EH222 E and Condensing Unit
Remote Low Side Cuber User Manual
Conguration
A remote low side cuber system includes two sub
Warranty
systems: an ice making head and a remote air cooled
condensing unit. This manual covers the EH222 head
and the condensing units that go with it.
Refer to the warranty coverage in effect when the
equipment was sold. Warranty statements are
included with each product.
The ice making heads are designed for use indoors
in a controlled environment. The remote condensing
units are designed to operate outdoors. Each subsystem has limits for power, water and temperature.
Operational Limitations:
Systems:
Ice making heads and condensing units have their
own model and serial numbers. They must be
combined to create a remote cuber low side system.
Notes: Voltage Codes are at the end of the model
Minimum Maximum
Air Temp (at head) 50
Air Temp (CU) -20
Water Temp40
o
F 100oF.
o
F. 120oF.
o
F. 100oF.
Water Pressure 20 psi 80 psi
Water Conductivity 10
microSiemens/cmany
Voltage (at head) 104 126
number. Codes read Voltage/Hertz/Phase. Those
related to these products include:
-1 = 115/60/1
-3 = 208-230/60/3
-32 = 208-230/60/1
System Information
Voltage (CU) 198 253
CU= Condensing Unit
Tubing kits are required to connect the head to the
condensing unit.
Do Not operate the machine in conditions beyond
these limitations. Doing so will void the warranty.
Interconnecting 24 volt control wire ships with the
condensing unit.
Scotsman ice systems are designed and
manufactured with the highest regard for safety and
performance. They meet or exceed common agency
standards.
Scotsman assumes no liability of responsibility of
any kind for products manufactured by Scotsman
that have been altered in any way, including the use
of any part and/or other components not specically
approved by Scotsman.
Scotsman reserves the right to make design changes
and/or improvements at any time. Specications and
design are subject to change without notice.
June 2017
Page 3
Page 4
EH222 E and Condensing Unit
Remote Low Side Cuber User Manual
Specications and Location Information
ModelElectrical
volts/Hz/phase
EH222SL-1E115/60/11.1315shipped w/none22 x 16.5 x 29~100
ECC0800-3E208-230/60/310.61519232 x 39 x 39.75~300
ECC1410-32E208-230/60/115.83024832 x 39 x 39.75
ECC1410-3E208-230/60/311.62024832 x 39 x 39.75
* See cabinet drawings for detailed dimensions.
Location Limitations
Maximum Distance between Head and Condensing
Unit: Limited to the length of the longest available
single tubing kit, 75 feet.
Maximum Condensing Unit Elevation over Ice Making
Head: 35 feet.
Note: Elevations greater than 20 feet require
installation of a suction line trap at the 20 foot mark.
Minimum
Circuit
Ampacity
Maximum
Fuse Size
Condensing unit
The dataplate on the end contains the model number,
serial number, electrical data and system refrigerant
charge.
A second plate, located behind the side panel on the
deck, also lists the model number, serial number and
refrigerant charge.
System Charge,
oz of R-404A
Cabinet Size*
w” x d” x h”
Unit
Weight (lb)
~310
~310
Maximum Ice Making Head Elevation over
Condensing Unit: 15 feet.
Line Routing:
• Allowed: One rise after a drop.
• Allowed: One drop after a rise.
• Not Allowed: More than one rise after a drop
• Not Allowed: More than one drop after a rise.
Model Number Locations
Ice Making Head
The dataplate on the back of the ice machine contains
the model number, serial number and electrical data.
A second plate, located behind the front panel at
the lower right front, also lists the model and serial
numbers.
June 2017
Page 4
Page 5
EH222 E and Condensing Unit
3.25
82.55
Remote Low Side Cuber User Manual
Cabinet Drawings, Ice Making Head
5.19
131.70
4.57
115.95
79.38
3.13
68.20
2.69
42.80
1.69
24
.95
ACCESS HOLE
INTERFACE CABLE
34.04
24.89
1.34
3/4" SUCTION LINE
DETAIL A
.98
POTABLE WATER INLET 3/8"
EH222
ICE HEAD
1.82
46.24
19.00
482.60
TOP VIEW
80.97
3.19
10.75
273.05
10.27
260.80
3.25
82.55
ICE DROP AREA
MINIMUM BIN
TOP OPENING
2.94
74.72
A
SENSOR
BIN LEVEL
ULTRA SONIC
ACCESS HOLE
ELECTRICAL CORD
3/8" LIQUID LINE
8.31
211.09
6.00
152.40
SEE DETAIL "A"
120V AC, AND INTERFACE CABLE
LINE SET, POTABLE WATER INLET 3/8",
1/2" COOL VAPOR LINE
16.72
424.70
22.70
576.68
67.56
2.66
34.04
1.34
29.00
736.60
381
15.00
22.00
558.80
16.41
416.92
LEFT SIDE VIEW
DRAIN 3/4" PVC FEMALE
REAR, LEFT AND RIGHT SIDE ACCESS
REAR VIEW
June 2017
Page 5
Page 6
EH222 E and Condensing Unit
Remote Low Side Cuber User Manual
Cabinet Drawings, Condensing Unit
TOP VIEW
992.81
39.09
814.22
32.06
FRONT VIEW
32.05
1.26
TYP.
