To the owner or user: This manual is intended to
provide you, and the maintenance or service
technician, with the information needed to install,
start up, clean, maintain, and service this ice
system.
This is a modular type ice system that fits a variety
of Scotsman ice storage bins.
Its features include: front service for the freezer,
gear motor, control box, water reservoir, and bin
control; an electronic circuit for monitoring ice and
water level; a thermostatic expansion valve; and
R-404A as the refrigerant.
Table of Contents
FOR THE INSTALLER ······································ Page 2
SAMPLEBINANDMACHINECOMBINATIONS························· Page 3
FOR THE INSTALLER ······································ Page 4
FOR THE INSTALLER: Location ································· Page 5
FORTHEPLUMBER······································· Page 6
FOR THE ELECTRICIAN ····································· Page 7
FOR THE INSTALLER ······································ Page 8
START UP············································· Page 9
COMPONENT DESCRIPTION ·································· Page 10
COMPONENT DESCRIPTION ·································· Page 11
CONTROL BOX: Components ·································· Page 12
ELECTRICAL SEQUENCE:··································· Page 13
OPERATION: Water········································ Page 14
OPERATION: Performance ···································· Page 15
SANITIZING AND CLEANING ·································· Page 16
SENSORMAINTENANCE ···································· Page 17
BEARING MAINTENANCE ···································· Page 18
MAINTENANCE: Air Cooled···································· Page 19
AUGERMAINTENANCE····································· Page 20
SERVICEDIAGNOSIS······································ Page 21
SERVICEDIAGNOSIS······································ Page 22
CONTROL SYSTEM DIAGNOSTICS ······························· Page 23
REMOVAL AND REPLACEMENT: Water Reservoir & Bin Controls ··············· Page 24
REMOVAL AND REPLACEMENT: Bearing And Breaker ····················· Page 25
REMOVAL AND REPLACEMENT: Auger····························· Page 26
REMOVAL AND REPLACEMENT: Water Seal ·························· Page 27
REMOVAL AND REPLACEMENT: Evaporator ·························· Page 28
REMOVAL AND REPLACEMENT: Gearmotor ·························· Page 29
REMOVAL AND REPLACEMENT: Fan Blade and Motor····················· Page 30
REFRIGERATION SYSTEM SERVICE ······························ Page 31
What to Do Before Calling for Service······························· Page 32
This manual was printed on recycled paper. Keep
it for future reference.
Note the warning symbol
where it appears. It marks a
possible hazard.
May 2001
Page 1
NME954 & FME1204
FOR THE INSTALLER
BACK VIEW: AIR COOLED
Note: Allow 6" behind
and 6" above either
unit for air circulation,
utility connections,
ELECTRICAL
5.25"
3"
WATER INLET
3
" FLARE
8
DRAIN
¾" FPT
2.1"
5.7"
These models are designed to fit the following
Scotsman storage bins:
·
SB480 and extensions (with bin top KBT18)
·
BH800 using bin top KBT15 (one unit) or KBT25
(two units).
·
BH801 using bin top KBT28
·
BH900 with KBT24 (one unit)
·
BH900 with KBT25 (two units side by side)
INLET
9.5"
Condenser Inlet
Condenser Drain ½" FPT
NME954 Dispenser Applications
The NME954 can be placed on and used with
certain ice and ice-beverage dispensers. Kits are
required for proper operation:
·
ID150 use adapter KBT42 and KNUGDIV
·
ID200 or ID250, use adapter KBT46 and
KDIL-N-ID2
·
Cornelius ED/DF200 beverage dispensers, use
KBT46 and KDIL-N-200
BACK VIEW: WATER COOLED
3
" FPT
8
DRAIN
¾" FPT
2.9"
3.4"
4.9"
7.46"
ELECTRICAL
INLET
WATER INLET
3
" FLARE
8
7.3"
5.25"
3"
9.43"
·
Cornelius ED/DF250 beverage dispensers, use
KBT46 and KDIL-N-250
SPECIFICATIONS: Ice Machine
Model NumberDimensions
(w/o bin)
WxDxH
FME1204AS-3B21" x 24" x 27" 208-230/60/3FLAKEAir8.41530 oz
FME1204WS-3AsamesameFLAKEWater7.91524 oz
FME1204WS-3BsamesameFLAKEWater7.91522 oz
FME1204AS-32B same208-230/60/1FLAKEAir11.31530 oz
FME1204WS-32A samesameFLAKEWater10.81524 oz
FME1204WS-32A samesameFLAKEWater10.81522 oz
NME954AS-3Bsame208-230/60/3NUGGET Air8.41530 oz
NME954WS-3AsamesameNUGGET Water7.91524 oz
NME954WS-3BsamesameNUGGET Water7.91522 oz
NME954AS-32Bsame208-230/60/1NUGGET Air11.31530 oz
NME954WS-32AsamesameNUGGET Water10.81524 oz
NME954WS-32BsamesameNUGGET Water10.81522 oz
Basic Electrical Ice Type Condenser
·
Lancer nugget IBD, use KDIL-N-L & Lancer kit.
