Scotsman F0522, F1222, F1522, N0422, N0622 Operation Manual

...
Page 1
Installation and User's Manual for Modular Flaked & Nugget Ice Machines
Models F0522, F0822, F1222, F1522, N0422, N0622, N0922 and N1322
Air Cooled, Water Cooled and Remote Air Cooled
Page 2
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522 Air, Water or Remote User Manual
Introduction
This ice machine is the result of years of experience with flaked and nugget ice machines. The latest in electronics has been coupled with the time tested Scotsman flaked ice system to provide reliable ice making and the features needed by customers. The features include easily accessible air filters, simple conductivity water level sensing, evaporator clearing at shut down, photo-eye sensing bin control and the ability to add options.
Table of Contents
Installation: ........................................... Page 2
Location: ............................................ Page 3
N0422, F0522, N0622, F0822, N0822 Cabinet Layout ..................... Page 4
N0922, F1222, N1322, F1522 Cabinet Layout ......................... Page 5
Unpacking & Install Prep .................................... Page 6
Water - Air or Water Cooled .................................. Page 7
Electrical - All Models ...................................... Page 8
Refrigeration - Remote Condenser Models ........................... Page 9
Remote Condenser Location - Limits .............................. Page 10
For The Installer: Remote Condenser ............................. Page 11
Precharged Line Routing - Remote Only ............................ Page 12
Coupling Instructions - Remote Only .............................. Page 13
Water - Remote Models ..................................... Page 14
Final Check List ......................................... Page 15
Initial Start Up and Maintenance ................................ Page 16
Maintenance: Scale Removal and Sanitation .......................... Page 17
Maintenance: Check Top Bearing ............................... Page 18
Bearing Service ......................................... Page 19
Maintenance: Sensors ..................................... Page 20
Options ............................................. Page 21
What to do before calling for service .............................. Page 22
This user and installation manual is organized in three main sections: installation, operation, and maintenance.
July 2009
Page 1
Page 3
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522 Air, Water or Remote User Manual
Installation:
This machine is designed to be used indoors, in a controlled environment. Operation outside the limits listed here will void the warranty.
Air temperature limits
Minimum Maximum
o
Ice maker 50
Remote condenser
F. 100oF.
o
F. 120oF.
-20
Water temperature limits
Minimum Maximum
o
All models 40
F. 100oF.
Water pressure limits (potable)
Minimum Maximum
All models 20 psi 80 psi
The quality of the water supplied to the ice machine will have an impact on the time between cleanings and ultimately on the life of the product. Water can contain impurities either in suspension or in solution. Suspended solids can be filtered out. In solution or dissolved solids cannot be filtered, they must be diluted or treated. Water filters are recommended to remove suspended solids. Some filters have treatment in them for suspended solids.
Check with a water treatment service for a recommendation.
RO water. This machine can be supplied with Reverse Osmosis water, but the water conductivity must be no less than 10 microSiemens/cm.
Potential for Airborne Contamination
Installing an ice machine near a source of yeast or similar material can result in the need for more frequent sanitation cleanings due to the tendency of these materials to contaminate the machine.
Water pressure limit to water cooled condenser is 150 PSI
Voltage limits
Minimum Maximum
115 volt 104 126
208-230 60 Hz 198 253
Minimum conductivity (RO water)
10 microSiemens / CM
Water Quality (ice making circuit)
Potable
Most water filters remove chlorine from the water supply to the machine which contributes to this situation. Testing has shown that using a filter that does not remove chlorine, such as the Scotsman Aqua Patrol, will greatly improve this situation.
Warranty Information
The warranty statement for this product is provided separately from this manual. Refer to it for applicable coverage. In general warranty covers defects in material or workmanship. It does not cover maintenance, corrections to installations, or situations when the machine is operated in circumstances that exceed the limitations printed above.
November 2009
Page 2
Page 4
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522 Air, Water or Remote User Manual
Location:
While the machine will operate satisfactorily within the listed air and water temperature limits, it will produce more ice when those temperatures are nearer the lower limits. Avoid locations that are hot, dusty, greasy or confined. Air cooled models need plenty of room air to breathe. Air cooled models must have at least six inches of space at the back for air discharge; however, more space will allow better performance.
Airflow
Air flows into the front of the cabinet and out the back. The air filters are on the outside of the front panel and are easily removed for cleaning.
Bin compatibility
All models have the same footprint: 22 inches wide by 24 inches deep. Confirm available space when replacing a prior model.
Bin & adapter list:
B222S or B322S – no adapter needed
B330P or B530P or B530S – Use KBT27
B842S – KBT39
B948S – KBT38 for single unit
B948S – KBT38-2X for two units side by side
BH1100, BH1300 and BH1600 upright bins
include filler panels to accommodate a 22 inch wide ice machine. No adapter is needed.
BH900: Use baffle kit KBBF1 for these models.
