– Ice Making Section or Head Unit - 115 volt
– Compressor Package - 208-230 volt
– Condenser - 208-230 volt
•Flexible Modular System
– One condenser fits two compressor packages
– One ice making head fits two compressor packages
– All are R-404A systems
Page 4
Ice Making Section
Ice Making Section
•CME686 or CME810
– Remote Low Side
•22” wide by 16.5” deep
– Three evaporators
–Three TXVs
– Three check valves
–CM3technology
•Water and Control
Systems
16.522”
•Rotomolded freezing
compartment
Page 5
•Refrigerant
Ice Making Section
Ice Making Section
Vapor
Liquid
Line
Connections
– Vapor
– Liquid
–Suction
•All on right
side
– Designed for
Drive-Up
Suction
Window
Applications
Page 6
•Ice making
compartment
•Three
evaporators
– Circuited in
parallel
– No braze joints in
Ice Making Section
Ice Making Section
freezing
compartment
– Access from the
left side or top
Page 7
•Purpose: Opens
during harvest
to allow vapor
to enter the
evaporators
•24 volt coil
Vapor Inlet Valve
Vapor Inlet Valve
•Different port
size between
CME686 and
CME810
Page 8
•Three internally
equalized valves
•Purpose: Control
individual
evaporator
superheats
– One valve per plate
Three
Three
TXVs
TXVs
– Promotes even
plate-to-plate ice
distribution
Page 9
•Check valves
keep each TXV’s
refrigeration flow
directed to a
single evaporator
– Eliminates cross-
flow during freeze
Three Check Valves
Three Check Valves
cycle
– Each TXV outlet
must flow to one
evaporator
Page 10
•115 volt pump
•Same for both
CME686 and CME810
•Pedestal type
•Pump motor separated
from reservoir
Water Pump
Water Pump
– Keeps motor drier
– Motor cap keeps
condensation off motor
Page 11
™
•AutoIQplus
•Uses sensors for
– ice harvest,
– bin full indications
– water reservoir
temperature
– water level
Controller
Controller
•Controls freeze and
harvest cycles
Page 12
CME Electrical Box
CME Electrical Box
•Transformer 115 to 24, 85 VA
•Purge valve timer
•Control wire connection
nearby
– Wire routes to compressor
package
– Controls contactor and solenoid
valves
Control Wire Connection
Page 13
•Provides access
when left and right
side access is
limited
•Access to:
– cascading shield
– water trough
Inspection Cover
Inspection Cover
– ice sensors
•Also covers
cascading shield
fastener
Page 14
•Removal
begins with
removal of the
inspection
cover
•Then remove
the one
Cascading Shield
Cascading Shield
retaining
screw
Cascading
Shield
Page 15
Cascading Shield
Cascading Shield
Page 16
Evaporator Covers
Evaporator Covers
Page 17
Freezing Compartment
Freezing Compartment
Water Trough
Cascading Shield
Page 18
Temperature Sensors
Temperature Sensors
Liquid Line
Water Temp Sensor
Page 19
Inlet Water Valve
Inlet Water Valve
•Located in right front corner
of unit
•1.25 GPM valve
– Same one as on CME256,
CME506 and many others
•Opens to add water and fill
reservoir
– Adds water during harvest
– Fills at beginning of freeze
– Refills once more during
freeze
Page 20
•Located in the front
of the unit
•115 volt coil
•Opens to drain the
reservoir during
harvest
Purge Valve
Purge Valve
•Controlled by purge
valve timer
Page 21
•Sensing position 3”
below base
•Control position
designed for
dispenser
Ice Sensors
Ice Sensors
applications
– Also works well on
bins
•Maximizes fill
without overfilling
3”
Page 22
•Three models
–CP686
–CP886
– CP1086
Compressor Package
Compressor Package
Page 23
Condenser Bypass Valve
Low Side
Access Valve
CP Unit
CP Unit
Headmaster
CPR Valve
Receiver
High
Pressure Cut
Out - Auto
Reset
Page 24
Crankcase Pressure Regulato
r
Crankcase Pressure Regulato
•CPR valve restricts
compressor dome
pressure during
harvest
– 55 to 60 PSIG
– Pre-set - don’t adjust
it!