Type
Minimum
Circuit
Ampacity
Maximum
Fuse Size
Refrigerant
Charge
R-404A*
* Refrigerant charge change on water cooled. Always check the nameplate for charge data.
December 2004
Page 2
NME954 & FME1204
SAMPLE BIN AND MACHINE COMBINATIONS
The Nameplate is
located on the back
of the machine.
FME1204 ON BH550*
NME954 ON BH800*
May 2001
Page 3
FME1204 ON BH900*
* Bin Top Kit Required
NME954 & FME1204
FOR THE INSTALLER
Notice:
Scotsman Ice Systems are designed and
manufactured with the highest regard for safety
and performance. They meet or exceed the
standards of UL, NSF and CUL.
Scotsman assumes no liability or responsibility of
any kind for products manufactured by Scotsman
that have been altered in any way, including the
use of any part and/or other components not
specifically approved by Scotsman.
Scotsman reserves the right to make design
changes and/or improvements at any time.
Specifications and design are subject to change
without notice.
Location:
Installation Limitations:
This ice system is designed to be installed indoors,
in a controlled environment:
MinMax
Air Temperature50
Water Temperature40
Water Pressure20 PSI80 PSI
Voltage198253
(Compared to the nameplate)
Operating the machine outside of the limitations is
misuse and can void the warranty.
RO Water Limitation: Water conductivity must be
no less than 35 microSiemens/cm.
Only install the machine in a location where there
is enough space around it so that it is accessible
for service.
Keep the back of air cooled machines a minimum
distance of 6" from a wall for air circulation. Try to
avoid hot, dirty and crowded locations. Be sure that
the location for the machine is within the
environmental limitations.
0
F1000F
0
F1000F
Storage Bin:
Tip the storage bin on its back, using parts of the
carton to protect the exterior finish. Remove the
skid and install the legs into the threaded holes in
the bottom of the bin. Turn the leg levelers all the
way in preparation for leveling later. Return the bin
to the upright position, remove paper covering the
bin gasket.
Note: Do not push bin into position, instead lift it
there. Pushing a bin, especially one with ice in it,
can cause damage to the legs and the leg mounts.
Install the appropriate bin top on the bin, according
to the instructions for the bin top.
Ice Machine:
The machine is heavy, so the use of a mechanical
lift is recommended for lifting the machine high
enough to install on top of the bin. After the unit is
placed on the bin, line it up so it is even with the
back side. Secure the machine to the bin with the
hardware provided with the machine.
Remove the front panel and remove any shipping
blocks.
June 2002
Page 4
FOR THE INSTALLER: Location
A proper installation locates the machine indoors, but in a
place where the heat and noise it produces are not
objectionable.
Air cooled machines discharge hot air out the back. 6" of space
behind the machine is the minimum required for adequate
operation of an air cooled unit.
Space for maintenance access is also important. If two units
are placed side by side on a bin, side access becomes even
more important.
NME954 & FME1204
May 2001
Page 5
NME954 & FME1204
FOR THE PLUMBER
CONFORM TO ALL APPLICABLE CODES
Water Inlet
Air Cooled Models: The recommended water
supply is clean, cold water. Use
tubing, connect to the
3
" male flare at the back of
8
the cabinet. Install a hand valve near the machine
to control the water supply.
Water Treatment: In most areas, a water filter of
some type will be useful. In areas where the water
is highly concentrated with minerals the water
should be tested by a water treatment specialist,
and the recommendations of the specialist
regarding filtration and/or treatment should be
followed.
Water Cooled Models: A separate
line is recommended, with a separate hand valve
to control it. Connect it to the
inlet at the back of the cabinet. The water pressure
to all lines must always be above 20 psig, and
below 80 psig.
3
" O.D. copper
8
3
" O.D. copper
8
3
" FPT condenser
8
Drains
Air Cooled Models: Connect a rigid drain tube to
3
the
" FPT drain fitting at the back of the cabinet.
4
The drain is a gravity type, and ¼ inch per foot fall
is the minimum acceptable pitch for the drain
tubing. There should be a vent at the highest point
of the drain line, and the ideal drain receptacle
would be a trapped and vented floor drain. Use
3
only
Water Cooled Models: Connect a separate drain
line to the
back of the cabinet. Do not vent this drain.
Storage Bin: Connect a separate gravity type
drain to the ice storage bin drain. Vent this drain if
there is a long horizontal run from the bin to the
floor drain. Insulation of this drain line is
recommended.
Field
Supplied
Filter
" rigid tubing.
4
1
" condenser drain connection at the
2
Hand
Valve
WATER
COOLED
Condenser
Inlet
Water Filter
Condenser
Drain
Hand
Valve
AIR COOLED
MODELS
Vented
Vented
Drain
Water
Inlet
May 2001
Page 6
Floor
FOR THE ELECTRICIAN
CONFORM TO ALL APPLICABLE CODES
NME954 & FME1204
Check the nameplate (located on the back panel)
for the voltage requirements, and for the minimum
circuit ampacity. The machine requires a solid
chassis to earth ground wire.