Dispenser compatibility
Airflow
Options
Side air flow kits KPFSA223 or KPFSA227 are available for air cooled models. A filter kit for the remote condenser is KERCF
Ice is made until it fills the bin enough to block an infrared light beam inside the base of the machine. A field installed kit is available to adjust the maintained ice level lower. The kit number is KVS.
The standard controller has excellent diagnostic capabilities and communicates to the user through the AutoAlert light panel, seen through the front panel. Field installed kits are available that can log data and provide additional information when the front panel is removed. The kit numbers are KSBU and KSB-NU. See page 21.
Only nugget ice models may be used with ice dispensers. Flaked ice is not dispensable.
ID150 – use KBT42 and KDIL-PN-150, includes KVS, KNUGDIV and R629088514
ID200 – use KBT43 and KNUGDIV and KVS
ID250 – use KBT43 and KNUGDIV and KVS
See sales literature for other brand model ice and beverage dispenser applications.
Other Bins & Applications:
Note the drop zone and ultrasonic sensor locations in the illustrations on the next pages.
Scotsman ice systems are designed and manufactured with the highest regard for safety and performance. Scotsman assumes no liability of responsibility of any kind for products manufactured by Scotsman that have been altered in any way, including the use of any part and/or other components not specifically approved by Scotsman.
Scotsman reserves the right to make design changes and/or improvements at any time. Specifications and design are subject to change without notice.
July 2009
Page 3
Page 5
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522
24.00 REF.
61
22.00 REF.
55.9
2.92
7.4
6.48
16.5
2.81
7.1
4.30
10.9
16.50
41.9
12.50
31.8
ICE DROP OPENING
PLAN VIEW
ULTRA SONIC BIN LEVEL SENSOR OPTIONAL
12.40
31.5
2.68
6.8
1.59
4
14.65
37.2
2.17
5.5
AIR COOLED
BACK VIEW
3/4" FPT DRAIN
.88 DIA. ELECTRICAL ACCESS
3/8" FLARE MACHINE WATER INLET
12.35
31.4
2.17
5.5
1.59
4
2.63
6.7
14.55
37
19.31
49
17.55
44.6
3.33
8.5
15.40
39.1
WATER COOLED
BACK VIEW
3/8" FLARE MACHINE WATER INLET
3/4" FPT DRAIN
.88 DIA. ELECTRICAL CONNECTION
3/8" FPT CONDENSER WATER INLET
1/2" FPT CONDENSER DRAIN
18.88
48
2.68
6.8
14.60
37.1
12.40
31.5
7.40
18.8
10.94
27.8
1.59
4
2.17
5.5
REMOTE COOLED
BACK VIEW
REMOTE COND. LIQUID LINE 3/8" MALE CPLG.
REMOTE COND. DISCHARGE LINE 1/2" MALE CPLG.
.88 DIA. ELECTRICAL CONNECTION
3/4" FPT DRAIN
22.00
55.9
23.00
[58.5]
22.89
58.1
FRONT VIEW
LOUVER AND REMOVABLE FILTER A/C UNITS ONLY
24.00
61
.92
[2.4]
LEFT SIDE VIEW
Air, Water or Remote User Manual
N0422, F0522, N0622, F0822 Cabinet Layout
Note: Bin Top Cut-outs for drop zone should include ultrasonic sensor location
[cm}
In
December 2009
Page 4
Page 6
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522
24.00 REF.
61
22.00 REF.
55.9
2.92
7.4
6.48
16.5
2.81
7.1
4.30
10.9
16.50
41.9
12.50
31.8
ULTRA SONIC BIN LEVEL SENSOR OPTIONAL
PLAN VIEW
ICE DROP OPENING
13.39
34
2.67
6.8
18.64
47.3
1.59
4
AIR COOLED
BACK VIEW
3/8" FLARE MACHINE WATER INLET
.88 DIA. ELECTRICAL ACCESS
3/4" FPT DRAIN
13.39
34
2.17
5.5
2.67
6.8
18.59
47.2
1.59
4
19.80
50.3
18.05
45.8
3.37
8.6
15.44
39.2
WATER COOLED
BACK VIEW
.88 DIA. ELECTRICAL ACCESS
3/8" FLARE MACHINE WATER INLET
3/4" FPT DRAIN
1/2" FPT CONDENSER DRAIN
13.39
34
2.67
6.8
18.59
47.2
1.59
4
2.17
5.5
7.39
18.8
10.93
27.8
21.84
55.5
REMOTE COOLED
BACK VIEW
.88 DIA. ELECTRICAL ACCESS
3/8" FLARE MACHINE WATER INLET
3/4" FPT DRAIN
3/8" FPT CONDENSER WATER INLET
REMOTE COND. LIQUID LINE 3/8" CPLG
REMOTE COND. DISCHARGE LINE 1/2" CPLG
27.00
[68.6]
22.00
55.9
22.89
58.1
FRONT VIEW
LOUVER AND REMOVABLE FILTER A/C UNITS ONLY
24.00
61
.92
2.3
LEFT SIDE VIEW
Air, Water or Remote User Manual
N0922, F1222, N1322, F1522 Cabinet Layout
Note: Bin Top Cut-outs for drop zone should include ultrasonic sensor location
[cm}
December 2009
In
Page 5
Page 7
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522 Air, Water or Remote User Manual
Unpacking & Install Prep
Remove the carton from the skid. Check for hidden freight damage, notify the carrier immediately if any is found. Retain the carton for the carrier’s inspection.
