 - 20010 Pogliano M.se - Milano - Italy Tel. +39-02-93960.1 (Aut. Sel.)- Telefax +39-02-93550500 Direct Line to Service & Parts: Phone +39-02-93960350 - Fax +39-02-93540449 Website: www.scotsman-ice.com E-Mail: scotsman.europe@frimont.it
ISO 9001 - Cert. n. 0080
SERVICE MANUAL
MV 306 MV 426 MV 456 MV 606 MV 806
MV 1006
Electronic
modular cubers
MS 1000.77 - REV. 02/2010
Page 2
Page 2
Page 2
TABLE OF CONTENTS
Table of contents 2 Specifications 3-4-5-6-7-8-9-10-11-12-13-14
FOR THE INSTALLER
Introduction 15 Storage bin 15 Standard legs 15 Important operating requirements 15 Select location 16 Storage bin 16 Ice machine 16 Final check list 17
FOR THE PLUMBER Conform to all applicable codes
Water inlet 16 Drains 17
For the electrician
Electrical connections 17
START-UP
Start-up cycle 18 Freezing cycle 18 Harvest cycle 18
OPERATION
Refrigeration during freeze 20 Water system during freeze 21 Refrigeration system during harvest 22 Water system during harvest 22 Control sequence 22 Alarm conditions 23 PC Board set up 24
SERVICE SPECIFICATIONS
Component 25 Operating characteristics 25
COMPONENT DESCRIPTION
Component description 26
WIRING DIAGRAM
MV 306 air/water cooled 30 MV 426-456-606-806 air/water cooled 31 MV 1006 air/water cooled 32
SERVICE DIAGNOSIS
Service diagnosis 33
MAINTENANCE & CLEANING INSTRUCTION
Icemaker 34 Ice storage bin 34 Cabinet exterior 34 Cleaning (Icemaker) 34-35
Page 3
Page 3
Page 3
SPECIFICATIONS
MODULAR CUBER MV 306
NOTE. To keep your Modular cuber performing at its maximum capacity, it is necessary to perform
periodic maintenance as outlined on the last pages of this manual.
ice making capacity
ICE PRODUCED PER 24 HRS
Kg.
32
°C
15
10
AIR COOLED MODELS
WATER TEMPERATURE
AMBIENT TEMPERA TURE
°C
10
21
32
38
WATER COOLED MODELS
21
200
180
160
140
120
100
80
60
ICE PRODUCED PER 24 HRS
Kg.
32
°C
10
WATER TEMPERATURE
AMBIENT TEMPERA TURE
°C
10
21
32 38
160
150
140
130
120
110
100
90
27
15
2127
Page 4
Page 4
Page 4
SPECIFICATIONS (CONT'D)
Accessoires Dimensions:
HEIGHT 575 mm. (22" 1/2) WIDTH 560 mm. (22") DEPTH 614 mm. (24" 3/16) WEIGHT 53 Kgs.
Model Cond. unit Finish Comp. HP
MV 306 - MACHINE SPECIFICATIONS
Water req.
lt/24 HR
Model
Basic
electr.
amps
Start
amps
watts
Electric power cons.
Kwhx24 HR.
N. of wires
Amps
Fuse
220-240/50/1
MV 306 - AS MV 306 - WS
3x1,5 mm
2
10
Cubes per harvest: 168 Full - 336 Half * With water at 15°C
Stainless Steel 3/4
3,8 3,3
20
780 610
17.0
13.5
MV 306 - AS Air 200* MV 306 - WS Water 2000*
560 mm (22”)
614 mm (24 3/16”)
575 mm (22 10/16”)
263.4 mm (10
6/16")
508.5 mm (20”)
263.4 mm (10 6/16”)
43.5 mm (1 1/16”)
75.2 mm (2 15/16”)
ARE A
178 mm (7”)
330mm(13”)
21 mm(13/16”)
25 mm(1”)
389mm(15 5/16”)
ICE DROP
Page 5
Page 5
Page 5
SPECIFICATIONS
MODULAR CUBER MV 426
NOTE. To keep your Modular cuber performing at its maximum capacity, it is necessary to perform
periodic maintenance as outlined on the last pages of this manual.
ice making capacity
ICE PRODUCED PER 24 HRS
Kg.
32
°C
10
AIR COOLED MODELS
WATER TEMPERATURE
AMBIENT TEMPERA TURE
°C
10
21
32
38
WATER COOLED MODELS
240
220
200
180
160
140
120
100
ICE PRODUCED PER 24 HRS
Kg.
32
°C
10
WATER TEMPERATURE
°C
10 21 32
38
260
240
220
200
180
160
140
120
15
2127
15
2127
AMBIENT TEMPERA TURE
Page 6
Page 6
Page 6
MV 426 - AS Air 300* MV 426 - WS Water 2400*
SPECIFICATIONS (CONT'D)
Accessoires Dimensions:
HEIGHT 660 mm. (26" ) WIDTH 560 mm. (22") DEPTH 614 mm. (24" 3/16) WEIGHT 68 Kgs.
Model Cond. unit Finish Comp. HP
MV 426 - MACHINE SPECIFICATIONS
Water req.
lt/24 HR
Model
Basic
electr.
amps
Start amps
watts
Electric power cons.
Kwhx24 HR.
N. of wires
Amps Fuse
220-240/50/1
MV 426 - AS MV 426 - WS
3x1,5 mm
2
16
Cubes per harvest: 204 Full - 408 Half * With water at 15°C
Stainless Steel 7/8
4,8 4,3
29
1050 850
23.0
19.5
598.5 mm (23 9/16”)
398.5 mm (15 1/16”)
43.5 mm (1 11/16”)
75.2 mm (2 15/16”)
560 mm (22”)
614 mm (24 3/16”)
660 mm (26”)
AREA
330mm (13)
178 mm (7”)
21 mm (13/16”)
25 mm (1”)
389 mm (15 5/16”)
Page 7
Page 7
Page 7
SPECIFICATIONS
MODULAR CUBER MV 456
NOTE. To keep your Modular cuber performing at its maximum capacity, it is necessary to perform
periodic maintenance as outlined on the last pages of this manual.
ice making capacity
ICE PRODUCED PER 24 HRS
Kg.
32
°C
15
10
AIR COOLED MODELS
WATER TEMPERATURE
AMBIENT TEMPERA TURE
°C 10
21
32
38
WATER COOLED MODELS
21
240
220
200
180
160
140
120
ICE PRODUCED PER 24 HRS
Kg.
32
°C
15
10
AMBIENT TEMPERA TURE
°C
10 21
32 38
21
255
235
215
195
175
155
135
WATER TEMPERATURE
Page 8
Page 8
Page 8
SPECIFICATIONS (CONT'D)
Model Cond. unit Finish Comp. HP
MV 456 - MACHINE SPECIFICATIONS
Water req.
lt/24 HR
Model
Basic electr.
amps
Start
amps
watts
Electric power cons.