1009.65
39.75
887.73
34.95
.88" ELECTRICAL INLET
1/2" COOL VAPOR LINE
3/4" SUCTION LINE
3/8" LIQUID LINE
83.67
3.29
SIDE VIEW
LINE SET AND ELECTRICAL ATTACHMENT SIDE
330.86
13.03
74.12
2.92
163.02
6.42
248.87
9.80
750.06
29.53
491.69
19.36
INTERFACE HARNESS
ACCESS HOLE
63.50
2.50
June 2017
Page 6
Page 7
EH222 E and Condensing Unit
Remote Low Side Cuber User Manual
Pre-Installation Details
Note: The ice making section cannot be stacked
vertically.
Accessories such as bin adapters and tubing kits are
required to complete the installation.
Dispenser Adapter Kits:
• Cornelius ABS: KBTABS ED150: KBT40
• Scotsman ID150: KBT40
• Scotsman ID200 or ID250: KBT41
Bin Adapter Kits:
• B530P or B530S: KBT32
• B948S: KBT34
Tubing Kits:
• 20 foot: 3BRTE20-EH
• 35 foot: 3BRTE35-EH
• 50 foot: 3BRTE50-EH
• 75 foot: 3BRTE75-EH
Note: Line set may have quick connects. The
condensing section may have quick connects. See
refrigeration system detailed instructions connection
details.
Water
Pure water does not exist. All water supplies contain
some amounts of impurities, although potable water
is, by denition, t for human consumption. Because
the contents of the water to an ice machine directly
impact its performance, consideration should be given
to improving the water’s quality.
There are two ways water can contain impurities:
in suspension or in solution. Suspended solids can
be ltered out of the water. In solution or dissolved
solids must be diluted or treated. Water lters are
recommended to remove the suspended solids.
Some lters or lter systems have treatment
chemicals in them for treating the suspended solids.
This ice machine has an adjustment for the amount
of water rinsed or purged. Water use adjustments
are customer convenience adjustments; they are not
factory defects and are not covered by warranty.
Items required for installation:
• Ice making head
• Condensing unit (includes interconnecting control
system wire)
• Tubing kit. 20’, 35', 50’ or 75’ triple line set (liquid,
vapor and suction)
• Bin or dispenser adapter
Special Considerations
The ice making section’s footprint is 22” wide by 16.5”
deep. The refrigeration connections can be routed up
or to the back. The drain may be routed out the back
at any position left to right; it may also be routed to
either side.
June 2017
Page 7
Page 8
EH222 E and Condensing Unit
Remote Low Side Cuber User Manual
Create the System
Plan the installation. The system consists of three
parts: the ice making head, the condensing unit and
the interconnecting tubing. Of these, the biggest
variable is the interconnecting tubing.
Tubing: The tubing consists of three insulated and
sealed soft copper tubes. One tube, the liquid line,
is 3/8” OD. The vapor tube is ½” OD and the suction
tube is ¾” OD. A site inspection will determine what
length of tubing is required for the installation.
In 2013 Scotsman made a change to the Eclipse
tubing kits:
• Prior Tubing Kits: They each contain a small
holding charge of R-404A and have quick
connects at the ends.
• Current Tubing Kits: The do not contain any
refrigerant and do not have quick connects.
Either type can be used to connect the head and
condensing unit.
Elevation: Condensing unit limited to 35 feet above
the ice making section.
Condensing Unit: Electrical power must be supplied to
the condensing unit, it will be separate from the head.
Ice making section location and attachment: The
unique footprint of the EH222 requires adapter kits to
allow placement on dispensers and bins.
The remote tubing connections are at the top of the
machine, and connections should not be made until
the machine is nearly in its nal installed position.
The 115/60 Hz ice making section is cord connected
and requires an outlet within 6 feet of the installation.
Interconnecting wires: An interconnecting wire
harness is included with the condensing unit. One end
plugs into the ice making section and the other into
the condensing unit. The system will NOT operate
without this harness.
Check condensing unit for quick connects. If none,
recover refrigerant from tubing and cut the quick
Exposed tubing: Minimize the amount of tubing
exposed outdoors.
connects off.
Lineset Ice machine head and condensing
unit both have stubs
Ice machine head has stubs, condensing
unit has quick connects.
Has Quick Connect FittingsCut quick connects off both endsCut off quick connects at condensing unit
end only
Does NOT have Quick
Connect Fittings
Use as suppliedUse as is at head, obtain kit KTE6-EH,
use 3 of 6 ttings on condensing unit end.