The machine is not bolted to the skid. If strapped remove the strap.
Place on Bin or Dispenser
If reusing an existing bin, be sure that the bin is in good shape and that the gasket tape on the top is not torn up. Water leaks, not covered by warranty, could result from a poor sealing surface. If installing a remote or a remote low side, a new bin is recommended due to the high cost to the user of replacing an old bin when a remote system is on top.
Install the correct adapter, following the directions supplied with that adapter.
Panel Removal
1. Locate and loosen the two screws at the front edge of the top panel.
Hoist the machine onto the adapter.
Note: The machine is heavy! Use of a mechanical lift is recommended.
Position the machine on the bin or adapter. Secure with straps from the hardware bag packed with the machine, or those supplied with the adapter.
Remove any plastic covering the stainless steel panels.
Note: The standard machine set up includes visible on and off switches. Those can be covered up by changing the bezel in the front panel’s trim strip. A cover-up bezel is included with the hardware bag.
Remove any packaging, such as tape or foam blocks, that may be near the gear reducer or ice chute.
Level the bin and ice machine front to back and left to right by using the bin leg levelers.
2. Pull the front panel out at the top until it clears the top panel.
3. Lift the front panel up and off the machine.
4. Remove two screws at the front of the top panel. Lift up the front of the top panel, push the top panel back an inch, then lift to remove.
5. Locate and loosen the screw holding each side panel to the base. Left side panel also has a screw holding it to the control box.
6. Pull the side panel forward to release it from the back panel.
Button Switch Bezel
To change bezels: Remove the front panel, and refer to the instruction label on the inside of the front panel. Push snaps of standard bezel in and pull the bezel out of the front panel trim strip.
Locate other bezel. Push into the trim strip from the front until it snaps into place. Return the front panel to its original position and secure it to the cabinet
July 2009
Page 6
Page 8
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522 Air, Water or Remote User Manual
Water - Air or Water Cooled
The water supply for ice making must be cold, potable water. There is a single
3
” male flare
8
potable water connection on the back panel. Water cooled models also have a
3
” FPT inlet connection
8
for the water cooled condenser. Chilled water can also be used for this connection.
Backflow
The design of the float valve and reservoir prevents potable water backflow by means of a 1" air gap between the reservoir's maximum water level and the float valve water inlet orifice.
Drain
There is one ¾” FPT condensate drain fitting at the back of the cabinet. Water cooled models also have a ½” FPT discharge drain connection on the back panel.
Attach Tubing
Water Inlet
Drain Vent
Condensate
Drain
Building Drain
Connect the potable water supply to the potable water fitting,
3
” OD copper tubing or the equivalent
8
is recommended.
Water filtration is recommended. If there is an existing filter, change the cartridge.
Connect the water cooled water supply to the condenser inlet.
Note: Do NOT filter water to the water cooled condenser circuit.
Drains - use rigid tubing: Connect the drain tube to the condensate drain fitting. Vent the drain.
Connect the water cooled condenser drain tube to the condenser outlet. Do not vent this drain.
Do not Tee ice machine drains into the drain tube from the ice storage bin or dispenser. Back ups could contaminate and / or melt the ice in the bin or dispenser. Be sure to vent the bin drain.
Air Cooled or Remote Plumbing
Potable
Water
Inlet
Drain Vent
Condensate
Drain
Condenser Water Inlet
Condenser Drain
Follow all local and national codes for tubing, traps and air gaps.
July 2009
Page 7
Water Cooled Plumbing
Page 9
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522 Air, Water or Remote User Manual
Electrical - All Models
The machine does not include a power cord, one must be field supplied or the machine hard wired to the electrical power supply.
Connect electrical power to wires inside the junction box in the back of the cabinet. Use a strain relief and connect a ground wire to the ground
screw. The junction box for the power cord is on the back panel. See the next page.
Remote models power the condenser fan motor
from marked leads in the junction box. Refer to the dataplate on the machine for minimum circuit ampacity and determine the proper wire size for the application. The dataplate (on the back of
Do not use an extension cord. Follow all local and
national codes.
the cabinet) also includes the maximum fuse size.