Kwhx24 HR.
N. of wires
Amps
Fuse
220-240/50/1
MV 456 - AS MV 456 - WS
3x1,5 mm
2
16
Cubes per harvest: 234 Full - 468 Half * With water at 15°C
Stainless Steel 7/8
MV 456 - AS Air 410* MV 456 - WS Water 2400*
4.5
4.0
29
1000 850
23
19.5
Dimensions: HEIGHT 575 mm. (22" 1/2) WIDTH 760 mm. (30") DEPTH 620 mm. (24" 1/2) WEIGHT 77 Kgs.
Page 9
Page 9
Page 9
SPECIFICATIONS
MODULAR CUBER MV 606
NOTE. To keep your Modular cuber performing at its maximum capacity, it is necessary to perform
periodic maintenance as outlined on the last pages of this manual.
ice making capacity
Kg.
32
°C
15
10
°C
10
21
32
38
21
335
315
295
275
255
235
215
195
175
Kg.
32
°C
15
10
°C
10
21
32 38
21
335
315
295
275
255
235
215
ICE PRODUCED PER 24 HRS
AIR COOLED MODELS
WATER TEMPERATURE
AMBIENT TEMPERA TURE
WATER COOLED MODELS
ICE PRODUCED PER 24 HRS
AMBIENT TEMPERA TURE
WATER TEMPERATURE
Page 10
Page 10
Page 10
MV 606 - AS Air 440* MV 606 - WS Water 2750*
SPECIFICATIONS (CONT'D)
Model Cond. unit Finish Comp. HP
MV 606 - MACHINE SPECIFICATIONS
Water req.
lt/24 HR
Model
Basic
electr.
amps
Start
amps
watts
Electric power cons.
Kwhx24 HR.
N. of wires
Amps
Fuse
220-240/50/1
MV 606 - AS MV 606 - WS
3x1,5 mm
2
16
Cubes per harvest: 234 Full - 468 Half * With water at 15°C
Stainless Steel 1 3/8
6.2
5.2
32
1300 1050
28 23
Dimensions: HEIGHT 575 mm. (22" 1/2) WIDTH 760 mm. (30") DEPTH 620 mm. (24" 1/2) WEIGHT 77 Kgs.
Page 11
Page 11
Page 11
SPECIFICATIONS
MODULAR CUBER MV 806
NOTE. To keep your Modular cuber performing at its maximum capacity, it is necessary to perform
periodic maintenance as outlined on the last pages of this manual.
ice making capacity
Kg.
32
°C
15
10
°C
10
21
32
38
21
445
425
405
385
365
345
325
305
285
265
245
225
Kg.
32
°C
15
10
°C
10
21
32
38
21
390
370
350
330
310
290
270
ICE PRODUCED PER 24 HRS
AIR COOLED MODELS
WATER TEMPERATURE
AMBIENT TEMPERA TURE
WATER COOLED MODELS
ICE PRODUCED PER 24 HRS
AMBIENT TEMPERA TURE
WATER TEMPERATURE
Page 12
Page 12
Page 12
MV 806 - AS Air 580* MV 806 - WS Water 3900*
SPECIFICATIONS (CONT'D)
Model Cond. unit Finish Comp. HP
MV 806 - MACHINE SPECIFICATIONS
Water req.
lt/24 HR
Model
Basic
electr.
amps
Start
amps
watts
Electric power cons.
Kwhx24 HR.
N. of wires
Amps
Fuse
MV 806 - AS MV 806 - WS
3x1,5 mm
2
16
Cubes per harvest: 342 Full - 684 Half * With water at 15°C
Stainless Steel 1 5/8
31
1850 1450
40
33.4
Dimensions: HEIGHT 725 mm. (28" 1/2) WIDTH 760 mm. (30") DEPTH 620 mm. (24" 1/2) WEIGHT 97 Kgs.
220-240/50/1
9.0
8.0
Page 13
Page 13
Page 13
SPECIFICATIONS
MODULAR CUBER MV 1006
NOTE. To keep your Modular cuber performing at its maximum capacity, it is necessary to perform
periodic maintenance as outlined on the last pages of this manual.
ice making capacity
Kg.
32
°C
15
10
°C
10
21
32
38
21
475
455
435
415
395
375
355
335
315
295
275
Kg.
32
°C
15
10
°C
10 21
32
38
21
425
405
385
365
345
325
305
ICE PRODUCED PER 24 HRS
AIR COOLED MODELS
WATER TEMPERATURE
AMBIENT TEMPERA TURE
WATER COOLED MODELS
ICE PRODUCED PER 24 HRS
AMBIENT TEMPERA TURE
WATER TEMPERATURE
Page 14
Page 14
Page 14
MV 1006 - AS Air 600* MV 1006 - WS Water 3800*
SPECIFICATIONS (CONT'D)
Model Cond. unit Finish Comp. HP
MV 1006 - MACHINE SPECIFICATIONS
Water req.
lt/24 HR
Model
Basic
electr.
amps
Start
amps
watts
Electric power cons.
Kwhx24 HR.
N. of wires
Amps
Fuse
Cubes per harvest: 342 Full - 684 Half * With water at 15°C
Stainless Steel 2
Dimensions: HEIGHT 725 mm. (28" 1/2) WIDTH 760 mm. (30") DEPTH 620 mm. (24" 1/2) WEIGHT 104 Kgs.
MV 1006 - AS MV 1006 - WS
3x2,5 mm
2
16
10,5
-
33
-
1900 1600
38,5,0
-
MV 1006 - AS MV 1006 - WS
5x1,5 mm
2
10
3,5 3,3
24
1900 1600
41,3,0
37 ,0
230/50/1
380-400/50/3
Page 15
Page 15
Page 15
FOR THE INSTALLER
INTRODUCTION
These instructions provide the specifications and the step-by-step procedures for the installation, start up and operation for the SCOTSMAN Model MV 306-426-456-606-1006 Modular Cubers. The Models MV 306-426-456-606-806-1006 Modular Cubers are quality designed, engineering and constructed, and are thoroughly tested icemaking systems, providing the utmost in flexibility to fit the needs of a particular user.
INSTALLATION NOTE: Allow 15 cm. minimum space at sides and back for ventilation and utility connections.
STORAGE BIN
The MV 306-426 stack on top of Scotsman bin model B 193; the MV 456-606-806-1006 stack onto SCOTSMAN bin model B 393.
Refrigerant R 404 A
Charge per nameplate rating.
