Scotsman Glykool 130+ Installation Manual

Page 1
Glykool 130+
Water Cooled Remote Cooler
INSTALLATION MANUAL
DO NOT REMOVE FROM COOLER
SERIAL NUMBER
PI52966/ WDS INS 111 ISSUE 1 APPROVED BY B Tam DATED August 2006
Page 2
Contents
Page
Glykool 130+ Service Programme 3
Glykool 130+ Installation Guide 4
Heat Dump General Guidelines 5
Glykool 130+ Installation Instructions 6
Glykool 130+ Dismantling / Decommissioning Procedure 7
Adjustment & Maintenance Requirements 8
Methods of Cleaning 8
Portable Appliance Testing (PAT) 9
Thermal Cut-Out 9
Prevention of Freezing 10
Electronic Control 11
Glycol Concentrations 13
Fault Diagnosis 14
Technical Specification 18
Spare Parts Identification 20
System Schematics 22
Heat Dump Installation Instructions 24
Heat Dump Dismantling / Decommissioning Procedure 26
Methods of Cleaning the Heat Dump 28
- 2 -
Page 3
Glykool 130+ Service Programme
The Glykool range of glycol coolers have been designed to be reliable and simple to operate. The coolers have been designed to offer a technical solution to the growing demand for colder and colder dispensed product; this is best achieved by the use of sub-zero glycol.
The Glykool cooler use well-known and well-proven mechanical refrigeration technology, but also encompasses a number of technical changes, which will enhance both the performance and reliability of this system.
Refrigerant flow around the system is controlled via a capillary tube that optimises the capacity of the unit under certain operating parameters.
This cooler underwent a number of through quality checks before leaving the factory to ensure the minimum number of faults occur during its life. However, to ensure that this cooler can meet the demands it has been designed for, it must be installed and maintained in accordance with the manufacturers guidelines. This information can be found later in this booklet, which must remain with the unit at all times.
- 3 -
Page 4
Glykool 130+ Installation Guide
On installation, a number of important rules must be observed to be sure the cooler operates correctly.
Ensure the cooler base is installed in a well-ventilated location with no obstructions to the side and rear panel ventilation slots. The unit must not be installed in an area where it will be exposed to temperatures that are likely to cause freezing (below 0°C) in excess of 32°C
Ensure the unit is installed on a level surface and is filled to the overflow, with a 50% glycol/cold water mix below 24°C.
Dose the water tank with Kleencare SP920 in accordance with instructions supplied with the Kleencare kit, taking note of the health and safety data sheets provided.
Ensure the header tank is filled to the maximum level with a 30% glycol/cold water mix to prevent freezing of the tubes connecting the heat dump to the base unit, which may be exposed to sub-zero temperatures (See Glycol Requirement Chart)
Before switching on the unit, turn the line clean switch to the ‘off’ position to enable the glycol lines to be fully primed. Once this is complete, turn the switch to the ‘on’ position.
Ensure that the coolant re-circulation pump and tubing connecting the heat dump are primed with coolant, that there are no air locks or restrictions and that the coolant is freely returning to the header tank. Top up the header tank to the maximum level after priming.
The header tank level must be regularly checked and maintained with the correct ratio of 30% glycol/water mix.
Ensure that all the tubing connections to the product coils and recirculation pump are well insulated with Armaflex.
Ensure that the python run is not excessive and is routed away from external heat sources. Maximum lift is 10 m. Maximum run is 50 m.
Notes:
All water cooled units are fitted with an auto reset thermal switch to protect the compressor should the glycol level drop, the heat dump become blocked or the glycol pump fail.
The electronic control is fitted with a delay on the power up. The delay allows for the control to self-check
- 4 -
Page 5
Heat Dump General Guidelines
It is important that the heat dump is sited correctly to enable it to work efficiently. The guidelines below should be adhered to wherever possible.
Ensure the unit is sited on an outside wall (preferably non-south facing) in the correct orientation out of direct sunlight.
Ensure there are no other heat sources, i.e. a condensing unit or another heat dump, in the immediate vicinity, where hot air may be re­circulating.
