To the owner or user: This service manual is
intended to provide you and the maintenance or
service technician with the information needed to
install, start up, clean, maintain and service this
ice system.
Parts Lists and Wiring Diagrams are located in the
center of this manual, printed on yellow paper.
This manual was printed on recycled paper.
April, 1993
Page 1
MCM1462R
FOR THE INSTALLER
The MCM1462R will fit Scotsman ice storage bin
MDB900 and is stackable with stacking kit
KSMCM48.
Either a Scotsman remote condenser or a Mac 6
condensing system are required to for this ice
system.
Scotsman Ice Systems are designed
and manufactured with the highest
regard for safety and performance.
They meet or exceed the standards of
U.L., N.S.F., and C.S.A.
Scotsman assumes no liability or
responsibility of any kind for products
manufactured by Scotsman that have
been altered in any way, including the
use of any parts and/or other
components not specifically approved
by Scotsman.
Other items required:
•• Precharged tubing kit
•• Power cord and receptical
•• Condenser power cord
•• If stacking two units, a stacking kit
•• If using one unit, a caster kit for the bin.
Scotsman reserves the right to make
design changes and/or improvements
at any time. Specifications and
designs are subject to change without
notice.
Back View
Model NumberDimensions
(without bin)
W" x D" x H"
MCM1462RS-3A
48 x 24
3
⁄8 x 271⁄2
Basic
Electrical
208-230/60/3 R-2220.530256 oz.Remote Air
Refrigerant
Type
Minimum
Circuit
Ampacity*
Maximum
Fuse Size
Refrigerant
Charge**
R-22
Condenser
Type
* Minimum Circuit Ampacity is used to determine wire size and type per the National Electric Code.
** The unit is shipped with the full charge in the receiver. For re-charging purposes, if the nameplate charge
is different than this number, go by the nameplate.
Use Scotsman remote condenser RC1422, or Mac 6. Use precharged tubing kit MLS2255 (55’) or
MLS2265 (65’) or MLS2275 (75’).
Power Cord is kit number: MPC
Caster Kit is number: KBC9
This ice system (except remote condenser) is designed to be installed indoors, in a controlled environment.
MINIMUMMAXIMUM
Air Temperature50
Water Temperature40
Water Pressure20 psi80 psi
Voltage-5%+10%
0
F.1000F.
0
F.1000F.
April, 1993
Page 2
FOR THE INSTALLER: Location & Assembly
SHIPPING
BRACKETS
Location:
After uncrating and inspection, the unit is ready for
installation. It is important that the machine be
installed in a location where it has enough space
around it to be accessible for service. Try to avoid
hot, dirty and crowded locations. Be sure that the
location for the machine is within the
envrionmental limitations.
MCM1462R
Storage Bin:
Tip the storage bin on its back, using parts of the
carton to protect the exterior finish. Install the
casters, use a heavy duty leg kit if stacking two ice
machines on one bin.
1. Arrange for proper electric, water and drain.
See instructions for the plumber and for the
electrician.
2. After mounting the casters, position the ice
storage bin in the selected location:
Note: Allow enough space to the left and back to
service the machine. Do NOT push the bin into
postion, instead, lift it there. Pushing a bin may
damage the legs and leg mounts.
Level the bin in both the front to rear and side to
side directions by adjusting the leg levelers.
3. Inspect the bin top mounting gasket which
should be flat, with no wrinkles, to provide a good
water seal when the cuber is installed on top of the
bin.
ICE MACHINE AND BIN ASSEMBLY
4. Install the bin bumpers onto the top edge of the
bin, so that they hang-over the back.
Ice Maker:
Install the modular cuber on top of the bin using
care to be sure a good seal is made between the
two cabinets. Use of a mechancial lift is
recommended. Align the holes in the bottom rear
of the cabinet to mate with the two mounting holes
on the top rear of the bin.
Use bolts and straps found on the back of the ice
machine to secure the ice machine to the bin.
When alignment and leveling are completed,
tighten the bolts to secure the mounting straps.
Remove the front panel, and remove the
evaporator shipping brackets and hardware.
April, 1993
Page 3
MCM1462R
FOR THE INSTALLER: Location & Assembly
Stacking Instructions
A stacking kit, KSMCM48, is required to
interconnect the ice level controls, seal the
freezing compartments, support the bin with heavy
duty legs, and retain the front panels.
Follow the installation instructions of the stacking
kit, but in general:
The first thing to do when adding a unit is to
replace the bin casters (if the unit has been
installed with casters) wtih heavy duty legs.
Casters must not be used with two ice
machines on one bin.
When stacking two units, remove the top panel
and the evaporator cover from the lower icemaker.
STACKING
(The top removed from the lower icemaker will no
longer have any function.)
Add a strip of gasket (from the stacking kit) to the
top edge of the bottom ice machines evaporator
compartment.