Model
N0422A-1 22 x 24 x 23 115/60/1 Air 15.2 20
N0422W-1 same 111/60/1 Water 14.4 20
F0522A-1 same 115/60/1 Air 15.2 20
F0522W-1 same 115/60/1 Water 14.4 20
N0622A-1 same 115/60/1 Air 18.3 25
N0622W-1 same 115/60/1 Water 16.7 25
N0622R-1 same 115/60/1 Remote 19.4 25
N0622A-32 same 208-230/60/1 Air 9.8 15
N0622W-32 same 208-230/60/1 Water 8.9 15
F0822A-1 same 115/60/1 Air 18.3 25
F0822W-1 same 115/60/1 Water 16.7 25
F0822R-1 same 115/60/1 Remote 19.4 25
F0822A-32 same 208-230/60/1 Air 9.8 15
F0822W-32 same 208-230/60/1 Water 8.9 15
N0922A-32 22 x 24 x 27 208-230/60/1 Air 12.5 15
N0922W-32 same 208-230/60/1 Water 11.3 15
N0922R-32 same 208-230/60/1 Remote 12.3 15
N0922A-3 same 208-230/60/3 Air 13.0 15
N0922R-3 same 208-230/60/3 Remote 12.8 15
F1222A-32 same 208-230/60/1 Air 12.5 15
F1222W-32 same 208-230/60/1 Water 11.3 15
F1222R-32 same 208-230/60/1 Remote 12.3 15
F1222A-3 same 208-230/60/3 Air 13.0 15
F1222W-3 same 208-230/60/3 Water 11.8 15
F1222R-3 same 208-230/60/3 Remote 12.8 15
N1322A-32 same 208-230/60/1 Air 19.1 30
N1322W-32 same 208-230/60/1 Water 17.9 30
N1322R-32 same 208-230/60/1 Remote 18.9 30
F1522A-32 same 208-230/60/1 Air 19.1 30
F1522W-32 same 208-230/60/1 Water 17.9 30
Dimensions w"xd"xh"
Voltage Volts/Hz/Phase
Condenser Type
Min Circ
Ampacity
Max Fuse Size or HACR
Type Circuit Breaker
November 2009
Page 8
Page 10
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522
To Remote
Condenser
Fan Motor
Blue
Ground
Wire
Connection
Black
White Ground
Power Supply Wires
Install Strain Relief
Install Strain Relief
Junction
Box
Cover
Ground
Wire
Connection
Black
White
Ground
Power
Supply
Wires
Install Strain Relief
Junction
Box
Cover
Air, Water or Remote User Manual
Refrigeration - Remote Condenser Models
Remote condenser models have additional installation needs.
The correct remote condenser fan and coil must be connected to the ice making head. Liquid and discharge tubing connections are on the back of the ice machine cabinet. Pre-charged tubing kits are available in several lengths to accommodate most installations. Order the one that just exceeds the length needed for the installation.
The kit numbers are:
RTE10
RTE25
RTE40
RTE75
Reference: Electrical Detail, air or water cooled.
There are limits as to how far away from the ice machine and where the remote condenser can be located. See page 10 for those limits.
The correct condenser must be used.
Ice Machine Model
F0822R, N0622R
F1222R, N0922R
Voltage
115 ERC111-1
208-230 ERC311-32
Condenser Model
N1322R 208-230 ERC311-32
Do not reuse condenser coils contaminated with
mineral oil (used with R-502 for example). They will
cause compressor failure and will void the
warranty.
A headmaster is required for all remote condenser
systems. Prior condensers did not have a
headmaster. New head / prior condenser retrofits
can use headmaster kit KPFHM.
Use of non-Scotsman condensers requires
pre-approval from Scotsman Engineering.
Reference: Electrical Detail - Remote
July 2009
Page 9
Page 11
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522
22.87"
17.15"
40.35"
Air, Water or Remote User Manual
Remote Condenser Location - Limits
Use the following for planning the placement of the condenser relative to the ice machine
Location Limits - condenser location must not exceed ANY of the following limits:
Maximum rise from the ice machine to the
condenser is 35 physical feet Maximum drop from the ice machine to the
condenser is 15 physical feet Physical line set maximum length is 100 feet.
Calculated line set length maximum is 150.
Calculation Formula:
Drop = dd x 6.6 (dd = distance in feet)
Rise = rd x 1.7 (rd = distance in feet)
Horizontal Run = hd x 1 (hd = distance in
feet) Calculation: Drop(s) + Rise(s) + Horizontal
Run = dd+rd+hd = Calculated Line Length
Do NOT:
Route a line set that rises, then falls, then
rises. Route a line set that falls, then rises, then
falls.
Calculation Example 1:
The condenser is to be located 5 feet below the ice
machine and then 20 feet away horizontally.