STANDARD LEGS: Furnished with storage bin. Four legs screw into mounting sockets on cabinet base. Provide 18.5 cm. (7’’) minimum height including adjustable leveling foot. Optional Kit Casters for B 193/393 (KRB 550) are available on request.
IMPORTANT OPERATING REQUIREMENTS
MINIMUM MAXIMUM
Air Temperature 10°C (50°F) 40°C (100°F) Water Temperature 5°C (40°F) 35°C (90°F)0 Water Pressures 1 bar gauge 5 bar gauge Electrical Voltage
Variations Voltage rating specified on nameplate -10% +10%
Extended periods of operation exceeding these limitations constitues misuse under the terms of Manufacturer’s Limited Warranty, resulting in a loss of warranty coverage.
Page 16
Page 16
Page 16
AIR BAFFLE
Install on the back side of the machine the air baffle as per instruction provided with it.
FOR THE PLUMBER
CONFORM TO ALL APPLICABLE CODES WATER INLET
AIR-COOLED MODELS: The recommended water supply is cold water connected to the - 3/4'’ gas - male fitting at the back of the cabinet. Install a hand valve near the machine to control the water supply.
1) Switch
2) Plug receptacle
3) Electrical plug
4) Water inlet
5) Shut-off valve
6) Water filter
7) Water outlet line
8) Bin water outlet line
9) Open vented water drain
10) Water outlet from the condenser: water cooled
version only.
SELECT LOCATION
The first step in installing the equipment is to select the location. The purchaser of the unit will have a desired spot in mind, check out that spot to insure that it is:
- indoors, in an environment that does not exceed the air and water temperature limitations for the equipment.
- that the necessary utilities are available including the correct voltage electrical power.
- that there be space around the installed machine for service, 15 cm. minimum left, right, and rear for air-cooled models.
STORAGE BIN
The Scotsman bins for these units are the B 193 and B 393. Other bins may be available with bin tops to vary the storage capacity. Lay the bin on its back, using cardboard from the carton to support it, screw in the legs. Stand the bin upright, and correct any possible small tears in the machine mounting gasket with food grade silicone sealant.
ICE MACHINE
The use of a mechanical lift is recommended for lifting the uncrated icemaker onto the bin. Remove front, top and sides panels. Place the unit directly onto the bin, align it with the back of the bin. Locate the hardware package, take out two mounting screws, and use them to secure the Icemaker to the two sides of the bin. See illustration below. Remove all shipping material as well as the masking tapes from the ice deflector/evaporator cover.
Remove first the ice deflector/evaporator cover then the masking tape from the ice thickness sensor.
Page 17
Page 17
Page 17
NOTE: All SCOTSMAN Cubers require a neutral wire and a solid earth ground wire to prevent possible severe Electrical Shock Injury to individuals or extensive damage to equipments.
FINAL CHECK LIST
1. Is the cabinet/bin level?
2. Is the cuber in a location where ambient temperatures are a minimum of 10°C (50-de­grees F.) all year around and to not exceed a maximum of 40°C. (100°F.).
3. Is there at least a 15 cm. clearance behind and around the cabinet for all connections and for proper air circulation?
4. Have all electrical and piping connections been made?
5. Has the electrical power supply wiring been properly connected and the voltage tested and checked against the nameplate rating? Has the unit properly grounded.
6. Is the water supply line shutoff valve installed and opened and has the inlet water supply pressure been checked to insure a minimum of 1 bar without exceeding a maximum of 5 bar.
7. Have the compressor holddown bolts been checked to be sure the compressor is snug on the mounting pads.
8. Check all refrigerant lines and conduit lines to gard against vibration and possible failure.
9. Has the cuber and the bin been wiped clean with clean damp cloths?
10. Has the owner/user been given the User Manual and instructed on how to operate the icemaker and the importance of periodic maintenance?
11. Has the owner/user been given the name and telephone number of the Authorized SCOTSMAN Distributor or Service Agency serving him?
12. Has the Manufacturer’s Registration Card been properly filled out? Check for correct Model and Serial Numbers from nameplate, then mail the completed card to the Manufactured.
When choosing the water supply for the MV Cuber, consideration should be given to:
A. Length of run. B. Water clarity and purity. C. Adequate water supply pressures. Since water is the most important single ingredient
in producing ice you cannot over emphasize the three items listed above. Low water pressure, below 1 bar may cause malfunction, of the icemaker unit. Water containing excessive minerals will tend to produce cloudy colored ice cubes, plus scale build-up on parts in the water system. Heavily chlorinated water can be controlled using charcoal or carbon filters.
DRAINS
AIR-COOLED MODELS: There is one 20 mm. dia sump drain fitting at the back of the cabinet. Insulations in high humidity areas is recom­mended. The ideal drain receptacle would be a trapped and vented floor drain. WATER-COOLED MODELS: Besides the above drain, a separate condenser drain must be run. Connect it to the - 3/4'’ gas - condenser drain connection at the back of the cabinet. STORAGE BIN: A separate gravity type drain needs to be run, similar to the air-cooled sump drain. Insulation of this drain line is recom-
mended.
FOR THE ELECTRICIAN
ELECTRICAL CONNECTIONS
The unit come equipped with an electrical cord for power supply. The lead wires must be connected to an electrical plug that corresponds to the local electrical codes and requirements or to a separate two poles disconnect box with opening to the contacts of about 3 millimeters. The disconnect box shoulds be placed close to the selected ice maker location to be easily and prompt reached. Undersized wiring or unproperly installed electrical circuit will result in major problems and malfunctions. Voltage variations shoud not exceed ten percent.
IMPORTANT - All plumbing and electrical connections must be made by licensed plumbers and electricians, this one must follow the electrical specifications printed on the ice maker nameplate.
Page 18
Page 18
Page 18
START-UP
START-UP CYCLE
1. Open the water tap/valve and switch ON the power on the electrical supply line.
2.
The models MV 306-426- 456 - 606-806 enter in
the Start Up
mode with the PC Board energized as
well
as the Green LED of the machine under power while the model MV 1006 enter in 90 minutes delay time controlled by a special Start-up Delay PC Board.
The Green LED of machine in operation is energized too, blinking fast for 40 seconds.
NOTE: The model MV 1006 is equipped
with a compressor crankcase heater and a Start up Delay PC Board set up at 90 minutes. During the first 90 minutes only the compressor crankcase heater is energized warning up the compressor.
3. During the Start Up cycle the components in operation are:
• Hot gas valve
• Water Drain Valve
• Water Pump
• Harvest assist solenoid (pusher).
FREEZING CYCLE
1. After the Start Up cycle the machine enters directly into the Freezing cycle with the following components energized:
• Water Inlet valve
• Compressor
• Fan motor (in continuous operation for the first 3 minutes).
