Scotsman C0522, C0530 User Manual

Prodigy Series Modular Cuber
Technical Service Manual
Models C0322, C0522, C0330, C0530, C0630, C0830, C1030, C1448, C1848 and C2148
also includes CB0522, CB0330, CB0530, CB0630, CB0830 and CB1030
Introduction
This technical manual covers the Prodigy line, excluding the Eclipse remote low side models. All models except Eclipse are shipped with an Installation and User's manual, which can be referred to separately. General installation information is included in this manual.
Table of Contents
Model Number Description ......... page 2
Water ....................page 3
General Installation - Air or Water Cooled . page 4
Water purge setting ............ page 8
General Installation - Remote ....... page 9
Pre-Charged Tubing Coupling Connections page 17
Adjustments ................ page 20
Prodigy Cuber System Information..... page 21
Controller Information ........... page 22
How It Works - Air Cooled ......... page 24
How It Works - Water Cooled ....... page 25
How It Works - Remote........... page 26
Electrical Sequence - Air or Water Cooled. page 27
Electrical Sequence - Remote Cooled . . . page 29
Diagnostics - Water Cooled ........ page 47
Low ice Making Capacity - Water Cooled . page 50
Makes Excessive Noise - Water Cooled . . page 51
Diagnostics - Remote Air Cooled ..... page 52
Low Ice Making Capacity - Remote .... page 55
Makes Excessive Noise - Remote ..... page 56
Test Procedures - Sensors......... page 57
Ice Thickness Sensor ........... page 58
Water Level Sensor ............ page 59
Temperature Sensors ........... page 60
Test Procedures - Loads .......... page 61
Compressor Electrical Chart ........ page 62
Refrigerant Charges ............ page 63
Test Procedures - Loads .......... page 64
Remote Schematics ............ page 31
Electrical Component Details ....... page 32
Refrigeration ................page 35
Water System ............... page 36
Control Operation ............. page 37
Control Safeties .............. page 38
Restarts................... page 39
Control Button Use (from standby) ..... page 40
Control Button Use - continued ...... page 41
Diagnostics – Air Cooled .......... page 42
Low Ice Making Capacity - Air Cooled . . . page 45
Makes Excessive Noise - Air Cooled.... page 46
May 2011 Page 1
Technical Information
Heat Load & Condenser Water GPM . . . page 73
Controller Differences ........... page 74
Thermistor Values ............. page 75
Performance Data ............. page 76
Performance Data - Remotes ....... page 86
Wiring Diagrams .............. page 94
Repair Procedures ............. page 107
Refrigeration Removal and Replacement Procedures
.......................page 115
Optional add-on control information .... page 120
........... page 72
Model Number Description
Example:
C0530SA-1C
C= cuber. CB = Prodigy Advanced Sustainability Cuber
05= nominal ice capacity in 100s of pounds
30= nominal width of cabinet. Other sizes are 22 and 48.
S= Cube size. S=small or half dice cube. M=medium or full dice cube
A=Condenser type. A=air cooled. W=water cooled. R = Remote
-1=Electrical code. -1=115 volts. -32=208-230 single phase. -3=208-230 three phase.
-6=230 50 Hz
C=Series revision code. C=third series
Note: In some areas of this manual model numbers may include only the first five characters of the model number, meaning that the cube size, condenser type and voltage differences are not critical to the information listed there.
Scotsman reserves the right to make design changes and/or improvements at any time. Specifications and design are subject to change without notice.
September 2011 Page 2
Water
The quality of the water supplied to the ice machine will have an impact on the time between cleanings and ultimately on the life of the product. There are two ways water can contain impurities: in suspension or in solution. Suspended solids can be filtered out. In solution or dissolved solids cannot be filtered, they must be diluted or treated. Water filters are recommended to remove suspended solids. Some filters have treatment in them for suspended solids. Check with a water treatment service for a recommendation.
