Scotsman CME1686, ECLIPSE Operator’s Manual

Introduction:
This manual covers the assembly, installation, start up, operation and maintenance of the 1300 and 1600 remote low side cuber systems.
Table of Contents
Eclipseä 1300,1600
Introduction: ·················· Page 1
Configuration: ················· Page 2
Technical Specifications ············ Page 3
Model Number Locations ··········· Page 4
Cabinet Drawings, Ice Making System ···· Page 5
Cabinet Drawings, Compressor Package and Condensers ·················· Page 6
Proper Combinations: ············· Page 7
Create the System··············· Page 8
System Examples ··············· Page 9
System Examples ··············· Page 10
Place Remote System ············· Page 11
System Location ················ Page 12
Route Tubing ················· Page 13
Ice Making Section ·············· Page 14
Compressor Package ············· Page 15
Condensing Section Assembly ········ Page 16
Condensing Section Assembly ········ Page 17
Ice making section: ·············· Page 18
Bin Thermostat - Routing ··········· Page 19
Bin Thermostat - Bracket & Bulb ······· Page 20
Water and Drain ················ Page 21
Water and Drain ················ Page 22
Ice Making Section Set Up ·········· Page 23
Condensing Unit Connections ········· Page 25
Final Placement ················ Page 26
Controller Operation ·············· Page 27
Initial Start Up - 1300 and 1600 ········ Page 28
Purge Adjustment ··············· Page 29
System Operation:··············· Page 30
Refrigeration Details: ············· Page 31
Technicians Only: Freeze Cycle Sequence of Operation
·························Page 32
Technicians Only: Harvest Cycle Sequence of Operation ··················· Page 33
Power and Water Interruptions ········ Page 34
Sanitation and Cleaning ············ Page 35
Other Maintenance ·············· Page 36
Water Distributors ··············· Page 37
Ice Sensors ·················· Page 38
Water Level Sensor Maintenance ······· Page 39
Service Diagnosis ··············· Page 40
Service Diagnosis ··············· Page 41
Service Diagnosis ··············· Page 42
Controller Features & Last Error Recall ···· Page 43
Operational Characteristics 1300 lb system · · Page 44
Operational Characteristics 1600 lb system · · Page 45
Refrigeration System Service ········· Page 46
Coupling Connections: ············ Page 24
An illustrated parts list and wiring diagram is in the
center of this manual.
Keep this manual for future reference.
Note this symbol when it appears. It
indicates a potential hazard.
Page 1
Eclipseä 1300, 1600
Configuration:
A remote low side cuber system includes several sub systems: an ice making section, a remote compressor package, and a remote air cooled condenser. Additionally, there are two models of each sub-system and this manual covers all of them.
The ice making sections are designed for use indoors in a controlled environment. The remote compressor packages and condensers are designed to operate outdoors. Each sub-system has limits for power, water and temperature.
Operational Limitations:
Minimum Maximum
o
Air Temp (IMS) 50
Air Temp (CU) -20
Water Temp 40
Water Pressure 20 psi 80 psi
Voltage (IMS) 104 126
Voltage (CU) 198 253
F 100oF.
o
F. 120oF.
o
F. 100oF.
IMS = Ice Making Section, CU= Condensing Unit
Do Not operate the machine in conditions beyond these limitations. Doing so will void the warranty.
Scotsman ice systems are designed and manufactured with the highest regard for safety and performance. They meet or exceed the standards of UL and NSF.
Scotsman assumes no liability of responsibility of any kind for products manufactured by Scotsman that have been altered in any way, including the use of any part and/or other components not specifically approved by Scotsman.
Scotsman reserves the right to make design changes and/or improvements at any time.
Specifications and design are subject to change without notice.
Warranty
Refer to the warranty coverage in effect when the equipment was sold. Warranty statements are included with each product.
Systems:
Each sub-system is a separate entity that carries its own model and serial number. They must be combined to create a remote cuber low side system.