•Low Side Access
valve has evaporator
pressure during
freeze, but not during
harvest
Page 25
Condenser Bypass Valve
Condenser Bypass Valve
•Normally Closed,
opens during harvest
•Bypasses condenser
coil and directs
discharge gas to vapor
line
•Ported valve - same
one as CME2006
Page 26
•Maintains discharge
pressure during
freeze
•Active at any temp
o
below 70
– Rated at 217 PSIG,
freeze cycle pressure
F.
Headmaster
Headmaster
may be between 220
and 230 during cold
ambient operation
Page 27
Liquid Inlet Valve
Liquid Inlet Valve
•Normally Open, closes
during harvest
•Controls liquid flow
into receiver
•Isolates refrigerant in
condenser during
harvest
•Improves cycle time
Page 28
•Shipped with
system charge
•Three ports
– Liquid inlet
– Liquid outlet
Receiver
Receiver
– Vapor outlet
Liquid Inlet
Liqui
d Out
Vapor
Out
Page 29
•Toggle switch controls
condensing unit
•Control Wire connection
from Ice Making Section
to control the system
•Electrical power
connected at contactor
Electrical Box
Electrical Box
Toggle Switch
•Remote condenser fan
connects at contactor
Control Wire Connection
Page 30
Condensers
Condensers
•Three models - ONLY for Eclipse
– ERC680 - used with CP686 and CP886
– ERC1086 - only used with CP1086
– and a two circuit model, ERC6810
•can be used with any CP unit
•No headmaster in condenser
– Headmaster is in CP unit
•Swivel nut connections for CP unit
– Don’t connect these condensers to a regular remote!
Page 31
•Three systems,
single and three
phase for each
– 600
– 800
– 1000
•Must match
System Installation
System Installation
components to
create system
Page 32
•600 -
– CME686, CP686, ERC680
•800 -
– CME810, CP886, ERC680
•1000 -
– CME810, CP1086, ERC1086
System Installation
System Installation
•CP units may also be connected to approved
central condenser coil using tubing kit RTE10
– Coil must NOT have headmaster
Page 33
Equipment Location
Equipment Location
•CME can be above or below
condensing unit
– If above, limit is 15 feet
•Pre-charged lines are used
–3 tubes per set
–20, 50 and 75 foot only
–No extra refrigerant charge required
–S trap required when condensing unit is
over 20’ above ice making head
•Must have bin or dispenser
adapter for the CME
Page 34
Two Circuit
Condenser -
ER2C6810, use
Other Configurations
Other Configurations
Approved
Central
Condenser
with 600, 800,
1000 or a mix of
any two
Page 35
Condensing Unit
Condensing Unit
– Modular system - connect
CP to ERC
– Assemble on roof or
ground
– ERC has back legs and
two braces
•Assemble legs and
braces to condenser
– Connect wires to junction
box
– Place ERC on back of CP -
lip on CP holds ERC up
Page 36
•Fasten CP to ERC
•Connect liquid and
discharge line
connections
•Route wire to CP
control box and
Condensing Unit
Condensing Unit
connect to contactor
Page 37
•Three tubes
•Reversible
•CME routing
determines which end
goes to CME
– Out the top - use
Line Set
Line Set
double-bend ends at
CME
– Out the back - use
single 90 degree ends
at CME
Ends for out the
CME top
Ends for
out the
CME
back
Page 38
Line Set Installation
Line Set Installation
•Route lines in two groups
– Liquid and Vapor
– Suction separately for ease of routing
•3/4” tube requires careful handling
– Check for holding charge before installation
– Route control wire with line set
– Only shorten if necessary
•Do before connections are made!
