Scotsman Prodigy Plus E Series, EH222 E, ECC0800-3E, ECC1410-32E, ECC0800-32E Installation And User Manual

...
Page 1
Installation and User Manual for Eclipse Cuber
Prodigy Plus E Series model
EH222 E with ECC Condensing Unit
Page 2
EH222 E and Condensing Unit Remote Low Side Cuber User Manual
This manual covers the assembly, installation, start up, operation and maintenance of the 800 and 1000 remote low side cuber systems.
Contents
Conguration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3
Specications and Location Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 4
Cabinet Drawings, Ice Making Head . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 5
Cabinet Drawings, Condensing Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 6
Pre-Installation Details. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 7
Create the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 8
Completed System Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 9
Place Remote System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 10
Tubing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 11
Place Ice Making Head . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 12
Drain Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 13
Water Supply: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 14
Electrical: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 15
Connect Refrigeration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 16
Complete the Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 17
Reference for Start Up: Controller Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 18
Initial Start Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 19
Ice Thickness and Water Purge Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 20
Adjustable Ice Level Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 21
Cleaning, Sanitation and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 22
Operational Characteristics 800 lb system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 24
Operational Characteristics 1000 lb system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 24
What to do before calling for service: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 25
EH222 Schematic Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 26
EH222 Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 27
ECC Three Phase Schematic Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 28
ECC Three Phase Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 29
ECC Single Phase Schematic Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 30
ECC Single Phase Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 31
June 2018
Page 2
Page 3
EH222 E and Condensing Unit Remote Low Side Cuber User Manual
Conguration
A remote low side cuber system includes two sub
Warranty
systems: an ice making head and a remote air cooled condensing unit. This manual covers the EH222 head and the condensing units that go with it.
Refer to the warranty coverage in effect when the equipment was sold. Warranty statements are
included with each product. The ice making heads are designed for use indoors in a controlled environment. The remote condensing units are designed to operate outdoors. Each sub­system has limits for power, water and temperature.
Operational Limitations:
Systems:
Ice making heads and condensing units have their
own model and serial numbers. They must be
combined to create a remote cuber low side system.
Notes: Voltage Codes are at the end of the model
Minimum Maximum
Air Temp (at head) 50 Air Temp (CU) -20 Water Temp 40
o
F 100oF.
o
F. 120oF.
o
F. 100oF. Water Pressure 20 psi 80 psi Water Conductivity 10
microSiemens/cm any
Voltage (at head) 104 126
number. Codes read Voltage/Hertz/Phase. Those related to these products include:
-1 = 115/60/1
-3 = 208-230/60/3
-32 = 208-230/60/1
System Information
Voltage (CU) 198 253
CU= Condensing Unit
Tubing kits are required to connect the head to the condensing unit.
Do Not operate the machine in conditions beyond these limitations. Doing so will void the warranty.
Interconnecting 24 volt control wire ships with the condensing unit.
System Size Condensing Unit (CU) Ice Making Head
Model Electrical (volts/Hz/phase Model Electrical (volts/Hz/phase) 800 ECC0800-32E 208-230/60/1 EH222SL-1E 115/60/1 800 ECC0800-3E 208-230/60/3 same same 1000 ECC1410-32E 208-230/60/1 same same 1000 ECC1410-3E 208-230/60/3 same same
Scotsman ice systems are designed and manufactured with the highest regard for safety and performance. They meet or exceed common agency standards.
Scotsman assumes no liability of responsibility of any kind for products manufactured by Scotsman that have been altered in any way, including the use
of any part and/or other components not specically
approved by Scotsman.
Scotsman reserves the right to make design changes
and/or improvements at any time. Specications and
design are subject to change without notice.
June 2017
Page 3
Page 4
EH222 E and Condensing Unit Remote Low Side Cuber User Manual
Specications and Location Information
Model Electrical
volts/Hz/phase
EH222SL-1E 115/60/1 1.13 15 shipped w/none 22 x 16.5 x 29 ~100 ECC0800-3E 208-230/60/3 10.6 15 192 32 x 39 x 39.75 ~300 ECC1410-32E 208-230/60/1 15.8 30 248 32 x 39 x 39.75
ECC1410-3E 208-230/60/3 11.6 20 248 32 x 39 x 39.75
* See cabinet drawings for detailed dimensions.
Location Limitations
Maximum Distance between Head and Condensing
Unit: Limited to the length of the longest available
single tubing kit, 75 feet.
Maximum Condensing Unit Elevation over Ice Making Head: 35 feet.
Note: Elevations greater than 20 feet require installation of a suction line trap at the 20 foot mark.
Minimum Circuit Ampacity
Maximum Fuse Size
Condensing unit
The dataplate on the end contains the model number, serial number, electrical data and system refrigerant charge.
A second plate, located behind the side panel on the deck, also lists the model number, serial number and refrigerant charge.
System Charge, oz of R-404A
Cabinet Size* w” x d” x h”
Unit Weight (lb)
~310 ~310
Maximum Ice Making Head Elevation over Condensing Unit: 15 feet.
