controlled environment. Operation outside the limits
listed here will void the warranty.
Air temperature limits
Minimum Maximum
Ice maker 50
Remote
o
F. / 10oC.100oF. / 38oC.
-20oF. / -28oC.120oF. / 48oC.
condenser
Water temperature limits
Minimum Maximum
All models 40
o
F. / 4.4oC.100oF. / 38oC.
Water pressure limits (potable)
MinimumMaximum
All models 20 psi / 1.3 bar80 psi / 5.5 bar
Water pressure limit to water cooled condenser is 150
PSI
Voltage limits
Minimum Maximum
115 volt 104 126
208-230 60 Hz 198 253
Minimum conductivity (RO water)
• 10 microSiemens / CM
Water Quality (ice making circuit)
• Potable
will have an impact on the time between cleanings
and ultimately on the life of the product. Water can
contain impurities either in suspension or in solution.
Suspended solids can be ltered out. In solution
or dissolved solids cannot be ltered, they must be
diluted or treated. Water lters are recommended
to remove suspended solids. Some lters have
treatment in them for dissolved solids.
Check with a water treatment service for a
recommendation.
RO water. This machine can be supplied with Reverse
Osmosis water, but the water conductivity must be no
less than 10 microSiemens/cm.
Potential for Airborne Contamination
Installing an ice machine near a source of yeast
or similar material can result in the need for more
frequent sanitation cleanings due to the tendency of
these materials to contaminate the machine.
Most water lters remove chlorine from the water
supply to the machine which contributes to this
situation. Testing has shown that using a lter that
does not remove chlorine, such as the Scotsman
Aqua Patrol, will greatly improve this situation.
Warranty Information
The warranty statement for this product is provided
separately from this manual. Refer to it for applicable
coverage. In general warranty covers defects
in material or workmanship. It does not cover
maintenance, corrections to installations, or situations
when the machine is operated in circumstances that
exceed the limitations printed above.
The quality of the water supplied to the ice machine
While the machine will operate satisfactorily within the
listed air and water temperature limits, it will produce
more ice when those temperatures are nearer the
lower limits. Avoid locations that are hot, dusty, greasy
or conned. Air cooled models need plenty of room
air to breathe. Air cooled models must have at least
six inches of space at the back for air discharge;
however, more space will allow better performance.
Airow
Air ows into the front of the cabinet and out the back.
The air lters are on the outside of the front panel and
are easily removed for cleaning.
Bin compatibility
All models have the same footprint: 22 inches wide
by 24 inches deep. Conrm available space when
replacing a prior model.
Bin & adapter list:
• B322S – no adapter needed
• B330P or B530P or B530S – Use KBT27
• B842S – KBT39
• B948S – KBT38 for single unit
• B948S – KBT38-2X for two units side by side
• BH1100, BH1300 and BH1600 upright bins include
ller panels to accommodate a single 22 inch wide
ice machine. No adapter is needed.
Dispenser compatibility
Only nugget ice models may be used with ice
dispensers. Flaked ice is not dispensable.
Options
Side air ow kits KPFSA223 or KPFSA227 are
available for air cooled models. A lter kit for the
remote condenser is KERCF
Ice is made until it lls the bin enough to block an
infrared light beam inside the base of the machine. A
eld installed kit is available to adjust the maintained
ice level lower. The kit number is KVS.
The standard controller has excellent diagnostic
capabilities and communicates to the user through the
AutoAlert light panel, seen through the front panel.
Field installed kits are available that can log data and
provide additional information when the front panel is
removed. The kit numbers are KSBU and KSB-NU.
See page 21.
• ID150 – use KBT42 and KDIL-PN-150, includes
KVS, KNUGDIV and R629088514
• ID200 – use KBT43 and KNUGDIV and KVS
• ID250 – use KBT43 and KNUGDIV and KVS
See sales literature for other brand model ice and
beverage dispenser applications.
Other Bins & Applications:
Note the drop zone and ultrasonic sensor locations in
the illustrations on the next pages.
Scotsman ice systems are designed and
manufactured with the highest regard for safety
and performance. Scotsman assumes no liability of
responsibility of any kind for products manufactured
by Scotsman that have been altered in any way,
including the use of any part and/or other components
not specically approved by Scotsman.
Scotsman reserves the right to make design changes
and/or improvements at any time. Specications and
design are subject to change without notice.
If reusing an existing bin, be sure that the bin is
in good shape and that the gasket tape on the
top is not torn up. Water leaks, not covered by
warranty, could result from a poor sealing surface. If
installing a remote or a remote low side, a new bin
is recommended due to the high cost to the user of
replacing an old bin when a remote system is on top.
Install the correct adapter, following the directions
supplied with that adapter.
Hoist the machine onto the adapter.
Note: The machine is heavy! Use of a mechanical lift
is recommended.
Position the machine on the bin or adapter. Secure
with straps from the hardware bag packed with the
machine, or those supplied with the adapter.
Remove any plastic covering the stainless steel
panels.
Note: The standard machine set up includes visible
on and off switches. Those can be covered up by
changing the bezel in the front panel’s trim strip. A
cover-up bezel is included with the hardware bag.
Remove any packaging, such as tape or foam blocks,
that may be near the gear reducer or ice chute.
Level the bin and ice machine front to back and left to
right by using the bin leg levelers.
Panel Removal A or B Series
1. Locate and loosen the two screws at the front edge
of the top panel.
2. Pull the front panel out at the top until it clears the
top panel.
