Scotsman FM1202RL User Manual

TO THE OWNER OR USER:
Single System RL
The service manual you are reading is intended to provide you, and the maintenance or service technician, with the information needed to install, start up, clean, maintain and service this ice system.
This Remote Low side unit is the freezer portion of a commercial ice machine. It is designed to be connected to the condensing section of a refrigeration system, specifically a supermarket R-404A system.
Table of Contents
FOR THE INSTALLER: Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 2
FOR THE INSTALLER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3
FOR THE ELECTRICIAN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 4
FOR THE PLUMBER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 5
FOR THE INSTALLER: Final Check List Initial Start Up . . . . . . . . . . . . . . . . . . Page 6
COMPONENT IDENTIFICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 7
COMPONENT DESCRIPTION: Control Box . . . . . . . . . . . . . . . . . . . . . . . . Page 8
COMPONENT DESCRIPTION: Evaporator . . . . . . . . . . . . . . . . . . . . . . . . . Page 9
ELECTRICAL SEQUENCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 10
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 11
OPERATION: Refrigeration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 12
MAINTENANCE AND CLEANING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 13
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 14
CLEANING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 15
SERVICE DIAGNOSIS: Condition - No Ice Being Produced . . . . . . . . . . . . . . . . Page 16
REMOVAL AND REPLACEMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 18
REMOVAL AND REPLACEMENT: Bearing And Breaker . . . . . . . . . . . . . . . . . . Page 19
REMOVAL AND REPLACEMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 20
REMOVAL AND REPLACEMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 21
REMOVAL AND REPLACEMENT: Evaporator . . . . . . . . . . . . . . . . . . . . . . . Page 22
REMOVAL AND REPLACEMENT: Gearmotor . . . . . . . . . . . . . . . . . . . . . . . Page 23
CIRCUIT BOARD TESTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 24
Parts lists and wiring diagrams are in the center of this manual, printed on yellow paper.
This manual was printed on recycled paper. Keep it for future reference.
Note the Warning symbol where it appears. It marks a potential hazard.
January 1997
Page 1
Single System RL
FOR THE INSTALLER: Specifications
The unit is designed to fit a variety of Scotsman storage bins. See sales literature for more information.
Installation Limitations: The remote low side is designed for indoor installations only. The machine must also be in a controlled environment where the air temperature does not fall below 500F., or go above 1000F.
The water temperature must be between 400F. and 1000F.
The electrical power supply must not drop below
-5% of the lowest nameplate voltage or go above 10% of the highest nameplate voltage.
SPECIFICATIONS:
Scotsman Ice Systems are designed and manufactured with the highest regard for safety and performance. They meet or exceed the standards of U.L., N.S.F., and C.U.L.
Scotsman assumes no liability or responsibility of any kind for products manufactured by Scotsman that have been altered in any way, including the use of any parts and/or other components not specifically approved by Scotsman.
Scotsman reserves the right to make design changes and/or improvements at any time. Specifications and designs are subject to change without notice.
Model Cabinet Size System Refrigerant BTUH required Voltage Ice Type FME1200RL 21"w x 27"h x 24"d R-404A 8,000 208-230 Flaker NME950RL 21"w x 27"h x 24"d R-404A 8,000 208-230 Nugget FM1202RL 21"w x 27"h x 24"d R-22 8,000 208-230 Flaker NM952RL 21"w x 27"h x 24"d R-22 8,000 208-230 Nugget FME1500RL 21"w x 27"h x 24"d R-404A 8,000 208-230 Flaker NME1250RL 21"w x 27"h x 24"d R-404A 8,000 208-230 Nugget
January 1997
Page 2
FOR THE INSTALLER
Select the Location:
The unit can only be installed indoors within the limitations described on page 2.
The ice machine will have to be connected to the building’s refrigeration system, check to be sure that the system has enough extra capacity to handle a minimum of additional 8,000 BTU’s per hour @ 1100F. liquid line temperature (assume a 00F. evaporator temperature).
Storage Bin:
Using a mechanical lift, install the ice machine onto the top of the storage bin.
Fasten the ice machine to the bin using (4) 5/15-18 2.5" cap screws.
Level the assembly by: a. Turning the leg levelers in or out
on the standard legs. b. Use shims under the heavy duty
legs of the KLP4. Locate the Nameplate: The
nameplate is located on the back panel of the machine, and contains the electrical characteristics particular to the unit being installed.
Refrigeration Installation:
The skills of a refrigeration technician are required to connect the ice machine to the buildings refrigeration system.
Notes:
Suction Line and Liquid Line
Stubs are at the back of the cabinet.
Single System RL
TYPICAL INSTALLATION: ALLOW ROOM FOR SERVICE ACCESS
FME1200RL
BX87 BIN
EXTENSION
B90 STORAGE BIN
1.5 ounces of the appropriate
refrigerant is in the system as a holding charge.
Be sure there is enough BTU capacity.
Be sure that the liquid connection is NOT in
series with another liquid line valve.
Local Codes must be observed.
A P-trap should be installed where there will be
more than 10’ of vertical rise in the suction line.
January 1997
Page 3
Single System RL
FOR THE ELECTRICIAN
CONFORM TO ALL APPLICABLE CODES
Electrical Connections:
Locate the nameplate for the current requirements, and then determine the wire size and type per the National Electric Code. The machine requires a solid chassis to earth ground wire. Refer to the wiring diagram. The ice machine should be connected to it’s own electrical circuit, and be individually fused.