Excess tubing must be shortened at the job site.
Installations with greater than 20 feet of vertical lift
between ice machine and the compressor require
a suction line trap. The suction line requires careful
handling and large radius bends to prevent kinking.
Roof mounting: Some installations will require the use
of a hoist to lift the components to the roof.
Pad mounting: The condensing unit may be located
below the ice making section, up to a limit of 15 feet.
Distance from unit: Limited to the length of the
available tubing.
June 2017
Page 8
Page 9
EH222 E and Condensing Unit
Remote Low Side Cuber User Manual
Completed System Example
June 2017
Page 9
Page 10
EH222 E and Condensing Unit
Remote Low Side Cuber User Manual
Place Remote System
Roof preparation
Most installations of this system will place the
condensing unit on the roof of a building. The roof
must be physically able to accept the load of the
equipment and the roong material must be prepared
to prevent water leaks.
Follow local codes for the placement and attachment
of the equipment.
Location
The condensing unit requires unobstructed air ow
to operate efciently. A four foot space between
each intake side and a wall or other cabinet is
recommended.
Do not place where it will pick up hot discharged air
from an air conditioner or other refrigeration system
condensing unit.
Space must also be reserved for service on the
condensing unit.
Roof Pipe Curb or Pitch Pocket:
To avoid potential kinking of the refrigeration tubing,
avoid small, tight radius types of covers on pitch
pockets.
Suggestions:
In most cases a mechanical lift, boom truck or crane
will be required to hoist the condensing unit.
Mount unit to roof rails or curbs and secure with lag
screws or similar eld supplied fasteners.
Orient the assembled unit so that the unit’s mounts
are parallel to the pitch of the roof to allow water to
drain freely.
Do NOT place the unit directly onto roof rock.
Roof Piercing:
The roof (or wall) must have a passage large enough
for the three refrigeration tubes and the control wire
to pass through. The minimum recommended size is
4” ID. In most areas the power supply may also pass
through the same passage. If there isn’t a passage
one must be created. In most cases this must be done
by a licensed and bonded roofer in order to maintain
the roof’s integrity.
In all cases the line set will need to be shortened to t.
Do NOT leave excess line set exposed outdoors,
especially on a roof.
Refrigerant Recovery and System Evacuation Notice
In the event the refrigerant must be recovered from this system and the system evacuated, recover and
evacuate from the three ball valve access valves with the ball valves open.
June 2017
Page 10
Page 11
EH222 E and Condensing Unit
Remote Low Side Cuber User Manual
Lower Light and Switch Panel
Open door to access
On and Off switch
buttons.
Lower Light and Switch Panel
This user accessible panel provides important
operational information and duplicates the lights
and switches on the controller. It also allows
access to the On and Off buttons that operate
the ice machine.
Sometimes access to the switches should be limited
to prevent unauthorized operation. For that
purpose a xed panel is shipped in the hardware
package. The xed panel cannot be opened.
To install the xed panel:
1. Remove the front panel and remove the bezel.
2. Spread the bezel frame open and remove
original door, insert xed panel into bezel. Be
sure it is in the closed position.
3. Return bezel to panel and install panel on unit.
June 2017
Page 11
Page 12
EH222 E and Condensing Unit
Remote Low Side Cuber User Manual
Place Ice Making Head
Remove from carton.
Place adapter kit onto bin or dispenser top. If adapter
does NOT have gasket tape install tape such as
Scotsman part number 19-0503-04. The adapter to
ice head base MUST be sealed with gasket tape or
food grade sealant.
Attachment
ABS (Automatic Beverage Dispenser) in drive up
installations: Route refrigerant tubing and install drain
and water supply tubing onto ice making section
before placing unit on the dispenser.
Place EH222 onto adapter, do not secure at this time.
Uncoil power cord and route to the power supply.
Plug interconnecting control wire to the wire harness
in the ice making head.
Located at the top panel:
• Refrigeration connections.
• Interconnecting control wire.
• Access port for water supply.
• Power cord.
The drain may be routed to the left or right, allowing
the ice making section to be placed with its back tight
against a wall.
Water and Drain
The ice maker requires an adequate potable water
supply and a gravity drain.
Determine how the drain will be connected to the ice
making section.
• If access is available behind the unit, route the
drain in from the back.
• If the unit is to be ush mounted to the back of
the dispenser and tight against the wall, route the
drain out either the left or right.
In some tight situations it will be necessary to
assemble the ice making section to the dispenser or
bin and install the water and drain connections before
placing the system in its installed position. A loop of
water supply tubing will aid movement of the system.
In other tight situations the unit should have its water
and drain tubing connected and stubbed out before
placing on the dispenser or bin.
The drain tting is adaptable to drain connections to
the left, right and back.
The unit is shipped ready to drain right. The drain
tting elbow with PVC adapter can be rotated to drain
right, left or back.
