Scotsman ECC Series Remote Condensing Unit, EH330 Prodigy Plus Eclipse 1400, EH430 Prodigy Plus Eclipse 1400, EH430 Prodigy Plus Eclipse 1800 Service Manual

Service Manual for Prodigy Eclipse Cubers models EH330 C and EH430 C, with ECC Condensing Unit ECC1200, ECC1410, ECC1800
Includes Prodigy Plus D Models
EH330, EH430 and ECC Condensing Unit Remote Low Side Cuber Service Manual
Introduction:
This manual covers the assembly, installation, start up, operation and maintenance of the 1200, 1400 and 1800 remote low side cuber systems.
Contents
Conguration .......................... Page 2
Technical Specications ................. Page 3
Cabinet Drawings, EH330C Ice Making Head Page 4
Cabinet Drawings, EH430C Ice Making Head Page 5
Cabinet Drawings, EH330D Ice Making Head Page 6
Cabinet Drawings, EH430D Ice Making Head Page 7
Cabinet Drawings, ECC Condensing Unit .... Page 8
Pre-Installation Details. . . . . . . . . . . . . . . . . . . Page 9
Create the System ...................... Page 10
System Example ....................... Page 11
Place Remote System ................... Page 12
Tubing ............................... Page 13
Place Ice Making Head .................. Page 14
EH430) .............................. Page 30
Controller Information ................... Page 32
Operation ............................. Page 33
System Operation: ...................... Page 34
Refrigeration Details: .................... Page 35
Freeze Cycle Sequence of Operation ....... Page 36
Harvest Cycle Sequence of Operation ...... Page 37
Control Safeties ........................ Page 38
Controller Operation .................... Page 39
Service Diagnosis ...................... Page 40
Service Diagnosis ...................... Page 41
Service Diagnosis ...................... Page 42
Refrigeration Data ...................... Page 43
Refrigeration Data - 1800 ................ Page 44
Condensing Unit Electrical ............... Page 15
Water and Drain ....................... Page 16
Connect Refrigeration ................... Page 17
Complete the Installation ................. Page 18
Reference for Start Up: Controller Operation . Page 19
Initial Start Up ......................... Page 20
Ice Thickness and Water Purge Adjustment .. Page 21
Cleaning, Sanitation and Maintenance ...... Page 22
Operational Characteristics 1200 lb system (ECC1200/
EH330) .............................. Page 29
Operational Characteristics 1400 lb system (ECC1410/
EH430) .............................. Page 29
Operational Characteristics 1800 lb system (ECC1800/
Refrigerant Recovery. . . . . . . . . . . . . . . . . . . . Page 45
System Isolation ....................... Page 46
Condenser Coil ........................ Page 47
EH330-C or EH430-C Schematic Diagram .. Page 48
EH330-C or EH430-C Wiring Diagram ...... Page 49
EH330-D or EH430-D Schematic Diagram ... Page 50
EH330-D or EH430-D Wiring Diagram ...... Page 51
ECC 3 Phase Schematic Diagram ......... Page 52
ECC 3 Phase Wiring Diagram ............. Page 53
ECC 1 Phase Schematic Diagram ......... Page 54
ECC 1 Phase Wiring Diagram ............. Page 55
May 2015
EH330, EH430 and ECC Condensing Unit Remote Low Side Cuber Service Manual
Conguration
A remote low side cuber system includes two sub systems: an ice head section and a remote condensing unit. Additionally, there are several models of each sub-system and this manual covers all of them.
The ice making sections are designed for use indoors in a controlled environment. The remote condensing units are designed to operate outdoors. Each sub­system has limits for power, water and temperature.
Operational Limitations:
Minimum Maximum
Air Temp (IH) 50oF 100oF.