Connect the power supply to the wires leads in the
junction box on the back of the machine.
Connect the ice machine to its own electrical circuit
so it is individually fused. Voltage variation must
WATER COOLED
remain within the limitations, even under starting
conditions.
All external wiring must conform to national,
state, and local electrical codes. The use of a
licensed electrician is required to perform the
electrical installation.
POWER
SUPPLY
AIR COOLED
May 2001
Page 7
NME954 & FME1204
FOR THE INSTALLER
Final Check List
____1. Is the ice system installed indoors in a
location where the air and water
temperatures are controlled, and where
they do not exceed the design limitations?
____2. Is there an electrical service disconnect
within sight of the installed machine? Has
the voltage been checked, and compared
to nameplate requirements?
____3. Have all the plumbing connections been
made and checked for leaks?
____4. Has the machine and bin been leveled?
____5. Is there a minimum of 6" clearance at the
back of the machine for proper service
access and air circulation?
____6. Is the water pressure a minimum of 20
psig?
____7. Has the machine been secured to the bin?
____8. Is there clearance over the top of the
machine for service access?
____9. Is there a water shut off valve installed near
the machine?
____10. Have all of the shipping blocks been
removed?
May 2001
Page 8
START UP
Pre-Start Inspection
1. Remove the front and side service panels.
2. Check that any shipping blocks have been
removed.
3. Inspect the interior of the machine for loose
screws or wires. Check that no refrigerant lines
are rubbing each other. Check that the fan blades
turn freely (air cooled).
4. Check that the unit is installed correctly
according to the final check list (page 8).
Start Up
NME954 & FME1204
1. Go through the prestart inspection.
2. Open the hand valve, observe that water enters
the water reservoir, fills the tube from the reservoir
to the evaporator, and then shuts off. Check for
leaks.
3. Switch the master (mode) switch on.
The electrical start up sequence is automatic.
A. There should be a short (15 second) delay
before the gear motor starts.
B. After the gear motor starts, the compressor will
start.
4. On air cooled models, the condenser will begin
to discharge warm air, on water cooled models, the
water regulating valve will open, and warm water
will be discharged into the drain.
5. The unit should soon be making ice, if desired,
the low side pressure may be checked: it should be
32 psig + or - 2 psig.
The suction line temperature at the compressor is
normally very cold, nearly to the point of frost up to
the compressor body, but not on it.
The air cooled discharge pressure will depend
upon air and water temperatures, but should be
between 200 psig and 280 psig.
The water cooled discharge pressure should be
constant at about 245 psig.
The above numbers are for new, clean machines,
you can expect to see some values higher, and
some lower between different units.
6. THERE ARE NO ADJUSTMENTS TO MAKE,
so replace the panels.
7. Clean and/or sanitize the storage bin interior,
wipe off the exterior with a clean, damp cloth.
8. Give the owner/user the service manual, instruct
him/her in the operation of the unit, and make sure
they know who to call for service.
9. Fill out the manufacturer's registration and mail it
to Scotsman.
May 2001
Page 9
NME954 & FME1204
COMPONENT DESCRIPTION
Control Box: Contains the electrical controls that
operate the machine.
High Pressure Cut Out Switch: An auto-reset
switch sensing the high side refrigeration pressure.
It will shut the machine off if the discharge
pressure should ever exceed 450 psig.
Low Pressure Cut Out Switch: An auto-reset
switch sending the low side of the refrigeration
system. It will disconnect power to the circuit board
and shut down the machine if the low side
pressure falls too low.
Evaporator: A vertical stainless steel tube,
refrigerated and water filled. In it there is a
stainless steel auger.
Compressor: The refrigerant vapor pump.
Reservoir: Float operated, it maintains the water
level in the evaporator at a constant level, it also
contains the water level sensor.
Water Level Sensor: Senses if there is water in
the reservoir to make ice
out of. Will shut the
machine off it there is
none.
Ice Discharge Chute:
Directs the ice produced
by the evaporator into the
storage bin.
Ice Level Sensor: An
electronic “eye”, it senses
the presence of ice in the
bottom of the ice
discharge chute.
Operates to turn the ice
machine on and off
automatically as the level
of ice in the bin changes.
Gear Motor: An oil filled,
speed reduction gearbox,
driving the auger.
Drain Tube: When
uncapped and lowered,
drains the evaporator.
Condenser: Air or water
cooled, where the heat
removed in ice making is
discharged.
Expansion valve: The
refrigerant metering
device.
Hi Pressure
Cut Out
Low
Pressure
Cut Out
Compressor
AIR COOLED
CONTROL BOX
Reservoir
Condenser
Expansion
Valve
Drain
Tube
Ice Chute
Ice Level
Sensors
May 2001
Page 10
Loading...
+ 22 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.