Scotsman MCS 46 A,MCS 46 W,MCM 1210 A,MCM 46 A,MCM 46 W,MCL 16 A,MCL 46 A,MCL 1210 A,MCXL 46 W Service Manual

Page 1
Page 1
Scotsman Ice Srl Via Lainate, 31 - 20010 Pogliano M.se - Milano - Italy Tel. +39-02-93960.1 (Aut. Sel.)- Telefax +39-02-93550500 Direct Line to Service & Parts: Phone +39-02-93960350 - Fax +39-02-93540449 Website: www.scotsman-ice.it E-Mail: scotsman.europe@scotsman.it
ISO 9001 - Cert. n. 0080
MC 46
Electronic
modular cubers
New PC Board
From s.n. 28850
REV. 09/2015
SERVICE MANUAL
LED STATUS
REASON WHY - SIGNIFICATION - SIGNIFICATO
ON STEADY
FIXE
FISSO
FREEZING CYCLE
EN RÉFRIGÉRATION
IN CONGELAMENTO
BLINKING
CLIGNOTANT
LAMPEGGIANTE
60 MINUTES DELAY AT START UP JUMPER J3 OUT
60 MINUTES DE RETARD AU DEMARRAGE - CAVALIER J3 OUVERTE
60 MINUTI RITARDO PARTENZA - CONTATTI J3 APERTI
ON STEADY
FIXE
FISSO
TOO HI DISCHARGE PRESSURE/TEMP.
COUPURE HP
FERMATA ALTA TEMP. CONDENSAZIONE
BLINKING
CLIGNOTANT
LAMPEGGIANTE
TOO HI EVAP. TEMP. (> 0°C) AFTER 15’ FROM START UP
COUPURE BP ( > 0°C LU PAR LA
SONDE EVAP. NON ATTEINTE APRES 15’ FONCT.)
TEMP. EVAP. > 0°C DOPO 15’ DA INIZIO CONGELAMENTO
ON STEADY
FIXE
FISSO
UNIT OFF AT BIN FULL
CABINE PLEINE
CONTENITORE PIENO
BLINKING SLOW
CLIGNOTANT LENT
LAMPEGG. LENTO
I/R BEAM CUTTED
FAISCEAU INFRA ROUGE CELLULE NIVEAU GLACE INTERROMPU
RAGGIO INFRAROSSO INTERROTTO
BLINKING FAST
CLIGNOTANT RAPIDE
LAMPEGG. VELOCE
I/R ON AFTER TRIP OFF AT BIN FULL
FAISCEAU INFRA ROUGE CELLULE NIVEAU GLACE ETABLI
RAGGIO INFRAROSSO RIPRISTINATO DOPO FERMATA A CONT. PIENO
ON STEADY
FIXE
FISSO
I/R CALIBRATION DONE
CALIBRATION FAISCEAU INFRA ROUGE CELL. NIVEAU GLACE REALISÉ
CALIBRAZIONE RAGGIO INFRAROSSO EFFETTUATA
BLINKING
CLIGNOTANT
LAMPEGGIANTE
UNIT IN CLEANING MODE OR TRIPPING OFF AFTER TEST - JUMPER TEST IN
MACHINE EN MODE DETARTRAGE OU ARRÊTE APRES LE TEST - CAVALIER TEST FERMÉ
MACCHINA NELLA FASE LAVAGGIO O FERMA DOPO IL TEST - PONTICELLO TEST CHIUSO
ON STEADY
FIXE
FISSO
CONDENSER SENSOR OUT OF ORDER
SONDE CONDENSEUR HS
SONDA CONDENSATORE MALFUNZIONANTE
BLINKING
CLIGNOTANT
LAMPEGGIANTE
EVAPORATOR SENSOR OUT OF ORDER
SONDE EVAPORATEURS HS
SONDA EVAPORATORE MALFUNZIONANTE
BLINKING ALTERNATIV.