Air Temp (CU) -20oF. 120oF.
Water Temp 40oF. 100oF.
Water Pressure 20 psi 80 psi
Water Conductivity 10 microSiemens/cm
Voltage (IH) 104 126
Voltage (CU) 198 253
IH = Ice Head, CU= Condensing Unit
Warranty
Refer to the warranty coverage in effect when the equipment was sold. Warranty statements are included with each product.
Systems:
Each sub-system is a separate entity that carries its own model and serial number. They must be combined to create a remote cuber low side system.
Notes: Voltage Codes are at the end of the model number. Codes read Voltage/Hertz/Phase. Those related to these products include:
-1 = 115/60/1
-3 = 208-230/60/3
-32 = 208-230/60/1
Tubing kits are required to interconnect the head to the CU
Do Not operate the machine in conditions beyond these limitations. Doing so will void the warranty.
Scotsman ice systems are designed and manufactured with the highest regard for safety and performance. They meet or exceed the standards of
20 foot: 3BRTE20-EH,
35 foot: 3BRTE35-EH
50 foot: 3BRTE50-EH
75 foot: 3BRTE75-EH
UL and NSF.
Interconnecting 24 volt control wire ships in the
Scotsman assumes no liability of responsibility of
condensing unit.
any kind for products manufactured by Scotsman that have been altered in any way, including the use
of any part and/or other components not specically
approved by Scotsman.
Scotsman reserves the right to make design changes
and/or improvements at any time. Specications and
design are subject to change without notice.
System Information
System Size Condensing Unit (CU) Ice Making Head (IH)
Model Electrical
(volts/Hz/phase)
1200 ECC1200-32A 208-230/60/1 EH330SL-1C/D or EH330ML-1C/D 115/60/1
1400 ECC1410-32A 208-230/60/1 EH430SL-1C/D or EH430ML-1C/D 115/60/1
1400 ECC1410-3A 208-230/60/3 EH430SL-1C/D or EH430ML-1C/D 115/60/1
1800 ECC1800-3A 208-230/60/3 EH430SL-1C/D or EH430ML-1C/D 115/60/1
May 2015
Model Electrical
(volts/Hz/phase)
EH330, EH430 and ECC Condensing Unit Remote Low Side Cuber Service Manual
Technical Specications
Model Electrical
(volts/Hz/
phase) EH330SL-1C or D 115/60/1 3 15 - 30 x 24 x 23 130 EH430SL-1C or D 115/60/1 3 15 - 30 x 24 x 29 165 ECC1200-32 208-230/60/1 17.8 30 224 32 x 39 x 39.75 ECC1410-3 208-230/60/3 9.1 20 224 32 x 39 x 39.75 ECC1410-32 208-230/60/1 14.5 30 224 32 x 39 x 39.75
ECC1800-3 208-230/60/3 19.0 30 232 32 x 39 x 39.75
* See Cabinet Drawings for exact dimensions.
Location Limitations
Maximum Distance between Head and Condensing Unit: Limited to the length of the longest available single tubing kit, 75 feet.
Maximum Condensing Unit Elevation over Ice Making Head: 35 feet.
Note: Elevations greater than 20 feet require installation of a suction line trap at the 20 foot mark.
Minimum Circuit Ampacity
Maximum Fuse Size
Condensing unit
The dataplate on the condensing unit contains the model number, serial number, electrical data and system refrigerant charge.
A second plate, located behind the front panel in front of the compressor, also lists the model number, serial number and refrigerant charge.
System Charge oz of R-404A
Cabinet Size* w” x d” x h”
Approx. Unit Weight (lb)
Maximum Ice Making Head Elevation over Condensing Unit: 15 feet.
Line Routing:
Allowed: One rise after a drop.
Allowed: One drop after a rise.
Not Allowed: More than one rise after a drop
Not Allowed: More than one drop after a rise.
Model Number Locations
Ice Making Head
The dataplate on the back of the ice machine contains the model number, serial number and electrical data.
A second plate, located behind the front panel at the lower right front, also lists the model and serial numbers.
July 2013
EH330, EH430 and ECC Condensing Unit Remote Low Side Cuber Service Manual