2. The LED energized are:
• Machine under power
• Machine in operation (steady)
3. Water is coming into the water through the Water Inlet Solenoid Valve till the water reservoir if filled up to the maximum level controlled by a Water Level Sensor.
4. 30 seconds later, the Water Pump starts up.
5. After few minutes (3-5) from the start up of the freezing cycle, the Water Inlet Solenoid Val­ve is activated again for few seconds to re-fill the water reservoir up to the maximum level so to reduce any possibility of slush ice formation.
6. In the meantime the condenser sensor starts to transmit the current to the PC Board keeping in operation the Fan Motor in ON-OFF mode or continuously according to the condenser tempe­rature.
NOTE: Do not remove the evaporator deflector cover as it will cause the switching off of the machine at "STORAGE BIN FULL".
7. The machine remains in the freezing cycle with the ice that become thicker till the two metal plates of the Ice Thickness Sensor are covered by the water cascading through the front surface of the ice plate.
8. When the Power is transmitted back to the PC Board continuously through the metal plates of the Ice Thickness Sensor for more then 6", the machine enters in the Pre-Harvest or directly into the Harvest Cycle mode according to:
FAN MOTOR IN ON-OFF MODE DURING
THE PREVIOUS FREEZING CYCLE
RISE UP THE CUT IN TEMPERATURE OF THE CONDENSER SENSOR TO 38°C (FAN MOTOR OFF) AND EXTEND THE LENGTH OF FREEZING CYCLE BY 30" MORE THEN GO INTO HARVEST CYCLE
FAN MOTOR ALWAYS IN OPERATION
DURING THE PREVIOUS FREEZING CYCLE
GO STRAIGHT TO THE HARVEST CYCLE
9. First freezing time will range between 13 and 17 minutes. Longer time for temperature above 25°C and shorter time required when temperature are below 25°C. Average complete cycle time is about 15 min.
HARVEST CYCLE
1. During the harvest cycle the components in operation are:
• Hot Gas valve
• Harvest assist solenoid (pusher)
• Water Drain/Purge Valve
• Water Pump for the first 6" every cycle and for all harvest time every 6 cycles
• Compressor
POWER OPER.
BIN
FULL ALARM
ALARM
HI
PRESS.
RE-SET
Page 19
Page 19
Page 19
NOTE: This type of machine produce an "ICE PLATE" that breaks when falls down into the storage bin. Setting the ice thickness sensor in order to have single ice cubes may
cause malfunction of the machine.
6. Observe second and third cube harvest.
Check if size and shape combination is correct. In areas where extreme problem water conditions exist, filtering or purifyng equipment is recommended.
NOTE: If water used is too soft, "demineralized" the ice thickness sensor might not be able to sense the water on its reeds, there by it will not switch the unit on harvest cycle. A safety system built in the P.C. Board switches the unit on harvest cycle whenever the freezing period gets longer then 30 or 40 minutes.
NOTE: To assure a correct operation of the machine the water must have a minimum
electrical conductivity of 20 us.
7. Check operation of magnetic switch
controlling it by keeping open the bottom end of plastic deflector for more than 30 seconds. The machine must switch off at storage bin full. Release the plastic deflector. The machine should restart in the freezing cycle mode within few seconds going through a 3 minutes delay time.
8. Place again all cabinet panels and screws
previously removed.
9. Thoroughly explain to owner/user the significant
specifications of the ice maker start-up, reset and operation, going through the procedures in the operating instructions. Answer all questions about the ice maker by the owner and inform the owner himseft of the name and telephone number of the authorized service agency serving him.
and both
• Machine Under Power
• Machine in Operation
2. 30 seconds after the beginning of the Harvest Cycle, the Water Inlet Solenoid Valve is energized for 10 seconds only in order to have a short flush of fresh water into the sump while the Water Pump is still in operation.
3. The Fan Motor remains in OFF mode unless the Condenser Sensor probe rise up to more then 38°C (same set up as per end of freezing cycle).
4. When the ice plate is falling down from the evaporator, the magnetic switch is activated for a while providing the signal to the PC Board to restart a new freezing cycle.
5. Observe first ice cube harvest and check size of ice cubes; if an adjustment is required thread down or out the adjusting screw as shown on below illustration (ice bridge must be approx. 2-3 mm).
This screw position determines the distance between the sensor reeds and the egg-crate evaporator thus keeping the ice cube at a proper thickness.
Page 20
Page 20
Page 20
REFRIGERATION DURING FREEZE:
This ice machine employes either air or water as
a condensing media, the refrigeration system for
either one is a follows:
At the hermetic compressor, Refrigerant is
compressed into a high temperature, high
pressure gas.
The gas moves through the discharge line into
the condenser, air or water-cooled. If air-cooled,
the discharge pressure will change with the heat
load and the ambient air temperature.
If water-cooled, the discharge pressure is
controlled by the amount of water flowing through
the condenser - which is determined by the
water regulating valve.
After the gas is cooled in the condenser, giving
up much of its heat, the gas condenses into a
high pressure liquid. This liquid travels through
the liquid line to the metering device, a
thermostatic expansion valve.
The thermostatic expansion valve meters how
much liquid refrigerant is to be allowed into the
evaporator section of the refrigeration system.
This is determined by the temperature of the TXV sensing bulb, located on the suction line manifold, at the outlet of the evaporator. If the bulb senses a warm suction line, more refrigerant is allowed into the evaporator, (common at the beginning of the freeze cycle) and when the temperature begins to fall, less refrigerant is allowed through. This is why the suction side gauge pressure will decline throughout the freeze cycle. At the evaporator, the liquid refrigerant released from high pressure, boils off in the low pressure environment and absorbs heat, thus cooling the evaporator surface and anything near it, such as water. The low pressure refrigerant vapor then is forced through the heat exchanger where any excess liquid refrigerant boils-off, allowing only refrigerant vapor to enter the compressor suction tube, where it is recompressed into high pressure, high temperature gas again and the cycle repeats.
OPERATION
FREEZE CYCLE
REFRIGERATION SYSTEM SCHEMATIC
Page 21
Page 21
Page 21
FREEZE CYCLE
water tube and then cascades down the evaporator surface by gravity. As it flows accross the refrigerated evaporator, some of the water will be chilled enough to change form, turn to ice, and stay frozen onto the evaporator cells. Most of the water returns to the reservoir, to be sucked back into the pump, and repumped over the evaporator.
WATER SYSTEM
A combination of a solenoid water inlet valve with
a water level sensor is used to control the level of
the water into the reservoir/sump.