CLIGNOTANT ALTERNÉ
LAMPEGGIO ALTERN.
I/R SENSOR OUT OF ORDER
SONDE INFRA ROUGE CELLULE NIVEAU GLACE HS
SONDA ALL’INFRAROSSO LIVELLO GHIACCIO MALFUNZIONANTE
PUSH
PUSH > 5” DURING WATER FILLING TO MOVE THE UNIT INTO FREEZING
PUSH > 5” DURING FREEZING TO MOVE THE UNIT INTO DEFROST PUSH > 5” DURING DEFROST TO MOVE THE UNIT INTO FREEZING
PUSH 2” ÷ 5” DURING WATER FILLING TO MOVE THE UNIT INTO CLEANING
PUSH DURING THE 60 MIN START UP DELAY TIME TO BY-PASS IT
START
AMPS
MC 16 SHORT A - 230 V MC 16 SHORT W - 230 V MC 16 SHORT A - 400 V MC 16 SHORT W - 400 V MC 46 A - 230 V MC 46 W - 230 V MC 46 A - 400 V MC 46 W - 400 V
MC 1210 A - 400 V MC 1210 W - 400 V
AMPS WATTS
KWH/24HRS
REFR. CHARGE
R404a
SUCT. PRESS.
END. FREEZE
DISCHARGE
PRESSURE
7,1
3
10
5,5
11
32
18
66
14
28
1300
1400
2400
4800
580 gr 450 gr 580 gr 450 gr
1300 gr
700 gr
1300 gr
700 gr
2 x 1300 gr
2 x 700 gr
1,6 ÷ 1,7 bar
1,6 ÷ 1,7 bar
2,5 bar
16 ÷ 18 bar
17 bar
16 ÷ 18 bar
17 bar
16 ÷ 18 bar
17 bar
16 ÷ 18 bar
17 bar
13 ÷ 14 bar
13,5 ÷ 14,5 bar
14 bar
1 2 3 4
MCS 16 A MCS 16 W MCM 16 A MCM 16 W MCL 16 A MCL 16 W MCS 46 A MCS 46 W MCM 46-1210 A MCM 46-1210 W MCL 46-1210 A MCL 46-1210 W MCXL 46 W
5 6 7 8 9
10
ON
ON OFF OFF OFF OFF
ON
ON
ON OFF
ON
ON OFF
OFF OFF OFF OFF OFF OFF OFF OFF
ON ON ON ON ON
ON ON ON
ON OFF OFF
ON
ON OFF OFF
ON
ON OFF
ON ON ON ON ON ON ON ON ON
ON OFF OFF OFF
OFF OFF OFF OFF OFF OFF
ON ON ON ON ON ON
OFF
ON ON ON ON ON ON ON ON ON ON ON ON ON
ON ON ON ON ON
ON OFF OFF OFF OFF OFF OFF
ON
ON ON ON ON ON ON ON ON ON ON ON ON
OFF
ON ON ON ON ON ON ON ON ON ON ON ON ON
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON OFF OFF
DIP SWITCH FACTORY SETTING COMBINATIONS (PER MODEL AND VERSION)
COMBINAISON DES COMMUTATEURS NUMERIQUES DU DIP SWITCH POUR MODELES ET VERSIONS
REGOLAZIONE TASTI DIP SWITCH PER MODELLO E VERSIONE
DIP SWITCH
FREEZING CYCLE
CYCLE DE CONGÉLATION
CICLO CONGELAMENTO
DEFROST CYCLE
CYCLE DE DÉMOULAGE
CICLO SBRINAMENTO
15/30"
1 2 3 4
ON ON ON ON 1 min.
OFF ON ON ON 3 min.
ON OFF ON ON 5 min.
OFF OFF ON ON 7 min.
ON ON OFF ON 9 min.
OFF ON OFF ON 11 min.
ON OFF OFF ON 13 min.
OFF OFF OFF ON 15 min.
ON ON ON OFF 17 min.