Line Routing:
Allowed: One rise after a drop.
Allowed: One drop after a rise.
Not Allowed: More than one rise after a drop
Not Allowed: More than one drop after a rise.
Model Number Locations
Ice Making Head
The dataplate on the back of the ice machine contains the model number, serial number and electrical data.
A second plate, located behind the front panel at the lower right front, also lists the model and serial numbers.
June 2017
Page 4
Page 5
EH222 E and Condensing Unit
3.25
82.55
Remote Low Side Cuber User Manual
Cabinet Drawings, Ice Making Head
5.19
131.70
4.57
115.95
79.38
3.13
68.20
2.69
42.80
1.69 24
.95
ACCESS HOLE
INTERFACE CABLE
34.04
24.89
1.34
3/4" SUCTION LINE
DETAIL A
.98
POTABLE WATER INLET 3/8"
EH222
ICE HEAD
1.82
46.24
19.00
482.60
TOP VIEW
80.97
3.19
10.75
273.05
10.27
260.80
3.25
82.55
ICE DROP AREA
MINIMUM BIN
TOP OPENING
2.94
74.72
A
SENSOR
BIN LEVEL
ULTRA SONIC
ACCESS HOLE
ELECTRICAL CORD
3/8" LIQUID LINE
8.31
211.09
6.00
152.40 SEE DETAIL "A"
120V AC, AND INTERFACE CABLE
LINE SET, POTABLE WATER INLET 3/8",
1/2" COOL VAPOR LINE
16.72
424.70
22.70
576.68
67.56
2.66
34.04
1.34
29.00
736.60
381
15.00
22.00
558.80
16.41
416.92
LEFT SIDE VIEW
DRAIN 3/4" PVC FEMALE
REAR, LEFT AND RIGHT SIDE ACCESS
REAR VIEW
June 2017
Page 5
Page 6
EH222 E and Condensing Unit Remote Low Side Cuber User Manual
Cabinet Drawings, Condensing Unit
TOP VIEW
992.81
39.09
814.22
32.06
FRONT VIEW
32.05
1.26
TYP.
1009.65
39.75
887.73
34.95 .88" ELECTRICAL INLET
1/2" COOL VAPOR LINE
3/4" SUCTION LINE
3/8" LIQUID LINE
83.67
3.29
SIDE VIEW
LINE SET AND ELECTRICAL ATTACHMENT SIDE
330.86
13.03
74.12
2.92
163.02
6.42
248.87
9.80
750.06
29.53
491.69
19.36
INTERFACE HARNESS ACCESS HOLE
63.50
2.50
June 2017
Page 6
Page 7
EH222 E and Condensing Unit Remote Low Side Cuber User Manual
Pre-Installation Details
Note: The ice making section cannot be stacked vertically.
Accessories such as bin adapters and tubing kits are required to complete the installation.
Dispenser Adapter Kits:
Cornelius ABS: KBTABS ED150: KBT40
Scotsman ID150: KBT40
Scotsman ID200 or ID250: KBT41
Bin Adapter Kits:
B530P or B530S: KBT32
B948S: KBT34
Tubing Kits:
20 foot: 3BRTE20-EH
35 foot: 3BRTE35-EH
50 foot: 3BRTE50-EH
75 foot: 3BRTE75-EH
Note: Line set may have quick connects. The
condensing section may have quick connects. See refrigeration system detailed instructions connection details.
Water
Pure water does not exist. All water supplies contain some amounts of impurities, although potable water
is, by denition, t for human consumption. Because
the contents of the water to an ice machine directly impact its performance, consideration should be given to improving the water’s quality.
There are two ways water can contain impurities: in suspension or in solution. Suspended solids can
be ltered out of the water. In solution or dissolved solids must be diluted or treated. Water lters are
recommended to remove the suspended solids.
Some lters or lter systems have treatment
chemicals in them for treating the suspended solids.
This ice machine has an adjustment for the amount of water rinsed or purged. Water use adjustments are customer convenience adjustments; they are not factory defects and are not covered by warranty.
Items required for installation:
Ice making head
Condensing unit (includes interconnecting control system wire)
Tubing kit. 20’, 35', 50’ or 75’ triple line set (liquid, vapor and suction)
Bin or dispenser adapter
Special Considerations
The ice making section’s footprint is 22” wide by 16.5” deep. The refrigeration connections can be routed up or to the back. The drain may be routed out the back at any position left to right; it may also be routed to either side.
June 2017
Page 7
Page 8
EH222 E and Condensing Unit Remote Low Side Cuber User Manual
Create the System
Plan the installation. The system consists of three parts: the ice making head, the condensing unit and the interconnecting tubing. Of these, the biggest variable is the interconnecting tubing.
Tubing: The tubing consists of three insulated and sealed soft copper tubes. One tube, the liquid line, is 3/8” OD. The vapor tube is ½” OD and the suction tube is ¾” OD. A site inspection will determine what length of tubing is required for the installation.