RO water. This machine can be supplied with Reverse Osmosis water, but the water conductivity must be no less than 10 microSiemens/cm.
Potential for Airborne Contamination
Installing an ice machine near a source of yeast or similar material can result in the need for more frequent sanitation cleanings due to the tendency of these materials to contaminate the machine. Most water filters remove chlorine from the water supply to the machine which contributes to this situation. Testing has shown that using a filter that does not remove chlorine, such as the Scotsman Aqua Patrol, will greatly improve this situation, while the ice making process itself will remove the chlorine from the ice, resulting in no taste or odor impact. Additionally, devices intended to enhance ice machine sanitation, such as the Scotsman Aqua Bullet, can be placed in the machine to keep it cleaner between manual cleanings.
Water Purge
Cube ice machines use more water than what ends up in the bin as ice. While most water is used during ice making, a portion is designed to be drained out every cycle to reduce the amount of hard water scale in the machine. That’s known as water purge, and an effective purge can increase the time between needed water system cleaning.
In addition, this product has the capability to automatically vary the amount of water purgeed based on the purity of the water supplied to it. The water purge rate can also be set manually. Adjustments of purge due to local water conditions are not covered by warranty.
September 2006 Page 3
General Installation - Air or Water Cooled
Location Limitations:
The product is designed to be installed indoors, in a controlled environment. Air cooled models discharge very warm air into the room out the back. Space must be allowed at the left side and back for air intake and discharge. Water cooled models discharge warm water into the building’s drain. Space needs to be provided on both sides and above for service access.
Space Limitations
Note: Although the machine will function, ice capacity of air cooled machines will be significantly reduced with minimal clearance at the sides, back and top. Some space is recommended for service and maintenance purposes on all models.
6" of space at the sides and back are required for adequate operation. To get the most capacity, locate the machine away from heat producing appliances and heating ducts.
22 and 30 inch wide models: Airflow is in the left side, out the back (as viewed from the front).
48 inch wide models: Air flow is in the front and left side and out the back.
Environmental Limitations
Minimum Maximum
o
Air temperature 50
Water temperature 40
F. 100oF.
o
F. 100oF.
Water pressure 20 psi 80 psi
Power supply – acceptable voltage ranges
Minimum Maximum
115 volt model 104 volts 126 volts
208-230 volt model 198 volts 253 volts
Warranty Information
The warranty statement for this product is provided separately from this manual. Refer to it for applicable coverage. In general warranty covers defects in material or workmanship. It does not cover maintenance, corrections to installations, or situations when the machine is operated in circumstances that exceed the limitations printed above.
September 2006 Page 4
General Installation - Air or Water Cooled
Plumbing Requirements
All models require connection to cold, potable water. A hand actuated valve within site of the machine is required. Air cooled models have a single 3/8” FPT inlet water connection; a 3/8” FPT to 3/8” male flare adapter is supplied with the machine and can be used if desired.
Water cooled models have the same inlet fitting plus an additional 3/8” FPT condenser inlet water connection.
Water Filters
If connecting to water filtration, filter only the water to the reservoir, not to the condenser. Install a new cartridge if the filters were used with a prior machine.
All models require drain tubing to be attached to them. Air cooled models have a single ¾” FPT drain fitting in the back of the cabinet. Water cooled models have the same fitting plus an additional ½” FPT drain fitting in the back of the cabinet.
Install new tubing when replacing a prior ice machine, as the tubing will have been sized for the old model and might not be correct for this one.
Note: This NSF listed model has a 1" anti-back flow air gap between the water inlet tube end and the highest possible reservoir water level, no back flow device is required for the potable water inlet.
Drain Tubing:
Use rigid drain tubes and route them separately – do not Tee into the bin’s drain and, if water cooled, do not Tee the condenser drain into the reservoir or bin drain.
Vent the reservoir drain. A vertical vent at the back of the drain, extended about 8 – 10” will allow the gravity drain to empty and also keep any surges during draining from discharging water out the vent..