Use the recommended tubing (15mm O/D, 10mm I/D Special EVA) to connect the base unit to the heat dump. Do not use PVC braided tube, as this is not compatible with glycol and will degrade over a period of time.
Do not exceed the recommended distance and lift from the base unit to the heat dump of 10 m lift / 50 m run.
The heat dump must be connected using a minimum of 1.5mm two core cable. If a smaller cable is used, a voltage drop will occur which may cause the fan motor to run at a reduced speed.
If the unit is to be installed inside a building or room, ensure that there is adequate ventilation within the room to enable the heat to be dissipated effectively. Temperatures within the room should not exceed 32°C.
Do not kink the flow and return tubes, which would restrict the coolant flow.
Do not insulate the flow and return lines.
The flow and return lines must not be strapped together, as heat
transfer between the two will affect the system performance.
Ensure that the heat exchanger matrix of the heat dump is kept clean and free from obstructions. It is recommended that it should be cleaned with a soft brush at regular intervals (see maintenance schedule).
To enable the heat dump to be mounted on a flat surface, a floor standing mounting kit is available as an option. (Order part number 09­0203-01)
For details on use and mounting of the heat dump, refer to installation instructions on page 24.
- 5 -
Page 6
Glykool 130+ Installation Instructions
This unit should be installed and serviced by a suitably trained person. Sealed plugs may be fitted to new units.
Installation Procedure
Unpack the unit from its transportation packaging and visually inspect for any signs of the damage.
Site the unit in a convenient location in the cellar or room and ensure that the mains electricity supply is within 2 m and in an area allowing free circulation of air.
The unit should be fitted with a correctly fused and wired 13 amp plug or alternatively to a standard Euro plug to IEC83: 1975.
Site the heat dump in a convenient location, preferably in a non-heat sensitive and shaded area on the outside of the building. If it cannot be installed outside, ensure that the area is well ventilated and free from other heat sources. Please check the Heat Dump General Guidelines on page 5 for further details.
WARNING: THIS EQUIPMENT MUST BE EARTHED
The Wires in this Mains Lead are Coloured in accordance with the following Code: Green and Yellow Earth Blue Neutral Brown Live
As the Colours of the Wires in the Mains Lead of this Appliance may not correspond with the Coloured Markings identifying the Terminals in the Plug to be fitted proceed as follows:
The Wire which is coloured Green and Yellow MUST be connected to the terminal in the Plug that is marked with the letter‚ E™ or by the earth symbol, coloured Green or Green and Yellow.
The Wire which is coloured Blue MUST be connected to the Terminal in the Plug that is marked with the letter‚ N™ or coloured Black.
The Wire which is coloured Brown MUST be connected to the Terminal in the Plug that is marked with the letter‚ L™ or coloured Red.
The mains plug must be located in an accessible position.
- 6 -
Page 7
Ways the Glykool 130+ should NOT be used
This unit is intended for use as a cooling unit to cool beers, largers and ciders and glycol to the correct temperature. It is designed to be installed in the system between the bulk storage facilities and the dispense head with the product(s) passing through the cooling coil(s) where fitted in the unit.
There are NO other recommended uses for the equipment
Correct Safe Handling
The weight of the units is such that other than moving it across flat ground (which is facilitated by integral castors/wheels) or lifting to a relatively safe height of 12 inches (30 cm) utilising two people, a mechanical lifting device should be used.
Unit Weight
Shipping Weight: 75 kg Operational Weight: 125 kg
WARNING: THIS UNIT IS UNSUITABLE FOR USE BY UNSUPERVISED
CHILDREN, THE ELDERLY AND THE INFIRM
Dismantling / Decommissioning Procedure
Isolate the unit from the mains electricity supply.
Isolate the product supply from where the unit is connected.
Isolate the unit from the coolant lines.
Drain the glycol mixture in the header tank into suitable containers.
Siphon or pump out the water mixture from the bath
WARNING: FAILURE TO REMOVE ALL WATER/GLYCOL COULD
RESULT IN SUBSTANTIAL AMOUNTS OF WATER/GLYCOL BEING
RELEASED FROM THE UNIT WHICH MAY BE DETRIMENTAL TO THE
UNIT AND/OR ITS SURROUNDINGS AND INCREASE THE MAXIMUM
WEIGHT OF THE UNIT.