System Information
System Model
Number
Eclipse 1300-42 CP1316-32A 208-230/60/1
Eclipse 1300-43 CP1316-3A 208-230/60/3
Eclipse 1600-42 CP1316-32A 208-230/60/1
Eclipse 1600-43 CP1316-3A 208-230/60/3
Compressor Package Condenser
Model Electrical Model Electrical Model Electrical
Condensing Unit (CU) Ice Making Section (IMS)
ERC1086 -32A 208-230/60/1 CME1386RLS-1A 115/60/1
ERC1086-32A 208-230/60/1 CME1686RLS-1A 115/60/1
Notes: Voltage Codes are at the end of the model number. Codes read Voltage/Hertz/Phase. Those related to these products include:
-1 = 115/60/1
-3 = 208-230/60/3
-32 = 208-230/60/1
Pre-charged tubing kits are required to interconnect the IMS to the CP.
Interconnecting 24 volt control wire ships with the CP unit.
-42 = 115/60/1 and 208-230/60/1 (separate units)
-43 = 115/60/1 and 208-230/60/3 (separate units)
Page 2
Technical Specifications
Ice Making Section (IMS)
Eclipseä 1300,1600
Model Voltage Minimum Circuit
Ampacity
CME1386RLS-1A 115/60/1 3 15 30”w x 24”d x 28”h 144
CME1686RLS-1A 115/60/1 3 15 same 154
Max Fuse Size Cabinet Size Weight (lb)
Compressor Package (CP)
Model Voltage Contains
Headmaster?
CP1316-32A 208-230/60/1 Yes 24.3 30 18 lb 29 ¾”wx18”dx34½”h 180
CP1316-3A 208-230/60/3 Yes 15.3 20 18 lb same 180
Minimum
Circuit
Ampacity
Max
Refrigerant
Fuse
Charge (R-404A)*
Size
Cabinet Size Weight
(lb)
* Includes entire system charge.
Condenser
Model Voltage Contains
Headmaster?
ERC1086-32A 208-230/60/1 No 1 1.25 15 29 ¾”w x 28 5/8”d x 38 ½”h 95
Number of Circuits
Minimum
Circuit
Ampacity**
Max
Fuse
Size**
Cabinet Size, with legs Weight
* * ERC condenser fan motor is powered from CP unit and the ERC’s ampacity is included in CP unit numbers.
Note: The ERC1086 does NOT contain a headmaster. The headmaster is in the CP units.
Note: 75 feet of interconnecting control wire (24 volt) is included with the CP units.
(lb)
Page 3
Eclipseä 1300, 1600
Model Number Locations
Ice Making Section
The dataplate on the back of the ice machine contains the model number, serial number and electrical data.
A second plate, located behind the front panel at the lower left front, also lists the model and serial numbers.
Compressor Package
The dataplate on the right side of the compressor package contains the model number, serial number, electrical data and system refrigerant charge.
A second plate, located behind the front panel in front of the compressor, also lists the model number, serial number and refrigerant charge.
Condenser
The dataplate lists the condenser’s electrical information plus the model and serial numbers.
On the ERC1086 it is located on the side opposite the refrigeration connections.
