Scotsman FME2400RH Operator’s Manual

TO THE OWNER OR USER:
FME2400RH
The service manual you are reading is intended to provide you, and the maintenance or service technician, with the information needed to install, start up, clean, maintain and service this ice system.
The FME2400RH (remote high side) is the freezer portion of a commercial ice machine. It is designed to be connected to the condensing section of a refrigeration system, specifically a supermarket R-404A system.
Table of Contents
FOR THE INSTALLER: Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 2
FOR THE INSTALLER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3
FOR THE ELECTRICIAN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 4
FOR THE PLUMBER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 5
FOR THE INSTALLER: Final Check List . . . . . . . . . . . . . . . . . . . . . . . . . . Page 6
INITIAL START UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 7
COMPONENT IDENTIFICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 8
COMPONENT DESCRIPTION: Control Box . . . . . . . . . . . . . . . . . . . . . . . . Page 9
COMPONENT DESCRIPTION: Evaporator . . . . . . . . . . . . . . . . . . . . . . . . . Page 10
ELECTRICAL SEQUENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 11
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 12
OPERATION: Refrigeration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 13
MAINTENANCE AND CLEANING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 14
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 15
CLEANING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 16
SERVICE DIAGNOSIS: Condition - No Ice Being Produced . . . . . . . . . . . . . . . . Page 17
REMOVAL AND REPLACEMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 18
REMOVAL AND REPLACEMENT: Bearing And Breaker . . . . . . . . . . . . . . . . . . Page 19
REMOVAL AND REPLACEMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 20
REMOVAL AND REPLACEMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 21
REMOVAL AND REPLACEMENT: Evaporator . . . . . . . . . . . . . . . . . . . . . . . Page 22
REMOVAL AND REPLACEMENT: Gearmotor . . . . . . . . . . . . . . . . . . . . . . . Page 23
CIRCUIT BOARD TESTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 24
Parts lists and wiring diagrams are in the center of this manual, printed on yellow paper.
This manual was printed on recycled paper, keep it for future reference.
Note the Warning symbol where it appears. It marks a potential hazard.
January 1995
Page 1
FME2400RH
FOR THE INSTALLER: Specifications
BACK VIEW
20.84"
9.43"
5.25" 3"
15.53"
17.8"
18.8"
21.66"
The FME2400RH is designed to fit the Scotsman storage bins BH800 or B90. Leg kit KLP4 is recommended when using both the B90 bin and an extension.
Installation Limitations: The FME2400RH is designed for indoor installations only. The machine must also be in a controlled environment where the air temperature does not fall below 50 go above 100
The water temperature must be between 40 and 100
0
F.
0
F.
0
F., or
0
F.
The electrical power supply must not drop below
-5% of the lowest nameplate voltage or go above 10% of the highest nameplate voltage.
3.1"
7
SUCTION LINE CONNECTION
LIQUID LINE CONNECTION
POTABLE WATER INLET 3/8" FLARE
DRAIN 3/4" FPT
⁄8"
1
⁄2"
ELECTRICAL INLET
Scotsman Ice Systems are designed and manufactured with the highest regard for safety and performance. They meet or exceed the standards of U.L., N.S.F., and C.U.L.
Scotsman assumes no liability or responsibility of any kind for products manufactured by Scotsman that have been altered in any way, including the use of any parts and/or other components not specifically approved by Scotsman.
Scotsman reserves the right to make design changes and/or improvements at any time. Specifications and designs are subject to change without notice.
SPECIFICATIONS:
Model Number Dimensions (w/o Bin)
W" x D" H"
FME2400RH-32A 42" x 24" x 27" Flake 208-230/60/1 2.7 15 16,000
Ice
Type
January 1995
Page 2
Basic
Electrical
Minimum
Circuit
Ampacity
Maximum
Fuse
Size
BTU’s
Required
FOR THE INSTALLER
Select the Location: The unit can only be installed indoors
within the limitations described on page 2.
The ice machine will have to be connected to the building’s R-404A refrigeration system, check to be sure that the system has enough extra capacity to handle a minimum of additional 16,000 BTU’s per hour @ 110 (assume a 0 temperature).
Storage Bin: Scotsman’s B90 will be the
presumed bin of choice. If using the bin extension BX87, install heavy duty leg kit KLP4 and place the bin into position.
Remove the paper tape from the bin edge gasket, and install the bin extension onto the B90.
Remove the paper tape from the bin extension top edge, and using a mechanical lift, install the FME2400RH onto the top of the storage bin assembly.
Fasten the ice machine to the bin using (4) 5/15-18 2.5" cap screws.
Level the assembly by: a. Turning the leg levelers in or out
on the standard legs. b. Use shims under the heavy duty
legs of the KLP4. Locate the Nameplate: The
nameplate is located on the back panel of the machine, and contains the electrical characteristics particular to the unit being installed.
Refrigeration Installation: The skills of a refrigeration technician are required
to connect the ice machine to the buildings refrigeration system.
0
F. liquid line temperature
0
F. evaporator
TYPICAL INSTALLATION: ALLOW ROOM FOR SERVICE ACCESS
FME2400RH
FME2400RH
BX87 BIN
EXTENSION
B90 STORAGE BIN
Local Codes must be observed. A P-trap should be installed where there will be
more than 10’ of vertical rise in the suction line.