OFF ON ON OFF 19 min.
ON OFF ON OFF 21 min.
OFF OFF ON OFF 23 min.
ON ON OFF OFF 25 min.
TIMED PORTION FREEZING CYCLE
TEMPS PHASE TEMPORISÉE CONGELATION
TEMPI FASE TEMPORIZZATA CONGELAMENTO
7 8
OFF OFF
WATER PUMP OFF DURING DEFROST
POMPE A L’ARRÊT PEND. DEGIVRAGE
POMPA ACQUA DURANTE SBRINAMENTO
7 8
ON ON 0
OFF ON 30 sec.
ON OFF 60 sec.
ADDITIONAL DEFROST TIME
TEMPS AJOUTÉS
TEMPI AGG. SCONGELAMENTO
AIR/EAU
ARIA/ACQUA
27,6
28,0
50
105
Page 2
Page 2
TABLE OF CONTENTS
Table of contents Specifications MC 46
GENERAL INFORMATION AND INSTALLATION
Introduction Unpacking and Inspection - Ice maker Unpacking and Inspection - Storage bin Location and levelling Stacking installation Electrical connections Water supply and drain connections Final check list Installation practice
OPERATING INSTRUCTIONS
Start up Operatiobnal checks
OPERATING PRINCIPLES (How it works)
Freezing cycle Harvest cycle Control sequence Component description
ADJUSTMENT, REMOVAL AND REPLACEMENT PROCEDURES
Adjustment of the cube size Wiring diagram Service diagnosis
MAINTENANCE AND CLEANING INSTRUCTIONS
General Icemaker Cleaning instructions of water system
2 3
15 17 18 19
24
25-26-27
28
30 30 31
10 11
5 5 5 5 6 8 8 8 9
Page 3
Page 3
310
300
290
280
270
260
250
240
230
220
210
200
190
180
Kg.
32
10 °C27 21 15
MODÈLES REFROIDIS PAR AIR
TEMPÉRATURE DE L'EAU
TEMPÉRATURE AMBIANTE
PRODUCTION DE GLACE EN 24 H
32
38
10 21
°C
MODÈLES REFROIDIS PAR EAU
310
300
290
280
270
260
250
240
230
220
210
200
190
180
Kg.
32
10 °C27 21 15
TEMPÉRATURE DE L'EAU
TEMPÉRATURE AMBIANTE
PRODUCTION DE GLACE EN 24 H
10
21
32
38
°C
ice making capacity
AIR COOLED MODELS
AMBIENT TEMPERATURE
WATER TEMPERATURE
ICE PRODUCED PER 24 HRS
AMBIENT TEMPERATURE
WATER TEMPERATURE
ICE PRODUCED PER 24 HRS
WATER COOLED MODELS
SPECIFICATIONS
ELECTRONIC CUBER MODEL MC 46
I
mportant operating requirements:
MIN. Air temperature 10°C (50°F) Water temperature 5°C (40°C) Water pressure 1 bar (14 psi) Electr. voltage variations from voltage rating specified on nameplate -10%
MAX.
40°C (100°F)
35°C (90°F)
5 bars (70 psi)
+10%
NOTE. The daily ice-making capacity is directly related to the condenser air inlet temperature, water temperature and age of the machine.
To keep your SCOTSMAN MODULAR CUBER at peak performance levels, periodic maintenance checks must be carried out as indicated on maintenance section of this manual.
Production charts shown are indicating the production of MCM and MCL models. For MCS models ice production is approx. 10% lower.
Page 4
Page 4
MC 46 AS 6 Air Stainless steel MC 46 WS 6 Water Stainless steel
2.5
Model Cond. unit Finish Comp. HP Water req. - lt/24 HR
SPECIFICATIONS
660
3700*
MC 46 - MACHINE SPECIFICATIONS
DIMENSIONS: HEIGHT 874 mm.
WIDTH 1074 mm. DEPTH 534 mm. WEIGHT 185 Kgs.