5 feet x 6.6 = 33. 33 + 20 = 53. This location would
be acceptable
Calculation Example 2:
The condenser is to be located 35 feet above and
then 100 feet away horizontally. 35 x 1.7 = 59.5.
59.5 +100 = 159.5. 159.5 is greater than the 150
maximum and is NOT acceptable.
Configurations that do NOT meet these requirements must receive prior written authorization from Scotsman to maintain warranty.
Remote Condenser located above ice machine.
rd
Max 35'
Max 15'
dd
Remote condenser located below ice machine.
Operating a machine with an unacceptable
configuration is misuse and will void the warranty.
hd
Condenser Distance & Location Schematic
July 2009
Page 10
Page 12
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522
To Remote Condenser
Air, Water or Remote User Manual
For The Installer: Remote Condenser
Locate the condenser as near as possible to the interior location of the ice machine. Allow it plenty of space for air and cleaning: keep it a minimum of two feet away from a wall or other rooftop unit.
Note: The location of the condenser relative to the ice machine is LIMITED by the specification on the prior page.
Roof penetration. In many cases a roofing contractor will need to make and seal the hole in the roof for the line sets. The suggested hole diameter is 2 inches.
Meet all applicable building codes.
Roof Attachment
Power Supply from Ice Machine
Install and attach the remote condenser to the roof of the building, using the methods and practices of construction that conform to the local building codes, including having a roofing contractor secure the condenser to the roof.
Pre-Charged Refrigeration
Tubing
Remote Condenser
Liquid and Discharge Quick-Connects
July 2009
Page 11
Page 13
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522
To Remote Condenser
Fan Motor
Air, Water or Remote User Manual
Precharged Line Routing - Remote Only
Do not connect the precharged tubing until all routing and forming of the tubing is complete. See the Coupling Instructions for final connections.
1. Each set of pre-charged tubing lines contains a 3/8” diameter liquid line, and a 1/2” diameter discharge line. Both ends of each line have quick connect couplings.
Note: The openings in the building ceiling or wall, listed in the next step, are the minimum sizes recommended for passing the refrigerant lines through.
2. Have the roofing contractor cut a minimum hole for the refrigerant lines of 2”. Check local codes, a separate hole may be required for the electrical power supply to the condenser.
Caution: Do NOT kink the refrigerant tubing while
routing it.
3. Route the refrigerant tubes thru the roof opening.
Follow straight line routing whenever possible.
Excess tubing may EITHER be coiled up INSIDE
the building OR cut out prior to connection to the
ice maker and condenser.
If the excess tubing is cut out, after re-brazing the
tubing must be evacuated prior to connection to the
ice maker or condenser.
If the excess tubing is to be coiled, spiral it
horizontally to avoid excess trapping in the lines.
5. Have the roofing contractor seal the holes in the
roof per local codes
Power Supply to Condenser
Potable Water
Supply
Pre-Charged Tubing Line Set
Condensate
Drain
July 2009
Page 12
Page 14
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522 Air, Water or Remote User Manual
Coupling Instructions - Remote Only
The couplings on the ends of the pre-charged line sets are self-sealing when installed properly.
Follow these instructions carefully.
These steps must be performed by an EPA Certified Type II or higher technician.
Initial Connections
1. Remove the protector caps and plugs. Wipe the seats and threaded surfaces with a clean cloth to remove any possible foreign matter.
2. Lubricate the inside of the couplings, especially the O-rings, with refrigerant oil. Oil packets are supplied with Scotsman line sets.
3. Position the fittings on the correct connections on the condenser and ice machine.
Liquid
Discharge
Final Connections:
4a. Begin by tightening the couplings together by hand until it is certain that the threads are properly engaged.
loose in the refrigeration system. Note: As the
couplings are tightened, the diaphragms in the
quick connect couplings will begin to be pierced. As
that happens, there will be some resistance to
tightening the swivel nut.
4c. Continue tightening the swivel nut until it
bottoms out or a very definite increase in
resistance is felt (no threads should be showing).
Critical Step!!!!!
5. Use a marker or pen to mark a line on the
coupling nut and unit panel. Then tighten the
coupling nut an additional one-quarter turn. The
line will show the amount that the nut turns. Do
NOT over tighten.
4b. Then using two wrenches tighten the coupling until it bottoms out or a definite increase in resistance is felt.
It is important that ONLY the nut on the pre-charged tube be turned, or the diaphragms will be torn out by the piercing knives and they will be
July 2009
Page 13
6. After all connections have been made, and after
the receiver outlet valve has been opened (do not
open yet), check the couplings for leaks.
Page 15
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522
To Remote Condenser
Air, Water or Remote User Manual
Water - Remote Models
The water supply for ice making must be cold, potable water. There is a single
3
” male flare
8
potable water connection on the back panel.
Backflow
The design of the float valve and reservoir prevents potable water backflow by means of a 1" air gap between the reservoir's maximum water level and the float valve water inlet orifice.