Dataplate location for ERC1086
Dataplate
location for
CP Unit
Dataplate location for Ice Making
Section
Page 4
Cabinet Drawings, Ice Making System
Eclipseä 1300,1600
ICEDROPAREA
4.85
17.08
2.53
TOP VEIW
17.31
Thermostat Routing Hole,
13” from front,
4.63” from side
UTILITY CHASE
TOP ACCESS REFRIGERANT LINE SETS
REFRIGERANT LINE SETS CONNECTIONS
30.00
REAR VEIW
DRAIN 3/4" PVC FEMALE
WATER INLET 3/8" FLARE
15.76
3.02
1.90
5.19
3.18
24.00
Page 5
Eclipseä 1300, 1600
Cabinet Drawings, Compressor Package and Condensers
1/2" CONDENSER DISCHARGE LINE (IN)
CONDENSER FAN WIRE ROUTING
3/8" CONDENSER LIQUID LINE (OUT)
1/2" COOL VAPOR LINE
0.88 ELECTRICAL INLET
INTERFACE HARNESS
ACCESS HOLE
3/4" SUCTION LINE
27.90
28.53
1.5”
RIGHT SIDE VIEW
3/8" LIQUID LINE
15”
1.5”
ERC680 or ERC1086: This Side Attaches to CP1316
BACK VIEW
FRONT VIEW
29.50
9/16” Mounting Hole
1.5”
23.5”
1.5”
9/16” Mounting Hole
2.75
35.72
Page 6
Discharge Line
38.47
33.19
6.68
22.51
Liquid Line
29.19
Proper Combinations:
Eclipseä 1300,1600
The three sub systems are designed to be connected together in certain combinations to meet the user’s needs:
Eclipse 1300 System:
CME1386, CP1316, ERC1086
·
Eclipse 1600 System:
CME1686, CP1316, ERC1086
·
ERC1086 may be substituted for by an approved central condenser coil & fan (coil must be without headmaster - headmaster is part of CP1316).
Condenser coil internal volume target is 165 cubic inches, BHTU target is 42,000 BTUH.
Note: The ice making section cannot be stacked vertically.
Accessories such as bin adapters and tubing kits are required to complete the installation.
Dispenser Adapter Kits:
Scotsman ID200 or ID250: KBT44
·
Note: Dispensers with two rotors. If possible, the ice making head should NOT be centered left to right between the two rotors. It should be shifted slightly to one side, and the agitation should be minimized.
Bin Adapter Kits:
·
BH800: KBT23
·
BH801: KBT29
·
BH900: KBT22
Tubing Kits:
·
20 foot: 3RTE20
·
35 foot: 3RTE35
·
50 foot: 3RTE50
·
75 foot: 3RTE75
·
Suction Line Trap: KSLT075
·
Interconnecting Tubing to Approved Rack Condenser Coil: RTE10
Items required for installation:
Ice making section
·
Compressor Package (includes interconnecting
·
control system wire)
Remote condenser or approved rack coil
·
w/tubing kit
20’, 35’, 50’ or 75’ triple line set (liquid, vapor
·
and suction)
Bin or dispenser adapter
·
Special Considerations
The ice making section’s footprint is 30” wide by 24” deep. The refrigeration connections can be made out the top panel or out the back. The electrical power cord and the water inlet line can also be routed through either of those areas. The drain may be routed out the back or to the left side.
The bin thermostat, when deployed, will be about 5” below the bottom of the cabinet, and that is where the ice will fill to. This ice level maximizes ice storage without overfilling the bin or dispenser.
Water
Pure water does not exist. All water supplies contain some amounts of impurities, although potable water is, by definition, fit for human consumption. Because the contents of the water to an ice machine directly impact its performance, consideration should be given to improving the water’s quality.
There are two ways water can contain impurities: in suspension or in solution. Suspended solids can be filtered out of the water. In solution or dissolved solids must be diluted or treated. Water filters are recommended to remove the suspended solids. Some filters or filter systems have treatment chemicals in them for treating the suspended solids.
This ice machine has an adjustment for the amount of water rinsed or purged. Water use adjustments are customer convenience adjustments; they are not factory defects and are not covered by warranty.
·
Line end kit: KTE6
Page 7
Eclipseä 1300, 1600
Create the System
Plan the installation. The system consists of four parts: the ice making section, the compressor package, the interconnecting tubing and the remote condenser. Of these, the biggest variable is the interconnecting tubing.
Tubing: The tubing consists of three pre-charged, insulated and sealed soft copper tubes. They each contain a small holding charge of R-404A. One tube, the liquid line, is 3/8” OD. The vapor tube is ½” OD and the suction tube is ¾” OD. A site inspection will determine what length of tubing is required for the installation.
Excess tubing must be either shortened at the job site (recovering the holding charge, purging with nitrogen when brazing and evacuating to 50 microns) or coiled up inside the building.