In 2013 Scotsman made a change to the Eclipse tubing kits:
Prior Tubing Kits: They each contain a small holding charge of R-404A and have quick connects at the ends.
Current Tubing Kits: The do not contain any refrigerant and do not have quick connects.
Either type can be used to connect the head and
condensing unit.
Elevation: Condensing unit limited to 35 feet above the ice making section.
Condensing Unit: Electrical power must be supplied to the condensing unit, it will be separate from the head.
Ice making section location and attachment: The unique footprint of the EH222 requires adapter kits to allow placement on dispensers and bins.
The remote tubing connections are at the top of the machine, and connections should not be made until
the machine is nearly in its nal installed position.
The 115/60 Hz ice making section is cord connected and requires an outlet within 6 feet of the installation.
Interconnecting wires: An interconnecting wire harness is included with the condensing unit. One end plugs into the ice making section and the other into the condensing unit. The system will NOT operate without this harness.
Check condensing unit for quick connects. If none, recover refrigerant from tubing and cut the quick
Exposed tubing: Minimize the amount of tubing exposed outdoors.
connects off.
Lineset Ice machine head and condensing
unit both have stubs
Ice machine head has stubs, condensing unit has quick connects.
Has Quick Connect Fittings Cut quick connects off both ends Cut off quick connects at condensing unit
end only
Does NOT have Quick Connect Fittings
Use as supplied Use as is at head, obtain kit KTE6-EH,
use 3 of 6 ttings on condensing unit end.
Excess tubing must be shortened at the job site.
Installations with greater than 20 feet of vertical lift between ice machine and the compressor require a suction line trap. The suction line requires careful handling and large radius bends to prevent kinking.
Roof mounting: Some installations will require the use of a hoist to lift the components to the roof.
Pad mounting: The condensing unit may be located below the ice making section, up to a limit of 15 feet.
Distance from unit: Limited to the length of the
available tubing.
June 2017
Page 8
Page 9
EH222 E and Condensing Unit Remote Low Side Cuber User Manual
Completed System Example
June 2017
Page 9
Page 10
EH222 E and Condensing Unit Remote Low Side Cuber User Manual
Place Remote System
Roof preparation
Most installations of this system will place the condensing unit on the roof of a building. The roof must be physically able to accept the load of the
equipment and the roong material must be prepared
to prevent water leaks.
Follow local codes for the placement and attachment of the equipment.
Location
The condensing unit requires unobstructed air ow to operate efciently. A four foot space between
each intake side and a wall or other cabinet is recommended.
Do not place where it will pick up hot discharged air from an air conditioner or other refrigeration system condensing unit.
Space must also be reserved for service on the condensing unit.
Roof Pipe Curb or Pitch Pocket:
To avoid potential kinking of the refrigeration tubing, avoid small, tight radius types of covers on pitch pockets.
Suggestions:
In most cases a mechanical lift, boom truck or crane will be required to hoist the condensing unit.
Mount unit to roof rails or curbs and secure with lag
screws or similar eld supplied fasteners.
Orient the assembled unit so that the unit’s mounts are parallel to the pitch of the roof to allow water to drain freely.
Do NOT place the unit directly onto roof rock.
Roof Piercing:
The roof (or wall) must have a passage large enough for the three refrigeration tubes and the control wire to pass through. The minimum recommended size is 4” ID. In most areas the power supply may also pass through the same passage. If there isn’t a passage one must be created. In most cases this must be done by a licensed and bonded roofer in order to maintain the roof’s integrity.
In all cases the line set will need to be shortened to t.
Do NOT leave excess line set exposed outdoors, especially on a roof.
Refrigerant Recovery and System Evacuation Notice
In the event the refrigerant must be recovered from this system and the system evacuated, recover and evacuate from the three ball valve access valves with the ball valves open.
June 2017
Page 10
Page 11
EH222 E and Condensing Unit Remote Low Side Cuber User Manual
Lower Light and Switch Panel
Open door to access
On and Off switch buttons.
Lower Light and Switch Panel
This user accessible panel provides important
operational information and duplicates the lights and switches on the controller. It also allows access to the On and Off buttons that operate the ice machine.
Sometimes access to the switches should be limited
to prevent unauthorized operation. For that
purpose a xed panel is shipped in the hardware package. The xed panel cannot be opened.
To install the xed panel:
1. Remove the front panel and remove the bezel.
2. Spread the bezel frame open and remove
original door, insert xed panel into bezel. Be
sure it is in the closed position.
3. Return bezel to panel and install panel on unit.
June 2017
Page 11
Page 12
EH222 E and Condensing Unit Remote Low Side Cuber User Manual
Place Ice Making Head
Remove from carton.
Place adapter kit onto bin or dispenser top. If adapter does NOT have gasket tape install tape such as Scotsman part number 19-0503-04. The adapter to ice head base MUST be sealed with gasket tape or food grade sealant.
Attachment
ABS (Automatic Beverage Dispenser) in drive up installations: Route refrigerant tubing and install drain and water supply tubing onto ice making section before placing unit on the dispenser.