- 7 -
Page 8
Adjustment & Maintenance Requirements
It is not recommended that the End User makes any adjustments or carries out any maintenance other than:
Visual checks on the mains leads and the plug for their condition
Visual checks of the unit and piper work for evidence of leaks
Visual checks of the condenser grills and vents that they are not
choked or obscured.
Note: There are no user serviceable parts
Methods of Cleaning
Persons performing cleansing and sanitising operations MUST be competent and fully trained in safe methods of use of cleansing and sanitising agents and applications.
Personal protective equipment should always be used.
DO NOT use a water or steam hose to clean the unit whilst still
installed.
It is important that all vents and grills are kept clear (including condenser grills where applicable).
Weekly Line Clean Procedure: By the End User
WARNING: IF THE LINE CLEAN PROCEDURE IS NOT FOLLOWED, THE
SUB-ZERO TEMPERATURE OF THE GLYCOL MIXTURE IN THE BATH WILL FREEZE THE CLEANSING SOLUTION IN THE BEER LINES AND
PYTHON.
Isolate unit from mains electricity supply.
Clean and sanitise the unit’s cooling coils and product lines using
proprietary cleanser/sanitizer of Alkaline Hypochlorite type in accordance to the manufacturer’s recommendations
Start the line clean switch located on the front of the cooler to the ON position and leave for 1 to 2 hours before commencing the line clean.
After the line clean procedure has been completed and the beer has been pulled through from the storage area to the dispense tap, the line clean switch should be switched to the OFF position.
The unit should be allowed to pull down to its normal operating temperature before normal operation is resumed.
The middle position on the line clean switch should not be used, as this will affect the operation of the unit.
- 8 -
Page 9
Annual Cleaning: By a competent Service/Maintenance Engineer
Isolate unit from mains electricity supply.
Remove any extraneous debris from the unit or it’s casing, preferably
with a vacuum cleaner or brush.
Check unit for electrical safety.
Power Isolation Method
The unit is fitted with a single phase, 3 pin, 13 amp plug, fitted with a 13 amp fuse or alternatively a standard Euro Plug to IEC83: 1975
Switch off unit at the socket the plug is installed into
Remove the plug from the socket
WARNING: IF THE MAINS LEAD FITTED TO THIS EQUIPMENT IS
DAMAGED IN ANY WAY, IT SHOULD BE REPLACED. ONLY A FULLY
TRAINED ENGINEER MUST UNDERTAKE THIS CHANGE.
Portable Appliance Testing (PAT)
An additional test point has been fitted to the top of the rear panel of the unit to provide a connection for PAT testing of the units on site. The tank drain exits the unit via a 1/2 “ bulk head situated on the lower part of the left hand panel. The shut-off valve can be accessed by removing the front lower grill. Glycol flow and return connections are indicated by a coloured disc (red disc for flow to the heat dump and blue for return from the heat dump).
Decommissioning of the glycol lines should be undertaken before decommissioning of the 24V electrical socket in order to prevent the ingress of glycol/water into the electrical socket.
Thermal Cut-Out
The unit is fitted with a thermal cut-out which will protect the refrigeration system in the unlikely event of a fault in the glycol /heat dump system. The thermal cut-out will isolate the power supply to the compressor if the heat of the discharge lines increases above 65°C. The compressor will not cut back in until the temperature in this line falls to below this temperature.
- 9 -
Page 10
Prevention of Freezing
Unit Freezing
It is recommended that the unit be sited in such a way as not to expose it to temperatures likely to cause freezing. If the unit is to be sited in an unheated area, it would be wise to the insulate all the pipe work and provide some form of emergency heating, which should be controlled by a frost-stat and sited in close proximity to the unit.