Installations with greater than 20 feet of vertical lift between ice machine and the compressor require a suction line trap. The suction line requires careful handling and large radius bends to prevent kinking.
Roof mounting: To make installation easier the compressor and condenser are designed to be assembled together on the roof. Some installations will require the use of a hoist to lift the components to the roof.
Pad mounting: The compressor and condenser may be located below the ice making section, up to a limit of 15 feet.
Distance from unit: Limited to the length of the available pre-charged tubing.
Interconnecting wires: An interconnecting wire harness is included with the CP unit. One end plugs into the ice making section and the other into the compressor package. The system will NOT operate without this harness.
Exposed tubing: Minimize the amount of tubing exposed outdoors.
Confirm Component Availability:
CME1386 or CME1686
·
CP1316
·
ERC1086 unless connecting to an approved
·
condenser coil.
Note: Only these condensers may be used. They do NOT contain a headmaster valve. That valve is in the Compressor Package. Do NOT use any other Scotsman condenser. Do NOT use these condensers on any other Scotsman remote product.
Interconnecting tubing kit
·
Note: Check tubing integrity before assembly by attaching a refrigeration compound gauge onto one of each tube’s schrader valves. If there is pressure, the tube is OK, if not it should be checked for damage and leaks.
·
Bin or dispenser adapter
Elevation: CP unit limited to 35 feet above the ice making section.
Compressor package: Electrical power must be supplied to the compressor package. The remote condenser fan motor takes its power from the compressor package.
Ice making section location and attachment:
The 115/60 Hz ice making section is cord connected and requires an outlet within 6 feet of the installation.
Page 8
System Examples
Eclipseä 1300,1600
The Eclipse system can be installed on a bin or dispenser. The CP unit can be installed on either a single circuit condenser or onto a coil in a separate rack condenser.
Separate coils must be:
Scotsman approved
·
The correct size and capacity
·
New or not have been part of a system that
·
used mineral oil.
System on Ice Storage Bin
System on Ice Dispenser
Page 9
Eclipseä 1300, 1600
System Examples
A variation of the typical system set up is one that uses a non-Scotsman condenser. In that case the CP unit is NOT bolted to the condenser and a RTE10 line set is used to connect the refrigeration system to the condenser’s coil.
IMS on Bin, CP Unit Connected to Approved Central
Condenser Coil
Page 10
Place Remote System
Eclipseä 1300,1600
Roof preparation
Most installations of this system will place the compressor package and condenser on the roof of a building. The roof must be physically stout enough to accept the load of the equipment and the roofing material must be prepared to prevent water leaks.
Follow local codes for the placement and attachment of the equipment.
Location
The air cooled condensing unit assembly requires unobstructed air flow to operate efficiently. A four foot space between each intake side and a wall or other cabinet is recommended. Provide at least 2 feet of space above the air cooled condenser for proper air flow.
Do not place where the air cooled condenser will pick up hot discharged air from an air conditioner or other refrigeration system condensing unit.
Space must also be reserved for service on the compressor package.
Roof Piercing:
The roof (or wall) must have a passage large enough for the three pre-charged, pre-bent tubes and the control wire to pass through. The minimum recommended size is 4” ID. In most areas the power supply may also pass through the same passage. If there isn’t a passage one must be created. In most cases this must be done by a licensed and bonded roofer in order to maintain the roof’s integrity.
Suggestions:
Hoist the compressor package and condenser to the roof in separate loads.
Note: In most cases a mechanical lift, boom truck or crane will be required to hoist the condensing unit components.
Assemble the compressor package to the condenser and mount both to either roof rails or pressure treated4x4s.
Orient the assembled unit so that the unit’s mounts are parallel to the pitch of the roof to allow water to drain freely.
Do NOT place the unit directly onto roof rock.
Page 11
Eclipseä 1300, 1600
System Location
Limitations:
Distance: Limited to the maximum length of a single pre-charged tubing kit, 75 feet.