Horizontal runs of drain tubing need a ¼” fall per foot of run for proper draining.
Follow all applicable codes.
September 2006 Page 5
General Installation - Air or Water Cooled
Electrical
See the spec sheet or User's Manual for Minimum Circuit Ampacity or Maximum Fuse Size ratings.
The machine is not supplied with a power cord, one must either be field installed or the machine hard-wired.
The dataplate on the back of the cabinet details the power requirements, including voltage, phase, minimum circuit ampacity and maximum fuse size. HACR type circuit breakers may be used in place of fuses. Extension cords are not permitted. Use of a licensed electrician is recommended.
Electrical connections are made inside the junction box in the back panel of the ice machine.
Follow all applicable local, state and national codes.
September 2006 Page 6
General Installation - Air or Water Cooled
Note: Indentations may be deeper on C0322 and C0330
Adjustments
Ice Bridge Thickness
Caution: Do not make the bridge too thin or the machine will not harvest properly. Bridge thickness adjustments are not covered by warranty.
Shut machine off.
Access the ice thickness sensor.
Too Big
Check gap between metal tip and evaporator grid. Small cube standard gap is 3/16 inch, medium cube standard gap is 7/32 inch. To set, place a 3/16" (small cube) or 7/32" (medium cube) drill bit between sensor tip and evaporator to check. Adjust gap using adjustment screw.
Ice Bridge Thickness Measurement
Adjustment Screw
1/8" indentation
1/8-3/16"
bridge
Just Right
Too Small
Restart unit and check ice bridge. Repeat as needed.
Evaporator
Ice Thickness Sensor
Gap
Ice Thickness Sensor Adjustment
Gap
Side View of Evaporator and Ice Thickness
Sensor
September 2006 Page 7
Water purge setting
The water purge is factory set to the Automatic setting. The setting can be changed to one of 5 manual settings or placed on automatic. The purge setting shows in the Code Display.
purge setting
Water Type
To set:
Switch the machine OFF by holding the Off button in until a number or the letter A shows on the display.
Press and release the On button repeatedly until the number on the display corresponds to the desired setting.
Press and release the Off switch again to return to the normal control state.
1­Minimum
RO water or equivalent, TDS less than 35
2­Moderate3-Standard
Low TDS non-RO water
Setting for typical water
4­Heavy
High TDS water
5­Maximum
Very high TDS water, greater than 256
A - Automatic
Any with conductivity not less than 10 microSiemens/ cm
September 2006 Page 8
General Installation - Remote
Location Limitations
This ice system is made up of three parts, the ice making machine, or head; the remote condenser; and the interconnecting tubing. The ice making machine must be installed indoors, in a controlled environment. Space must be provided near the machine for service access. The remote condenser may be installed above or below the ice machine, per the limits stated later in this manual. The remote condenser may be installed outdoors within the temperature limits listed below. The interconnecting tubing must be installed per the directions stated in this manual, and the amount of tubing exposed to uncontrolled temperatures must be minimized.
Space Limitations
Although the machine will function with no clearance to the top and sides, some space must be allowed for service access. Building the machine in with no access will cause higher service cost, in many cases this extra cost may not be covered by warranty.
Environmental Limitations, ice machine:
Minimum Maximum
o
Air temperature 50
Water temperature 40
F. 100oF.
o
F. 100oF.
Water Pressure 20 psi 80 psi
Environmental Limitations, remote condenser
Minimum Maximum
o
Air temperature -20
F. 120oF.
Power Supply
Minimum Maximum
115 volt model 104 volts 126 volts
208-230 volt model 198 volts 253 volts
Warranty Information
The warranty statement for this product is provided separately from this manual. Refer to it for applicable coverage. In general warranty covers defects in material and workmanship. It does not cover maintenance, corrections to installations, or situations when the ice machine is operated in circumstances that exceed the limitations printed above.