Drain Fitting
EH222 Back View
June 2017
Page 12
Page 13
EH222 E and Condensing Unit
Remote Low Side Cuber User Manual
Drain Connections
Right Draining:
1. Connect ¾” PVC to the female PVC tting.
If copper is required by code, remove the PVC
connector and install a ¾” FPT female copper tting
onto the ¾” NPT male tting. Do all soldering before
connecting to the male tting.
2. In tight locations do the next step after the unit is
placed on the dispenser or bin.
3. Connect rigid drain tubing to the reservoir drain
tube. Route the drain either out the back, under the
unit (through the notch in the base) to the left side
or to the right side. A vent is built into the unit, so no
external vent is required.
Run the drain tubing to the building drain. Do not
“Tee” into any other drain, including the bin or
dispenser drain.
Left Draining: Rotate elbow to the other direction.
Connect ¾” PVC to the PVC tting.
Back Draining: Rotate elbow to face the back or
connect PVC directly into the ¾” FPT drain tting.
No external drain vent is required, venting is internally
provided for.
Note: External drain tubing must be supported to
insure that it does not move and kink the internal
rubber tube.
June 2017
Page 13
Page 14
EH222 E and Condensing Unit
Remote Low Side Cuber User Manual
Water Supply:
A 3/8" are nut on tubing is located at the top panel,
near the refrigeration tubing.
Inside the hardware bag, inside the cabinet, a
3/8" inch double male are adapter (are union) is
supplied. Use the supplied adapter to make a 3/8"
male are tting for the water inlet.
Connect a cold, potable water supply to the 3/8” water
inlet tting installed above. Use 3/8" OD copper or
other comparable sized tubing for the water supply.
Note: This is an NSF listed ice machine and contains
provisions for back-ow prevention in its design. No
external back ow preventer is required.
Communication Cable
Suction Line Insulation
Water Supply Connection
June 2017
Page 14
Page 15
EH222 E and Condensing Unit
Remote Low Side Cuber User Manual
Electrical:
Condensing Unit
Route interconnecting control wire through proper
hole end of condensing unit and plug into the
connection on the control box.
Route power conduit (liquid tight) and wires to the
junction box of the ECC unit. Secure with the proper
type of connector.
Note: The power supply wires must be the correct
size and type per the National Electric Code.
Locate the nameplate on the ECC unit for the Voltage,
Phase, Minimum Circuit Ampacity and Maximum Fuse
Size. Either fuses or HACR type circuit breakers may
be used.
Follow all Local, State and National Codes.
Three Phase Notice: Check voltage between legs
at contactor. If there is a “wild leg” in the three phase
power supply move supply wires at the contactor so
the higher voltage is on L3, which connects to the
compressor motor only.
Head
Plug head’s power cord into a nearby 115 volt
electrical outlet.
Connect Cable Here
Electrical Junction Box
Dataplate Location
Communication Cable
June 2017
Page 15
Page 16
EH222 E and Condensing Unit
Remote Low Side Cuber User Manual
Connect Refrigeration
Requires brazing, steps must be performed by an
EPA certied type II or higher technician.
At Head:
1. Remove protective plugs from all three
connections and vent the nitrogen from the ice
machine.
2. Route the each of the three tubes to its
connection.
3. Remove the top panel and attach a refrigeration
hose with depressor to the 1/2” vapor line access
valve so the valve is OPEN. This is a vent for
nitrogen purging.
4. Remove screws holding tubing bracket to back
panel and lower it out of the way for brazing.
5. Clean tubing ends and position into couplings.
At Condensing Unit
At Head
1. With nitrogen owing from condensing unit, braze
the liquid, vapor and suction line connections.
2. Remove refrigeration hose from head. Be sure
valve cap is on tight.
3. Pull tubing bracket up and secure to back panel.
At Condensing Unit
1. Remove nitrogen source.
2. Return valve cores to access valves.
3. Connect vacuum pump to all three access valves
(use two manifolds or two extra hoses and a tee)
and evacuate the tubing and head to at least a
300 micron level.
4. Remove vacuum pump and add R-404A vapor to
all three tubes to provide a positive pressure.
1. Conrm connection
valves are fully
closed.
2. Remove protective
plugs from all three
connections.
Valves Closed
3. Remove caps from access valve connections.
4. Remove cores from access valves.
5. Connect refrigeration hoses to access valves.
6. Connect dry nitrogen source to liquid line
connection and vapor line connection.
7. Shorten tubing to correct length, clean ends and
insert them into valve ends and couplings.
Note: Be sure tube and stubs are round, dress with
swage tool if needed.
8. Add heat sink material to ball valve body.
5. Leak check the braze connections and repair any
leaks.
6. Open all three valves to full open.
Note: The full refrigerant charge is contained in the
receiver of the ice machine.