A pump, running continuously, after the first 30"
of freezing cycle, forces the water to the top of the
evaporator, where it is distributed through a
EBUTYARPSRETAW EVLAVEGRUP
RETAW
TELNI
EVLAV
PMUPRETAW
ROSNESLEVELRETAW
Page 22
Page 22
Page 22
HARVEST (DEFROST) CYCLE
REFRIGERATION SYSTEM SCHEMATIC
REFRIGERATION SYSTEM DURING HARVEST
The refrigeration system performs the harvest of
ice by use of a hot gas bypass valve. When the
time comes to de-ice the evaporators, the hot
gas valve is energized, and the high temperatu-
re, high pressure gas bypasses the condenser,
and is allowed directly into the evaporator. The
high pressure gas is cooled by the cold evaporator
so it condenses into a liquid, giving up its heat as
it does so. This heat warms the evaporator and
the ice frozen onto the evaporator surface melts,
releasing the frozen cubes. Ice then falls into the
storage bin pushed out by means of the harvest
assist solenoid.
The liquid refrigerant goes through the suction
line into the heat exchanger where it boils-off so
that only refrigerant vapor is drawn into the
suction tube of the compressor.
WATER SYSTEM
During the harvest cycle, the electric water
drain valve is energized thereby opening the
drain line.
Most of the water remained in the reservoir at the end of freezing cycle is pumped-out, to the waste, through the water solenoid and drain line during the first part of the defrost cycle eliminating any possible build-up and accumulation of minerals concentration and impurities in the water reservoir. When the released ice cubes drop into the bin, they open-up for a while the bottom end of plastic deflector. This deflector swinging motion is enough to reset the contact of the magnetic switch which - via electronic control board - moves back the unit to a new freezing cycle. The harvest cycle lasts about 1÷1.5 minutes.
CONTROL SEQUENCE
At the start of the freezing cycle, the contacts of the magnetic switch mechanically operated by the actuator plate of the deflector cover are closed, thereby - via electronic control board ­closing the circuit to the main contactor coil and
Page 23
Page 23
Page 23
consequently to the compressor and fan motors
and 30" later, to the water pump motors.
Then, as the ice thickness reaches the value that
corresponds to the full cube size, the film of water
that constantly cascades over the slab of ice
formed on the evaporator, arrives to establish a
contact between the two fingers (energised at
low voltage) of the ice sensor control, located on
the front upper right side of the evaporator. If the
contact between the two fingers of the ice sensor
remains established - by the film of water - for
more than 10 seconds, a small relay of the
electronic board, get energized, controlling -
simultaneously the hot gas valve, the water drain
valve and the harvest assist solenoid.
NOTE: in case of failure of ice level sensor, the P.C. Board turns - on automatically the unit into the defrost cycle when the freezing cycle reaches 30 or 40 minutes according to the operation of the fan motor during the freezing cycle.
At this point, the unit initiates the defrost cycle.
The hot gas circulating into the evaporator
serpentine causes a slight melting of ice cubes
which get released from their molds. In the mean
time the harvest assist solenoid is also energized
pushing out the ice plate.
Once entirely released the ice cubes drop
simultaneously into the ice storage bin below; by
doing so they move apart from the evaporator
bottom end the plastic deflector.
This plastic deflector has on its side a magnetic
switch that on account of the deflector swinging
motion, caused by the ice while dropping in the
bin, opens and closes their contacts.
This will, in turn, disactivate the relay contacts
that controls the hot gas, harvest assist solenoid
and water drain valve which get deenergized
allowing the unit to start a new freezing cycle.
When the ice bin is full of ice, the last batch of ice
cubes released from the evaporator accumulates
to keep the bottom end of the plastic deflector in
open position; with the magnetic switch contacts
open for longer than 30'’ the entire unit stops with
the glowing of the corresponding LED.
The machine will restart when the ice deflector will
be back in its normal vertical position provided
that 3' are elapsed from unit stop. If not the
machine will delay its restart till 3' are elapsed with
the blinking of the green LED.
ALARM CONDITIONS
Both the last two Red LED are ON STEADY: Condenser Sensor OUT OF ORDER.
Both the last two Red LED are BLINKING SLOW: WATER ERROR
Water level inside the water sump too low after 3' from the activation of the Water Inlet Valve.
Both the last two Red LED are BLINKING FAST:
RESET MODE: Charging water through the Water inlet Solenoid Valve after the tripping OFF on WATER ERROR
The fourth Red LED is ON STEADY: Harvest
Cycle longer then 3' 30" The fourth Red LED is BLINKING SLOW: TOO HI
CONDENSING TEMPERATURE. The condenser
sensor detected a temperature > 65°C The fourth Red LED is BLINKING FAST:
RESET MODE: Condenser Sensor < 50°C Fan motor in operation for 3' then back on Start Up Cycle Mode
The fifth Red LED is ON STEADY: TOO HI
DISCHARGE PRESSURE > 33 bar (460 PSI)
The fifth Red LED is BLINKING FAST:
RESET MODE: After pushing the Reset Button of the Pressure Control the fan motor starts up first for 3' then the machine enters on the Start Up Cycle Mode.
The PC Board is also checking the maximum time of the freezing cycle that changes according to the operation of the fan motor during the freezing cycle (room temperature):
• Fan motor in Max. freezing cycle length ON-OFF mode: equal to 30'
• Fan motor ON Max. freezing cycle length All the time: equal to 40'
Whenever the machine remains in the Freezing Cycle for the Maximum time (30 or 40 minutes), the PC Board moves the unit directly into the Harvest Cycle.
POWER OPER.
BIN
FULL ALARM
ALARM
HI
PRESS.
RE-SET
POWER OPER.
BIN
FULL ALARM
ALARM
HI
PRESS.
RE-SET
POWER OPER.
BIN
FULL ALARM
ALARM
HI
PRESS.
RE-SET
Page 24
Page 24
Page 24
PC BOARD SET UP
The PC Board can be set up for: Manual reset mode and water purge out for a
short time only at beginning of every harvest cycle - Suggested for soft water - JUMP IN J2
Manual reset mode and water purge out for a short time only at beginning of every harvest cycle plus a full water purge every six cycles ­Recommended for normal/hard water - JUMP IN TWO contacts of J1
Automatic reset - JUMP OUT
Page 24
Page 25
Page 25
Page 25
Disch. Disch. Hi Suction Suction Amps Amps
Pressure Pressure Pressure Pressure Pressure
Compressor Compressor
Freeze max Freeze min CUT OUT Beginning end Freeze Beginning end
bar bar bar Freeze bar bar Freeze Freeze
MV 306 A - 230/50/1
17,5 15,5 30 5,4 3,2 17 3,8 3
MV 306 W - 230/50/1
17 17 30 4,9 3,2 17,5 3,3 2,9
MV 426 A - 230/50/1
18 15,6 30 5,1 3,1 13 4,8 3,8
MV 426 W - 230/50/1
17 16,6 30 4,6 3,1 13,6 4,3 3,6
MV 456 A - 230/50/1
17,5 15,5 33 3,5 2,0 15 4,7 3,6
MV 456 W - 230/50/1
16,5 16,5 33 3,5 2,2 16 4,2 3,4
MV 606 A - 230/50/1
18 16 33 2,7 1,5 13 6,2 4,8
MV 606 W - 230/50/1
16,5 16,5 33 3,2 1,7 13 5,8 4,5
MV 806 A - 230/50/1
18,5 16,5 33 2,0 1,8 12,5 8,6 6,4
MV 806 W - 230/50/1
16,5 16,5 33 3,5 1,9 14,5 9,0 6,7
MV 1006 A - 400/50/3
16 14 33 2,9 1,6 12 3,7 3,0
MV 1006 W - 400/50/3
16,5 16,5 33 3,2 1,8 13,5 3,6 2,8
Cycle time
minutes
MODEL
Refrigerant charge R 404 A - gr.