September 2006 Page 9
General Installation - Remote
Product Description and Electrical Requirements
- See spec sheet or User's Manual for Minimum Circuit Ampacity or Maximum Fuse SIze
Dimensions w”xd”xh”
22 x 24 x 23 C0522SR-1 115/60/1 ERC111-1
same same same ERC211-1**
30 x 24 x 23 C0530SR-1 115/60/1 ERC111-1
same same same ERC211-1**
same C0630SR-32 208-230/60/1 ERC311-32
30 x 24 x 29 C0830SR-32 208-230/60/1 ERC311-32
same C0830SR-3 208-230/60/3 ERC311-32
same C1030SR-32 208-230/60/1 ERC311-32
same C1030SR-3 208-230/60/3 ERC311-32
48 x 24 x 29 C1448SR-32 208-230/60/1 ERC311-32
same C1448SR-3 208-230/60/3 ERC311-32
same C1848SR-32 208-230/60/1 ERC611-32
Model Electrical Use condenser
same C1848SR-3 208-230/60/3 ERC611-32
same C2148SR-32 208-230/60/1 ERC611-32
same C2148SR-3 208-230/60/3 ERC611-32
** ERC211 has two circuits, when two C0522s or C0530s are connected to it, fan motor relay kit KCMR120 must be used to control the fan motor.
Ratings include the remote condenser motor, as it is designed to be powered by the ice machine. If connecting remote condenser independently of the ice machine, use the information on the condenser's dataplate for fuse and wire sizes.
Table notes: Medium cube models have the same electrical characteristics as Small. Series revision code omitted. All the listed condensers include a headmaster valve.
September 2006 Page 10
General Installation - Remote
Central Condenser Coils
The ice machine may be connected to a central condenser coil. The requirements are:
Coil – not previously used with mineral oil system. Virgin coil preferred.
Correct size (internal volume) and capacity (BTUH).
Includes a headmaster valve for discharge pressure control. Headmaster kit available for
certain MAC condensers, kit number is Fan motor on all the time or controlled to be on whenever the ice machine is operating.
Non-Scotsman condensers must have prior Scotsman Engineering approval for warranty
coverage to be in effect.
Precharged tubing kits:
The ice making head’s and the remote condenser’s refrigeration circuits must be connected. They are designed to be connected using precharged refrigerant tubing, supplied in kits of liquid and discharge tubes. Several lengths are available, order the one that just exceeds the length needed for the site.
RCKCME6GX.
10” 25’ 40’ 75’
RTE10 RTE25 RTE40 RTE75
No additional refrigerant is required. Note: Refrigerant charge is supplied with the ice machine.
January 2009 Page 11
General Installation - Remote
Water
The quality of the water supplied to the ice machine will have an impact on the time between cleanings and ultimately on the life of the product. There are two ways water can contain impurities: in suspension or in solution. Suspended solids can be filtered out. In solution or dissolved solids cannot be filtered, they must be diluted or treated. Water filters are recommended to remove suspended solids. Some filters have treatment in them for suspended solids. Check with a water treatment service for a recommendation.
RO water. This machine can be supplied with Reverse Osmosis water, but the
conductivity must be no less than 10 microSiemens/cm.
Potential for Airborne Contamination
Installing an ice machine near a source of yeast or similar material can result in the need for more frequent sanitation cleanings due to the tendency of these materials to contaminate the machine. Most water filters remove chlorine from the water supply to the machine which contributes to this situation. Testing has shown that using a filter that does not remove chlorine, such as the Scotsman Aqua Patrol, will greatly improve this situation, while the ice making process itself will remove the chlorine from the ice, resulting in no taste or odor impact. Additionally, devices intended to enhance ice machine sanitation, such as the Scotsman Aqua Bullet, can be placed in the machine to keep it cleaner between manual cleanings.