Install the panel retaining bracket onto the bottom
ice machine before placing the upper unit on it.
Place additional gasket onto the top edges of the
bottom ice machine.
Carefully lift the uncrated top unit onto the bottom
one and align the two cabinets. Use of a
mechanical lift is recommended for this step.
At the back of the two icemakers, bolt the upper
icemaker cabinet to the lower icemaker cabinet
using the mounting straps and bolts from the
hardware package.
Add the relay kit to interconnect the two ice
machine’s bin control circuits.
PANEL RETAINING
BRACKET
EVAPORATOR COVER
April, 1993
Page 4
FOR THE INSTALLER: Scotsman Remote Condenser
MCM1462R
Locate the condenser as near as possible to
the interior location of the ice maker.
Location of the condenser is limited by the specific
length of precharged refrigerant tubing supplied for
the application. The pre-charged tubing connects
the icemaker to the remote condenser. The
condenser must be above the ice maker.
Select the best available location, protecting the
condenser from extremes of dirt, dust, and sun.
Meet all applicable building codes.
Roof Attachment:
Install and attach the remote condenser unit to the
roof of the building, using the methods and
practices of construction that conform to the local
building codes, including having a roofing
contractor secure the condenser to the roof.
REFRIGERANT
CONNECTIONS
Precharged Line Routing
/////////////////////////////CAUTION///////////////////////////////
Do not connect precharged tubing until all routing
and forming of the tubing is complete. See the
coupling instructions for connecting instructions.
1. Each set of precharged refrigerant lines consists
of a 3/8 inch diameter liquid line, and a 1/2 inch
diameter discharge line. Both ends of each line
have quick connect couplings, the end without
access valves goes to the icemaker.
Note: The openings in the building ceiling or wall,
listed in the next step, are the minimum sizes
recommended for passing the refrigerant lines
through.
2. Have the roofing contractor cut a minimum hole
for the refrigerant lines of 1.75". Check local
codes, a separate hole may be required for the
electrical power to the condenser.
/////////////////////////////CAUTION////////////////////////////////
DO NOT KINK OR CRIMP REFRIGERANT
3. Route the refrigerant lines through the roof
opening.
Follow straight line routing whenever possible.
Any excess tubing MUST be retained within the
building.
4. Spiral any excess length of
pre charged tubing inside the
building. Use a horizontal spiral
to avoid any traps in the lines.
5. Have the roofing contractor
seal the holes in the roof per
local codes.
6. The flexible end of the tubing
must be installed behind the
icemaker; it is to be looped
down from the ice machine
connection area then back up
the wall behind the ice machine.
This allows un-stacked units to
be pulled out for service.
April, 1993
Page 5
ELECTRICAL
CONNECTION TO
ICE MACHINE
MCM1462R
FOR THE INSTALLER: Mac 6 Remote Condenser
MAC 6 INSTALLATION
DISCHARGE LINE
FROM ICE
MACHINE
LIQUID LINE
TO ICE
MACHINE
Precharged Line Routing
/////////////////////////////CAUTION///////////////////////////////
Do not connect precharged tubing until all routing
and forming of the tubing is complete. See the
coupling instructions for connecting instructions.
1. Each set of precharged refrigerant lines consists
of a 3/8 inch diameter liquid line, and a 1/2 inch
diameter discharge line. Both ends of each line
have quick connect couplings, the end without
access valves goes to the icemaker.
Note: The openings in the building ceiling or wall,
listed in the next step, are the minimum sizes
recommended for passing the refrigerant lines
through.
2. Have the roofing contractor cut a minimum hole
for the refrigerant lines of 1.75". Check local
codes, a separate hole may be required for the
electrical power to the condenser.
/////////////////////////////CAUTION////////////////////////////////
DO NOT KINK OR CRIMP REFRIGERANT
TUBING WHEN INSTALLING IT.
////////////////////////////////////////////////////////////////////////////
3. Route the refrigerant lines through the roof
opening.
Follow straight line routing whenever possible.
Any excess tubing MUST be retained within the
building.
4. Spiral any excess length of pre charged tubing
inside the building. Use a horizontal spiral (as
illustrated) to avoid any traps in the lines.
5. Have the roofing contractor seal the holes in the
roof per local codes.
6. The flexible end of the tubing must be installed
behind the icemaker; it is to be looped down from
the ice machine connection area then back up the
wall behind the ice machine. This allows
un-stacked units to be pulled out for service
Mac 6 Connections:
The condenser circuits used for the ice machine
are located in the area shown, and are labeled.
This Scotsman ice machine uses R-22, be certain
that the circuit being used also contains R-22, not
dry air or R-502.
If in doubt about the type of refrigerant, do not
complete the connections at the ice machine end
until the tubing and condenser circuit have been
connected, evacuated and a few ounces of R-22
added.
