Scotsman FM2402R Manuel de service

INTRODUCTION
FM2402R
To the owner or user: The service manual you are reading is intended to provide you, and the maintenance or service technician, with the information needed to install, start up, clean, maintain, and service this ice system.
The FM2402R is a remote condenser modular ice system. It features: front service for the freezer, gearmotor, control box, water reservoir, and bin control; an electronic circuit for monitoring ice and water level; a thermostatic expansion valve; and R-22 as the refrigerant.
TABLE OF CONTENTS
For the Installer
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Remote Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
For the Plumber . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
For the Electrician . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Final Check List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Start Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Component Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Maintenance & Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Service Diagnosis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Removal and Replacement
Water Reservoir & Bin Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Thrust Bearing & Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Auger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Water Seal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Evaporator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Gearmotor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Refrigeration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Circuit Board Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Parts Lists and Wiring Diagrams are located in the center of this manual, printed on yellow paper.
December, 1992
Page 1
Drain 3/4" FPT
18.28"
FM2402R
FOR THE INSTALLER
The FM2402R is designed to fit the following Scotsman storage bins:
••B90 and extentions, with bin top
KBT18.
••BH800 no bin top needed.
••BH900 using bin top KBT14.
When installing a new system, check to be sure that you have everything you need before beginning:
••Correct Bin
••Correct Ice Machine
••Correct Bin Top
••All kits, legs, and information
required for the specific job.
There are two separate ice making
and refrigeration systems in this model. The liquid and discharge
lines from each system must go to
separate circuits in one remote
condenser (RC1222).
TOP VIEW
Ice Chute
6.7" x 6.2"
BACK VIEW
Allow 6" of space behind the machine
for utility connections.
34.84"
Liquid Line Connection
(right system)
15.53"
3.1"
21"
3.1"
13.84"
Discharge Line
Connection
(left system)
Allow 6"
above
machine for
service.
20.84"
5.25"
3"
Remote Condenser
17.8"
18.8"
21.66"
Electrical Inlet
Water Inlet 3/8" Flare
SPECIFICATIONS: ICEMAKER
Model
Number
FM2402RE-32A
FM2402RE-3A
Dimensions
(w/o bin)
H X W X D
27" x 42" x 24"
same
Basic
Electrical
208-230/60/1 208-230/60/3
Ice
Type
FLAKE
same
Cond.
Type
R/Air R/Air
* The Standard Finish is Enamel - Sandalwood. There is an optional stainless steel panel kit, SPKFM42
available to convert the unit to Stainless Steel. It is field installed.
December, 1992
Page 2
4.5"
9.43"
Junction Box
FOR THE INSTALLER
Installation Limitations:
This ice system is designed to be installed indoors, in a controlled environment:
Min Max
0
Air Temperature 50 (Not including the remote condenser) Water Temperature 40 Water Pressure 20 PSIG 80 PSIG Voltage -5% +10% (Compared to the nameplate)
Operating the machine outside of the limitations is misuse and can void the warranty.
Water Limitations:
An ice machine is a food manufacturing plant; it takes a raw material, water, and turns it into a food product, ice. The purity of the water is very important in obtaining pure ice and in maximizing product life. This is not intended as a complete resource for water related questions, but it does offer these general recommendations:
1. Check with a water treatment specialist for a water test, and recommendations regarding filters and treatment.
2. In most cases, the water used to make ice should be filtered or treated, depending upon the water.
There is no one type of water filter that
will be effective in all situations.
water test is important.
F 1000F
0
F 1000F
That is why a
FM2402R
Scotsman Ice Systems are designed and manufactured with the highest regard for safety and performance. They meet or exceed the standards of UL, NSF, and CSA.
Scotsman assumes no liability or responsibility of any kind for products manufactured by Scotsman that have been altered in any way, including the use of any part and/or other components not specifically approved by Scotsman.
Scotsman reserves the right to make design changes and/or improvements at any time. Specifications and design are subject to change without notice.
1.25"
December, 1992
Page 3
Typical Storage Bin - B90
21.12"
Drain
3/4" FPT
19.86"
FM2402R
REMOTE CONDENSER SPECIFICATIONS
1/2" MALE QUICK CONNECT
COUPLING FOR USE WITH
R22625 OR RT2240
PRECHARGED LINE SET
22"
5.75"
5.38"
32.56"
27.81"
5.0"
MODEL USE WITH MINIMUM CIRC.
RC1222 27.8" X 22 X 37.94" 1 FM2402R 2 208-230/60/1
+Included with the icemakers minimum circuit ampacity. Use this
value to determine wire size between icemaker and fan motor.
DIMENSIONS H" X W" X D"
6.5"
3.5"
1.9" LIQUID LINE 3/8" MALE
QUICK CONNECT
COUPLING FOR USE WITH
RT2225 OR RT2240
PRECHARGED LINE SET
RT-2225 Precharged line set, 25’, R-22 - 2 required. Or: RT-2240. Precharged line set, 40’, R-22 - 2 required.
