section, low side
pressure rapidly
increases to 90 - 95
PSIG or higher in hot
ambient conditions
System Pressures
System Pressures
– At the CP unit
compressor access
valve, dome pressure
is limited by the CPR
valve to 55 - 60 PSIG
during harvest
Page 61
•CP Unit
– Discharge during low
ambient freeze will be
about 240 PSIG
– Discharge during harvest
will be about 100 PSIG
– High Pressure Cut Out
System Pressures
System Pressures
opens at 450, closes at
350 PSIG
Page 62
Maintenance
Maintenance
•De-lime with Scotsman Ice Machine Cleaner
– Push & release clean button
– Pour in 24 ounces of ice machine cleaner
– Clean for 10 minutes, then push and release clean
button again, wait 20 minutes and shut unit off
•Check distributors for scale build up
Page 63
Service Diagnosis
Service Diagnosis
•What happens if?
•Vapor Inlet Valve Does
Not Open
– Vapor line hot
– Discharge pressure
increases
– Low side pressure does
not change
– No ice release - large
slabs of ice
– 2 blink refrigeration light
Page 64
Service Diagnosis
Service Diagnosis
•What happens if?
•Control wire becomes
unplugged
– CP unit does not
operate
– Exceeds maximum
freeze time
•Controller shows
continuous
refrigeration diagnostic
light
Page 65
•What happens if?
•Condenser by pass
valve does not open
– High pressure cut out
opens
•Note: High discharge
pressure during
Service Diagnosis
Service Diagnosis
harvest will not be
present at liquid
connection
– Ice may release, but
slowly
Page 66
•What happens if?
•Receiver inlet valve
does not close during
harvest
– Very little change
•If it sticks closed
Service Diagnosis
Service Diagnosis
– Hi discharge pressure
cut out opens
– Controller shows
continuous diagnostic
light
Page 67
Service Diagnosis
Service Diagnosis
•What happens if?
•Headmaster is stuck in
bypass
– Very little liquid flow to
TXVs
– Long freeze cycle
– Controller shows
continuous refrigeration
diagnostic light
Page 68
Service Diagnosis
Service Diagnosis
•What happens if?
•There is a refrigerant leak
– No change until refrigerant level drops below the
operational threshold for the ambient
•Headmaster will try to maintain minimum discharge
pressure - but will be hissing as gas flows through
•Ice formation will be poor
•Low capacity/long freeze cycle will result
– Add charge to confirm, if ice making resumes with
normal discharge pressure there is a leak
Page 69
Service Diagnosis
Service Diagnosis
•What happens if?
•There is no water to the ice making section
– Water is part of the recipe for ice!
– Controller will stop unit operation but retry filling every
20 minutes until water is restored
Page 70
•What happens if?
•The purge valve
leaks through
– May result in small
cubes
– Short freeze cycle
Service Diagnosis
Service Diagnosis
– May have long
harvest cycle
Page 71
•What happens if?
•The inlet water
valve leaks through
– Keeps adding water
(heat load) to
reservoir
Service Diagnosis
Service Diagnosis
– Result is a long
freeze cycle
Page 72
Service Diagnosis
Service Diagnosis
•What happens if?
•The condenser fan stops
– CP unit’s hi pressure cut out will open
– Maximum freeze time will be exceeded
– CME unit will shut system off
– Controller will display continuous refrigeration
diagnostic light
Page 73
•What happens if?
•The CPR valve fails
– Pressure during harvest will not be at the pre-set point
•55 to 60 PSIG
– Will not hold an adjustment
– No external symptom
Service Diagnosis
Service Diagnosis
•CPR setting should be checked if compressor is
replaced
Page 74
Service Diagnosis
Service Diagnosis
•What happened if?
•The controller is showing a one blink refrigeration
diagnostic light
– This indicates that the ice harvest was very slow and
the controller timed-out on maximum harvest time
– Ice was sensed by the control system
– Likely causes include
•Beginning to freeze up
Page 75
Service Diagnosis
Service Diagnosis
•What happened if?
•The controller is showing a two blink refrigeration
diagnostic light
– This indicates that the ice harvest was very slow and
the controller timed-out on maximum harvest time
– Ice was NOT sensed by the control system
– Likely causes include
•Freeze up
•Vapor inlet valve did not open
•Ice sensor can’t “see” ice well
Page 76
Service Diagnosis
Service Diagnosis
•What happened if?
•The controller is showing a continuous
refrigeration diagnostic light
– Maximum freeze time exceeded
– Dirty condenser coil
– Fan motor inoperative
Page 77
Service Diagnosis
Service Diagnosis
•What happened if?
•The controller is showing a two blink water
diagnostic light
– Slow or no water fill
•Possible clogged water filters
– Low water level - leaks out
– Water level sensor not working or harness connection
poor
Page 78
Service Diagnosis
Service Diagnosis
•What happened if?
•The controller is showing both diagnostic lights
on continuously
– This indicates that the temperature sensors are not
working or not plugged in. They need to be plugged
back in or replaced.
– The ice machine will operate without the thermistors
working, but it is limited in its diagnostics that way
Page 79
Summary
Summary
•Eclipse is a three part ice making system
– Ice making head
– Compressor Package
– Condenser
•There are 6 systems
– 600
– 800
– 1000
– 1300
– 1600
– 2000