Place EH222 onto adapter, do not secure at this time. Uncoil power cord and route to the power supply.
Plug interconnecting control wire to the wire harness in the ice making head.
Located at the top panel:
Refrigeration connections.
Interconnecting control wire.
Access port for water supply.
Power cord.
The drain may be routed to the left or right, allowing the ice making section to be placed with its back tight against a wall.
Water and Drain
The ice maker requires an adequate potable water supply and a gravity drain.
Determine how the drain will be connected to the ice making section.
If access is available behind the unit, route the drain in from the back.
If the unit is to be ush mounted to the back of the dispenser and tight against the wall, route the drain out either the left or right.
In some tight situations it will be necessary to assemble the ice making section to the dispenser or bin and install the water and drain connections before placing the system in its installed position. A loop of water supply tubing will aid movement of the system.
In other tight situations the unit should have its water and drain tubing connected and stubbed out before placing on the dispenser or bin.
The drain tting is adaptable to drain connections to
the left, right and back.
The unit is shipped ready to drain right. The drain
tting elbow with PVC adapter can be rotated to drain
right, left or back.
Drain Fitting
EH222 Back View
June 2017
Page 12
Page 13
EH222 E and Condensing Unit Remote Low Side Cuber User Manual
Drain Connections
Right Draining:
1. Connect ¾” PVC to the female PVC tting.
If copper is required by code, remove the PVC
connector and install a ¾” FPT female copper tting onto the ¾” NPT male tting. Do all soldering before connecting to the male tting.
2. In tight locations do the next step after the unit is placed on the dispenser or bin.
3. Connect rigid drain tubing to the reservoir drain tube. Route the drain either out the back, under the unit (through the notch in the base) to the left side or to the right side. A vent is built into the unit, so no external vent is required.
Run the drain tubing to the building drain. Do not “Tee” into any other drain, including the bin or dispenser drain.
Left Draining: Rotate elbow to the other direction.
Connect ¾” PVC to the PVC tting.
Back Draining: Rotate elbow to face the back or
connect PVC directly into the ¾” FPT drain tting.
No external drain vent is required, venting is internally provided for.
Note: External drain tubing must be supported to insure that it does not move and kink the internal rubber tube.
June 2017
Page 13
Page 14
EH222 E and Condensing Unit Remote Low Side Cuber User Manual
Water Supply:
A 3/8" are nut on tubing is located at the top panel,
near the refrigeration tubing.
Inside the hardware bag, inside the cabinet, a
3/8" inch double male are adapter (are union) is
supplied. Use the supplied adapter to make a 3/8"
male are tting for the water inlet.
Connect a cold, potable water supply to the 3/8” water
inlet tting installed above. Use 3/8" OD copper or
other comparable sized tubing for the water supply.
Note: This is an NSF listed ice machine and contains
provisions for back-ow prevention in its design. No external back ow preventer is required.
Communication Cable
Suction Line Insulation
Water Supply Connection
June 2017
Page 14
Page 15
EH222 E and Condensing Unit Remote Low Side Cuber User Manual
Electrical:
Condensing Unit
Route interconnecting control wire through proper hole end of condensing unit and plug into the connection on the control box.
Route power conduit (liquid tight) and wires to the junction box of the ECC unit. Secure with the proper type of connector.
Note: The power supply wires must be the correct size and type per the National Electric Code.
Locate the nameplate on the ECC unit for the Voltage,
Phase, Minimum Circuit Ampacity and Maximum Fuse Size. Either fuses or HACR type circuit breakers may be used.
Follow all Local, State and National Codes.
Three Phase Notice: Check voltage between legs at contactor. If there is a “wild leg” in the three phase power supply move supply wires at the contactor so
the higher voltage is on L3, which connects to the
compressor motor only.
Head
Plug head’s power cord into a nearby 115 volt electrical outlet.
Connect Cable Here
Electrical Junction Box
Dataplate Location
Communication Cable
June 2017
Page 15
Page 16
EH222 E and Condensing Unit Remote Low Side Cuber User Manual
Connect Refrigeration
Requires brazing, steps must be performed by an
EPA certied type II or higher technician.
At Head:
1. Remove protective plugs from all three connections and vent the nitrogen from the ice machine.
2. Route the each of the three tubes to its connection.
3. Remove the top panel and attach a refrigeration hose with depressor to the 1/2” vapor line access valve so the valve is OPEN. This is a vent for nitrogen purging.
4. Remove screws holding tubing bracket to back panel and lower it out of the way for brazing.
5. Clean tubing ends and position into couplings.
At Condensing Unit
At Head
1. With nitrogen owing from condensing unit, braze the liquid, vapor and suction line connections.
2. Remove refrigeration hose from head. Be sure valve cap is on tight.
3. Pull tubing bracket up and secure to back panel.
At Condensing Unit
1. Remove nitrogen source.
2. Return valve cores to access valves.
3. Connect vacuum pump to all three access valves (use two manifolds or two extra hoses and a tee) and evacuate the tubing and head to at least a 300 micron level.