Drain
There is one ¾” FPT condensate drain fitting at the back of the cabinet.
Attach Tubing
Connect the potable water supply to the potable water fitting,
3
” OD copper tubing or the
8
equivalent is recommended.
Potable Water
Water filtration is recommended. If there is an existing filter, change the cartridge.
Drains - use rigid tubing: Connect the drain tube to
the condensate drain fitting. Vent the drain.
Do not Tee ice machine drains into the drain tube
from the ice storage bin or dispenser. Back ups
could contaminate and / or melt the ice in the bin or
dispenser. Be sure to vent the bin drain.
Follow all local and national codes for tubing, traps
and air gaps.
Drain Vent
Condensate
Drain
July 2009
Page 14
Page 16
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522 Air, Water or Remote User Manual
Final Check List
After connections:
1. Wash out the bin. If desired, the interior of the bin could be sanitized.
2. Locate the ice scoop (if supplied) and have it available for use when needed.
3. Remote only: Switch on the electrical power
to warm up the compressor. Do not start the machine for 4 hours.
Final Check List:
1. Is the unit located indoors in a controlled environment?
2. Is the unit located where it can receive adequate cooling air?
3. Has the correct electrical power been supplied to the machine?
4. Have all the water supply connections been made?
Control Operation
Use and Operation
Once started, the ice machine will automatically
make ice until the bin or dispenser is full of ice.
When ice level drops, the ice machine will resume
making ice.
Caution: Do not place anything on top of the ice
machine, including the ice scoop. Debris and
moisture from objects on top of the machine can
work their way into the cabinet and cause serious
damage. Damage caused by foreign material is not
covered by warranty.
Power
Status
No
Water
Time to
Clean
On
Off
5. Have all the drain connections been made?
6. Has the unit been leveled?
7. Have all unpacking materials and tape been removed?
8. Has the protective covering on the exterior panels been removed?
9. Is the correct bezel installed in the trim strip?
10. Is the water pressure adequate?
11. Have the drain connections been checked for leaks?
12. Has the bin interior been wiped clean or sanitized?
13. Have any water filter cartridges been replaced?
14. Have all required kits and adapters been properly installed?
There are four indicator lights at the front of the
machine that provide information on the condition
of the machine.
Indicator Lights:
Power
Status
Water
De-scale & Sanitize
Note: If the De-Scale & Sanitize light is ON,
following the cleaning process will clear the light for
another cleaning time internal.
Two button switches are at the front – On and Off.
To switch the machine OFF, push and release the
Off button. The machine will shut off at the end of
the next cycle.
To switch the machine ON, push and release the
On button. The machine will go through a start up
process and then resume ice making.
July 2009
Page 15
Page 17
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522 Air, Water or Remote User Manual
Initial Start Up and Maintenance
1. Turn the water supply on.
2. Switch the electrical power on. Confirm voltage
is correct for the model.
3. Push and release the On button. The machine
will start in about two minutes.
4. Soon after starting, air cooled models will begin
to blow warm air out the back of the cabinet and water cooled models will drain warm water from the condenser drain tube. Remote models will be discharging warm air from the remote condenser. After about 5 minutes, ice will begin to drop into the bin or dispenser.
5. Check the machine for unusual rattles. Tighten
any loose screws, be sure no wires are rubbing moving parts. Check for tubes that rub.
6. Fill out the warranty registration form and either
file it on line or mail it.
7. Notify the user of the maintenance
requirements and whom to call for service.
Maintenance
This ice machine needs five types of maintenance:
Air cooled and remote models need their air filters or condenser coils cleaned regularly.
All models need scale removed from the water system.
All models require regular sanitization.
All models require sensor cleaning.
All models require a top bearing check.
Sensor Cleaning
Top bearing check
time the scale is removed.
Maintenance:
1. Pull air filter(s) from panel.
2. Wash the dust and grease off the filter(s).
3. Return it(them) to their original position(s).
Do not operate the machine without the filter in
place except during cleaning.
Maintenance:
If the machine has been operated without a filter
the air cooled condenser fins will need to be
cleaned.
They are located under the fan blades. The
services of a refrigeration technician will be
required to clean the condenser.
Maintenance:
The condenser fins will occasionally need to be
cleaned of leaves, grease or other dirt. Check the
coil every time the ice machine is cleaned.
Maintenance:
The front and side panels are durable stainless
steel. Fingerprints, dust and grease will require
cleaning with a good quality stainless steel cleaner
: Every time the scale is removed.
: At least twice a year or every
Air filters
Air cooled condenser
Remote air cooled condenser
Exterior Panels
Maintenance Frequency:
Air filters greasy air, monthly.
Scale removal conditions it might be every 3 months. The yellow De-Scale & Sanitize light will switch on after a set period of time as a reminder. The default time period is 6 months of power up time.