•Purge with nitrogen while brazing
– Schraders at both ends for purging
•Evacuate to 300 microns or less
•Add holding charge if connecting later
Page 39
s
Two Circuit Condenser Install
s
Two Circuit Condenser Install
•Mark Lines, Wires and CP Units
•Example:
– Mark one unit “A”
– Mark line set “A” and control wire “A”
– Unit A’s pre-charged lines route to Unit A
– Unit A’s control wire connects to Unit A
– Confirm before connecting
•Start one unit at a time to confirm proper
operation and control wire routing
Page 40
•Flush against wall
Install CME
Install CME
capability
•Drains left, right or back
•Water inlet and power
inlet from the top or
back
•Refrigerant line
connections back or top
•115 volt unit, cord
provided
Water Inlet
Fitting
Drain
Fitting
Page 41
•Attach water inlet
•Attach drain - 3/4”
– Unit ships with left
drain hose installed,
•Right drain hose in
plastic bag
– No vent required,
Flush Installations
Flush Installations
vent is internal
– Secure drain with
tape for ease of
mounting
Internal Vent
Page 42
Place on Adapter
Place on Adapter
•Many different
adapters
– Use gasket tape at
mounting area
– Sealing area
•22” wide x 15” deep
•Remove all panels
•Place unit
•Connect control wire
Space for Drain at Back
15”
Top View
Page 43
•Add foam
tape/cork tape
to suction line
nut
•Secure unit at
sides or back
with provided
Connect Pre--
Connect Pre
Charged Lines
Charged Lines
strap-clips
Page 44
•Connect precharged
lines
– Use refrigerant oil
– Use two wrenches to
prevent quickconnect diaphragm
damage from rotating
Condensing Unit
Condensing Unit
tube
•Connect control wire
•Connect power,
check voltage
Page 45
•Check installation
– Power
– Water
–Drain
– Tube Routing
•No soak out needed
Initial Start Up
Initial Start Up
– Plug in CME unit
– Check EEPROM code
– Push Freeze to start
Page 46
•CME unit
– Opens & closes Purge Valve
– Fills with water
– Switches on Pump
– Switches on Condensing Unit
•Compressor and fan begin to operate
Start Up
Start Up
•Adjustments
– Purge is adjustable
Page 47
Operation --
Operation
•CM3control system
– Water level sensor for
•Reservoir water fill
•Freeze cycle termination
– Ice sensors to sense
•Ice harvest
•Bin full
Control System
Control System
– Controller determines cycles and operates
components
•Uses water level to determine freeze cycle length
•Uses length of time for ice to fall to determine next
harvest
•Uses ice sensor signal blockage to determine bin full
Page 48
•Water level sensor
– Two photo-electric eyes
in housing
– Top eye blocked tells
controller water level is
low
– Bottom eye blocked
Control Details
Control Details
tells controller water
reservoir is full
Page 49
•Ice sensors - photo-
eyes
– Located at bottom of
ice drop zone
– One side is an emitter,
the other a detector
– Creates a light curtain
Control Details
Control Details
that can sense groups
of cubes falling during
harvest
Page 50
Operation --
Operation
Freeze
Freeze
•Similar to conventional remote ice cubers
– Condensing unit forces liquid refrigerant to the ice
making section
•Each TXV meters refrigerant to its own evaporator
– At a pre-determined water temperature, the pump
stops for 30 seconds
– As ice forms on the evaporators, the water level drops
– About half way through the cycle the water reservoir
re-fills
– The next time the water level drops to the point where
the top of the slot in the float stick blocks the eyes, the
system goes into the harvest cycle
Page 51
Operation --
Operation
Harvest
Harvest
•Eclipse features Cold Temperature Harvest
– Condensing Unit may be located outside
•Temperature Range between -20 and 120 F.