7.5"
AMPACITY+
BASIC
ELECTRICAL
ICEMAKER NAMEPLATE
LOCATED ON BACK PANEL
SERIAL PLATE LOCATED
BEHIND FRONT PANEL
December, 1992
Page 4
FOR THE INSTALLER
Typical Storage Bin with Extension and Bin Top
FM2402R
Location
After uncrating and inspection, the unit is ready for installation. It is important that the machine be installed in a location where it has enough space around it to be accessible for service, usually a minimum of 6 inches. Try to avoid hot, dirty and crowded locations. Be sure that the location for the machine is within the limitations described on page
3.
Storage Bin
Tip the storage bin on its back, using parts of the carton to protect the exterior finish. Install the legs into the threaded holes in the bottom of the bin. Turn the leg levelers all the way in preparation for leveling later. Return the bin to the upright position, remove paper covering the bin gasket.
Install the bin top according to the directions with the bin top.
Note: Do not push bin into position, but lift it there. Pushing a bin, especially one with ice in it, can cause damage to the legs and the leg mounts.
Ice Maker
The machine is heavy, so the use of a mechanical lift is recommended for lifting the machine high enough to install on top of the bin. After the unit is placed on the bin, line it up so it is even with the back side. Secure the machine to the bin with the hardware provided with the machine.
Remove the front panel and remove any shipping blocks.
Note: Be sure to allow a 6" minimum space above the top of the machine for service.
December, 1992
Page 5
REMOTE CONDENSER
SPIRAL
EXCESS
TUBING
INSIDE
BUILDING
FM2402R
FOR THE INSTALLER: Remote Condenser
Location
Limited to a 40 foot or a 25 foot length of precharged refrigerant tubing connecting the icemaker to the remote condenser. The condenser must be above or level with the icemaker.
Select the best available location, protecting the condenser from extremes of dirt, dust, and sun.
Meet all applicable building codes. Usually the services of a licensed electrician are required.
Roof Attachment
1. Install and attach the remote condenser to the roof of the building, using the methods and practices of construction that conform to the local building codes, including having a roofing contractor secure the condenser to the roof.
2. Have an electrician connect the remote condenser fan motor to the icemaker, using the junction box at the back of the icemaker.
PRECHARGED LINE ROUTING
CAUTION Do not connect precharged tubing until all routing
and forming of the tubing is complete. See the coupling instructions for connecting instructions.
4. Spiral the excess length of pre charged tubing inside the building. Use a horizontal spiral (as illustrated) to avoid any traps in the lines.
5. Have the roofing contractor seal the holes in the roof per local codes.
Note: Tight spiral shown is not required, bend
tubing to a practical radius.
Refrigerant charge is in the ice maker. Only a
holding charge is in the "pre-charged" lines.
1. Each set of precharged refrigerant lines (either 25 foot or 40 foot) consists of a 3/8 inch diameter liquid line and a 1/2 inch diameter discharge line. Both ends of each line have quick connect couplings, one end has a schrader valve connection, that end goes to the condenser.
Note: The openings in the building ceiling or wall, listed in the next step, are the minimum sizes recommended for passing the refrigerant lines through.
2. Have the roofing contractor cut a minimum hole for the refrigerant lines of 1 3/4 inch. Check local codes, a separate hole may be required for the electrical power to the condenser.
CAUTION DO NOT KINK OR CRIMP REFRIGERANT
TUBING WHEN INSTALLING IT.
3. Route the refrigerant lines through the roof opening.
Follow straight line routing whenever possible. Any excess tubing MUST be retained within the
building.
LOCATE REMOTE
CONDENSER
ABOVE ICEMAKER
December, 1992
Page 6
FOR THE INSTALLER: Precharged Lines
COUPLING INSTRUCTIONS
CAUTION The couplings on the sets of precharged lines are
self sealing when installed properly. Carefully follow the instructions:
1. Remove the protector caps and plugs. Wipe the seats and threaded surfaces with a clean cloth to be certain that no foreign matter remains on them.
2. Lubricate the inside of the couplings, especially the O-Rings with refrigerant oil.
••Connect the 3/8 inch liquid line (schrader valve
end) to the remote condenser fitting marked "liquid line".
••Connect the other end of the liquid line to the
icemaker fitting marked "liquid line."
••Connect the 1/2 inch discharge line (schrader
valve end) to the remote condenser fitting marked "discharge line".
••Connect the other end of the liquid line to the
icemaker fitting marked "discharge line".
3. Begin tightening the couplings together by hand, then using two wrenches (it is important that ONLY the nut on the precharged lines be turned, the other parts of the couplings must NOT be allowed to turn or the process will tear out the diaphragms and they will be loose in the refrigeration system) tighten the coupling until it bottoms out or a definite increase in resistance is felt.
