The service manual you are reading is intended to
provide you, and the maintenance or service
technician, with the information needed to install,
start up, clean, maintain and service this ice
system.
Table of Contents
FOR THE INSTALLER: Specifications ······························ Page 2
FOR THE INSTALLER ······································ Page 3
FOR THE ELECTRICIAN ····································· Page 4
FOR THE PLUMBER ······································· Page 5
FOR THE INSTALLER: Final Check List ····························· Page 6
INITIAL START UP ········································ Page 7
The is the freezer portion of a commercial ice
machine. It is designed to be connected to the
condensing section of a refrigeration system,
specifically a supermarket system.
CLEANING and SANITATION ·································· Page 14
SERVICE DIAGNOSIS ······································ Page 18
SERVICE DIAGNOSIS ······································ Page 19
CONTROL SYSTEM DIAGNOSTICS······························ Page 20
REMOVAL AND REPLACEMENT ································ Page 21
REMOVAL AND REPLACEMENT: Bearing And Breaker···················· Page 22
REMOVAL AND REPLACEMENT ································ Page 23
REMOVAL AND REPLACEMENT ································ Page 24
REMOVAL AND REPLACEMENT: Evaporator ·························· Page 25
REMOVAL AND REPLACEMENT: Gearmotor ·························· Page 26
This manual was printed on recycled paper, keep it
for future reference.
Note the Warning symbol where it appears. It
marks a potential hazard.
November 2000
Page 1
Double System RL
FOR THE INSTALLER: Specifications
BACK VIEW
15.53"
20.84"
9.43"
5.25"
3"
17.8"
18.8"
21.66"
The machine is designed to fit a variety of
Scotsman storage bins such as BH800 or SB480.
Installation Limitations: The machine is designed
for indoor installations only.
MinimumMaximum
o
Air Temp50
Water Temp40
F100oF
o
F100oF
Voltage198 VAC253 VAC
Water Pressure20 psi80 psi
RO Water Limitation: Water conductivity must be
no less than 35 microSiemens/cm.
3.1"
SUCTION LINE CONNECTION
LIQUID LINE CONNECTION
POTABLE WATER INLET 3/8" FLARE
DRAIN 3/4" FPT
7
"
8
1
"
2
ELECTRICAL INLET
Scotsman Ice Systems are designed and
manufactured with the highest regard for safety
and performance. They meet or exceed the
standards of U.L., N.S.F., and C.U.L.
Scotsman assumes no liability or responsibility of
any kind for products manufactured by Scotsman
that have been altered in any way, including the
use of any parts and/or other components not
specifically approved by Scotsman.
Scotsman reserves the right to make design
changes and/or improvements at any time.
Specifications and designs are subject to change
without notice.
SPECIFICATIONS:
ModelCabinet SizeSystem RefrigerantBTUH required*VoltageIce Type
FME2404RL42"w x 27"h x 24"dR-404A12,000208-230Flake
NME1854RLsameR-404A12,000208-230Nugget
FM2402RL-CsameR-2212,500208-230Flake
NM1852RL-CsameR-2212,500208-230Nugget
FME3004RLsameR-404A15,000208-230Flake
NME2504RLsameR-404A15,000208-230Nugget
* Use to determine needed condensing unit capacity. Not an AC load.
January 2004
Page 2
FOR THE INSTALLER
Select the Location:
The unit can only be installed indoors within
the limitations described on page 2.
The ice machine will have to be connected
to the building’s R-404A refrigeration
system, check to be sure that the system
has AT LEAST enough extra capacity to
handle the BTUs (from table on page 2) per
hour @ 110
(assume a 0
Storage Bin:
Scotsman’s B90 will be the presumed bin of
choice. If using the bin extension BX87,
install heavy duty leg kit KLP4 and place the
bin into position.
Remove the paper tape from the bin edge
gasket, and install the bin extension onto
the B90.
Remove the paper tape from the bin
extension top edge, and using a mechanical
lift, install the machine onto the top of the
storage bin assembly.
Fasten the ice machine to the bin using (4)
5/15-18 2.5" cap screws.
Level the assembly by:
a. Turning the leg levelers in or out on the
standard legs.
b. Use shims under the heavy duty legs of
the KLP4.
Locate the Nameplate: The nameplate is
located on the back panel of the machine,
and contains the electrical characteristics
particular to the unit being installed.
0
F. liquid line temperature
0
F. evaporator temperature).
Double System RL
TYPICAL INSTALLATION: ALLOW ROOM FOR SERVICE ACCESS
Ice Machine
BX87 BIN
EXTENSION
B90 STORAGE BIN
Refrigeration Installation:
The skills of a refrigeration technician are
required to connect the ice machine to the
building’s refrigeration system.
Notes:
·
Suction Line and Liquid Line Stubs are at the
back of the cabinet.
·
R-404A models: 1.5 ounces of R-404A
refrigerant is in the system as a holding charge.
·
R-22 models: Nitrogen is the holding charge
·
Be sure there is enough BTU capacity.
·
Be sure the liquid connection is NOT in series
with another liquid line valve.
·
Local Codes must be observed.
·
A P-trap should be installed where there will be
more than 10’ of vertical rise in the suction line.
November 2000
Page 3
Double System RL
FOR THE ELECTRICIAN
CONFORM TO ALL APPLICABLE CODES
Electrical Connections:
Locate the nameplate for the current
requirements, and then determine the
wire size and type per the National
Electric Code. The machine requires a
solid chassis to earth ground wire.