MODEL MV 306 MV 426 MV 456 MV 606 MV 806 MV 1006
Air cooled 500 800 700 850 1300 1600 Water cooled 450 600 500 550 650 1200
Refrigerant metering device
Thermostatic expansion valve.
SERVICE SPECIFICATION
In servicing a machine, it is often, useful to
compare that individual units operating
characteristics to those of a normally operating
machine. The data that follows gives those
characteristics; however, be aware that these
values are for NEW, CLEAN machine operating
at 21 °C ambient and 15 °C water. USE THESE
NUMBERS AS A GUIDELINE ONLY.
OPERATING CHARACTERISTICS
On air-cooled models during the freezing cycle, the discharge pressure is maintained between two preset values by means of fan control (condenser sensor); and at the same time, the suction pressure will also decline reaching it’s lowest point just before harvest. Compressor amps experience a similar drop. On water-cooled, the discharge pressure is constantly, maintained during the freeze cycle by the water regulating valve. However, suction pressure and compressor amps, will still decline as the machine freezes ice.
NOTE: Always check nameplate on individual icemachine for special refrigerant charge before charging the refrigeration system. Such refrigerant charge is the average charge for the MVP Modular Cubers. However it is important to check nameplate for each machine.
Page 26
Page 26
Page 26
COMPONENT DESCRIPTION
1. Front Console Panel
Equipped with five LED plus a push button that when glow or blink are monitoring:
LED Nr. 1
Electrical power supply.
LED Nr. 2
Operation.
LED Nr. 3
Bin full./Washing.
LED Nr. 4
Alarm.
2. P.C. Board Located in the control box, this board is the brain
of the system as it governs the ice machine cyclematic through sensors, relays and switch. It consists of two separated printed circuits one at high and the other at low voltage integrated with a fuse, of four connectors for the sensors/switches (condenser sensor - BLACK -, magnetic switch
- GREEN - ice thickness sensor - RED - water level sensor - BLUE), of two jumpers (one J1 for factory use only - and the second J2 for the selection between one water fill up or continuous water fill up), of one outlet connector (front LED display - black) one serial port connector (black) and of four plug in terminals for input and output power. With J2 closed the P.C. Board is set up for water fill up at beginning freeze mode. When J2 is open
the PC Board is set up for continuous water filling mode. The P.C. Board is equipped by an electronic safety timer that turns-on automatically the unit to defrost cycle when freezing cycle is longer then 30 or 40 minutes and trips-off completely unit when defrost cycle is longer then 3,5 minutes (4th Red LED ON). A trimmer, located close to the transformer, can change the current received back from the Ice Tickness Sensor according to the Electrical Conductivity of the water.
3. Compressor Contactor Located in the control box, the compressor
contactor functions to carry the compressor line current. The contactor is wired to receive power from the P.C. Board.
LED Nr. 5
Alarm high pressure.
BUTTON B
Reset/Washing.
MV SERIES
PC BOARD
2J
1J
RESNEDNOC
RESNEDNOC
ROSNES
ROSNES
CITENGAM
CITENGAM
HCTIWS
HCTIWS
SSENKCIHTECI
SSENKCIHTECI
ROSNES
ROSNES
YALPSID
YALPSID
ROTCENNOC
ROTCENNOC
ESUF
ESUF
NIREWOP
NIREWOP
YTEFASDNA
YTEFASDNA
ERUSSERP
ERUSSERP
SLORTNOC
SLORTNOC
NAF
NAF
SROTOM
SROTOM
PMUPRETAW
PMUPRETAW
RETAW,SAGTOH,ROSSERPMOC
RETAW,SAGTOH,ROSSERPMOC
SEVLAVNIARDDNATELNI
SEVLAVNIARDDNATELNI
RETAW
RETAW
YTIVITISNES
YTIVITISNES
TNEMTSUJDA
TNEMTSUJDA
TUOPMUJ-.O.N
TUOPMUJ-.O.N
SUOUNITNOC
SUOUNITNOC
GNILLIFRETAW
GNILLIFRETAW
NIPMUJ-.C.N
NIPMUJ-.C.N
PULLIFRETAW
PULLIFRETAW
GNINNIGEB
GNINNIGEB
YLNOEZEERF
YLNOEZEERF
-
-
+
+
LEVELRETAW
LEVELRETAW
ROSNES
ROSNES
LAIRES
LAIRES
ROTCENNOC
ROTCENNOC
YROTCAFROF
YROTCAFROF
YLNOESU
YLNOESU
Page 27
Page 27
Page 27
6. Hot Gas Solenoid Valve The Hot Gas Solenoid Valve functions only during
the Harvest Cycle, to divert the hot discharge gas from the Compressor, bypassing the Condenden­ser and thermostatic expansion valve, for direct flow to the Evaporator Platen Assembly to release ice cubes from the ice cube molds. The Hot Gas Solenoid Valve is comprised of two parts, the Body & Plunger and the Coil assembles. Installed in the discharge line of the Compressor, the energized solenoid coil lifts the valve stem within the valve body to cause the hot discarge gas to be diverted when the ice Thickness sensor has signalled to the P.C. Board to start the Harvest Cycle.
7. Condenser temperature sensor The condenser temperature sensor probe
(located in contact with the condenser tube coil) detects the condenser temperature variations and signals them by supplying current, at low voltage, to the P.C. BOARD. In the air cooled versions, in relation to the different current received, the micro processor of the P.C. BOARD supplies, through a TRIAC, the power at high voltage to the fan motor so to cool the condenser and to reduce its temperature. In case the condenser temperature rises and reaches 65°C (150°F) the current arriving to the micro processor is such to cause an immediate and total stop of the machine operation with the
blinking of the Red LED.
