Scotsman FME1500 Service Manual

INTRODUCTION
FME1500
To the owner or user: The service manual you are reading is intended to provide you, and the maintenance or service technician, with the information needed to install, start up, clean, maintain, and service this ice system.
The FME1500 features: front service for the evaporator, gearmotor, control box, water reservoir and bin control; electronic circuitry for monitoring ice and water level; a thermostatic expansion valve; and HP62 as the refrigerant.
TABLE OF CONTENTS
FOR THE INSTALLER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
FOR THE INSTALLER: Environmental Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
FOR THE PLUMBER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
FOR THE ELECTRICIAN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
FOR THE INSTALLER: Final Check List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
START UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
COMPONENT DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
ELECTRICAL SEQUENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
CLEANING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
MAINTENANCE: Auger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
SERVICE DIAGNOSIS: Condition - No Ice Being Produced . . . . . . . . . . . . . . . . . . . . . . . . 18
SERVICE DIAGNOSIS: Condition - Low Ice Production . . . . . . . . . . . . . . . . . . . . . . . . . . 21
REMOVAL AND REPLACEMENT: Water Reservoir & Bin Control . . . . . . . . . . . . . . . . . . . . 22
REMOVAL AND REPLACEMENT: Bearing And Breaker . . . . . . . . . . . . . . . . . . . . . . . . . 23
REMOVAL AND REPLACEMENT: Auger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
REMOVAL AND REPLACEMENT: Water Seal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
REMOVAL AND REPLACEMENT: Evaporator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
REMOVAL AND REPLACEMENT: Gearmotor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
REFRIGERATION SERVICE: HP62 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
CIRCUIT BOARD TESTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Parts Lists and Wiring Diagrams are located in the center of this manual, printed on yellow paper.
This manual was printed on recycled paper. Keep it for future reference.
Note this symbol when it appears.
It marks a potential hazard.
August 1993
Page 1
)0(
)257+(,167$//(5
7KHVHPDFKLQHVDUHGHVLJQHGWRILWWKHIROORZLQJ
6FRWVPDQVWRUDJHELQV
%DQGH[WHQVLRQV
ZLWKELQWRS.%7
+7%RU%+
%+XVLQJELQWRS
.%7
%+XVLQJELQWRS
.%7
7KHQRUPDOILQLVKIRUWKH
PDFKLQHLVHQDPHOEXWDQ
RSWLRQDOVWDLQOHVVVWHHO
SDQHONLW63.&0'PD\
EHDGGHGWRWKHPDFKLQH
:KHQLQVWDOOLQJDQHZ
V\VWHPFKHFNWREHVXUH
WKDW\RXKDYHHYHU\WKLQJ
\RXQHHGEHIRUHEHJLQQLQJ
&RUUHFW%LQ
&RUUHFW,FH0DFKLQH
&RUUHFW%LQ7RSLIUHTXLUHG
$OONLWVOHJVDQG
LQIRUPDWLRQUHTXLUHGIRUWKH
VSHFLILFMRE
63(&,),&$7,216,&(0$.(5
0RGHO1XPEHU &DELQHW
'LPHQVLRQV
:['[+
)0($($ [[  $LU&RROHG RXQFHV  
)0(:($ [[  :DWHU&RROHG RXQFHV  
0LQLPXPFLUFXLWDPSDFLW\LVXVHGWRGHWHUPLQHZLUHVL]HSHU1DWLRQDO(OHFWULF&RGH
%DVLF
(OHFWULFDO
&RQGHQVHU
7\SH
$XJXVW
3DJH
5HIULJHUDQW
&KDUJH
5$
0LQLPXP
&LUFXLW
$PSDFLW\
0D[LPXP
)XVH6L ]H
FOR THE INSTALLER: Environmental Limitations
FME1500
Installation Limitations:
This ice system is designed to be installed indoors, in a controlled environment:
Min. Max.
0
Air Temperature 50 Water Temperature 40 Water Pressure 20 psi 80 psi
Voltage -5% +10% (Compared to the nameplate) Operating the machine outside of the limitations is
misuse and can void the warranty.
F 1000F
0
F 1000F
Water Limitations
An ice machine is a food manufacturing plant; it takes a raw material, water, and turns it into a food product, ice. The purity of the water is very important in obtaining pure ice and in maximizing product life. This section is not intended as a complete resource for water questions, but it does offer these general recommendations:
1. Filter the water used to produce ice. That is the water going to the "potable" water connection. Water filters vary in ability and function. Install one that filters out suspended solids to a dimension of 5 microns or smaller. The finer the filter the better, but finer filters will clog sooner than course ones. It may be necessary to add a course filter ahead of the fine filter to prolong filter life.