Water purge
Cube ice machines use more water than what ends up in the bin as ice. While most water is used during ice making, a portion is designed to be drained out every cycle to reduce the amount of hard water scale in the machine. That’s known as water purge, and an effective purge can increase the time between needed water system cleaning.
water
In addition, this product is designed to automatically vary the amount of water purged based on the purity of the water supplied to it. The water purge rate can also be set manually. Adjustments of purge due to local water conditions are not covered by warranty.
September 2006 Page 12
General Installation - Remote
Remote Condenser Location
Use the following for planning the placement of the condenser relative to the ice machine - see illustration on the following page.
Location Limits - condenser location must not exceed ANY of the following limits:
Maximum rise from the ice machine to the condenser is 35 physical feet
Maximum drop from the ice machine to the condenser is 15 physical feet
Physical line set maximum length is 100 feet.
Calculated line set length maximum is 150.
Calculation Formula:
Drop = dd x 6.6 (dd = distance in feet)
Rise = rd x 1.7 (rd = distance in feet)
Horizontal Run = hd x 1 (hd = distance in feet)
Calculation: Drop(s) + Rise(s) + Horizontal Run = dd+rd+hd = Calculated Line Length
Configurations that do NOT meet these requirements must receive prior written authorization from Scotsman.
Do NOT:
Route a line set that rises, then falls, then rises.
Route a line set that falls, then rises, then falls.
Calculation Example 1:
The condenser is to be located 5 feet below the ice machine and then 20 feet away horizontally.
5 feet x 6.6 = 33. 33 + 20 = 53. This location would be acceptable
Calculation Example 2:
The condenser is to be located 35 feet above and then 100 feet away horizontally. 35 x 1.7 =
59.5. 59.5 +100 = 159.5. 159.5 is greater than the 150 maximum and is NOT acceptable.
Operating a machine with an unacceptable configuration is misuse and will void the warranty.
September 2006 Page 13
General Installation - Remote
22.87"
17.15"
40.35"
For The Installer: Remote Condenser
Locate the condenser as near as possible to the interior location of the ice machine.
Note: The location of the condenser is relative to the ice machine is LIMITED by the specification on the prior page.
Meet all applicable building codes.
Roof Attachment
Install and attach the remote condenser to the roof of the building, using the methods and practices of construction that conform to the local building codes, including having a roofing contractor secure the condenser to the roof.
rd
dd
Max
35'
Max
15'
Remote Condenser Locate ABOVE
Remote Condenser Locate BELOW
hd
Condenser Distance & Location
September 2006 Page 14
General Installation - Remote
Precharged Line Routing
Do not connect the precharged tubing until all routing and forming of the tubing is complete. See the Coupling Instructions for final connections.
1. Each set of pre-charged tubing lines contains a 3/8” diameter liquid line, and a 1/2” diameter discharge line. Both ends of each line have quick connect couplings, the end without access valves goes to the ice maker.
Note: The openings in the building ceiling or wall, listed in the next step, are the minimum sizes recommended for passing the refrigerant lines through.
2. Have the roofing contractor cut a minimum hole for the refrigerant lines of 1 3/4”. Check local codes, a separate hole may be required for the electrical power supply to the condenser.
Caution: Do NOT kink the refrigerant tubing while routing it.
3. Route the refrigerant tubes thru the roof opening. Follow straight line routing whenever possible. Excess tubing may EITHER be coiled up INSIDE the building OR cut out prior to connection to the ice maker and condenser.
If the excess tubing is cut out, after re-brazing the tubing must be evacuated prior to connection to the ice maker or condenser.
Note brazing requires a nitrogen purge.
If the excess tubing is to be coiled, spiral it horizontally to avoid excess trapping in the lines.
5. Have the roofing contractor seal the holes in the roof per local codes
September 2006 Page 15
General Installation - Remote
Coupling Instructions
The couplings on the ends of the pre-charged line sets are self-sealing when installed properly. Follow these instructions carefully.
These steps must be performed by an EPA Certified Type II or higher technician.
Initial Connections
1. Remove the protector caps and plugs. Wipe the seats and threaded surfaces with a clean cloth to remove any possible foreign matter.