Suction
Vapor
Liquid
9. Open nitrogen and ow 1 psi nitrogen into liquid
line and vapor line tubes and braze the liquid
line, vapor line and suction line tubes to the valve
stubs.
Refrigeration Connections
June 2018
Page 16
Page 17
EH222 E and Condensing Unit
Remote Low Side Cuber User Manual
Complete the Installation
After the utilities and refrigeration connections have
been made, secure the unit to the dispenser or bin
top.
Secure ice making section to dispenser or bin
adapter.
Use strap/clips to secure unit:
• When used with Cornelius ABS adapter, install
clip on the side of the cabinet. Clip under edge of
adapter and secure to ice making section using
the screws provided in the hardware bag.
Clip
Note: The refrigerant lines above the machine must
be able to move freely while the machine is being
moved into position.
Final Check List Before Initial Start Up
1. Conrm that the ice making section is installed
indoors in a controlled environment.
2. Conrm that all packing materials have been
removed from all products.
3. Conrm that the ice making section is level.
4. Conrm that all the refrigerant connections have
been made and checked for leaks.
5. Conrm that the proper power supply has been
turned on to the condensing unit.
6. Conrm that cold, potable water has been supplied
to the ice making section and checked for leaks.
7. Conrm that the water supply is adequate.
Note: If one side will be against a wall, do not use a
clip on that side. One clip is sufcient to secure the
unit.
• For use on bin adapter, use clip (as a strap) on
back.
8. Conrm that there is adequate water pressure and
that any water lters have been checked to conrm
that the cartridges do not need changing.
9. Conrm that the proper size drain tubing has been
installed and properly routed.
10. Conrm that the ice making section has been
connected to the proper power supply.
11. Conrm that the interconnecting wire has been
routed and connected between the ice making section
and the condensing unit.
If the ice maker & bin or dispenser is not yet in its nal
position gently move it there.
June 2017
Page 17
Page 18
EH222 E and Condensing Unit
Remote Low Side Cuber User Manual
Reference for Start Up: Controller Operation
The controller has four indicator lights, a code display,
four push buttons, and eleven component indicator
lights.
Indicator Lights
• Power - on when there is power to the controller
• Status - on in ice making mode
• Water - on and blinking when there is no water
• De-scale & Sanitize - on when it is time to clean
the machine
Code Display
• Displays status and diagnostic codes
Push Buttons
• On
• Off
• Manual Harvest
• Clean
Component indicator lights
• Fan - not used on this model
• Water Pump - on when the pump is
• Purge Valve - on when the purge valve is
• Water Solenoid - on when the inlet water solenoid
valve is
• Hot Gas - on when the vapor inlet valve and
harvest assist solenoid have power
• Compressor - on when the compressor contactor
is energized
• Ready to Harvest - on when the ice thickness
sensor has water touching it
• Sump Empty - on when there is no water touching
the mid-length probe
• Sump Full - on when water is touching the
shortest probe
• SW2 - on when the curtain is open
• SW1 - on when the curtain is open
Cycle Denitions:
Freeze: The refrigeration system is operating to
remove heat from the evaporators. The compressor,
fan motor, and water pump are on.
Harvest: The refrigeration system and water system
are operating to harvest the ice and rinse the
reservoir. The compressor is on for the full cycle, the
pump is on until the purge valve closes.
The inlet water valve opens and rells the reservoir.
The vapor and condenser by-pass valves are open
during the entire harvest cycle, as is the harvest assist
mechanism.
June 2017
Page 18
Page 19
EH222 E and Condensing Unit
Remote Low Side Cuber User Manual
Initial Start Up
Pre Start
A soak-out period of four hours is optional for this
system. If desired, powering the compressor unit
for four hours prior to start up allows the crankcase
heater to warm up the oil in the compressor.
Start Up
1. Connect power to the condensing unit and move
its toggle switch to Run or On.
2. Open the water supply valve.
3. Switch on the electrical power to the EH222.
Observe that some of the lower control’s indicator
lights glow and its display shows O.
4. Locate lower light and control panel.
5. Push and release the ON button on the lower
panel. The code display will begin to blink F.
The purge valve opens, the water pump starts and the
inlet water valve opens to add water to the reservoir.
In a few seconds the purge valve closes and the
water pump stops. Water will ow into the machine
until the reservoir is full. The vapor valve and harvest
assist device will activate, then the compressor and
water pump will start. F will be on steady.
Note: Because the condensing unit is external to the
ice making section, no visible signs of operation will
be noticeable until the water begins to cool and frost
forms on the evaporator tubing.
Note: Moving the curtain during the Freeze cycle has
no affect on control function, but will cause water to
ow into the cube chute.
When enough ice has frozen, the Ready for Harvest
indicator light will be on steady. After it’s been on
steady for a few seconds Harvest will begin.