8. High Pressure Control The high Pressure Control, a safety control, is
factory set to cut-out, at 30 bar and cut-in at 22 bar.
4. Ice Thickness Sensor Located in the front upper right side off the
evaporator, the sensor is made with two metal reeds in which passes power at low voltage. The two metal reeds, which are individually insulated, are set, through a setting screw, to maintain a minimum clearence from the evaporator (3÷5 mm). Once ice is formed into each mold and is thick enough to fill-up that minimum clearance existing between the two sensor reeds and the evaporator, the water that cascades over the ice has gradually approached to make contact between the two sensor reeds. It is enough that this contact remains there for about 10 seconds that the P.C. Board receives the signals to put the ice machine on defrost.
5. Magnetic Switch Located in the front of the evaporator plastic
curtain, this switch sends a pulse to the P.C. Board which switches the machine back in the freezing cycle.
Page 28
Page 28
Page 28
The control, functions as a precautionary device to shut OFF electrical power to Icemaker, should a loss of water occur to the water cooled Condenser or a burnt out of the fan motor on air cooled versions. The high Pressure Control is manual reset with reset button located on the rear side of the machine and a monitoring light on the Front Console Panel.
9. Water Regulating Valve
(Water Cooled Models)
The Water Regulating Valve functions maintain a constant Compressor head pressure, by regulating the amount of incoming water flow through the Condenser, on water-cooled models. The valve operate through the refrigerant system high side pressure. Rotating the adjusting screw located on top of the valve, can INCREASE or DECREASE the water flow through the water­cooled Condenser, which in turn, will DECREASE or INREASE the Compressor operating head pressure.
10. Water Distribution System The Water Distribution System function to eventy
supply water to all cells of the evaporator plate. The water pump pumps water from the sump to the tee. From there water is channeled through the vertical tygon tube to the water distributors, above the evaporator plate, and from the holes in the distributor tube water flows to the cells on one side of the evaporator plate. Gravity flow returns the unfrozen excess portion of water to the sump reservoir for recirculation.
11. Water Drain Solenoid Valve The Water Outlet Solenoid Valve functions in
co
njunction with the water pump to flush-out the sump assembly at the beginning (first 40") of every harvest cycle. This action cleans-up and rinses the sump during each harvest cycle pre­venting dangerous water minerales concentration.
12. Thermostatic Expansion Valve The Thermostatic Expansion Valve regulates
the flow of refrigerant to the evaporator and reduces pressure of liquid refrigerant from condensing pressure to evaporating pressure.
13. Water pump The water pump primes the water from the sump
to the water distributor tube and through the distributing holes it cascades down onto the evaporator cells by gravity so to be frozen into clear ice cubes. The water pump remains off during the first 30" seconds of the freezing cycle (to avoid any cavitation problem) while it's kept running during the first 10" of defrost/harvest cycle to drain out (purge) the remaining water from the sump (reach in mineral salts).
Page 29
Page 29
Page 29
14. Water inlet solenoid valve - 3/4" male
fitting
The Water Inlet Solenoid valve is energised by the P.C. Board during the beginning of the freezing cycle till the water reaches the maximum level into the sump (controlled by the Water Level Sensor). After 3 minutes, from the start up of the freezing cycle, the Water Inlet Valve is energised again for a short period to re-fill the sump with water till again to the max. level so to minimise any possibility of slush ice formation A flow control, fitted into its outlet port, reduces the pressure of the water flow.
15. Water level sensor The Water Level Sensor, located on the front of
the water sump, works in conjunction with the P.C. Board in order to control the water level at beginning of the freezing cycle by receiving a low power current passing through the water. When the current reaches the PC Board, the water inlet solenoid valve is de-energised. In case the PC Board doesn’t receive any signal (current) from the Water Level Sensor within the first 3 minutes of the freezing cycle, the PC Board
trips OFF the operation of the machine with the switching ON of the Water Error LEDs.
16.
Start up delay PC Board (only for MV 1006)
Located in the back side of the unit it delays the start up of the entire machine by 90' so to avoid that compressor can start up w/out be pre-heated.
17. Start up delay PC Board by-pass switch
(only for MV 1006)
Located in the back side of the machine allows to by-pass the delay time controlled by the delay PC Board.
WARNING. It is IMPERATIVE to by-pass the delay time only when sure of proper warm up of compressor.
18. Harvest Assist Solenoid (Not used on
MV 306)
Operated by the controller in parallel with the hot gas valve. Cycles on and off at the beginning of a restart. Energized throughout the harvest cycle. Line voltage coil.
Page 30
Page 30
Page 30
MV 306 - WIRING DIAGRAM
220 V. 50 Hz. 1 ph.
A - Input terminal board B - Compressor contactor C - Compressor D - Ice sensor E - End defrosting switch F - Water level sensor G - Condenser temperature probe H - Led card
I - PC Board
J - Hi pressure switch
K - Manual/Automatic reset jumper
L - Water pump M - Water inlet valve N - Water drain/purge valve O - Hot gas valve
P - Fan Motor (only AIR cooled unit) Q - Fan Motor (only WATER cooled unit)
RC
- Compressor relay
CS
- Start capacitor
CM
- Run capacitor
m = brown bc = light blue gv = yellow green b = white n = black r = red a = orange
Page 31
Page 31
Page 31
MV 426/456/606/806 - WIRING DIAGRAM
220 V. 50 Hz. 1 ph.
A - Input terminal board B - Compressor remote control switch C - Compressor D - Ice sensor E - End defrosting switch
F - Water level sensor G - Condenser temperature probe H - Led card
I - Electronic card
J - Max pressure switch K - Automatic reset switch
L - Water pump M - Water inlet valve N - Water discharge valve
O - Hot gas valve SP- Solenoid harv assist P1- Fan Motor (only AIR cooled unit) P2- Fan Motor (only WATER cooled unit) RC
- Compressor relay
CS
- Start condenser
CM
- Run condenser
m = brown bc = light blue gv = yellow green b = white n = black r = red a = orange v = violet
L
SP
F
E
G
v
v
bc
m
bc
n
b
r
a
m
n
bc
n
n
n
bcm
bc
n
bc
n
v
v
N
b
bc
M
r
bc
D
m
P1
P2
A
Page 32
Page 32
Page 32
MV 1006 - WIRING DIAGRAM
400 V. 50 Hz. 3 ph.
A - Input terminal board B - Compressor remote control switch C - Compressor D - Ice sensor E - End defrosting switch F - Water level sensor
G - Condenser temperature probe
H - Led card
I - Electronic card
J - Max pressure switch
K - Automatic reset switch L - Water pump M - Water inlet valve N - Water discharge valve
O - Hot gas valve SP- Solenoid harv assist P1- Fan Motor 1 (only AIR cooled unit) P2- Fan Motor 2 (only WATER cooled unit)
R - Cranckase heater
S - Start delay by-pass switch
T - Start delay electronic board
m = brown bc = light blue gv = yellow green b = white n = black r = red a = orange v = violet
L
SP
F
E
G
v
v
bc
m
bc
n
b
r
a
m
n
bc
n
n
n
nm
bc
n
bc
n
v
v
N
b
bc
M
r
bc
D
n
m
P1
P2
Page 33
Page 33
Page 33
SYMPTOM POSSIBLE CAUSE CORRECTION
Warning Red LED ON See page 20 See page 20 No warning LED/LIGHT ON P.C. Board inoperative. Remove board and check.