In the event of freezing up occurring, the following action is recommended:
Isolate unit form the mains electricity supply
Isolated product supply from unit
Apply gentle warmth to the general area of the unit and its pipe work
Check for obvious leaks
Turn on water supply whilst continually watching for leaks
Reconnect product supply
Reconnect mains electricity supply
Observe unit running for a short period watching out for leaks, strange
noises and the any other form of malfunction
If no problems are observed, then normal operation of the unit may be resumed.
Product Freezing
A product freeze up will only occur if the line clean procedure is not followed. In the event of a product freeze up, the following procedure should be followed:
Switch the line clean to the ON position.
Allow the unit to run in ‘line clean’ mode for one hour.
Check to see if the lines are still frozen by opening the dispense tap.
If no flow is observed from the dispense tap, the unit should remain in
‘line clean’ mode for another hour before checking the dispense tap again for flow.
When flow is observed from the dispense tap, switch the line clean to the OFF position.
Operational Temperature Range
Minimum Temperature: 5°C Maximum Temperature: 32°C
This unit may contribute to the ambient temperature
- 10 -
Page 11
Electronic Control
The electronic control is intended to the used to control the temperature within the water/glycol bath. There are no other recommended uses for this electronic control. The control is fitted with a delayed start and the compressor will start within 4 minutes of the unit being turned on.
Adjustment & Maintenance Requirements
The electronic control has no serviceable parts and requires no maintenance. It is not recommended that the end user make any adjustments to the electronic control as this may change the function /operation of the control.
Electronic Control Setting Procedure
This unit has been supplied with an electronic control thermostat. The electronic control is of the ELREHA type and is preset to cut-out at a temperature of –2°C. The control is factory set and a fully trained engineer should only undertake any adjustments. If a lower temperature setting is required adjustment of the electronic thermostat is as follows:
With the unit switched on, press button ‘P’ and the display will show ‘P01’
Using the ‘UP’ arrow key, press in single operations until ‘P09’ is displayed
Press button ‘P’ to display the preset code ‘00’ and scroll using the arrow keys until ’21’ is displayed
Press button ‘P’ to enter the programming mode and then scroll back to ‘P02’ using the arrow keys and press button ‘P’ again
The preset temperature will now be shown and using the arrow keys, adjust the display to the required temperature.
Press button ‘P’ to confirm the temperature and either wait for approximately 1 minute or turn the unit off/on to revert the display back to showing the bath temperature
Elreha Electronic Control
- 11 -
Page 12
Parameter List for Elreha TARN1179 K004
No. Description Code Default
Setting
P01
P02 Control set point can be changed
P03 Switching differential (hysteresis)
P04 Highest adjustable set point 21 P05 Lowest adjustable set point 21 P06 Sensor Correction 21 0.0K -10.0K…10.0K P07 Minimum idle time of refrigeration 21 3 min 0…99 min P08 Minimum run time of refrigeration 21 3 min 0…99 min P09 Access code - 0 -100…100
Actual sensor temperature in °C (display only)
at any time within the limits set by P04 and P05
of control set point
- -
-
21 0.2K 0.2K…10K
-2.0°C
5.0°C -35°C…100°C
-10°C -35°C…P04
Range
-40°C …110°C
P04…P05
- 12 -
Page 13
Glycol Concentrations
Food grade mono propylene glycol should only be used with this unit. The freeze point of glycol depends on the concentration of glycol to clean water mixture. If insufficient concentrations of glycol are used, the system may freeze.
Glycol Concentration for Glycol Bath
It is recommended that a 50% glycol / 50% clean water mix is used for the glycol bath. This will protect a system down to –15°C and below
Glycol Concentration for Heat Dumps
A 30% glycol / 70% clean water mix will protect the system down to –13°C.
The amount of glycol required for the heat dump, Add 2.5 pints (1.4 Litres) for the glycol tank to the length of pipe work as shown in the following table:
Glycol Quantities for Heat Dump Pipe Work Length (flow and return)*
Feet 10 20 30 40 50 60 70 80 90 10 11 12 13 14 17 19
Pints .5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0
Metres 3 6 9 12 15 18 21 24 27 30 33 36 39 42 45 48
Litres .3 .6 .9 1.2 1.5 1.8 2.1 2.4 2.7 3.0 3.3 3.6 3.9 4.2 4.5 4.8
*based on the use of the correctly specified tube with an internal bore of 10mm
- 13 -
Page 14
FAULT DIAGNOSIS FLOW CHART No.1
Has there been
running?
or exposed to high
temperatures?