Cabinet Drawings, EH330C Ice Making Head

ELECTRICAL CORD ACCESS HOLE
3/8" FPT WATER INLET
141.73
5.58
110.46
4.35
94.72
3.73
3/4" SUCTION LINE
1/2" COOL VAPOR LINE
3/8" LIQUID LINE
609.60
24.00
464.82
18.30
50.80
2.00
393.70
15.50
MINIMUM BIN
TOP OPENING
PLAN VIEW
762
30.00
244.60
9.63
ICE DROP OPENING
228.60
9.00
784.55
30.89
432.56
17.03
3/4" FPT DRAIN
703.20
27.69
BACK VIEW
88.62
3.49
69.32
2.73
313.69
12.35
56.64
2.23
INFERFACE CABLE ACCESS HOLE
381.76
15.03
448.56
17.66
530.86
20.90
38.23
1.51
UTILITY
CASE
190.50
7.50
153.16
6.03
609.60
24.00
LEFT SIDE VIEW
584.20
23.00
762
30.00
FRONT VIEW
July 2013
EH330, EH430 and ECC Condensing Unit
3/4" FPT
Remote Low Side Cuber Service Manual

Cabinet Drawings, EH430C Ice Making Head

141.73
5.58
108.46
4.27
93.98
3.70
85.06
3.35
ELECTRICAL CORD ACCESS HOLE
3/8" FPT WATER INLET
3/4" SUCTION LINE
1/2" COOL VAPOR LINE
3/8" LIQUID LINE
609.60
24.00
464.82
18.30
50.80
2.00
393.70
15.50
MINUMUM
TOP OPENING
PLAN VIEW
762
30.00
244.60
9.63
ICE DROP OPENING
228.60
9.00
30.89
508.76
20.03
477.01
18.78
533.62
21.01
600.71
23.65
681.74
26.84
228.60
9.00
216.15
8.51
736.60
29.00
July 2013
EH330, EH430 and ECC Condensing Unit Remote Low Side Cuber Service Manual

Cabinet Drawings, EH330D Ice Making Head

May 2015
EH330, EH430 and ECC Condensing Unit Remote Low Side Cuber Service Manual

Cabinet Drawings, EH430D Ice Making Head

May 2015
EH330, EH430 and ECC Condensing Unit Remote Low Side Cuber Service Manual

Cabinet Drawings, ECC Condensing Unit

TOP VIEW
992.81
39.09
814.22
32.06
FRONT VIEW
32.05
1.26
TYP.
1009.65
39.75
887.73
34.95 .88" ELECTRICAL INLET
1/2" COOL VAPOR LINE
3/4" SUCTION LINE
3/8" LIQUID LINE
83.67
3.29
SIDE VIEW
LINE SET AND ELECTRICAL ATTACHMENT SIDE
330.86
13.03
74.12
2.92
163.02
6.42
248.87
9.80
750.06
29.53
491.69
19.36
INTERFACE HARNESS ACCESS HOLE
63.50
2.50
July 2013
EH330, EH430 and ECC Condensing Unit Remote Low Side Cuber Service Manual

Pre-Installation Details

Note: The ice making head cannot be stacked vertically.
Accessories such as bin adapters and tubing kits are required to complete the installation.
Dispenser Adapter Kits:
Scotsman ID200 or ID250: KBT44
Bin Adapter Kits:
B948S: KBT22A
Tubing Kits:
20 foot: 3BRTE20-EH
35 foot: 3BRTE35-EH
50 foot: 3BRTE50-EH
75 foot: 3BRTE75-EH
Note: Line set may have quick connects. See refrigeration system detailed instructions connection details.
Items required for installation:
Water
Pure water does not exist. All water supplies contain some amounts of impurities, although potable water
is, by denition, t for human consumption. Because
the contents of the water to an ice machine directly impact its performance, consideration should be given to improving the water’s quality.
There are two ways water can contain impurities: in suspension or in solution. Suspended solids can
be ltered out of the water. In solution or dissolved solids must be diluted or treated. Water lters are
recommended to remove the suspended solids.
Some lters or lter systems have treatment
chemicals in them for treating the suspended solids.
This ice machine has an adjustment for the amount of water rinsed or purged. Water use adjustments are customer convenience adjustments; they are not factory defects and are not covered by warranty.
Ice making head
Condensing unit (includes interconnecting control
system wire)
Tubing kit. 20’, 35', 50’ or 75’ triple line set (liquid, vapor and suction)
Bin or dispenser adapter
Special Considerations
The ice making section’s footprint is 30” wide by 24” deep plus another 1.5” for a utility chase on the back panel. The refrigeration connections can be made to go up or out the back by bending the line set tubing. The electrical power cord and the water inlet line can also be routed through either of those areas. The drain may be routed out the back or to the left side.
July 2013
EH330, EH430 and ECC Condensing Unit Remote Low Side Cuber Service Manual