4. Remove vacuum pump and add R-404A vapor to all three tubes to provide a positive pressure.
1. Conrm connection valves are fully closed.
2. Remove protective plugs from all three connections.
Valves Closed
3. Remove caps from access valve connections.
4. Remove cores from access valves.
5. Connect refrigeration hoses to access valves.
6. Connect dry nitrogen source to liquid line connection and vapor line connection.
7. Shorten tubing to correct length, clean ends and insert them into valve ends and couplings.
Note: Be sure tube and stubs are round, dress with swage tool if needed.
8. Add heat sink material to ball valve body.
5. Leak check the braze connections and repair any leaks.
6. Open all three valves to full open.
Note: The full refrigerant charge is contained in the receiver of the ice machine.
Suction
Vapor
Liquid
9. Open nitrogen and ow 1 psi nitrogen into liquid line and vapor line tubes and braze the liquid line, vapor line and suction line tubes to the valve stubs.
Refrigeration Connections
June 2018
Page 16
Page 17
EH222 E and Condensing Unit Remote Low Side Cuber User Manual
Complete the Installation
After the utilities and refrigeration connections have been made, secure the unit to the dispenser or bin top.
Secure ice making section to dispenser or bin adapter.
Use strap/clips to secure unit:
When used with Cornelius ABS adapter, install clip on the side of the cabinet. Clip under edge of adapter and secure to ice making section using the screws provided in the hardware bag.
Clip
Note: The refrigerant lines above the machine must be able to move freely while the machine is being moved into position.
Final Check List Before Initial Start Up
1. Conrm that the ice making section is installed
indoors in a controlled environment.
2. Conrm that all packing materials have been
removed from all products.
3. Conrm that the ice making section is level.
4. Conrm that all the refrigerant connections have
been made and checked for leaks.
5. Conrm that the proper power supply has been
turned on to the condensing unit.
6. Conrm that cold, potable water has been supplied
to the ice making section and checked for leaks.
7. Conrm that the water supply is adequate.
Note: If one side will be against a wall, do not use a
clip on that side. One clip is sufcient to secure the
unit.
For use on bin adapter, use clip (as a strap) on back.
8. Conrm that there is adequate water pressure and that any water lters have been checked to conrm
that the cartridges do not need changing.
9. Conrm that the proper size drain tubing has been
installed and properly routed.
10. Conrm that the ice making section has been
connected to the proper power supply.
11. Conrm that the interconnecting wire has been
routed and connected between the ice making section and the condensing unit.
If the ice maker & bin or dispenser is not yet in its nal
position gently move it there.
June 2017
Page 17
Page 18
EH222 E and Condensing Unit Remote Low Side Cuber User Manual
Reference for Start Up: Controller Operation
The controller has four indicator lights, a code display, four push buttons, and eleven component indicator lights.
Indicator Lights
Power - on when there is power to the controller
Status - on in ice making mode
Water - on and blinking when there is no water
De-scale & Sanitize - on when it is time to clean the machine
Code Display
Displays status and diagnostic codes
Push Buttons
On
Off
Manual Harvest
Clean
Component indicator lights
Fan - not used on this model
Water Pump - on when the pump is
Purge Valve - on when the purge valve is
Water Solenoid - on when the inlet water solenoid valve is
Hot Gas - on when the vapor inlet valve and harvest assist solenoid have power
Compressor - on when the compressor contactor is energized
Ready to Harvest - on when the ice thickness sensor has water touching it
Sump Empty - on when there is no water touching the mid-length probe
Sump Full - on when water is touching the shortest probe
SW2 - on when the curtain is open
SW1 - on when the curtain is open
Cycle Denitions:
Freeze: The refrigeration system is operating to remove heat from the evaporators. The compressor, fan motor, and water pump are on.
Harvest: The refrigeration system and water system are operating to harvest the ice and rinse the reservoir. The compressor is on for the full cycle, the pump is on until the purge valve closes.
The inlet water valve opens and rells the reservoir.
The vapor and condenser by-pass valves are open during the entire harvest cycle, as is the harvest assist mechanism.
June 2017
Page 18
Page 19
EH222 E and Condensing Unit Remote Low Side Cuber User Manual
Initial Start Up
Pre Start
A soak-out period of four hours is optional for this system. If desired, powering the compressor unit for four hours prior to start up allows the crankcase heater to warm up the oil in the compressor.
Start Up
1. Connect power to the condensing unit and move its toggle switch to Run or On.
2. Open the water supply valve.
3. Switch on the electrical power to the EH222. Observe that some of the lower control’s indicator lights glow and its display shows O.
4. Locate lower light and control panel.
5. Push and release the ON button on the lower panel. The code display will begin to blink F.
The purge valve opens, the water pump starts and the inlet water valve opens to add water to the reservoir. In a few seconds the purge valve closes and the
water pump stops. Water will ow into the machine
until the reservoir is full. The vapor valve and harvest assist device will activate, then the compressor and water pump will start. F will be on steady.