The display shows an H. The vapor valve in the
EH222 opens, and the harvest assist mechanism
activates. In the CU the condenser bypass valve
opens and the receiver inlet valve closes. In the
EH222, the purge valve opens to drain some water,
when it does the inlet water valve opens to rell the
reservoir. After a few seconds the purge valve closes
but the inlet water valve continues to ll the reservoir.
Harvest continues until the ice is released as a unit
and forces the curtain to open.
When the curtain opens it signals the controller that
harvest is complete, and it returns the unit to a freeze
cycle.
7. Check the ice harvested for proper bridge
thickness. The ice bridge is factory set at 1/8 inch.
If needed, adjust bridge thickness. Do NOT make
it too thin.
8. Instruct the user in the operation of the machine
and its maintenance requirements.
9. Fill out and mail the warranty registration form or
register it on line at www.scotsman-ice.com.
6. Go to the condensing unit and conrm that the
compressor and fan motor are operating. Warm
air will be discharged from the condenser.
Observe the Ready for Harvest indicator light. It may
blink early in the cycle, that is normal. The control will
ignore that signal for the rst 6 minutes of freeze.
During the Freeze cycle move the curtain and observe
that either the SW1 or SW2 light on the control
board blinks On when the curtain moves away from
the evaporator and Off when returned to its normal
position.
June 2017
Page 19
Page 20
EH222 E and Condensing Unit
Remote Low Side Cuber User Manual
Ice Thickness and Water Purge Adjustment
Bridge Thickness - For the Service Tech Only
1. Push and hold Off till the machine stops.
2. Remove evaporator cover.
3. Remove curtain.
4. Use a hex wrench and rotate the bridge thickness
adjustment screw in 1/16 turn increments CW to
increase bridge thickness.
5. Rotate CCW to decrease bridge thickness.
Caution: Do not make the bridge too thin or the
machine will not harvest properly. Bridge thickness
adjustments are not covered by warranty.
6. Return curtain and evaporator cover to their
normal positions.
1/8 to 3/16”
Bridge
ice Bridge Thickness
7. Push and release the On button. Check next
harvest of ice. Repeat steps 1-6 if needed.
Water Purge Setting
The water purge is factory set to the automatic
position, suitable for most water conditions. The
setting can be changed to one of 5 manual settings or
left on automatic.
Setting Water Type
1 Minimum - RO water or equivalent
2 Moderate - Low TDS, non RO
3 Standard - Use with typical water
4 Heavy - High TDS
5 Maximum - Very high TDS
A Automatic - Factory setting
To set:
1. Switch the machine OFF by holding the Off button
in until a number or the letter A shows on the
display.
Adjustment
Screw
Bridge Thickness Adjustment Mechanism
2. Press and release the On button repeatedly until
the number on the display corresponds to the
desired setting.
3. Press and release the Off switch again to return to
the normal control state.
June 2017
Page 20
Page 21
EH222 E and Condensing Unit
Remote Low Side Cuber User Manual
Adjustable Ice Level Control
There is an adjustment post and an additional
indicator light to the right of the four indicator lights.
The ultrasonic ice level control allows the user to
control the point that the ice machine will stop making
ice before the bin or dispenser is full. Reasons for this
include:
• Seasonal changes in ice used
• Planning to sanitize the bin
• Certain dispenser applications where maximum
ice level is not desired
Use of control
There are several positions the ice level can be set
to, including Off (knob and label indicators lined up),
where it lls the bin until the standard bin control shuts
the machine off.
Ice
The cuber drops ice in large sections. That ice will
break up into random parts as it falls into the bin, but
some large sections may remain on top of the ice
in the bin. In a dispenser this ice will break up into
mostly individual cubes as the dispense mechanism
moves the ice.
Noise
The ice machine will make little noise when it is in
ice making mode. The compressor and fan motor are
remote from the ice making head. The water pump
in the ice making head will produce some sound. It
is also normal to hear some cracking just before the
harvest cycle begins. In addition, during the harvest
cycle the harvest assist solenoid will click twice as it
pushes the ice out and returns to its normal position.
The ice harvests as a unit or slab, which makes some
noise when it impacts the bin or dispenser. These
noises are all normal for this machine.
Rotate the adjustment post to the desired ice level.
The machine will ll up to that level and when it shuts
off the indicator light next to the adjustment post will
be On.
Suggested Adjustment Knob Position for use with the
ABS or Freestyle: rst CW position - as shown above.
DO NOT ADJUST TOO LOW OR THE MACHINE
WILL STOP MAKING ICE
Note: Ice will build up in the bin or dispenser at an
angle, the distance set will be from the sensor to the
top of the ice. The sensor position is shown in the
cabinet layout diagrams.
The actual distance between the highest point of the
ice may be closer or further away than the distance
set, depending upon the angle of the ice.