January 1995
Page 3
FME2400RH
FOR THE ELECTRICIAN
CONFORM TO ALL APPLICABLE CODES
Electrical Connections: Locate the nameplate for the current
requirements, and then determine the wire size and type per the National Electric Code. The machine requires a solid chassis to earth ground wire. Refer to the wiring diagram. The ice machine should be connected to it’s own electrical circuit, and be individually fused.
Voltage, when the unit is under full load, must remain within the limitations listed on page 2.
LOW VOLTAGE CAN CAUSE EQUIPMENT MALFUNCTION AND/OR DAMAGE
All external wiring should conform to the National, State, and local electrical codes. Usually the services of a licensed electrician will be required.
DETAIL OF
JUNCTION BOX
JUNCTION
BOX
POWER SUPPLY
January 1995
Page 4
FOR THE PLUMBER
CONFORM TO ALL APPLICABLE CODES
FME2400RH
Water Supply: The recommended water supply line is 3/8" O.D.
copper tubing, with a minimum operation pressure of 20 PSIG, and a maximum of 80 PSIG. Connect to cold water using the male flare connection at the back of the machine. Install a shut off valve in an accessible space between the ice maker and the water supply.
SHUT OFF
VALVE
Drain System: All drains are of the gravity type, and must have a
minimum of 1/4" fall per foot of horizontal run. The drains must be installed to conform to local plumbing codes. The use of a vent at the machine and at the bin will allow the system to drain properly. Use only rigid tubing for drains; insulation of the bin drain is recommended.
3/8" MALE FLARE
3/4" FPT
VENT THIS DRAIN
WATER INLET
BIN DRAIN
FLOOR DRAIN
FIELD
SUPPLIED
WATER FILTER
January 1995
Page 5
FME2400RH
FOR THE INSTALLER: Final Check List
1. Is the unit installed where the air and water temperatures are within and will remain within the limitations for the unit?
2. Is there 6" clearance at the rear of the machine for utility connections?
3. Has the water supply line be checked for pressures between 20 and 80?
4. Has the unit been leveled?
5. Has the shipping material been removed from inside the cabinet?
6. Have the electrical connections been made?
7. Have the drains been installed and checked for leaks?
8. Has the refrigeration supply been installed and checked for leaks?
9. Has the bin and cabinet been wiped clean or sanitized?
10. Has the warranty registration card been properly filled out and mailed to Scotsman?
11. Has the owner been given the service manual and been instructed on how to maintain the ice maker?
13. Has the owner been given the name and telephone number of the local Scotsman service agency?
January 1995
Page 6
INITIAL START UP
FME2400RH
1. Remove the top and front panels.
2. Open the water valve, and observe that the two float reservoirs fill up with water and shut off.
3. Switch on the electrical power.
4. Open the hand valves (in the liquid lines).
5. Open the ball valves (in the suction lines).
6. Switch on one master switch, and observe: The liquid line valve opens The gearmotor runs Within a short time, that side of the machine
begins to make ice. Water flows from the water reservoir, and the float
drops, letting in more water.
7. Switch on the other master switch, observe that: The liquid line valve opens The gearmotor runs Within a short time, that side of the machine
begins to make ice. Water flows from the water reservoir, and the float
drops, letting in more water.
8. With both sides operating, the sight glass
should remain full, and the low side pressure will be about 30 psig, + or - 2 psig. Gearmotor amp draw should not exceed the nameplate rating.
9. Check the system very carefully for any
refrigerant leaks, repair as needed.
January 1995
Page 7
FME2400RH
COMPONENT IDENTIFICATION
Liquid line valve(s) These valves operate to turn the ice making
process on and off. When the ice level drops in the ice chute, the ice
level sensor will cause the circuit board to close the liquid line relay, which energizes the liquid line valve for that side of the system. The liquid line valve opens, and liquid refrigerant flows to the thermostatic expansion valve.
Thermostatic Expansion Valve The metering device of each system, the valve(s)
sense the temperature of the suction line and vary the amount of liquid refrigerant that passes through the valve into the evaporator, thus maintaining a constant level of refrigeration. TXV’s are factory set. Do not adjust unnecessarily.
DO NOT ADJUST THE TXV UNTIL THE EPR HAS BEEN SET.
The superheat setting is 4-8 temperature of the evaporator outlet at the TXV bulb, and check the low side pressure at the EPR valve. Convert the pressure to temperature (using a temperature pressure chart) and subtract the amount from the outlet temperature. The result is the superheat. Use an electronic thermometer.
EPR: Evaporator Pressure Regulator Valve This valve maintains a constant pressure on its
inlet (evaporators) side regardless of the pressure on the outlet (suction) side. The EPR is factory set, adjust only if needed. After adjusting, re-check TXV superheat.
Evaporators: Where the water is frozen into ice crystals. As the
water cools, it begins to turn into ice, and the slowly turning auger lifts the ice, as it is being made, and forces it up and out of the “breaker” or spout where the extra water is compressed out of the ice. The ice then drops through the chute, into the storage bin.
0
F. Measure the
THERMO VALVE
LIQUID LINE
VALVE
EPR VALVE
THERMO
VALVE
EVAPORATOR
January 1995
Page 8
Loading...
+ 16 hidden pages