Sanitizing often as needed to maintain a sanitary unit.
: At least twice a year, but in dusty or
. At least twice a year, in some water
: Every time the scale is removed or as
July 2009
Note: If using a sanitizer or a cleaner that contains
chlorine on the panels, after use be sure to wash
the panels with clean water to remove chlorine
residue.
Maintenance:
If the machine has been connected to water filters,
check the cartridges for the date they were
replaced or for the pressure on the gauge. Change
cartridges if they’ve been installed more than 6
months or if the pressure drops too much during
ice making.
Page 16
Water filters
Page 18
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522
Disconnect
From Sensor
Tubing
Air, Water or Remote User Manual
Maintenance: Scale Removal and Sanitation
Note: Following this procedure will reset the de-scale and sanitize light.
1. Remove front panel.
2. Push and release the Off button.
3. Remove ice from bin or dispenser.
4. Turn the water supply to the ice machine OFF.
5. Drain the water and evaporator by
disconnecting the leg of the hose connected to the water sensor and draining it into the bin. Return the hose to its original position.
6. Remove the water reservoir cover.
7. Mix a solution of 8 ounces of Scotsman Clear
One Scale Remover and 3 quarts of 95-115 degree F. potable water.
Ice machine scale remover contains acids. Acids can cause burns. If concentrated cleaner comes in contact with skin, flush with water. If swallowed, do NOT induce vomiting. Give large amounts of water or milk. Call Physician immediately. Keep out of the reach of children.
8. Pour the scale remover solution into the
reservoir. Use a small cup for pouring.
9. Push and release the Clean button: the auger
drive motor and light are on, C is displayed and the De-scale light blinks. After 20 minutes the compressor will start.
Drain Water
the water sensor and draining it into the bin or a bucket. Return the hose to its original position. Discard or melt all ice made during the previous step.
13. To sanitize the water system, mix a locally approved sanitizing solution. An example of a sanitizing solution is mixing one ounce of liquid household bleach and two gallons of 95 – 115 degree F. water.
14. Pour the sanitizing solution into the reservoir.
15. Push and release the On button.
16. Switch the water supply to the ice machine on.
17. Operate the machine for 20 minutes.
18. Push and release the Off button.
19. Wash the reservoir cover in the remaining sanitizing solution.
20. Return the reservoir cover to its normal position.
10. Operate the machine and pour the scale remover into the reservoir until it is all gone. Keep the reservoir full. When all the scale remover solution has been used, turn the water supply back on. After 20 minutes of ice making the compressor and auger motor will shut off.
11. Turn the water supply to the ice machine OFF
12. Drain the water reservoir and evaporator by disconnecting the leg of the hose connected to
July 2009
21. Melt or discard all ice made during the sanitizing process.
22. Wash the inside of the ice storage bin with the sanitizing solution.
23. Push and release the On button.
24. Return the front panel to its original position and secure with the original screws.
Page 17
Page 19
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522
Bail Clamp
Air, Water or Remote User Manual
Maintenance: Check Top Bearing
This task should only be done by a qualified service technician
The bearing in the breaker should be checked at least two times per year.
Check the bearing by:
1. Removing the bail clamp and ice chute cover
3. Removing the water shed & unscrewing the breaker cover (left hand threads).
Breaker Cover
2. Unscrewing the ice sweep
Inspect the top of the bearing. When new the grease is white, over time some gray will appear over the rollers, that is normal. Add grease to replace the gray grease or if gaps between rollers are visible. If grease is watery, all gray or rust is visible, have the bearing replaced. See the next page for more information.
Note: When checking the top bearing, always inspect the drip pan for water seal leaks. If water is present in the drip pan, service the water seal and check the gear reducer's lubricant. See the next page.
July 2009
Page 18
Page 20
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522 Air, Water or Remote User Manual
Bearing Service
This task should only be done by a qualified service technician
If the grease is uniformly white, no further action is needed. If very gray, rusty, wet or has any embedded metal, have the bearing replaced.
Grease
If the bearing only needs grease, or to confirm the quality of the grease low in the bearing, inject grease into the lower part of the bearing using Scotsman grease needle pn 02-3559-01 and Scotsman bearing grease cartridge, pn A36808-001. Be sure to inject grease evenly and thoroughly.
Bearing
Needle, pn 02-3559-01
Drip Pan
Check Drip Pan For Water
Change De-Scale Notification Interval
This feature is accessible only from standby (Status Light Off).
1. Press and hold Clean button for 3 seconds.
This starts the Time to Clean Adjustment State and displays the current time to clean setting.
2. Press the clean button repeatedly to cycle through the 4 possible settings:
3. Push Off to confirm the selection.
July 2009
Page 19
1 year
0 (disabled)
4 months
6 months(default)
Page 21
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522 Air, Water or Remote User Manual
Maintenance: Sensors
The control that senses bin full and empty is a photo-electric eye, therefore it must be kept clean so it can “see”. At least twice a year, remove the ice level sensors from the base of the ice chute, and wipe the inside clean, as illustrated.