2. Check with a water treatment specialist for a water test, and recommendations regarding filters and treatment.
Scotsman Ice Systems are designed and manufactured with the highest regard for safety and performance. They meet or exceed the standards of UL, NSF, and CSA.
Scotsman assumes no liability or responsibility of any kind for products manufactured by Scotsman that have been altered in any way, including the use of any part and/or other components not specifically approved by Scotsman.
Scotsman reserves the right to make design changes and/or improvements at any time. Specifications and design are subject to change without notice.
August 1993
Page 3
LEVEL THE ASSEMBLY
FME1500
FOR THE INSTALLER
Location
After uncrating and inspection, the unit is ready for installation. It is important that the machine be installed in a location where it has enough space around it to be accessible for service, and minimum of 6" be allowed to the left, right and top for air circulation on air cooled models. Try to avoid hot, dirty and crowded locations. Be sure that the location for the machine is within the limitations described on page 3.
Storage Bin
Tip the storage bin on its back, using parts of the carton to protect the exterior finish. Install the legs into the threaded holes in the bottom of the bin. Turn the leg levelers all the way in preparation for leveling later. Return the bin to the upright position, remove paper covering the bin gasket.
Install bin top if required. Note: Do not push bin into position, but
lift it there. Pushing a bin, especially one with ice in it, can cause damage to the legs and the leg mounts.
GASKET
Ice Maker
The machine is heavy, so the use of a mechanical lift is recommended for lifting the machine high enough to install on top of the bin. After the unit is placed on the bin, line it up so it is even with the back, left, and right sides. Secure the machine to the bin with the hardware provided with the machine.
FASTEN THE MACHINE
TO THE BIN WITH THE
HARDWARE SUPPLIED
WITH THE ICE MAKER
June 1994
Page 4
FOR THE PLUMBER
Use only 3/4" rigid tubing.
CONFORM TO ALL APPLICABLE CODES
FME1500
Water Inlet
Air Cooled Models: The recommended water supply is cold water. Use 3/8" O.D. copper tubing, connect to the 3/8" male flare at the back of the cabinet. Install a hand valve near the machine to control the water supply.
WATER
COOLED
WATER INLET
HAND SHUT
OFF VALVE
CONNECT TO
COLD WATER
3/8" FLARE
Drains
Air Cooled Models: There is one 3/4" FPT drain at the back of the cabinet, the drain line is of the gravity type, and 1/4 inch per foot fall is an acceptable pitch for the drain tubing. There should be a vent at the highest point of the drain line, and the ideal drain receptacle would be a trapped and vented floor drain.
FILTER, FIELD
INSTALLED
(OPTIONAL)
Water Cooled Models: A separate 3/8" O.D.
copper line is recommended, with a separate hand valve to control it. It is connected to a 3/8" FPT condenser inlet at the back of the cabinet. The water pressure to all lines must always be above 20 psig, and below 120 psig.
ICE MAKER
DRAIN
3/4" FPT
BIN DRAIN
3/4" FPT
Water Cooled Models: In addition to the above
mentioned drain, a separate condenser drain must be installed. Connect it to the 1/2" condenser drain connection at the back of the cabinet.
Storage Bin: A separate gravity type drain needs to be run, similar to the air cooled drain.
Insulation of this drain line is recommended.
August 1993
Page 5
ICE MAKER
JUNCTION BOX
FME1500
FOR THE ELECTRICIAN
CONFORM TO ALL APPLICABLE CODES
The electrical power to the unit is supplied through the junction box at the rear of the machine.
Check the nameplate (located on the back panel) for the voltage requirements, and for the minimum circuit ampacity. The machine requires a solid chassis to earth ground wire.
The ice maker should be connected to its own electrical circuit so it would be individually fused.
Voltage variation must remain within design limitations, even under starting conditions.
POWER
SUPPLY
All external wiring must conform to national, state, and local electrical codes. The use of a licensed electrician is required to perform the electrical installation.
THIS UNIT MUST BE
GROUNDED
June 1994
Page 6
FOR THE INSTALLER: Final Check List
1. Is the ice system installed indoors in a location where the air and water temperatures are controlled, and where they do not exceed the design limitations?
FME1500
2. Is there an electrical service disconnect within sight of the installed machine? Has the voltage been checked, and compared to nameplate requirements?
3. Have all the plumbing connections been made and checked for leaks?
4. Has the machine and bin been leveled?
5. Is there a minimum of 6" clearance at the rear, left, and right of the machine for proper service access and air circulation?
6. Is the water pressure a minimum of 20 psig?
7. Has the machine been secured to the bin?
8. Is there a water shut off valve installed near the machine?
LEVELED?
POWER
SUPPLY?
PLUMBING?
MACHINE
SECURE TO
BIN?