April, 1993
Page 6
FOR THE INSTALLER: Coupling Instructions
MCM1462R
////////////////////////////////CAUTION/////////////////////////////////
The couplings on the sets of precharged lines are
self sealing when installed properly. Carefully
follow the instructions:
1. Remove the protector caps and plugs. Wipe the
seats and threaded surfaces with a clean cloth to
be certain that no foreign matter remains on them.
2. Lubricate the inside of the couplings, especially
the O-Rings with refrigerant oil.
••The 1/2 inch discharge line (schrader valve
end) goes to the remote condenser fitting
marked “discharge line”.
••The 3/8 inch liquid line (schrader valve end)
goes to the remote condenser fitting marked
“liquid line”.
Final Connections:
3. Begin tightening the couplings together by
hand, then using two wrenches (it is important that
ONLY the nut on the precharged lines be turned,
the other parts of the couplings must NOT be
allowed to turn or the process will tear out the
diaphragms and they will be loose in the
refrigeration system) tighten the coupling until it
bottoms out or a definite increase in resistance is
felt.
TIGHTENING THE QUICK CONNECTS
SCHRADER
VALVES
••The 1/2 inch discharge line goes to the
icemaker fitting marked “discharge line”.
••
The 3/8 inch liquid line goes to the icemaker
fitting marked “liquid line.”
LIQUID LINEDISCHARGE LINE
INSULATION
4. Using a marker or pen, mark a line lengthwise
from the coupling union nut to the bulkhead. Then
tighten the coupling and additional 1/4 turn. As the
nut turns, the line will show when 1/4 turn is made.
5. After all connections are made, and after the
king valve has been opened, check the couplings
for leaks.
April, 1993
Page 7
DETAIL OF JUNCTION BOX
MCM1462R
FOR THE ELECTRICIAN
SEE NAMEPLATE for current requirements to
determine wire size to be used for electrical
hookup. When the cuber and the remote
condenser are connected, each must be grounded
to the other using the ground screws provided in
the respective junction boxes. The cuber then
requires a solid chassis to chassis earth ground
wire. See Wiring Diagram.
Be certain the cuber is connected to its own
electrical circuit and individually fused. Voltage
variation should not exceed ten percent of the
nameplate rating, even under starting conditions.
Low voltages can cause erratic operation and may
be responsible for serious damage to the
icemaker.
ELECTRICAL CONNECTIONS
The Scotsman remote condenser is designed to
be powered from the ice machine. There is a
separate electrical junction box at the back of the
ice maker for the remote condenser. Wire the
remote condenser to the ice maker in accordance
with local and national electric codes. All outdoor
wiring must be in rainproof conduit.
The Mac 6 is connected to the ice machine’s
electrical circuit, but draws no power from it.
The condenser fan motor will run whenever the
compressor is running.
Electrical connections are made at the rear of
the icemaker, inside the junction box.
All external wiring should conform to the
national, state and local electrical code
requirements. Usually an electrical permit and
services of a licensed electrician will be
required.
GROUND
SCREW
HAND
DISCONNECT
SWITCH
POWER
SUPPLY
INTERCONNECTING
WIRES
REMOTE CONNECTION
April, 1993
Page 8
FOR THE PLUMBER
MCM1462R
The recommended water supply line is a 3/8-inch
O.D. copper tubing with a minimum operating
pressure of 20 PSIG and a maximum of 80 PSIG.
Connect to cold water supply line with standard
plumbing fittings, with shut off valve installed in an
accessible place between the water supply and
the cuber. ln some cases a plumber will be
required.
Water Limitations:
An ice machine is a food manufacturing plant, it
takes in a raw material, water, and turns it into a
food product, ice. The purity of the water is very
important in obtaining pure ice and in maximizing
product life. It is generally better to filter the water,
although there is no one filter that will cure all
water problems. A good filter combined with a
polyphosphate feeder gives about the best overall
performance.
DRAIN
Connections: All drains are gravity type and must
have a minimum of 1/4-inch fall per foot on
horizontal runs. The drains to be installed to
conform with the local plumbing code. Install a
vertical open vent on drain line high point to insure
good draining. The ideal drain receptacle is a
trapped and vented floor drain. Recommended bin
drain is 5/8 inch O.D. copper tubing and should be
vented and run separately. Insulation for high
humidity areas is recommended.
The ice machine sump drain is 3/4" FPT. There
must be a vent at this connection for proper sump
draining.
POTABLE
WATER
SUPPLY
HAND
SHUT OFF
VALVE
AIR GAP BETWEEN
DRAIN LINES AND
BUILDING DRAIN
SUMP DRAIN MUST
BE VENTED
3/4" FPT
OPTIONAL
FILTER
3/8" MALE FLARE
BIN
DRAIN
WATER SUPPLY AND DRAIN CONNECTION
April, 1993
Page 9
Loading...
+ 21 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.