June 2017
Page 21
Page 22
EH222 E and Condensing Unit
Remote Low Side Cuber User Manual
Cleaning, Sanitation and Maintenance
This ice system requires three types of maintenance:
• Remove the build up of mineral scale from the ice
machine’s water system and sensors.
• Sanitize the ice machine’s water system and the
ice storage bin or dispenser.
• Clean the remote air cooled condenser.
It is the User’s responsibility to keep the ice machine and ice storage bin in a sanitary condition. Without
human intervention, sanitation will not be maintained. Ice machines also require occasional cleaning of their
water systems with a specically designed chemical. This chemical dissolves mineral build up that forms during
the ice making process.
Sanitize the ice storage bin as frequently as local health codes require, and every time the ice machine is
cleaned and sanitized.
The ice machine’s water system should be cleaned
and sanitized a minimum of twice per year.
Note: If unit has not been de-scaled for an extended
period of time and signicant mineral scale remains,
repeat steps 5 - 10.
1. Remove the front panel.
7. Mix a cleaning solution of 1 oz of ice machine
2. Remove the evaporator cover.
3. Remove all ice from the storage bin or dispenser.
4. Push and release the Clean button. The yellow
Clean light will blink and the display will show
cleaner to 12 ounces of water.
8. Remove curtain from unit.
9. Locate ice thickness sensor. Squeeze mounting
legs together to release sensor.
C. The machine will harvest any ice, drain the
reservoir and begin to rell it.
10. Remove water distributor from ice machine by
disconnecting its hose, squeezing the retaining
Note: Curtain must be in the closed position. Move
curtain to release any ice trapped after ice is
harvested.
5. Observe code display, when it blinks the
characters “A d 1” immediately go to the next step.
Ice machine scale remover
contains acids. Acids can
cause burns.
snaps together and pushing the distributor to the
right as far as possible. Lift up to remove. Inspect
distributor for restricted orice holes. Be sure all
holes are full open.
11. Locate water level sensor. Squeeze catches
together and pull up to remove sensor. Separate
probes from housing and wash all surfaces with
ice machine scale remover solution. Return
probes to holder.
If concentrated cleaner comes
in contact with skin, ush with
water. If swallowed, do NOT
induce vomiting. Give large
amounts of water or milk. Call
Physician immediately. Keep
out of the reach of children.
12. Wash the metal surfaces of the ice thickness
sensor and the adjustment screw with ice machine
cleaner solution. Also wash the water distributor,
water level sensor probes and curtain with the ice
machine cleaner solution.
13. Create a solution of sanitizer by mixing a 1 gallon
or 4 liter solution of locally approved sanitizer
6. Pour 8 ounces of Scotsman Clear 1 ice machine
scale remover into the reservoir. The unit will
circulate the scale remover, then drain and ush
it. This will take 35 minutes, then the machine will
stop and the display will show O.
and clean, warm water. Use an EPA approved
food equipment sanitizer at the solution mix
recommended by the sanitizer manufacturer.
Scotsman offers Stera Sheen Green Label
sanitizer, part number 14-0382-01.
June 2017
Page 22
Page 23
EH222 E and Condensing Unit
Inspect Orifice Holes
Remote Low Side Cuber User Manual
the machine will stop and the display will show O.
20. Return all panels and covers removed to their
original positions.
21. Push and release the On button to resume ice
making.
Other Maintenance
The remote air cooled condenser coil must be
cleaned occasionally to keep the system operating at
high efciency.
Remove any large debris from the outside of the coil.
Vacuum accumulated dust.
Step 15.
Release
probes by
pushing in on
white buttons
and pulling
probe down
out of holder.
14. Thoroughly wash all surfaces of the ice thickness
sensor, water level sensor, curtain and water
distributor with the sanitizer solution.
15. Wash all interior surfaces of the freezing
compartment, including evaporator cover and right
side panel liner with the sanitizer solution.
16. Return water level sensor, ice thickness sensor,
water distributor and curtain to their normal
positions. Be sure water level sensor and ice
thickness sensor are completely dry.
Wash out the coils with water.
Caution: Do NOT use excessive water pressure as
that will bend the ns.
If the coils have become coated with grease, a coil
cleaner will have to be used to wash the coils.
Disconnect power to the condensing unit and remove
the condenser top.
Inspect the fan blade to be sure it is not cracked and
is clean.
Return the condenser top to its original position and
reconnect the power supply.
17. Push and release the Clean button. The yellow
Clean light will blink and the display will show C.
The machine will go through a harvest cycle, drain
the reservoir and begin to rell it.
18. Observe code display, when it blinks the
characters “Ad1” immediately go to the next step.
19. Pour the sanitizing solution into the reservoir until
it is full. The unit will circulate the sanitizer, then
drain and ush it. This will take 35 minutes, then
June 2017
Page 23
Page 24
EH222 E and Condensing Unit
Remote Low Side Cuber User Manual
Operational Characteristics 800 lb system
Cycle Times @ Condenser Temp/Cabinet Temp/Water Temp in degrees F.