No power to unit. Check electrical source.
Bin full Yellow LED ON Bin Full of ice. Nome.
Magnetic switch inoperative. Check and replace.
Machine runs, compressor P.C. Board compressor Test and replace. does not. relay open.
Compressor contactor open. Test and replace. Compressor relay open. Test and replace. Compressor winding open. Test and replace.
Machine runs, makes ice, Ice thickness control open. Check sensor fingers does not try to harvest. if are not covered
with scale sediment.
Too soft water. Water electrical conductivity
must be higher then 20 µS. Machine can't run with demineralized water.
Built-in relay on Check and replace P.C. Board. P.C. Board open.
Machine runs, makes Low refrigerant charge. Check system for correct refr. charge. and harvests ice Check for leak weight in charge. but very slowly.
Low ice capacity. High discharge pressure Evacuate and weigh
due to not-condensable in charge. or overcharge.
Inefficient compressor. Replace. Condenser dirty. Clean.
Low water flow Check and repair. (Water-cooled).
High air temperature Check temperature of air (air-cooled). entering condenser.
Machine makes irregular ice. Plugged water distributor. Clean water distributor.
TXV supertheat wrong. Adjust or replace. Refrigerant charge low. Adjust-check for leak.
recharge.
SERVICE DIAGNOSIS
The table below is intended as a quick reference to aid the Service Agent in determining the cause of a particular type of malfunction, as well as the recommended repair. It is not intended to be an exclusive list.
Reference to other portions of this manual, inclusing wiring diagrams, installation, and operation are recommended to better determine the cause of a problem.
Page 34
Page 34
Page 34
MAINTENANCE & CLEANING & SANITATION INSTRUCTIONS
A SCOTSMAN Ice System represent a sizable investment of time and money in any company’s business. In order to receive the best return for that investment, in MUST receive periodic maintenance. It is the USER’S RESPONSIBILITY to see that preferable, and less costly in the long run, to avoid possible down time by keeping it clean, adjusting it as needed and by replacing worn parts before they can cause failure. The following is a list of recommended maintenance that will help keep your machine running with a minimum of problems. Maintenance and Cleaning should be scheduled at MINIMUM twice per year while sanitation once per month.
ICEMAKER
THE FOLLOWING MAINTENANCE SHOULD BE SCHEDULED AT LEAST TWO TIMES PER YEAR ON THIS ICEMAKER. CALL YOUR AUTHORIZED SCOTSMAN SERVICE AGENCY.
1. Check and clean or service any optional water treatment devices, if any installed.
2. Clean water strainer.
3. Check that the cabinet is level, in the side­to-side and front-to-back directions.
4. Clean/Sanitise the water system, evaporator plate and sump assembly, using a solution ot Ice Machine Cleaner/Sanitiser. Refer to CLEANING ­Icemaker.
NOTE: Cleaning/Sanitising requirements vary according to local water conditions and individual user operation. Continuous check of the clarity of ice cubes and visual inspection of the water system parts, evaporator plates and the sump assembly before and after cleaning will indi­cate frequency and procedure to be followed in local areas.
5. Check and tighten all bolts and screws.
6. Check for water leaks and make corrections.
7. Check the bin control to test shut-off. Holding the evaporator deflector in open Position for more that 30", shold cause the ice maker to shut-off. Once the evaporator deflector is released in its closed position, the ice maker will restart.
8. Check cube size, adjust if required through setting screw of ice thickness control sensor.
9. With unit out of operation, clean the condenser using vacuum, cleaner, wisk broom or brush. Instruct customer to clean condenser frequently DO NOT USE A WIRE BRUSH.
ICE STORAGE BIN
The interior liner of the bin is in contact with a food product, ice, and should be cleaned and sanitised regularly. Once a week sanitise it with a commercial food grade sanitiser compling with the manufacturer dilution.
CABINET EXTERIOR
Wipe clean unit and bin cabinet exterior with a clean cloth or disposable paper wipers, soaked in warm water with mild detergent solution.
CLEANING - Ice maker
WARNING - Ice Machine Cleaner contains Phosphoric and Hydroxyacetic acids. These compounds are corrosive and may cause burns. If swallowed, DO NOT indu­ce vomiting. Give large amounts of water or milk. Call physician immediately. In case of sxternal contact, flush with water. KEEP OUT OF THE REACH OF CHILDREN.
1. Empty bin of ice.
2. Remove front panel.
3. Wait till the end of the defrost/harvest cycle then push the RESET BUTTON for 6-8 seconds. The machine should stop with the blinking of the Yellow LED (slow blink).
4. Pour on
- MV 306-426 150 cc
- MV 456-606 250 cc
- MV 806-1006 350 cc of Scotsman Ice Machine Clea-ner directly into
the reservoir then push again the RESET BUTTON for a while. The water pump starts to operate with the fast blinking of the Yellow LED while the water inlet valve will be energized till the fill up of the water sump.
5. After 15 minutes push the RESET BUTTON for a while. The P.C. Board put the machine in automatic rinsing mode with the special blinking (blink twice and repeat) of the Yellow LED.
Page 35
Page 35
Page 35
NOTE: RINSING mode consists of: a) energize the water drain valve and the
water pump for 40 seconds to empty the reservoir
b) deenergize the water drain valve and the
water pump for 1 minute
c) energize the water inlet valve till the fill up
of the water sump d) energize the water pump for 1,5 minutes. The above sequence is repeted 7 times so to be sure to have removed any possible trace of Ice Machine Cleaner.
6. At the end of the 7th Rinsing cycle the P.C. Board stops the operation of the machine with the blinking (slow) of the Yellow LED.
7. Pushing the RESET BUTTON for 6-8 seconds the machine restarts in the freezing cycle.
8. Replace the evaporator cover deflector and front panel.
9. Check the next batch of cubes to be sure all the cleaner is gone (no sour taste).
CAUTION - DO NOT use ice cubes produced from the cleaning solution. Be sure none remains in the bin.
10. Pour hot water into the storage bin melt the cubes, and to also clean the bin drain.
Loading...