Voltage, when the unit is under full load, must remain within the limitations listed on page 2.
LOW VOLTAGE CAN CAUSE EQUIPMENT MALFUNCTION AND/OR DAMAGE
All external wiring should conform to the National, State, and local electrical codes. Usually the services of a licensed electrician will be required.
DETAIL OF
JUNCTION BOX
JUNCTION
BOX
POWER SUPPLY
January 1997
Page 4
FOR THE PLUMBER
CONFORM TO ALL APPLICABLE CODES
Single System RL
Water Supply:
The recommended water supply line is 3/8" O.D. copper tubing, with a minimum operation pressure of 20 PSIG, and a maximum of 80 PSIG. Connect to cold water using the male flare connection at the back of the machine. Install a shut off valve in an accessible space between the ice maker and the water supply.
SHUT OFF
VALVE
Drain System:
All drains are of the gravity type, and must have a minimum of 1/4" fall per foot of horizontal run. The drains must be installed to conform to local plumbing codes. The use of a vent at the machine and at the bin will allow the system to drain properly. Use only rigid tubing for drains; insulation of the bin drain is recommended.
3/8" MALE FLARE
3/4" FPT
VENT THIS DRAIN
WATER INLET
BIN DRAIN
FLOOR DRAIN
FIELD
SUPPLIED
WATER FILTER
January 1997
Page 5
Single System RL
FOR THE INSTALLER:
Final Check List
1. Is the unit installed where the air and water temperatures are within and will remain within the limitations for the unit?
2. Is there 6" clearance at the rear of the machine for utility connections?
3. Has the water supply line be checked for pressures between 20 and 80?
4. Has the unit been leveled?
5. Has the shipping material been removed from inside the cabinet?
6. Have the electrical connections been made?
7. Have the drains been installed and checked for leaks?
8. Has the refrigeration supply been installed and checked for leaks?
9. Has the bin and cabinet been wiped clean or sanitized?
10. Has the warranty registration card been properly filled out and mailed to Scotsman?
11. Has the owner been given the service manual and been instructed on how to maintain the ice maker?
Initial Start Up
1. Remove the top and front panels.
2. Open the water valve, and observe that the two float reservoirs fill up with water and shut off.
3. Switch on the electrical power.
4. Open the hand valve (in the liquid line).
5. Open the ball valve (in the suction line).
6. Switch on the master switch, and observe: The liquid line valve opens The gearmotor runs Within a short time, that side of the machine
begins to make ice. Water flows from the water reservoir, and the float
drops, letting in more water.
7. When operating, the sight glass should remain
full, and the low side pressure will be about: RLE1202/952 - 25 PSIG + or - 2 PSIG RLE1200/950 - 36 PSIG + or - 2 PSIG RLE1500/1250 - 25 PSIG + or - 2 PSIG Gearmotor amp draw should not exceed the
nameplate rating.
8. Check the system very carefully for any
refrigerant leaks, repair as needed.
13. Has the owner been given the name and telephone number of the local Scotsman service agency?
November 1999
Page 6
COMPONENT IDENTIFICATION
Single System RL
Liquid line valve
This valve operates to turn the ice making process on and off.
When the ice level drops in the ice chute, the ice level sensor will cause the circuit board to close the liquid line relay, which energizes the liquid line valve. The liquid line valve opens, and liquid refrigerant flows to the thermostatic expansion valve.
Thermostatic Expansion Valve
The metering device of the system, the valve senses the temperature of the suction line and varies the amount of liquid refrigerant that passes through the valve into the evaporator, thus maintaining a constant level of refrigeration. TXV’s are factory set. Do not adjust unnecessarily.
DO NOT ADJUST THE TXV UNTIL THE EPR HAS BEEN SET.
The superheat setting is 4-8 temperature of the evaporator outlet at the TXV bulb, and check the low side pressure at the EPR valve. Convert the pressure to temperature (using a temperature pressure chart) and subtract the
0
F. Measure the
amount from the outlet temperature. The result is the superheat. Use an electronic thermometer.
EPR: Evaporator Pressure Regulator Valve
This valve maintains a constant pressure on its inlet (evaporator) side regardless of the pressure on the outlet (suction) side. The EPR is factory set, adjust only if needed. After adjusting, re-check TXV superheat.
EPR Settings: RLE1202/952: 25 PSIG + or - 2 PSIG RLE1200/950: 36 PSIG + or - 2 PSIG RLE1500/1250: 25 PSIG + or - 2 PSIG
Evaporator:
Where the water is frozen into ice crystals. As the water cools, it begins to turn into ice, and the slowly turning auger lifts the ice, as it is being made, and forces it up and out of the “breaker” or spout where the extra water is compressed out of the ice. The ice then drops through the chute, into the storage bin.
THERMO VALVE
LIQUID LINE
VALVE
EPR VALVE
November 1999
Page 7
Single System RL
COMPONENT DESCRIPTION: Control Box
Circuit Board: Controlling the ice machine through sensors and relays. The sensors are: ice level, and water level. The relays are for the gear motor (with a built in time delay to clear the evaporator of ice when the unit turns off) and for the liquid line valve.
Transformer: Supplies low voltage to the circuit board.
On/Off Switch: Manual control for that side of the machine.
ON/OFF SWITCH
TRANSFORMER
CIRCUIT
BOARD
TERMINAL STRIP
January 1997
Page 8
Loading...
+ 16 hidden pages