-20/50/4070/70/50 90/90/70 120/110/100
Freeze 9 to 10 minutes10 to 12 minutes 13 to 15 minutes 19 to 21 minutes
Harvest 2 to 3 minutes1 to 1.5 minutes 1 to 1.5 minutes .5 to 1 minute
System Pressures @ Condenser Temp/Cabinet Temp/Water Temp in degrees F
-20/50/4070/70/50 90/90/70 120/110/100
Suction at head, end of Freeze 26 to 27 PSIG26 to 31 PSIG 26 to 31 PSIG 30 to 35 PSIG
Suction at head, Harvest - Peak 88 PSIG85 to 105 PSIG 105 to 125 PSIG 140 t0 160 PSIG
Discharge at Condensing Unit:
217 PSIG230 to 250 PSIG 250 to 270 PSIG 330 to 350 PSIG
Freeze - 5 minutes in
Operational Characteristics 1000 lb system
Cycle Times @ Condenser Temp/Cabinet Temp/Water Temp in degrees F.
20/70/4070/70/50 90/90/70 120/110/100
Freeze 7 to 8 minutes8 to 9 minutes 10 to 11 minutes 16 to 18 minutes
Harvest 2 to 3 minutes1 to 1.5 minutes 1 to 1.5 minutes .5 to 1 minute
System Pressures @ Condenser Temp/Cabinet Temp/Water Temp in degrees F
-20/50/4070/70/50 90/90/70 120/110/100
Suction at head, end of Freeze 22 PSIG26 to 31 PSIG 27 to 32 PSIG 30 to 35 PSIG
Suction at head, Harvest - Peak 88 PSIG85 to 105 PSIG 90 to 110 PSIG 140 to 160 PSIG
Discharge at Condensing Unit:
Freeze - 5 minutes in
219 PSIG230 to 250 PSIG 240 to 250 PSIG 345 to 380 PSIG
Below information applies to both size systems:
Headmaster maintains a minimum discharge pressure during freeze of 217 PSIG + 25, -15 PSIG.
CPR Valve Setting: 55 - 60 PSIG.
Note: CPR allows a maximum low side pressure at the compressor. Maximum only occurs during harvest.
Refrigerant Charge
• 800: 192 oz.
• 1000: 248 oz
Compressor Amps, 800 model
• Single Phase - 6 to 8 Three Phase - 5 to 7
Compressor Amps, 1000 model
• Single Phase - 8 to 9, Three Phase - 6.3 to 5.2
Batch Weight: 8 lb
Discharge Pressure Cut Out Switch
• Cuts Out at: 450 PSIG Resets at: 350 PSIG
June 2017
Page 24
Page 25
EH222 E and Condensing Unit
Remote Low Side Cuber User Manual
What to do before calling for service:
Reasons the machine might shut itself off:
• Lack of water.
• Freeze cycle takes too long.
• Harvest cycle takes too long.
• High discharge pressure.
• Ice level control set wrong
Check the following:
1. Has the water supply to the ice machine or building been shut off? If yes, the ice machine will automatically
restart within 25 minutes after water begins to ow to it.
2. Has power been shut off to the ice machine? If yes, the ice machine will automatically restart when power
is restored.
3. Is the curtain open because some ice is stuck under it? If so, remove the ice and the machine should start
in a few minutes.
4. Check the adjustment knob of the ice level control. See page 21.
Note: Curtain can be removed & replaced anytime the machine is in a standby mode or when it is in a freeze
cycle. However, removal of the curtain during freeze will result in water owing into the bin. Removal of the
curtain during harvest terminates harvest at that point and, if left off, will result in the machine shutting off.
To Manually Reset the machine.
1. Open the switch door.
2. Push and release the Off button.
3. Push and release the On button.
To Shut the Machine Off:
1. Push and hold the Off button for 3 seconds
or until the machine stops.
June 2017
Page 25
Page 26
EH222 E and Condensing Unit
Remote Low Side Cuber User Manual
EH222 Schematic Diagram
June 2018
Page 26
Page 27
EH222 E and Condensing Unit
Remote Low Side Cuber User Manual
EH222 Wiring Diagram
June 2018
Page 27
Page 28
EH222 E and Condensing Unit
Remote Low Side Cuber User Manual
ECC Three Phase Schematic Diagram
June 2018
Page 28
Page 29
EH222 E and Condensing Unit
Remote Low Side Cuber User Manual
ECC Three Phase Wiring Diagram
June 2018
Page 29
Page 30
EH222 E and Condensing Unit
Remote Low Side Cuber User Manual
ECC Single Phase Schematic Diagram
June 2018
Page 30
Page 31
EH222 E and Condensing Unit
Remote Low Side Cuber User Manual
ECC Single Phase Wiring Diagram
June 2018
Page 31
Page 32