9. Have the shipping blocks been removed from under the gearmotor, the top of the ice chute, and from between the gearmotor and the right side panel?
DRAINS?
August 1993
Page 7
FME1500
START UP
Pre-Start Inspection
1. Remove the front, and left side service panels.
2. Check that the styrofoam shipping blocks under the gearmotor, on top of the ice discharge chute, and between the gearmotor and the right side panel have been removed.
Start Up
1. Go through the prestart inspection.
2. Open the hand valve, observe that water enters the water reservoir, fills the tube from the reservoir to the evaporator, and then shuts off. Check for leaks.
3. Switch the master switch on. The electrical start up sequence is now on
automatic. A. There should be a short (15 second) delay
before the gearmotor starts. B. After the gearmotor starts, the compressor will
start.
3. Inspect the interior of the machine for loose screws or wires. Check that no refrigerant lines are rubbing each other. Check that the fan blade turns freely (air cooled).
4. Check that the unit is installed correctly according to the final check list (page 8).
The suction line temperature at the compressor is normally very cold, nearly to the point of frost up to the compressor body, but not on it.
The air cooled discharge pressure will depend upon air and water temperatures, but should be between 220 psig and 330 psig.
The water cooled discharge pressure should be constant at about 245 psig.
The above numbers are for new, clean machines, you can expect to see some values higher, and some lower between different units.
6. THERE ARE NO ADJUSTMENTS TO MAKE, so replace the panels.
4. On air cooled models, the condenser will begin to discharge warm air, on water cooled models, the water regulating valve will open, and warm water will be discharged into the drain.
5. The unit should soon be making ice, if desired, the low side pressure can be checked: it should be between 30 and 32 psig. Low side pressure may be lower than 30 PSIG when the ambient is under
o
70
F. and higher than 32 when ambient is over
o
90
F.
7. Clean and/or sanitize the storage bin interior, wipe off the exterior with a clean, damp cloth.
8. Give the owner/user the service manual, instruct him/her in the operation of the unit, and make sure they know who to call for service.
9. Fill out the Customer Evaluation and Registration form, and mail it to Scotsman.
June 1994
Page 8
COMPONENT DESCRIPTION
CLEANING DRAIN
TUBE
FME1500
Control Box: Contains the electrical controls that
operate the machine. Low Pressure Cut Out: "A" models only: A
manual reset switch set to shut the machine off should the low side pressure go below 0-4 psig.
High Pressure Cut Out: A manual reset switch sensing the high side refrigeration pressure. It is set to shut the machine off at 450 psig.
Evaporator: A vertical stainless steel tube, refrigerated, and water filled. In it, there is a stainless steel auger.
Reservoir: Float operated, it maintains the water level in the evaporator at a constant level, it also contains the water level sensor.
Water Level Sensor: Senses if there is water in the reservoir to make ice out of. Will shut the machine off it there is none.
CONTROL BOX
Ice Discharge Chute: Directs the ice made by the
evaporator into the storage bin. Ice Level Sensor: An electronic "eye", it senses
the presence of ice in the bottom of the ice discharge chute. Operates to turn the ice machine on and off automatically as the level of ice in the bin changes.
Gear Motor: An oil filled, speed reduction gearbox, driving the auger.
Cleaning Drain Tube: When uncapped and lowered, drains the evaporator.
Compressor: The refrigerant vapor pump. Condenser: Air or water cooled, where the heat
removed in ice making is discharged. Expansion valve: The refrigerant metering
device.
LOW PRESSURE
CUT OUT
RESERVOIR
WATER LEVEL SENSOR
(INSIDE RESERVOIR)
STRAINER
COMPRESSOR
HIGH PRESSURE
CUT OUT
CONDENSER
ICE CHUTE
EXPANSION
VALVE
EVAPORATOR
GEARMOTOR
ICE LEVEL
SENSOR
August 1993
Page 9
CONTACTOR
FME1500
COMPONENT DESCRIPTION: Control Box
Contactor: A definite purpose contactor connecting the compressor to the power supply.
Circuit Board: Controlling the ice machine through sensors and relays. The sensors are: ice level, and water level. The relays are for the gear motor (with a built in time delay to clear the evaporator of ice when the unit turns off) and for the compressor.
Transformer: Supplies low voltage to the circuit board.
Low Pressure Control (Cut Out): A manual reset control to shut off the ice machine when the low side pressure drops below a preset point, 0-4 psig.
Potential Relay: The compressor start relay. On/Off Switch: Manual control for the machine.
LOW PRESSURE
CUT OUT
ON/OFF SWITCH
TRANSFORMER
CIRCUIT BOARD
POTENTIAL RELAY
June 1994
Page 10
Loading...
+ 21 hidden pages