Is the unit’s bath
temperature at
its set point?
No
Change capacitor
and start relay
No
Is the
compressor
No
Faulty Compressor
No
Yes
Yes
Is line clean
switch on?
End
COMPRESSOR
No
Yes
Switch line clean off
Is the
compressor
running?
Is the python
length excessive
No
Check for
refrigerant leaks
Yes
Re-site Unit
No
Yes
Is the unit in a
high ambient
temp (+32°C)?
Yes
Re-route python
and re-site unit
closer to dispense
point
No
excessive
product draw?
Yes
Leave unit to
recover
- 14 -
Page 15
FAULT DIAGNOSIS FLOW CHART No.2
min
marks?
the pump?
Plug pump into
Top up to maximum
level and check for
Go to Diagnostic
e tubing is the
Is pump plugged
No
Check for 240v
No
GLYCOL PUMP (HEAT DUMP)
Yes
supply at
connection
Yes
Faulty pump motor
No
Faulty Pump
into its mating
connection?
No
Internal wiring fault
Ensure pipes are
together and away
from heat sources
No
connection
Chart No.3
Yes
Is the glycol
mixture re-
circulating?
not secured
ensur
Does the pump
run?
leaks
Yes
No
Clear blockage or
restriction and
correct type
Yes
No
Open shut off
valves
Yes
Is header tank
glycol level
between max-
Yes
Is the glycol
mixture
recirculating?
No
Are the John
Guest shut off
valves open on
Yes
Have the glycol lines collapsed, been restricted,
blocked or
secured together?
- 15 -
Page 16
FAULT DIAGNOSIS FLOW CHART No.3
flow?
Change transformer
Is the heat dump
Plug heat dump
connection into
Clean radiator
Heat dump is sited in full
blown
HEAT DUMP
No
Yes
Check for 24v supply at heat
dump
Check outlet socket on base unit for 24 volts
connected to
unit?
Yes
No
No
socket
Replace Fan Motor
Yes
Is the heat dump
fan running?
Wiring fault
between base unit
and heat dump
matrix
Yes
Yes
Is the radiator
matrix blocked,
restricting air-
No
sunlight or near other
sources of heat without
adequate ventilation
Re-site heat dump
No
Check if fuses in
transformer have
Yes
Replace Fuses
Check for wiring
fault before
restarting unit
- 16 -
No
Page 17
ump is ok and
FAULT DIAGNOSIS FLOW CHART No.4
LID PUMP
Replace Motor
Yes
Check pump is
plugged into
socket
No
Reconnect plug
with socket
Is the lid pump
running?
Change Pump
Yes, But Slow
Yes
P there is no fault
Yes
Is there flow
around the
system?