Note: Because the condensing unit is external to the ice making section, no visible signs of operation will be noticeable until the water begins to cool and frost forms on the evaporator tubing.
Note: Moving the curtain during the Freeze cycle has no affect on control function, but will cause water to
ow into the cube chute.
When enough ice has frozen, the Ready for Harvest indicator light will be on steady. After it’s been on steady for a few seconds Harvest will begin.
The display shows an H. The vapor valve in the EH222 opens, and the harvest assist mechanism activates. In the CU the condenser bypass valve opens and the receiver inlet valve closes. In the EH222, the purge valve opens to drain some water,
when it does the inlet water valve opens to rell the
reservoir. After a few seconds the purge valve closes
but the inlet water valve continues to ll the reservoir.
Harvest continues until the ice is released as a unit and forces the curtain to open.
When the curtain opens it signals the controller that harvest is complete, and it returns the unit to a freeze cycle.
7. Check the ice harvested for proper bridge thickness. The ice bridge is factory set at 1/8 inch. If needed, adjust bridge thickness. Do NOT make it too thin.
8. Instruct the user in the operation of the machine and its maintenance requirements.
9. Fill out and mail the warranty registration form or register it on line at www.scotsman-ice.com.
6. Go to the condensing unit and conrm that the compressor and fan motor are operating. Warm air will be discharged from the condenser.
Observe the Ready for Harvest indicator light. It may blink early in the cycle, that is normal. The control will
ignore that signal for the rst 6 minutes of freeze.
During the Freeze cycle move the curtain and observe that either the SW1 or SW2 light on the control board blinks On when the curtain moves away from the evaporator and Off when returned to its normal position.
June 2017
Page 19
Page 20
EH222 E and Condensing Unit Remote Low Side Cuber User Manual
Ice Thickness and Water Purge Adjustment
Bridge Thickness - For the Service Tech Only
1. Push and hold Off till the machine stops.
2. Remove evaporator cover.
3. Remove curtain.
4. Use a hex wrench and rotate the bridge thickness adjustment screw in 1/16 turn increments CW to increase bridge thickness.
5. Rotate CCW to decrease bridge thickness.
Caution: Do not make the bridge too thin or the machine will not harvest properly. Bridge thickness adjustments are not covered by warranty.
6. Return curtain and evaporator cover to their normal positions.
1/8 to 3/16” Bridge
ice Bridge Thickness
7. Push and release the On button. Check next harvest of ice. Repeat steps 1-6 if needed.
Water Purge Setting
The water purge is factory set to the automatic position, suitable for most water conditions. The setting can be changed to one of 5 manual settings or left on automatic.
Setting Water Type 1 Minimum - RO water or equivalent 2 Moderate - Low TDS, non RO 3 Standard - Use with typical water 4 Heavy - High TDS 5 Maximum - Very high TDS A Automatic - Factory setting
To set:
1. Switch the machine OFF by holding the Off button in until a number or the letter A shows on the display.
Adjustment Screw
Bridge Thickness Adjustment Mechanism
2. Press and release the On button repeatedly until the number on the display corresponds to the desired setting.
3. Press and release the Off switch again to return to the normal control state.
June 2017
Page 20
Page 21
EH222 E and Condensing Unit Remote Low Side Cuber User Manual
Adjustable Ice Level Control
There is an adjustment post and an additional indicator light to the right of the four indicator lights. The ultrasonic ice level control allows the user to control the point that the ice machine will stop making ice before the bin or dispenser is full. Reasons for this include:
Seasonal changes in ice used
Planning to sanitize the bin
Certain dispenser applications where maximum ice level is not desired
Use of control
There are several positions the ice level can be set to, including Off (knob and label indicators lined up),
where it lls the bin until the standard bin control shuts
the machine off.
Ice
The cuber drops ice in large sections. That ice will break up into random parts as it falls into the bin, but some large sections may remain on top of the ice in the bin. In a dispenser this ice will break up into mostly individual cubes as the dispense mechanism moves the ice.
Noise
The ice machine will make little noise when it is in ice making mode. The compressor and fan motor are remote from the ice making head. The water pump in the ice making head will produce some sound. It is also normal to hear some cracking just before the harvest cycle begins. In addition, during the harvest cycle the harvest assist solenoid will click twice as it pushes the ice out and returns to its normal position. The ice harvests as a unit or slab, which makes some noise when it impacts the bin or dispenser. These noises are all normal for this machine.
Rotate the adjustment post to the desired ice level.
The machine will ll up to that level and when it shuts
off the indicator light next to the adjustment post will be On.
Suggested Adjustment Knob Position for use with the
ABS or Freestyle: rst CW position - as shown above.
DO NOT ADJUST TOO LOW OR THE MACHINE WILL STOP MAKING ICE
Note: Ice will build up in the bin or dispenser at an angle, the distance set will be from the sensor to the top of the ice. The sensor position is shown in the cabinet layout diagrams.