2. Lubricate the inside of the couplings, especially the O-rings, with refrigerant oil.
3. Position the fittings on the correct connections on the condenser and ice machine.
The 1/2" discharge line (schrader valve end) goes to the remote condenser fitting marked “discharge line”.
The 3/8" liquid line (schrader valve end) goes to the remote condenser fitting marked “liquid line”.
The 1/2" discharge line goes to the ice maker fitting marked “discharge line”.
The 3/8" liquid line goes to the ice maker fitting marked “liquid line”.
Final Connections:
4a. Begin by tightening the couplings together by hand until it is certain that the threads are properly engaged.
4b. Then using two wrenches tighten the coupling until it bottoms out or a definite increase in resistance is felt.
It is important that ONLY the nut on the pre-charged tube be turned, or the diaphragms will be torn out by the piercing knives and they will be loose in the refrigeration system. Note: As the couplings are tightened, the diaphragms in the quick connect couplings will begin to be pierced. As that happens, there will be some resistance to tightening the swivel nut.
4c. Continue tightening the swivel nut until it bottoms out or a very definite increase in resistance is felt (no threads should be showing).
5. Use a marker or pen to mark a line on the coupling nut and unit panel. Then tighten the coupling nut an additional one-quarter turn. The line will show the amount that the nut turns. Do NOT over tighten.
6. After all connections have been made, and after the receiver valve has been opened (open at Initial Start Up), check the couplings for leaks.
September 2006 Page 16
Pre-Charged Tubing Coupling Connections
Inspect couplings, wipe clean and lubricate both parts with polyolester refrigerant oil.
Hand tighten to be sure threads are properly engaged.
Use two wrenches and continue tightening the couplings. As the diaphragms being to pierce, the couplings will be harder to turn. Be sure only the swivel nut is rotated.
Continue tightening until the swivel nut feels like it is tight, then go to the next step. No threads will be seen when the couplings are tight.
After the swivel nut feels like it is tight, mark the nut and the panel. Then tighten one quarter turn more. That ensures that there is a brass-to-brass joint inside the coupling.
September 2006 Page 17
General Installation - Remote
Plumbing Requirements
All models require connection to cold, potable water. A hand actuated valve within site of the machine is required. There is a single 3/8” FPT inlet water connection, a 3/8” FPT to 3/8” male flare adapter is supplied with the machine and can be used if desired.
Water Filters
Install a new cartridge if the filters were used with a prior machine.
All models require drain tubing to be attached to them. There is a single ¾” FPT drain fitting in the back of the cabinet.
Install new tubing when replacing a prior ice machine, as the tubing will have been sized for the old model and might not be correct for this one.
Connect water supply to water inlet fitting.
Note: This NSF listed model has a 1" anti-back flow air gap between the potable water inlet tube end and the highest possible reservoir water level, no back flow device is required.
Connect drain tubing to drain fitting.
Route the drain tubing to building drain. Follow local codes for drain air gap.
Use rigid drain tubes and route them separately – do not Tee into the bin’s drain.
Vent the reservoir drain. A vertical vent at the back of the drain, extended about 8 – 10” will allow the gravity drain to empty and also keep any surges during draining from discharging water.
Horizontal runs of drain tubing need a ¼” per fall per foot of run for proper draining.
Follow all applicable codes.
September 2006 Page 18
General Installation - Remote
Electrical
The machine is not supplied with a power cord, one must either be field installed or the machine hard-wired.
The dataplate on the back of the cabinet details the power requirements, including voltage, phase, minimum circuit ampacity and maximum fuse size. HACR type circuit breakers may be used in place of fuses. Extension cords are not permitted. Use of a licensed electrician is recommended.
The ice maker is designed to operate on its own electrical circuit and must be individually fused. Voltage variation must not exceed the limits listed earlier.
The remote condenser is designed to be powered from the ice machine. A separate knockout hole has been provided in the ice maker electrical junction box.