No No
Ensure service valves
are open
- 17 -
Page 18
Technical Specification
Unit Type Glykool 130+ Water Cooled Remote Cooler Compressor
Cubic Capacity Refrigeration Capacity Starting Current Run Current
Water Pump
Lift Flow Rate Motor Output Motor Speed IP Rating Electrical Connection Water Connection
Glycol Pump
Lift Flow Rate Drive Motor Output Motor Speed IP Rating
Switches & indicators
Compressor On Line Clean Switch
Condenser/Compressor Fan Motor
Motor Output Motor Speed IP Rating
Fan
Diameter Material Rotation
Water Bath
Material Insulation Capacity
Glycol Tank
Material Capacity
Heat Exchanger
Type Material Brazed Joints
Totally Sealed Hermetic Compressor 34 cc 1320 W @ -6C 32 A
7.2 A Totten 3 Stage Top Mounted 16 m 13 Litres/min 80 W 1475 rpm IP 52 Euro Plug/Socket (Dura plug in lead) 15 mm Plain Tails (John Guest) Totten 2 Stage Base Mounted 12 m 13 Litres/min Magnetically Coupled 80 W 1475 rpm IP 52
Red neon located on electronic control Single pole switch with red neon located on front of unit
10 W 1400 rpm IP 22
10” (250 mm) Aluminium Counter Clockwise (back to front)
ABS CFC free PU foam ES65 low density 60 Litres
Medium density polyethylene (Natural) 9 Pints (see Glycol Requirement Chart)
20 Plate Stainless Steel 99% Copper
- 18 -
Page 19
Unit Type Glykool 130+ Water Cooled Remote Cooler Overall Dimensions
Height Depth Width
Weight
Lid Base Heat Dump Total Shipping Weight Total Operating Weight
Power Requirements
Mains Supply Protection Power Consumption Fuse Requirements
Transformer
Input Voltage Output Voltage VA rating Primary Fusing Secondary Fusing
Product Coils
Length Options Diameter Material No. Off 3.5m (short) No. Off 8 m (medium) No Off 12 m (long)
Refrigerant
Type Amount
Expansion Valve
Type
Kleencare Kit
3 x 50ml Bottles Application Label
Electronic Control
Dimensions (HxWxD) Voltage Switch Capacity Peak Switching Capacity Power Consumption Protection Class Probe Accuracy
Heat Dump
Dimensions (HxWxD) Weight Fan Motor Fan Blade Cover Water Connections Flat Roof Mounting Bracket
950 mm 660 mm 540 mm
13 kg 52 kg
8.6 kg 75 kg 125 kg
220 V – 240 V 50 Hz Must be installed with RCD 1597 W 13 A
220 V – 240 V 50 Hz 24 V AC 90 VA 1 A (F1Amp)
6.25 A (T6.3Amp)
3.5 m up to 12 m 3/8” OD (10 mm) 316 Grade Stainless Steel 12 max 10 max 8 max
R134a (HFC) 375 g
0.64 mm Capillary
One kit supplied with each unit
35 mm x 76 mm x 56 mm 220 V – 240 V 50-60 Hz 14 A 30 A for 4s
0.2 VA IP 54 from front +/- 0.05°C (-1°C to –18°C temperature range)
360 mm x 3410 mm x 600 mm
8.6 kg 10 W 24 V AC 10” x 31° Pitch ABS 15 mm Copper Tube (John Guest) Option for floor standing operation
- 19 -
Page 20
Spare Parts Identification Sheet
CM46450 34cc Compressor
MO46690 Condenser fan motor 240 Volt
OP71381 Fan blade 10” sucker
PI42589 Thermal protection switch
PU42641 SPC43 Lid mounted water pump
PU72046-01 Base mounted glycol/water pump
- 20 -
Page 21
MO46688 Heat Dump fan motor 24 Volt
PI51518 Electronic Control
PI42544 90 VA Transformer
PU73983 RG 500 Pump
- 21 -
Page 22
System Schematics Wiring Diagram: Water Cooled Cooler
- 22 -
Page 23
System Schematic – Typical Layout
- 23 -
Page 24
Heat Dump Installation Instructions
This unit should be installed and serviced by a suitable trained person
Site the dump in a convenient location, preferably in a non-heat sensitive and shaded location on the outside of the building. If it cannot be installed outside, ensure that the area is free from other heat sources and is adequately ventilated to prevent heat build up form the hot exhaust air from the heat dump. In either situation, ensure that there is free air circulation around the heat dump. The maximum height that the heat dump should be above the cooler is 10 metres.
Fitting Instructions
Unpack the unit from its transportation packaging and visually inspect for signs of damage.
Remove the wall-mounting bracket from the assembly, (mounted on lift off hinges). Slacken the two fixing screws securing the cover/fan assembly to the condenser matrix, swing the cover open and lift off the assembly.
With reference to drawing above, drill the surface onto which the heat dump is to be fitted at the stated mounting hole centres ensuring that adequate clearance is allowed around the heat dump to allow future access for cleaning. The wall-mounting bracket can be used as a guide for marking its hole centres. Ensure that the wall-mounting bracket is mounted squarely to ensure level movement of the condenser matrix when fitted.