ACCESSORIES KSC 11: Cube stacking kit
220-230/50/1 7 2400 50 3 x
Basic electr. Amps Watts N. of wires Amps. fuse
230/50/1N 10 66 3 x 1.5 m/m
2
20
400/50/3N 5.5 14 5 x 1.5 m/m
2
10
Starts Electric power cons. amps. Kwh x 24 HR
Cubes per harvest: MCL-46 144 large - MCM-46 204 medium - MCS 46 396 small * At 15°C (60°F) water temperature
Page 5
Page 5
A. INTRODUCTION
This manual provides the specifications and the step-by-step procedures for the installation, start­up and operation, maintenance and cleaning for the SCOTSMAN MODULAR CUBERS. The Electronic Modular Cubers are quality designed, engineered and manufactured. Their ice making systems are thoroughly tested providing the utmost in flexibility to fit the needs of a particular user. These icemakers have been engineered to our own rigid safety and performence standards.
NOTE. To retain the safety and performance built into this icemaker, it is important that installation and maintenance be conducted in the manner outlined in this manual.
Storage Bin
Since the MC series Modular Cubers do not have their own attached ice storage bins, it is necessary to use an auxiliary bin such as the Bin SB 550.
B. UNPACKING AND INSPECTION Modular Cuber
1. Call your authorized SCOTSMAN Distributor or Dealer for proper installation.
2. Visually inspect the exterior of the packing and skid. Any severe damage noted should be reported to the delivering carrier and a concealed damage claim form filled in subjet to inspection of the contents with the carrier’s representative present.
3. a) Cut and remove the plastic strip securing the carton box to the skid.
b) Remove the packing nails securing the
carton box to the skid.
c) Cut open the top of the carton and remove
the polystyre protection sheet.
d) Pull out the polystyre posts from the
corners and then remove the carton.
4. Remove top and sides panels of the unit and inspect for any concealed damage. Notify carrier of your claim for the concealed damage as stated in step 2 above.
5. Loose two nuts on left and rights side of the unit base and remove it from the skid. Save the two bolts and nuts to mount the machine on storage bin or on top of another Modular Cuber.
GENERAL INFORMATION AND INSTALLATION
6. Remove all internal support packing and masking tape and the hardware package.
7. Check that refrigerant lines do not rub against or touch other lines or surfaces, and that the fan blade moveS freely.
8. Check that the compressor fits snugly onto all its mounting pads.
9. See data plate on the rear side of the unit and check that local main voltage corresponds with the voltage specified on it.
CAUTION. Incorrect voltage supplied to the icemaker will void your parts replacement program.
10. Remove the manufacturer’s registration card from the inside of the User Manual and fill­in all parts including: Model and Serial Number taken from the data plate. Forward the completed self-addressed registration card to Frimont/Scotsman Europe factory.
C. LOCATION AND LEVELLING
WARNING. This Ice Cuber is designed for indoor installation only. Extended periods of operation at temperature exceeding the following limitations will constitute misuse under the terms of the SCOTSMAN Manufacturer’s Limited Warranty resulting in LOSS of warranty coverage.
1. Position the Bin in the selected permanent location. Criteria for selection of location include:
a) Minimum room temperature 10°C (50°F)
and maximum room temperature 40°C (100°F).
b) Water inlet temperatures: minimum 5°C
(40°F) and maximum 35°C (90°F).
c) Well ventilated location for air cooled
models.
d) Service access: adequate space must be left for all service connections through the rear of the ice maker. A minimum clearance of 15 cm (6") must be left at the sides of the unit for routing cooling air drawn into and exhausted out of the compartment to maintain proper condensing operation of air cooled models.
Page 6
Page 6
2. Level the Storage Bin Assy in both the left to right and front to rear directions by means of the adjustable legs.
3. Inspect the Storage Bin top mounting gasket which should be flat with no wrinkles, to provide a good sealing when the Modular Cuber is installed on top of it.