The actual distance between the highest point of the ice may be closer or further away than the distance set, depending upon the angle of the ice.
June 2017
Page 21
Page 22
EH222 E and Condensing Unit Remote Low Side Cuber User Manual
Cleaning, Sanitation and Maintenance
This ice system requires three types of maintenance:
Remove the build up of mineral scale from the ice machine’s water system and sensors.
Sanitize the ice machine’s water system and the ice storage bin or dispenser.
Clean the remote air cooled condenser.
It is the User’s responsibility to keep the ice machine and ice storage bin in a sanitary condition. Without human intervention, sanitation will not be maintained. Ice machines also require occasional cleaning of their
water systems with a specically designed chemical. This chemical dissolves mineral build up that forms during
the ice making process.
Sanitize the ice storage bin as frequently as local health codes require, and every time the ice machine is cleaned and sanitized.
The ice machine’s water system should be cleaned and sanitized a minimum of twice per year.
Note: If unit has not been de-scaled for an extended
period of time and signicant mineral scale remains,
repeat steps 5 - 10.
1. Remove the front panel.
7. Mix a cleaning solution of 1 oz of ice machine
2. Remove the evaporator cover.
3. Remove all ice from the storage bin or dispenser.
4. Push and release the Clean button. The yellow Clean light will blink and the display will show
cleaner to 12 ounces of water.
8. Remove curtain from unit.
9. Locate ice thickness sensor. Squeeze mounting legs together to release sensor.
C. The machine will harvest any ice, drain the
reservoir and begin to rell it.
10. Remove water distributor from ice machine by disconnecting its hose, squeezing the retaining
Note: Curtain must be in the closed position. Move curtain to release any ice trapped after ice is harvested.
5. Observe code display, when it blinks the characters “A d 1” immediately go to the next step.
Ice machine scale remover contains acids. Acids can cause burns.
snaps together and pushing the distributor to the
right as far as possible. Lift up to remove. Inspect distributor for restricted orice holes. Be sure all
holes are full open.
11. Locate water level sensor. Squeeze catches together and pull up to remove sensor. Separate probes from housing and wash all surfaces with ice machine scale remover solution. Return probes to holder.
If concentrated cleaner comes
in contact with skin, ush with
water. If swallowed, do NOT induce vomiting. Give large amounts of water or milk. Call Physician immediately. Keep out of the reach of children.
12. Wash the metal surfaces of the ice thickness sensor and the adjustment screw with ice machine cleaner solution. Also wash the water distributor, water level sensor probes and curtain with the ice machine cleaner solution.
13. Create a solution of sanitizer by mixing a 1 gallon or 4 liter solution of locally approved sanitizer
6. Pour 8 ounces of Scotsman Clear 1 ice machine scale remover into the reservoir. The unit will
circulate the scale remover, then drain and ush
it. This will take 35 minutes, then the machine will stop and the display will show O.
and clean, warm water. Use an EPA approved food equipment sanitizer at the solution mix recommended by the sanitizer manufacturer.
Scotsman offers Stera Sheen Green Label
sanitizer, part number 14-0382-01.
June 2017
Page 22
Page 23
EH222 E and Condensing Unit
Inspect Orifice Holes
Remote Low Side Cuber User Manual
the machine will stop and the display will show O.
20. Return all panels and covers removed to their original positions.
21. Push and release the On button to resume ice making.
Other Maintenance
The remote air cooled condenser coil must be cleaned occasionally to keep the system operating at
high efciency.
Remove any large debris from the outside of the coil.
Vacuum accumulated dust.
Step 15. Release probes by pushing in on white buttons and pulling probe down out of holder.
14. Thoroughly wash all surfaces of the ice thickness sensor, water level sensor, curtain and water distributor with the sanitizer solution.
15. Wash all interior surfaces of the freezing compartment, including evaporator cover and right side panel liner with the sanitizer solution.
16. Return water level sensor, ice thickness sensor, water distributor and curtain to their normal positions. Be sure water level sensor and ice thickness sensor are completely dry.
Wash out the coils with water.
Caution: Do NOT use excessive water pressure as
that will bend the ns.
If the coils have become coated with grease, a coil cleaner will have to be used to wash the coils.
Disconnect power to the condensing unit and remove the condenser top.
Inspect the fan blade to be sure it is not cracked and is clean.
Return the condenser top to its original position and reconnect the power supply.
17. Push and release the Clean button. The yellow Clean light will blink and the display will show C. The machine will go through a harvest cycle, drain
the reservoir and begin to rell it.
18. Observe code display, when it blinks the characters “Ad1” immediately go to the next step.
19. Pour the sanitizing solution into the reservoir until it is full. The unit will circulate the sanitizer, then
drain and ush it. This will take 35 minutes, then
June 2017
Page 23
Page 24
EH222 E and Condensing Unit Remote Low Side Cuber User Manual
Operational Characteristics 800 lb system
Cycle Times @ Condenser Temp/Cabinet Temp/Water Temp in degrees F.