•Receiver is with the condensing unit
•Vapor line connects discharge gas and receiver vapor to
vapor inlet line in ice making section
•High vapor flow rates achieved with no compressor
impact due to use of CPR valve
•Vapor contains latent heat - even at sub-zero
temperatures
•Condensing vapor in the evaporators transfers the heat
•Evaporators warm up and ice is released
Page 52
Operation --
Operation
•Vapor inlet valve opens
•Condenser bypass valve opens
•Receiver inlet valve closes
•Purge valve opens
•Pump stops for a time then restarts to purge the
reservoir of water
Harvest Details
Harvest Details
•Purge valve closes after 40 seconds
•Inlet water valve opens for a few seconds to add
water to the reservoir for harvest assist
•Harvest continues until the controller stops it
Page 53
Operation --
Operation
•Controller begins timing harvest
•Ice falling interrupts the signal from the ice sensor
emitter to the receiver
– The time of that interrupt is recorded by the controller
– The last time the controller receives an interrupt signal
is saved as the cube release time
Harvest Control
Harvest Control
– Extra time is calculated from the actual cube release
time
Measured Cube Release Time + Calculated Extra Time =
Harvest Time
Page 54
•Freeze Cycle Time:
– 1000 - between 12 and 19 minutes
– 800 - between 14 and 22 minutes
– 600 - between 16 and 25 minutes
•600’s cycle is longer in very high ambient
•Harvest Cycle Time
– 1000 - between 1 and 3 minutes
Operation
Operation
– 800 - between 1 and 3 minutes
– 600 - between 2 and 3 minutes
– Extreme low temperatures - harvest lengthens
•up to 6 minutes
Page 55
Condenser
Compressor
Package
Refrigeration Schematic
Refrigeration Schematic
Ice Making Section
Page 56
Condensing Unit
Condensing Unit
Condenser Bypass Valve
Headmaster
Compressor
CPR
Liquid
Inlet
Valve
(N.O.)
Rec
.
Page 57
Ice Making Section
Ice Making Section
SuctionVaporLiquid
Vapor Inlet
Valve
TXVs
Check
Valves
Evaporato
rs
Page 58
•Freeze Cycle
– Rapid Pull Down to
between 80 and 60
PSIG
– Gradual Pull Down to
28 - 30 PSIG just before
Harvest
System Pressures
System Pressures
– Pressures at CP unit or
CME will be the same
during Freeze
Page 59
•Harvest Cycle
– At the ice making
section, low side
pressure rapidly
increases to 90 - 120
PSIG
– At the CP unit
System Pressures
System Pressures
compressor access
valve, dome pressure
is limited by the CPR
valve to 55 - 60 PSIG
during harvest
Page 60
•CP Unit
– Discharge during low
ambient freeze will be
about 225 PSIG
•Headmaster rated for 217,
there is some variation
unit to unit
– Discharge during harvest
System Pressures
System Pressures
will be about 100 PSIG
– High Pressure Cut Out
opens at 450, closes at
350 PSIG
Page 61
•De-lime with Scotsman
Ice Machine Cleaner
– Push & release clean
button
– Pour in 24 ounces of IM
cleaner through handy
fill-plug in sump cover
Maintenance
Maintenance
– Clean for 10 minutes,
then push and release
clean button, wait 20
minutes and shut unit off
•Check distributors for
scale build up
Page 62
Maintenance
Maintenance
Top Cover Lifts Up
Notch in Wall for Front Access
Page 63
•What happens if?
•Vapor Inlet Valve
Does Not Open
– Vapor line hot
– Discharge pressure
increases
Service Diagnosis
Service Diagnosis
– Low side pressure
does not change
– No ice release - large
slabs of ice
– 2 blink refrigeration
light
Page 64
Service Diagnosis
Service Diagnosis
•What happens if?
•Control wire becomes
unplugged
– CP unit does not
operate
– Exceeds maximum
freeze time
•Controller shows
continuous
refrigeration diagnostic
light
Page 65
•What happens if?
•Condenser by pass
valve does not open
– High pressure cut out
opens
•Note: High discharge
pressure during
Service Diagnosis
Service Diagnosis
harvest will not be
present at liquid
connection
– Ice may release, but
slowly
Page 66
•What happens if?