Condensing Unit Elevation over Ice Making Section: 35 feet.
Note: Elevations greater than 20 feet require installation of a suction line trap at the 20 foot mark.
Ice Making Section Elevation over Condensing Unit: 15 feet.
S-Trap
Limit of Line Set
Max Length -
40.35"
Condensing Unit Located Above Ice Machine
Line Routing:
Allowed: One rise after a drop.
·
Allowed: One drop after a rise.
·
Not Allowed: More than one rise after a drop
·
Not Allowed: More than one drop after a rise.
·
Max Rise: 35 Feet
22.87"
Max Drop: 15 Feet
17.15"
Condensing Unit Located Below Ice Machine
Condensing Unit Distance Schematic
Page 12
Route Tubing
Eclipseä 1300,1600
Scotsman’s pre-charged tubing kits are pre-bent to fit the connection path at the ice making section.
If the tubing is to be routed out the back, use
·
the double-bend ends.
Suction
Vapor
Liquid
If the tubing is to be routed out the back and
·
then up, use the ends with the single 90 degree bends.
Suction
Select the correct end to send to the roof.
The method or technique used to route the tube is left to the installer. However, in many cases it is easier to position the tubing inside the building first, then feed the outside portion through the tubing passage (pitch pot). Installation of tubing will be easier if the suction line is run first, followed by the liquid and vapor lines. Use of two persons is suggested to prevent kinking of the tubing, long runs may require three people.
Allow enough tubing to make large radius bends
·
from the roof passage to the compressor unit. Do NOT leave excess tubing on the roof.
If a trap must be installed, the suction line
·
tubing must be cut apart to install it.
Identify the ice machine end of the tubing. Each
·
tube has one end formed to route through the hole in the unit’s top.
Tape the ends of the vapor and liquid line tubes
·
together along with the interconnecting wire. Extend the end of the interconnecting wire about 2 feet beyond the end of the precharged tubes and then tape it back onto the tubes.
·
Route the three tubes and the wire from the roof, or other entrance, to the ice making section’s planned position. Avoid uncoiling and recoiling the tubing, as that can lead to kinks.
Vapor
Liquid
Note: Units mounted flush against the wall require refrigerant connections out the top, water supply in from the top, power supply routed through the top and drain routed to the left side.
·
Support long runs of tubing with hangers.
·
Repair any tears in the tubing insulation, especially those on the suction line that are inside the building.
Shortening Tubing
The precharged tubing kits are available in a variety of lengths, they should only be shortened if absolutely necessary.
To Shorten Tubes:
1. Recover the 3 ounce R-404A holding charge from each tube.
2. Cut out the required length of tubing, do not cut the tubing right at the quick connects.
3. Attach nitrogen bottle to one quick connect and a hose with a depressor to the other end, purge nitrogen through each tube while brazing.
4. Remove nitrogen, evacuate to 200 microns.
Note: If tubes are connected to the IMS, evacuate the vapor & suction lines to get the entire system.
Page 13
Eclipseä 1300, 1600
Ice Making Section
The CME1386 and CME1686 are similar in layout. They differ in evaporator count, controller, float stem and vapor inlet valve.
Major Components:
TXV - one feeding a refrigerant distributor
Water Pump - same for both models
Water Level Sensor - signals reservoir water level
to the controller
Controller - operates both the ice machine section and the compressor unit.
Drain Valve - opens to allow pump to drain the reservoir
Water Inlet Valve - 2.77 GPM solenoid valve that opens to fill the reservoir
Low Side Access Valve - allows connection for diagnosis of ice machine section refrigeration operation. Not for recovery.
Liquid, Vapor and Suction Connections - where the
pre-charged tubing kits connect to.
Vapor
Connection
Suction
Connection
Freezing Compartment
Low Side Access Valve
Connection
Bin
Thermostat
Liquid
Vapor Inlet
Valve
Drain Valve
TXV
Water Inlet
Solenoid
Valve
Water Pump
Controller
Front Ice Sensor
Water Level Sensor
Page 14