Create the System

Plan the installation. The system consists of three parts: the ice making head, the condensing unit and the interconnecting tubing. Of these, the biggest variable is the interconnecting tubing.
Tubing: The tubing consists of three insulated and sealed soft copper tubes. One tube, the liquid line, is 3/8” OD. The vapor tube is ½” OD and the suction tube is ¾” OD. A site inspection will determine what length of tubing is required for the installation.
In 2013 Scotsman made a change to the Eclipse tubing kits:
Prior Tubing Kits: They each contain a small holding charge of R-404A and have quick connects at the ends.
Current Tubing Kits: The do not contain any refrigerant and do not have quick connects.
Either type can be used to connect the head and condensing unit.
Quick Connect type: Check ice making head and condensing unit for quick connects. If none, recover refrigerant from tubing and cut the quick connects off.
Condensing Unit: Electrical power must be supplied to the condensing unit, it will be separate from the head.
The remote tubing connections are at the top of the machine, and connections should not be made until
the machine is nearly in its nal installed position.
The 115/60 Hz ice making section is cord connected and requires an outlet within 6 feet of the installation.
Interconnecting wires: A low voltage interconnecting wire harness is included with the condensing unit. One end plugs into the ice making head and the other into the condensing unit. The system will NOT operate without this harness.
Exposed tubing: Minimize the amount of tubing exposed outdoors.
If the head or condensing unit has a quick connect, recover refrigerant and only cut off the quick connect at the system with the stub connections.
Tubing without quick connects: Check head and condensing unit, if neither have quick connects, use as is. If one or both do, obtain kit KTE6 to add quick connects to the line set.
Excess tubing must be shortened at the job site.
Installations with greater than 20 feet of vertical lift between ice machine and the compressor require a suction line trap. The suction line requires careful handling and large radius bends to prevent kinking.
Roof mounting: Some installations will require the use of a hoist to lift the components to the roof.
Pad mounting: The condensing unit may be located below the ice making section, up to a limit of 15 feet.
Distance from unit: Limited to the length of the available tubing.
Elevation: Condensing unit limited to 35 feet above the ice making head.
July 2013
Page 10
EH330, EH430 and ECC Condensing Unit Remote Low Side Cuber Service Manual

System Example

July 2013
Page 11
EH330, EH430 and ECC Condensing Unit Remote Low Side Cuber Service Manual

Place Remote System

Roof preparation
Most installations of this system will place the condensing unit on the roof of a building. The roof must be physically able to accept the load of the
equipment and the roong material must be prepared
to prevent water leaks.
Follow local codes for the placement and attachment of the equipment.
Location
The condensing unit requires unobstructed air ow to operate efciently. A four foot space between
each intake side and a wall or other cabinet is recommended.
Do not place where it will pick up hot discharged air from an air conditioner or other refrigeration system condensing unit.
Space must also be reserved for service on the condensing unit.
Roof Pipe Curb or Pitch Pocket:
To avoid potential kinking of the refrigeration tubing, avoid small, tight radius types of covers on pitch pockets.
Suggestions:
In most cases a mechanical lift, boom truck or crane will be required to hoist the condensing unit.
Mount unit to roof rails or curbs and secure with lag
screws or similar eld supplied fasteners.
Orient the assembled unit so that the unit’s mounts are parallel to the pitch of the roof to allow water to drain freely.
Do NOT place the unit directly onto roof rock.
Roof Piercing:
The roof (or wall) must have an opening large enough for the three refrigeration tubes and the control wire to pass through. The minimum recommended size is 4” ID. In most areas the power supply may also pass through the same passage. If there isn’t a passage one must be created. In most cases this must be done by a licensed and bonded roofer in order to maintain the roof’s integrity.
July 2013
Page 12
EH330, EH430 and ECC Condensing Unit Remote Low Side Cuber Service Manual

Tubing

The line set must be routed between the condensing unit and the ice maker’s location. During the transition from quick connects to braze connections, the ice maker, condensing unit and line set may or may not have quick connects, use this chart as a guideline for the proper action based on what is available at the site.
Condensing unit has sweat connections Condensing unit has quick connects
Ice making head has sweat connections
Ice making head has quick connects (prior models of EH330 and EH430)
If line set does not have quick connects, route and use as is.
If line set has quick connects, recover refrigerant from line set and cut all quick connects off.
If line set has quick connects, recover refrigerant from line set and cut one end of quick connects off.
If line set does not have quick connects, must use KTE6-EH stub kit to add for ice machine end.
Compressor packs C1200CP, C1410CP and C1800CP may be connected to this head and will have quick connects. If line set has quick connects, recover refrigerant from line set and cut one end of quick connects off.
If line set does not have quick connects, must use KTE6-EH stub kit to add for condensing unit end.
If line set does not have quick connects, must use KTE6-EH stub kit to add for ice machine end.
Use the quick connects to make the connection.
In all cases the line set will need to be shortened to t.
Do NOT leave excess line set exposed outdoors, especially on a roof.
Refrigerant Recovery and System Evacuation Notice
In the event the refrigerant must be recovered from this system and the system evacuated, recover and evacuate from the three ball valve access valves.
July 2013
Page 13
EH330, EH430 and ECC Condensing Unit Remote Low Side Cuber Service Manual