1. Remove front panel.
2. Pull photo eye holders forward to release them.
3. Wipe clean as needed. Do not scratch the photo-eye portion.
4. Return the eye holders to their normal positions and return the front panel to its original position.
Note: Eye holders must be mounted properly. They snap into a centered position and are properly located when the wires are routed to the back and the left eye is the one with 2 wires at the connector.
The ice machine senses water by a probe located near the water reservoir. At least twice a year, the probe should be wiped clean of mineral build-up.
Probes
1. Shut off the water supply.
2. Remove front panel.
3. Remove the hose from the water sensor, use a hose clamp pliers for this.
5. Wipe probes clean,
July 2009
Page 20
Page 22
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522
02-4294-01 Rev.A.
Adjust Ice Level
L
o
w
e
r
Bin
Full
Smart-Board Advanced Feature Control
See Instructions for Available Features
34
SEL
02-4293-01
ENTER
ESC
01/07
02-4294-01 Rev. A.
Adjust Ice Level
L
o
w
e
r
Bin
Full
02-4294-01 Rev. A.
Adjust Ice Level
L
o
w
e
r
Bin
Full
Air, Water or Remote User Manual
Options
Vari-Smart
Optional adjustable ice level control (KVS)
When this option is present there is an adjustment post and an additional indicator light to the right of the four indicator lights mentioned earlier.
KVS
The ultrasonic ice level control allows the user to control the point that the ice machine will stop making ice before the bin or dispenser is full. Reasons for this include:
Seasonal changes in ice used
Planning to sanitize the bin
Faster turnover for fresher ice
Certain dispenser applications where
maximum ice level is not desired
Use of adjustable ice level control
There are several positions the ice level can be set to, including Off (knob and label indicators lined up), where it fills the bin until the standard bin control shuts the machine off. See the kit’s instructions for complete details.
Rotate the adjustment post to the desired ice level. The machine will fill up to that level and when it shuts off the indicator light next to the adjustment post will be On.
Note: The maximum fill position is when the arrow on the knob points to the arrow on the label.
Dispenser applications ­Nugget ice only:
Set the adjustment knob to either the first or second position CW after the maximum fill position.
Smart-Board
Optional Advanced Feature Board (KSBU)
The Advanced Feature Board’s features include:
Seven day programmable ice level setting when used with the optional KVS ultrasonic ice level control
Recording of machine operation
Recall of malfunctions with the time they occurred.
Optional Remote Lock Out (KSL)
This add on allows remote on-off control of the machine, and is generally installed by leasing companies. When the board has been remotely locked out and shut off it must be reset by the
person or company that locked it out. It cannot be reset on site.
July 2009
Page 21
Page 23
N0422, F0522, N0622, F0822, N0922, F1222, N1322, F1522 Air, Water or Remote User Manual
What to do before calling for service
Normal Operation:
Ice
The machine will make either flaked or nugget ice, depending upon the model. The ice will be produced continuously until the bin is full. It is normal for a few drops of water to occasionally fall with the ice.
Heat
Noise
Does not make ice
Auger motor overload
High discharge pressure.
Low refrigeration system pressure.
Controller self test failure.
Check the following:
1. Has the water supply to the ice machine or building been shut off? If yes, the ice machine will automatically restart within minutes after water begins to flow to it.
2. Has power been shut off to the ice machine? If yes, the ice machine will automatically restart when power is restored.
3. Has someone shut the power off to the remote condenser while the ice machine still had power? If yes, the ice machine may need to be manually reset.
The ice machine will make noise when it is in ice making mode. The compressor and gear reducer will produce sound. Air cooled models will add fan noise. Some ice making noise could also occur.
These noises are all normal for this machine.
Reasons the machine might shut itself off:
Lack of water.
Indicator Lights & Their Meanings
Power Status Water
Steady Green
Blinking Green
Blinking Red
Normal Normal - -
Switching on or off. Self Test Failure
- Diagnostic shut down Lack of water -
When Smart-Board
used, machine attention
recommended.
To Manually Reset the machine.
Push and release the Off button.
Push and release the On button.
To Shut the Machine Off:
Push and hold the Off button for 3 seconds or until the machine stops.
De-Scale & Sanitize
--
Yellow
Light Actions
Blinking Yellow
Light Off
All Blinking
-- -
-- -
No power Switched to Off Normal Normal
Unit is remotely locked out - check with leasing company
July 2009
Page 22
Time to descale and sanitize
In Cleaning Mode
Page 24
SCOTSMAN ICE SYSTEMS 775 Corporate Woods Parkway, Vernon Hills, IL 60061 800-533-6006 www.scotsman-ice.com
17-3222-01
Loading...