3. Lift the front panel up and off the machine.
4. Remove two screws at the front of the top panel.
Lift up the front of the top panel, push the top panel
back an inch, then lift to remove.
5. Locate and loosen the screw holding each side
panel to the base. Left side panel also has a screw
holding it to the control box.
6. Pull the side panel forward to release it from the
back panel.
Button Switch Bezel A or B Series
To change bezels: Remove the front panel, and refer
to the instruction label on the inside of the front panel.
Push snaps of standard bezel in and pull the bezel
out of the front panel trim strip.
Locate other bezel. Push into the trim strip from the
front until it snaps into place. Return the front panel to
its original position and secure it to the cabinet.
Panel Removal D Series
1. Locate and loosen the two screws at the bottom of
the front panel.
2. Pull the front panel out at the bottom until it clears.
3. Lower the front panel down and off the machine.
4. Remove two screws at the front of the top panel.
Lift up the front of the top panel, push the top panel
back an inch, then lift to remove.
5. Locate and loosen the screw holding each side
panel to the base. Left side panel also has a screw
holding it to the control box.
6. Pull the side panel forward to release it from the
back panel.
The water supply for ice making must be cold, potable
water. There is a single 3/8” male are potable water
connection on the back panel. Water cooled models
also have a 3/8” FPT inlet connection for the water
cooled condenser. Chilled water can also be used for
this connection.
Drain
Water Inlet
Connection
There is one ¾” FPT condensate drain tting at the
back of the cabinet. Water cooled models also have a
½” FPT discharge drain connection on the back panel.
Tubing
Connect the potable water supply to the potable water
tting, 3/8” OD copper tubing or the equivalent is
recommended.
Water ltration is recommended. If there is an existing
lter, change the cartridge.
Connect the water cooled water supply to the
condenser inlet.
Note: Do NOT lter water to the water cooled
condenser circuit.
Connect the drain tube to the condensate drain tting.
Connect the water cooled condenser drain tube to the
condenser outlet.
Do not Tee ice machine drains into the drain tube
from the ice storage bin or dispenser. Back ups
could contaminate and / or melt the ice in the bin or
dispenser.
Follow all local and national codes for tubing, traps
Remote condenser models have additional installation
needs.
The correct remote condenser fan and coil must
be connected to the ice making head. Liquid and
discharge tubing connections are on the back of the
ice machine cabinet. Pre-charged tubing kits are
available in several lengths to accommodate most
installations. Order the one that just exceeds the
length needed for the installation.
The kit numbers are:
• RTE10
• RTE25
• RTE40
• RTE75
There are limits as to how far away from the ice
machine and where the remote condenser can be
located. See the next page for those limits.
Prior Head Prior Condenser New Head
NME654R ERC101 N0622R
FME804R ERC101 F0822R
NME954R ERC151 N0922R
FME1204R ERC151 F1222R
NME1254R ERC201 N1322R
FME1504R ERC201 F1522R
Do not reuse condenser coils contaminated with
mineral oil (used with R-502 for example). They will
cause compressor failure and will void the warranty.
The correct condenser must be used.
Ice Machine Model Condenser Model
F0822R-1 ERC111-1
F1222R-32, F1222R-3 ERC311-32
N0622R-1, N0822R-1ERC111-1
N0922R-32, N1222R-3 ERC311-32
N1322R-32 ERC311-32
Note: A headmaster is required for all remote
condenser systems. Prior condensers did not have
a headmaster. New head / old condenser retrots
can use headmaster kit KPFHM. See chart below for
applications.
interior location of the ice machine. Allow it plenty of
space for air and cleaning: keep it a minimum of two
feet away from a wall or other rooftop unit.
Note: The location of the condenser relative to the ice
machine is LIMITED by the specication on the prior
page.
Roof penetration. In many cases a roong contractor
will need to make and seal the hole in the roof for the
line sets. The suggested hole diameter is 2 inches.
Meet all applicable building codes.
Roof Attachment
Install and attach the remote condenser to the roof
of the building, using the methods and practices of
construction that conform to the local building codes,
These steps must be performed by an EPA Certied
Type II or higher technician.
Initial Connections
1. Remove the protector caps and plugs. Wipe the
seats and threaded surfaces with a clean cloth to
remove any possible foreign matter.
2. Lubricate the inside of the couplings, especially
the O-rings, with refrigerant oil. Oil packets are
supplied with Scotsman line sets.
3. Position the ttings on the correct connections on
the condenser and ice machine.
Final Connections:
4. Tighten the couplings together by hand until it is
certain that the threads are properly engaged.
6. Continue tightening the swivel nut until it bottoms
out or a very denite increase in resistance is felt
(no threads should be showing).
Critical Step!!!!!
7. Mark a line on the coupling nut and unit panel.
Then tighten the coupling nut an additional one-
quarter turn. The line will show the amount that
the nut turns. Do NOT over tighten.
5. Use two wrenches tighten the coupling until it
bottoms out or a denite increase in resistance is
felt. It is important that ONLY the nut on the pre-
charged tube be turned, or the diaphragms will
be torn out by the piercing knives and they will be
loose in the refrigeration system.
Note: As the couplings are tightened, the diaphragms
in the quick connect couplings will begin to be
pierced. As that happens, there will be some
resistance to tightening the swivel nut.
December 2014
Page 17
8. After all connections have been made, and after
the receiver outlet valve has been opened (do not
open yet), check the couplings for leaks.
Loading...
+ 37 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.