Place Ice Making Head

Remove from carton.
Remove all panels.
Utility Connection Route:
Electrical: The unit is supplied with a power cord. There is also an interconnecting control wire that must be routed between the ice making head and the condensing unit.
Water Supply: The water supply can be routed from the top or back.
Drain: The drain must be routed out the back.
Refrigeration Tubing: Field bending will allow the tubing to be routed up or towards the back.
Adapters:
In many cases an adapter kit will be required when placing the head unit on a bin or dispenser. See sales information for the correct kit. Place adapter kit onto bin or dispenser top. If adapter does NOT have gasket tape install tape such as Scotsman part number 19-0503-04.
Note: External drain tubing must be supported to insure that it does not move and kink the internal rubber tube.
Communication Cable
Plug the interconnecting communication cable into the harness at the back of the head unit’s electrical box.
Connect Communication Cable Here
July 2013
Page 14
EH330, EH430 and ECC Condensing Unit Remote Low Side Cuber Service Manual

Condensing Unit Electrical

Route interconnecting control wire through proper hole in side of CU unit and plug into the connection on the side of the control box.
Route power conduit (liquid tight) and wires to the hole in the side of the CU unit. Connect to wire leads or terminal strip, if used, with the proper type of connector.
Note: The power supply wires must be the correct size and type per the National Electric Code.
Locate the nameplate on the CU unit for the Voltage, Phase, Minimum Circuit Ampacity and Maximum Fuse Size. Either fuses or HACR type circuit breakers may be used.
Follow all Local, State and National Codes.
Three Phase Notice: Check voltage between legs at contactor. If there is a “wild leg” in the three phase power supply move supply wires so the higher voltage is on L3 of the contactor, which connects to the compressor motor only.
Connect Cable Here
Electrical Junction Box
Dataplate Location
Communication Cable
July 2013
Page 15
EH330, EH430 and ECC Condensing Unit Remote Low Side Cuber Service Manual

Water and Drain

All models require connection to cold, potable water. A hand actuated valve within sight of the machine is required. There is a single 3/8” FPT inlet water connection.
Water Filters
Install a new cartridge if the lters were used with a
prior machine.
All models require drain tubing to be attached to them.
There is a single ¾” FPT drain tting in the back of the
cabinet.
Install new tubing when replacing a prior ice machine, as the tubing will have been sized for the old model and might not be correct for this one.
1. Connect water supply to water inlet tting.
Note: This NSF listed model has a 1" anti-back ow
air gap between the potable water inlet tube end and the highest possible reservoir water level, no back
ow device is required.
2. Connect drain tubing to drain tting.
3. Route the drain tubing to building drain. Follow local codes for drain air gap. Use rigid drain tubes and route them separately – do not Tee into the bin’s drain.
Vent the reservoir drain. A vertical vent at the back of the drain, extended about 8 – 10” will allow the gravity drain to empty and also keep any surges during draining from discharging water.
Horizontal runs of drain tubing need a ¼” per fall per foot of run for proper draining.
Follow all applicable codes.
Water Inlet
Refrigeration Connections
Reservoir Drain Fitting
July 2013
Page 16
EH330, EH430 and ECC Condensing Unit Remote Low Side Cuber Service Manual

Connect Refrigeration

Requires brazing, steps must be performed by an
EPA certied type II or higher technician.
At Head:
1. Remove protective plugs from all three connections and vent the nitrogen from the ice machine.
2. Route the each of the three tubes to its connection.
3. Remove the top panel and attach a refrigeration hose with depressor to the 1/2 inch ID vapor line access valve so the valve is OPEN. This is a vent for nitrogen purging.
4. Clean tubing ends and position into the couplings.
At Condensing Unit
1. Conrm connection valves are fully closed.
At Head
1. With nitrogen owing from condensing unit, braze the liquid, vapor and suction line connections.
2. Remove refrigeration hose from head. Be sure valve cap is on tight.
At Condensing Unit
1. Remove nitrogen supply.
2. Return valve cores to access valves.
3. Connect vacuum pump to all three access valves and evacuate the tubing and head to at least a 300 micron level.
4. Remove vacuum pump and add R-404A vapor to all three tubes to provide a positive pressure.
5. Leak check the braze connections and repair any leaks.
6. Open all three valves to full open.
2. Remove protective plugs from all three connections.
3. Remove caps from access valve connections.
4. Remove cores from access valves.
5. Connect refrigeration hoses to access valves.
6. Connect dry nitrogen source to liquid line connection and vapor line connection.
7. Shorten tubing to correct length, clean ends and insert them into valve stubs.
Note: Be sure tube and stubs are round, dress with swage tool if needed.
8. Add heat sink material to ball valve body.
9. Open nitrogen and ow 1 psi nitrogen into liquid line and vapor line tubes and braze the liquid line, vapor line and suction line tubes to the valve stubs.
Valves Closed
Note: The full refrigerant charge is contained in the receiver of the condensing unit.
Refrigeration Connections
July 2013
Page 17
Loading...
+ 39 hidden pages