4. Place the Modular Cuber on top of Storage bin using care not to wrinkle or tear the gasket.
5. Lift a little bit the Modular Cuber right side in order to be able to mount the ice level control bracket taking care to align the hole located on unit base to mate with the one on the top of the Bin.
6. Remove the PVC plastic plug closing the round hole located on the right side of the ice chute opening.
7. Trace the ice level control assy, secured for the transport on top of the evaporator of the Modular Cuber, and direct it down through the round hole into the Storage Bin.
8. Fasten the ice level control assy on its bracket by means of the two screws found in the hardware package supplied with the unit.
9. Make a cut (shear) in the PVC plastic plug that goes from its edge to the center; insert the ice level control cable in the center of the plastic plug so to prevent it from any sort of contact with the unit frame, then place again the PVC plug in the round hole keeping the cable exceeding portion inside the unit.
10. Install the plastic ice cube deflector by hooking it on the flange of the ice chute opening in unit base (see illustration).
11. Secure the Modular Cuber on the top of the Storage Bin using the two bolts and diber washer found in the hardware package supplied with the unit.
D. STACKING INSTALLATION
A Stacking Kit KSC 11 is available as an accessory on request to allow the installation of two Modular Cubers one on top of the other.
The Stacking Kit is consisting of:
a) unit base gasket
b) plastic reinforced ice chute
connections
Use the ice chute connections supplied in the
KSC Kits..........
... to connect the ice chute of the bottom machine with the one of the top machine
Page 7
Page 7
Page 8
Page 8
E. ELECTRICAL CONNECTIONS
See data plate for current requirements to determine wire size to be used for electrical connections. All SCOTSMAN icemakers require a solid earth wire. All SCOTSMAN ice machines are supplied from the factory completely pre-wired and require only electrical power connections to the wire cord provided at the rear of the unit. Make sure that the ice machine is connected to its own circuit and individually fused (see data plate for fuse size). The maximum allowable voltage variation should not exceed -10% and +10% of the data plate rating. Low voltage can cause faulty functioning and may be responsible for serious damage to the overload switch and motor windings.
NOTE. All external wiring should conform to national, state and local standards and regulations.
Check voltage on the line and the ice maker’s data plate before connecting the unit.
F. WATER SUPPLY AND DRAIN
CONNECTIONS
General
When choosing the water supply for the ice flaker consideration should be given to:
a) Length of run b) Water clarity and purity c) Adequate water supply pressure
Since water is the most important single ingredient in producting ice you cannot emphasize too much the three items listed above. Low water pressure, below 1 bar may cause malfunction of the ice maker unit. Water containing excessive minerals will tend to produce cloudy coloured ice cubes, plus scale build-up on parts of the water system.
Water supply
Connect the 3/4" GAS male fitting of the solenoid water inlet valve, using flexible tubing or a 3/8" O.D. copper pipe, to the cold water supply line with regular plumbing fitting and a shut-off valve installed in an accessible position between the water supply line and the unit.
Water supply - Water cooled models
The water cooled versions of SCOTSMAN Ice Makers require two separate inlet water supplies, one for the water sprayed for making the ice cubes and the other for the water cooled condenser. Connect the 3/4" GAS male fitting of the water inlet, using the flexible tubing or a 3/8" O.D. copper pipe, to the cold water supply line with regular plumbing fitting and a shut-off valve installed in an accessible position between the water supply line and the unit.
Water drain
The recommended drain tube is a plastic or flexible tube with 18 mm (3/4") I.D. which runs to an open trapped and vented drain. When the drain is a long run, allow 3 cm pitch per meter (1/4" pitch per foot). A vent at the unit drain connection is also required for proper sump drainage.
Water drain - Water cooled models
Connect the 3/4" GAS male fitting of the condenser water drain, utilizing a second flexible tubing or a 3/8" O.D. copper tubing, to the open trapped and vented drain.