4. Using a marker or pen, mark a line lengthwise from the coupling union nut to the bulkhead. Then tighten the coupling and additional 1/4 turn. As the nut turns, the line will show when 1/4 turn is made.
5. After all connections are made, and after the king valve has been opened, check the couplings for leaks.
FM2402R
SERVICE PORTS
REMOTE CONDENSER
3/8" LIQUID LINE
1/2" DISCHARGE
LINE
3/8" LIQUID LINE
SCHRADER
VALVE
CONDENSER
TO REMOTE
1/2" DISCHARGE
LINE
NO SCHRADER
VALVE
TO ICEMAKER
December, 1992
Page 7
ICEMAKER
FM2402R
FOR THE INSTALLER: Location
CONTACT ROOFING
CONTRACTOR
EXCESS
PRECHARGED
TUBING INSIDE
BUILDING
REMOTE
CONDENSER
ROOF
CUTAWAY
SERVICE
ACCESS
SERVICE ACCESS
SIDE AND BACK
WALL
CUTAWAY
December, 1992
Page 8
FOR THE PLUMBER
CONFORM TO ALL APPLICABLE CODES
FM2402R
Water Inlet
CONNECT TO
COLD WATER
FIELD
SUPPLIED
WATER FILTER
HAND SHUT
OFF VALVE
WATER INLET
3/8" MALE
FLARE
VENT
ICEMAKER
DRAIN,
3/4" FPT
The recommended water supply is cold water. Use 3/8" O.D. copper tubing, connect to the 3/8" male flare at the back of the cabinet. Install a hand valve near the machine to control the water supply.
Drains
There is one 3/4" FPT drain at the back of the cabinet, the drain line is of the gravity type, and 1/4 inch per foot fall is an acceptable pitch for the drain tubing. There should be a vent at the highest point of the drain line, and the ideal drain receptacle would be a trapped and vented floor drain. Use only 3/4" rigid tubing.
Storage Bin: A separate gravity type
drain needs to be run. Insulation of this drain line is recommended.
VENT BIN DRAIN
3/4" FPT
FLOOR DRAIN
December, 1992
Page 9
FM2402R
FOR THE ELECTRICIAN
CONFORM TO ALL APPLICABLE CODES
The electrical power to the unit is supplied through the junction box at the rear of the machine.
Check the nameplate (located on the back panel) for the voltage requirements, and for the minimum circuit ampacity. The machine requires a solid chassis to earth ground wire.
The ice maker should be connected to its own electrical circuit so it would be individually fused. Voltage variation must remain within design limitations, even under starting conditions.
Electrically the remote condenser fan motor is connected to the icemaker at the contactor
TERMINAL STRIP
FOR REMOTE
CONDENSER
ICEMAKER
JUNCTION BOX
POWER
SUPPLY
terminals for the compressor and the fan motor operates whenever the compressor operates.
Electrical connections are made at the junction box at the back of the icemaker and at the junction box on the remote condenser.
The remote condenser must be wired to the icemaker in accordance with local and national electrical codes with a minimum of 18 Awg. wire with an ground bonding wire connected to the ground screws provided in both the condenser and machine field wiring boxes. All outdoor wiring must be in rain proof conduit.
All external wiring must conform to national, state, and local electrical codes. The use of a licensed electrician is required to perform the electrical installation.
GROUND
THE
CHASSIS
RAIN PROOF
CONDUIT
December, 1992
Page 10
FOR THE INSTALLER: Completed Installation
INSULATED
PRECHARGED
REFRIGERANT
TUBING
A typical installation should generally appear as illustrated below. The remote condenser must be located above the icemaker and the precharged lines installed per the instructions on page 6.
FM2402R
December, 1992
Page 11
FM2402R
FOR THE INSTALLER: Final Check List
1. Is the ice system installed indoors in a location where the air and water temperatures are controlled, and where they do not exceed the design limitations?
2. Is there an electrical service disconnect within sight of the installed machine? Has the voltage been checked, and compared to nameplate requirements?
3. Have all the plumbing connections been made and checked for leaks?
4. Has the machine and bin been leveled?
5. Is there a minimum of 6" clearance at the rear, left, right and above the machine for proper service access?
6. Is the water pressure a minimum of 20 psig?
7. Has the machine been secured to the bin?
8. Is there a water shut off valve installed near the machine?
9. Is the remote condenser installed per local building codes, and in a place where it has adequate ventilation and minimal solar heat gain?
10. Has all shipping material and literature (inside the front panel) been removed from the units?
121 Have the remote condenser and precharged lines been properly installed?
12. Has the electrical connection between the icemaker and the condenser been made?
13. Verify that the master switches are in the OFF position.
14. Switch on the electrical power.
REMOTE
CONDENSER
SECURED?
LEVELED?
PLUMBING?
15. Refer to Pre-Start instructions, the next page.
ROOF
HOLES
SEALED?
POWER
SUPPLY?
December, 1992
Page 12