-20/50/40 70/70/50 90/90/70 120/110/100
Freeze 9 to 10 minutes 10 to 12 minutes 13 to 15 minutes 19 to 21 minutes Harvest 2 to 3 minutes 1 to 1.5 minutes 1 to 1.5 minutes .5 to 1 minute
System Pressures @ Condenser Temp/Cabinet Temp/Water Temp in degrees F
-20/50/40 70/70/50 90/90/70 120/110/100 Suction at head, end of Freeze 26 to 27 PSIG 26 to 31 PSIG 26 to 31 PSIG 30 to 35 PSIG Suction at head, Harvest - Peak 88 PSIG 85 to 105 PSIG 105 to 125 PSIG 140 t0 160 PSIG Discharge at Condensing Unit:
217 PSIG 230 to 250 PSIG 250 to 270 PSIG 330 to 350 PSIG
Freeze - 5 minutes in
Operational Characteristics 1000 lb system
Cycle Times @ Condenser Temp/Cabinet Temp/Water Temp in degrees F.
20/70/40 70/70/50 90/90/70 120/110/100 Freeze 7 to 8 minutes 8 to 9 minutes 10 to 11 minutes 16 to 18 minutes Harvest 2 to 3 minutes 1 to 1.5 minutes 1 to 1.5 minutes .5 to 1 minute
System Pressures @ Condenser Temp/Cabinet Temp/Water Temp in degrees F
-20/50/40 70/70/50 90/90/70 120/110/100 Suction at head, end of Freeze 22 PSIG 26 to 31 PSIG 27 to 32 PSIG 30 to 35 PSIG Suction at head, Harvest - Peak 88 PSIG 85 to 105 PSIG 90 to 110 PSIG 140 to 160 PSIG Discharge at Condensing Unit:
Freeze - 5 minutes in
219 PSIG 230 to 250 PSIG 240 to 250 PSIG 345 to 380 PSIG
Below information applies to both size systems:
Headmaster maintains a minimum discharge pressure during freeze of 217 PSIG + 25, -15 PSIG.
CPR Valve Setting: 55 - 60 PSIG.
Note: CPR allows a maximum low side pressure at the compressor. Maximum only occurs during harvest.
Refrigerant Charge
800: 192 oz.
1000: 248 oz
Compressor Amps, 800 model
Single Phase - 6 to 8 Three Phase - 5 to 7
Compressor Amps, 1000 model
Single Phase - 8 to 9, Three Phase - 6.3 to 5.2
Batch Weight: 8 lb
Discharge Pressure Cut Out Switch
Cuts Out at: 450 PSIG Resets at: 350 PSIG
June 2017
Page 24
Page 25
EH222 E and Condensing Unit Remote Low Side Cuber User Manual
What to do before calling for service:
Reasons the machine might shut itself off:
Lack of water.
Freeze cycle takes too long.
Harvest cycle takes too long.
High discharge pressure.
Ice level control set wrong
Check the following:
1. Has the water supply to the ice machine or building been shut off? If yes, the ice machine will automatically
restart within 25 minutes after water begins to ow to it.
2. Has power been shut off to the ice machine? If yes, the ice machine will automatically restart when power is restored.
3. Is the curtain open because some ice is stuck under it? If so, remove the ice and the machine should start in a few minutes.
4. Check the adjustment knob of the ice level control. See page 21.
Note: Curtain can be removed & replaced anytime the machine is in a standby mode or when it is in a freeze
cycle. However, removal of the curtain during freeze will result in water owing into the bin. Removal of the
curtain during harvest terminates harvest at that point and, if left off, will result in the machine shutting off.
To Manually Reset the machine.
1. Open the switch door.
2. Push and release the Off button.
3. Push and release the On button.
To Shut the Machine Off:
1. Push and hold the Off button for 3 seconds
or until the machine stops.
June 2017
Page 25
Page 26
EH222 E and Condensing Unit Remote Low Side Cuber User Manual
EH222 Schematic Diagram
June 2018
Page 26
Page 27
EH222 E and Condensing Unit Remote Low Side Cuber User Manual
EH222 Wiring Diagram
June 2018
Page 27
Page 28
EH222 E and Condensing Unit Remote Low Side Cuber User Manual
ECC Three Phase Schematic Diagram
June 2018
Page 28
Page 29
EH222 E and Condensing Unit Remote Low Side Cuber User Manual
ECC Three Phase Wiring Diagram
June 2018
Page 29
Page 30
EH222 E and Condensing Unit Remote Low Side Cuber User Manual
ECC Single Phase Schematic Diagram
June 2018
Page 30
Page 31
EH222 E and Condensing Unit Remote Low Side Cuber User Manual
ECC Single Phase Wiring Diagram
June 2018
Page 31
Page 32
SCOTSMAN ICE SYSTEMS
101 Corporate Woods Parkway
Vernon Hills, IL 60061
www.scotsman-ice.com
800-726-8762
17-3599-05 Rev. A