NOTE. The water supply and the water drain must be installed to conform with the local code. In some case a licensed plumber and/ or a plumbing permit is required.
G. FINAL CHECK LIST
1. Is the unit in a room where ambient temperatures are within a minimum of 10°C (50°F) even in winter months?
2. Is there at least a 15 cm (6") clearance around the unit for proper air circulation?
3. Is the unit level? (IMPORTANT)
4. Have all the electrical and plumbing connections been made, and is the water supply shut-off valve open?
5. Has the voltage been tested and checked against the data plate rating?
6. Has the water supply pressure been checked to ensure a water pressure of at least 1 bar (14 psi).
7. Have the bolts holding the compressor down been checked to ensure that the compressor is snugly fitted onto the mounting pads?
8. Check all refrigerant lines and conduit lines to guard against vibrations and possible failure.
9. Have the bin liner and cabinet been wiped clean?
10. Has the owner/user been given the User Manual and been instructed on the importance of periodic maintenance checks?
11. Has the Manufacturer’s registration card been filled in properly? Check for correct model and serial number against the serial plate and mail the registration card to the factory.
Page 9
Page 9
H. INSTALLATION PRACTICE
1. Hand shut-off valve
2. Water filter
3. Water supply line (flexible hose)
4. 3/4" gas male fitting
5. Power line
6. Main switch
7/9. Drain fitting
8/10. Vented drain line
11. Open trapped vented drain
WARNING. This icemaker is not designed for outdoor installation and will not function in ambient temperatures below 10°C (50°F) or above 40°C (100°F).
This icemaker will malfunction with water temperatures below 5°C (40°F) or above 35°C (90°F).
Page 10
Page 10
OPERATING INSTRUCTIONS
NOTE.
Ice maker pcb is equipped by jumper
cleaning reminding setting (see pag. 20)
suitable to alert users after certain time of unit operation. This would advice for preventive maintenance. This time can be adjusted for 6 or 12 months operation (upon installer advice related to installation site water and ambient condition); once selected time is elapsed RED front panel lamp blinks slowly and ice maker will keep on working anyway. Pcb is also equipped by 3 (standard) or 60 (machines operating at 400/50/3) minutes jumper setting start up delay (see pag. 20). In case of pcb setting to 60 minutes ice maker doesn't start until this time is elapsed. After having correctly installed the ice maker and completed the plumbing and electrical connections, perform the following “Start-up” procedure.
START UP
After having correctly installed the ice maker and completed the plumbing and electrical connections, perform the following “Start-up” pro­cedure.
A. Give power to the unit to start it up by switching "ON" the power line main disconnect switch.
NOTE.
Every time the unit returns under power, after having been switched off, the water inlet valve, the hot gas valve and the water drain valve get energized for a period of 5 minutes, thus to admit new water to the machine sump reservoir to fill it up and, eventually, to wash-off any dirt that can have deposited in it during the unit off period (Fig.1).
B. During the water filling operation, check to see that the incoming water dribbles, through the evaporator platen dribbler holes, down into the sump reservoir to fill it up and also that the incoming surplus of water flows out through the overflow pipe into the drain line. During the water filling phase the components energized are:
THE WATER INLET SOLENOID VALVE THE HOT GAS SOLENOID VALVE THE WATER DRAIN SOLENOID VALVE/S
for the first 30 seconds.
16
15
14
13
2
1
7 8
9 10
3 4
5 6
11 12
Rx Tx
WATER IN VALVE
HOT GAS VALVE
CONTACTOR COIL
FAN MOTOR
WATER PUMP
- EVAPORATOR
- AMBIENT
- CONDENSER
TEMPERATURE SENSORSBINCOMPRESSOR
TRANSF.
DATA
PROCESSOR
ELECTR.
TIMER
DIP SWITCH
ELECTRONIC CARD
L N
RELAYS
RELAY
TRIAC
WATER DRAIN VALVE
FIG. 1
Loading...
+ 23 hidden pages