Refer to the wiring diagram. The ice
machine should be connected to it’s
own electrical circuit, and be
individually fused.
Voltage, when the unit is under full
load, must remain within the limitations
listed on page 2.
LOW VOLTAGE CAN CAUSE
EQUIPMENT MALFUNCTION AND/OR
DAMAGE
All external wiring should conform to
the National, State, and local electrical
codes. Usually the services of a
licensed electrician will be required.
DETAIL OF
JUNCTION BOX
JUNCTION
BOX
POWER SUPPLY
November 2000
Page 4
FOR THE PLUMBER
CONFORM TO ALL APPLICABLE CODES
Double System RL
Water Supply:
The recommended water supply line is 3/8" O.D.
copper tubing, with a minimum operation pressure
of 20 PSIG, and a maximum of 80 PSIG. Connect
to cold water using the male flare connection at the
back of the machine. Install a shut off valve in an
accessible space between the ice maker and the
water supply.
SHUT OFF
VALVE
Drain System:
All drains are of the gravity type, and must have a
minimum of 1/4" fall per foot of horizontal run. The
drains must be installed to conform to local
plumbing codes. The use of a vent at the machine
and at the bin will allow the system to drain
properly. Use only rigid tubing for drains; insulation
of the bin drain is recommended.
3/8" MALE FLARE
3/4" FPT
VENT THIS DRAIN
WATER INLET
BIN DRAIN
FLOOR DRAIN
FIELD
SUPPLIED
WATER FILTER
November 2000
Page 5
Double System RL
FOR THE INSTALLER: Final Check List
1. Is the unit installed where the air and water
temperatures are within and will remain within the
limitations for the unit?
2. Is there 6" clearance at the rear of the machine
for utility connections?
3. Has the water supply line be checked for
pressures between 20 and 80?
4. Has the unit been leveled?
5. Has the shipping material been removed from
inside the cabinet?
6. Have the electrical connections been made?
7. Have the drains been installed and checked for
leaks?
8. Has the refrigeration supply been installed and
checked for leaks?
9. Has the bin and cabinet been wiped clean or
sanitized?
10. Has the warranty registration card been
properly filled out and mailed to Scotsman?
11. Has the owner been given the service manual
and been instructed on how to maintain the ice
maker?
13. Has the owner been given the name and
telephone number of the local Scotsman service
agency?
November 2000
Page 6
INITIAL START UP
Double System RL
1. Remove the top and front panels.
2. Open the water valve, and observe that the two
float reservoirs fill up with water and shut off.
3. Switch on the electrical power.
4. Open the hand valves (in the liquid lines).
5. Open the ball valves (in the suction lines).
6. Switch on one master (mode) switch, and
observe:
That liquid line valve opens
·
The gearmotor runs
·
Within a short time, that side of the machine
·
begins to make ice.
Water flows from the water reservoir, and the
·
float drops, letting in more water.
7. Switch on the other master (mode) switch,
observe that:
The liquid line valve opens
·
The gearmotor runs
·
Within a short time, that side of the machine
·
begins to make ice.
Water flows from the water reservoir, and the
·
float drops, letting in more water.
8. With both sides operating, the sight glass should
remain full, and the low side pressure will be about
model types 2404 or 1854 (R-404A):
30 PSIG, + or - 2
·
model types 2402 or 1852 (R-22):
25 PSIG, + or - 2
·
Gearmotor amp draw should not exceed the
nameplate rating.
9. Check the system very carefully for any
refrigerant leaks, repair as needed.
July 2010
Page 7
Double System RL
COMPONENT IDENTIFICATION
Liquid line valve(s)
These valves operate to turn the ice making
process on and off.
When the ice level drops in the ice chute, the ice
level sensor will cause the circuit board to close
the liquid line relay, which energizes the liquid line
valve for that side of the system. The liquid line
valve opens, and liquid refrigerant flows to the
thermostatic expansion valve.
Thermostatic Expansion Valve
The metering device of each system, the valve(s)
sense the temperature of the suction line and vary
the amount of liquid refrigerant that passes through
the valve into the evaporator, thus maintaining a
constant level of refrigeration. TXV’s are factory
set. Do not adjust unnecessarily.
DO NOT ADJUST THE TXV UNTIL THE EPR HAS
BEEN SET.
The superheat setting is 4-8
temperature of the evaporator outlet at the TXV
bulb, and check the low side pressure at the EPR
valve. Convert the pressure to temperature (using
a temperature pressure chart) and subtract the
amount from the outlet temperature. The result is
the superheat. Use an electronic thermometer.
THERMO VALVE
0
F. Measure the
EPR VALVE
EPR: Evaporator Pressure Regulator Valve
This valve maintains a constant pressure on its
inlet (evaporators) side regardless of the pressure
on the outlet (suction) side. The EPR is factory set,
adjust only if needed. After adjusting, re-check
TXV superheat.
EPR Settings:
R-22 models (2402/1852): 25 PSIG
·
R-404A models (2404/1854, 3004/2504): 36
·
PSIG
Evaporators:
Where the water is frozen into ice crystals. As the
water cools, it begins to turn into ice, and the
slowly turning auger lifts the ice, as it is being
made, and forces it up and out of the “breaker” or
spout where the extra water is compressed out of
the ice. The ice then drops through the chute, into
the storage bin.
THERMO
VALVE
LIQUID LINE
VALVE
EVAPORATOR
November 2000
Page 8
Loading...
+ 18 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.