•Receiver inlet valve
does not close during
harvest
– Very little change
•If it sticks closed
Service Diagnosis
Service Diagnosis
– Hi discharge pressure
cut out opens
– Controller shows
continuous diagnostic
light
Page 67
Service Diagnosis
Service Diagnosis
•What happens if?
•Headmaster is stuck in
bypass
– Very little liquid flow to
TXVs
– Long freeze cycle
– Controller shows
continuous refrigeration
diagnostic light
Page 68
Service Diagnosis
Service Diagnosis
•What happens if?
•There is a refrigerant leak
– No change until refrigerant level drops below the
operational threshold for the ambient
•Headmaster will try to maintain minimum discharge
pressure - but will be hissing as gas flows through
•Ice formation will be poor
•Low capacity/long freeze cycle will result
– Add charge to confirm, if ice making resumes with
normal discharge pressure there is a leak
Page 69
Service Diagnosis
Service Diagnosis
•What happens if?
•There is no water to the ice making section
– Water is part of the recipe for ice!
– Controller will stop unit operation but retry filling every
20 minutes until water is restored
Page 70
•What happens if?
•The purge valve
leaks through
– May result in small
cubes
– Short freeze cycle
Service Diagnosis
Service Diagnosis
– May have long
harvest cycle
Page 71
•What happens if?
•The inlet water
valve leaks through
– Keeps adding water
(heat load) to
reservoir
Service Diagnosis
Service Diagnosis
– Result is a long
freeze cycle
Page 72
Service Diagnosis
Service Diagnosis
•What happens if?
•The condenser fan stops
– CP unit’s hi pressure cut out will open
– Maximum freeze time will be exceeded
– CME unit will shut system off
– Controller will display continuous refrigeration
diagnostic light
Page 73
Service Diagnosis
Service Diagnosis
•What happens if?
•Both the solenoid valves in the condensing unit
do not work
– Very, very unlikely, but
•The discharge pressure during harvest will be about 150
PSIG
•The low side pressure during harvest will be less than 90
PSIG
•The ice will harvest slowly
•The refrigerant flowing out of the receiver will make a
whistling noise
Page 74
•What happens if?
•The CPR valve fails
– Pressure during harvest will not be at the pre-set point
•55 to 60 PSIG
– Will not hold an adjustment
– No external symptom
Service Diagnosis
Service Diagnosis
•CPR setting should be checked if compressor is
replaced
Page 75
Service Diagnosis
Service Diagnosis
•What happened if?
•The controller is showing a one blink refrigeration
diagnostic light
– This indicates that the ice harvest was very slow and
the controller timed-out on maximum harvest time
– Ice was sensed by the control system
– Likely causes include
•Beginning to freeze up
Page 76
Service Diagnosis
Service Diagnosis
•What happened if?
•The controller is showing a two blink refrigeration
diagnostic light
– This indicates that the ice harvest was very slow and
the controller timed-out on maximum harvest time
– Ice was NOT sensed by the control system
– Likely causes include
•Freeze up
•Vapor inlet valve did not open
•Ice sensor can’t “see” ice well
Page 77
Service Diagnosis
Service Diagnosis
•What happened if?
•The controller is showing a continuous
refrigeration diagnostic light
– Maximum freeze time exceeded
– Dirty condenser coil
– Fan motor inoperative
Page 78
Service Diagnosis
Service Diagnosis
•What happened if?
•The controller is showing a two blink water
diagnostic light
– Slow or no water fill
•Possible clogged water filters
– Low water level - leaks out
– Water level sensor not working or harness connection
poor
Page 79
Service Diagnosis
Service Diagnosis
•What happened if?
•The controller is showing both diagnostic lights
on continuously
– This indicates that the temperature sensors are not
working or not plugged in. They need to be plugged
back in or replaced.
– The ice machine will operate without the thermistors
working, but it is limited in its diagnostics that way
Page 80
Summary
Summary
•Eclipse is a three part ice making system
•There are two ice making heads
–Using CM3Technology
•There are three compressor packages
•There are two single circuit condensers
•There is one two circuit condenser
•R-404A refrigerant
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.