Either mark the position of the third mounting screw at the time of marking the wall mounting bracket position, or after fitting the wall mounting bracket hang the condenser matrix on, close against the
- 24 -
Page 25
mounting surface and mark the fixing position. The third fixing screw will pass through the hole in the condenser matrix. The retaining clamp is fitted over the screw (as shown below), which can then be tightened to retain the condenser matrix.
Connect the flow and return pipe work from the base unit to the fittings on the heat dump labelled “FLOW” and “RETURN” and secure the pipes to the mounting surface so that the weight of the pipes is not being carried on the heat dump fittings. Do not kink the pipe work, as this will restrict coolant flow. Do not insulate the pipe work. (Pipe work mounted on an exterior surface may be insulated if it is felt that due to extreme conditions freezing may occur). Do not strap the flow and return pipes together as heat transfer between the two will affect the system’s performance.
Route a twin core 24-volt supply cable through the lower guide tube and then through the strain relief grommet positioned below the two way terminal block on the condenser matrix. The wires are not polarised and may be fitted either way round.
Ensure that the amount of cable entering through the main cover is not excessive and cannot become entangled in the fan blade. Tighten the strain relief grommet to support the cable. This should not be the only means of support for the cable, therefore fix back to the mounting surface at regular intervals along the cable length.
After the condenser matrix is fully fitted to the mounting surface, hang the cover/fan assembly onto its hinges.
With the cover/fan assembly open, connect the wires from the fan to the terminal block. Ensure that the wiring from the fan is routed through the plastic clip provided to prevent the possibility of the wires becoming entangled in the fan blade (as shown on the next page)
- 25 -
Page 26
Connect the wiring and the pipe work to the cooler following the instructions supplied with the cooler.
Recommended Materials for Heat Dump to Cooler Connections
Pipe work: 15 mm OD x 10 mm ID COBRACOL tubing Cable: 1.5 mm sq, 2 core PVC covered (no earth)
This unit is intended for use in conjunction with cooling units manufactured by Scotsman Beverage Systems. It is designed to be connected at the end of the water/glycol recirculation lines as a means of removing heat.
There are NO other recommended uses for this unit.
Heat Dump Dismantling /Decommissioning Procedure
Isolate the unit from the base cooler electricity supply
Disconnect the recirculating coolant inlet and outlet pipes
Correct Safe Handling
Handling of this unit offers no specific hazard Unit weight: 9 kg (20 lbs) dry.
- 26 -
Page 27
Minimum distances from mounting the heat dump from vertical and horizontal surfaces.
Drilling positions for mounting holes
- 27 -
Page 28
Methods of Cleaning the Heat Dump
Personal protective equipment should always be worn.
Do not use a water or steam hose to clean the unit whilst still installed
It is important that all the vents and grills are kept clear (including
condenser grills where applicable).
Maintenance Twice Annually: By a competent service maintenance engineer
Isolate the unit from the base cooler electricity supply
Open the unit to access both sides of the condenser matrix and remove
any extraneous debris from the unit or its casing, preferably using a vacuum cleaner or brush
Check the unit for electrical safety
Power Isolation Method for the Heat Dump
Switch off the socket that the base cooler unit is installed into Remove the plug from the socket
Prevention of Freezing
The recommended concentration of glycol to water is 30%/70% which will protect the system down to –13°C. In the event of extreme weather
conditions and the unit freezing, the following action is recommended:
Isolate the unit from the base cooler electricity supply
Apply gentle warmth to the general area of the unit and its pipe work,
taking care not to scorch or burn the insulation tubing surrounding the pipes
Check for obvious leaks
Reconnect the base cooler mains electricity supply
Observe the unit running to a short time, watching for leaks, strange
noises and any form of malfunction. If no problems are observed, the normal operation of the unit may be resumed.
Recommended Minimum and Maximum Ambient Temperatures
Minimum –5°C (nb 30% glycol/ 70% water mix) Maximum 32°C
WARNING: THIS UNIT IS UNSUITABLE FOR USE BY UNSUPERVISED
CHILDREN, THE ELDERLY AND THE INFIRM
- 28 -
Loading...