Electrical connections are made inside the junction box in the back panel of the ice machine.
Remove the junction box cover and route the power cord through the access hole and properly attach the power supply wires to the leads in the junction box.
Attach the remote condenser fan motor wires to the wires in the junction box tagged “fan motor leads”.
Install field supplied strain reliefs per code. Attach a ground wire to the ground connection in the junction box.
Check voltage when complete.
Return the junction box cover to its original position and secure with the original screws.
Follow all applicable local, state and national codes.
September 2006 Page 19
Adjustments
Bridge Thickness - For the Service Tech Only
Adjustment
Push and hold Off till the machine stops.
Access ice thickness sensor.
Check gap between metal tip and evaporator grid. Small cube standard gap is 3/16 inch, medium cube standard gap is 7/32 inch. To set, place a 3/16" (small cube) or 7/32" (medium cube) drill bit between sensor tip and evaporator to check. Adjust gap using adjustment screw.
Restart unit and check ice bridge. Repeat as needed
Caution: Do not make the bridge too thin or the machine will not harvest properly. Bridge thickness adjustments are not covered by warranty.
Screw
Gap
Water purge setting
The water purge is factory set to Automatic. The setting can be changed to one of 5 manual settings or left on automatic.
purge setting
Water Type
To set:
Switch the machine OFF by holding the Off button in until a number or the letter A shows on the display.
Press and release the On button repeatedly until the number on the display corresponds to the desired setting.
1­Minimum
RO water or equivalent, TDS less than 35
2­Moderate3-Standard
Low TDS non-RO water
Setting for typical water
4­Heavy
High TDS water
5­Maximum
Very hHigh TDS water, greater than 256
A - Automatic
Any with conductivity not less than 10 microSiemens/ cm
Press and release the Off switch again to return to the normal control state.
September 2006 Page 20
Prodigy Cuber System Information
Overall System Type:
Refrigeration: Mechanical, either air cooled, water cooled or remote cooled.
Water System: Inlet water solenoid valve fills reservoir once per cycle. Purge solenoid
valve opens to discharge some reservoir water once per cycle. Control System: Electronic
Harvest cycle sensor: Conductivity probe
Water full/empty sensor: Conductivity probe
Bin Control: Curtain Switch
Ice type: Unified
Harvest system: Hot gas defrost with mechanical assist
Electrical Components:
Compressor
Contactor
Water Pump
Inlet Water Solenoid Valve
Purge or purge Valve
Fan Motor(s)
Fan motor pressure control
High pressure cut out – certain AC models only
Harvest Assist Solenoid(s)
Hot Gas Valve(s)
Controller
Transformer – 12v AC for the controller only
Water Level Sensor
Ice Thickness Sensor
Curtain Switch(es)
September 2006 Page 21
Controller Information
Machine Indicator Lights
Power
Status
Water
Clean
Code Display
Main codes - automatically displayed
F .......Freeze Cycle
F flashes . . Freeze Cycle is Pending
H .......Harvest Cycle
H flashes . . Manual Harvest
b .......BinisFull
C .......Clean Cycle
L .......Board Locked
d .......Test Mode
O .......Off
E .......Self Test Failed
1 flashes . . Max Freeze - Retrying
1 .......MaxFreeze Time Shut Down
2 flashes . . Max Harvest - Retrying
2 .......MaxHarvest Time Shut Down
3 .......Slow Water Fill
4 .......High Discharge Temp
5 .......Sump Temp Sensor Failure
7 .......Discharge Temp Sensor Failure
8 flashes . . Short Freeze - Retrying
8 .......Short Freeze - Thin ice
Setting Codes - requires push button sequence
Change De-Scale Notification Interval ­This feature is accessible only from standby (Status Light Off).
1. Press and hold harvest button for 3 seconds.
This starts the Time to Clean Adjustment Mode and displays the current time to clean setting.
2. Press the clean button repeatedly to cycle through the 4 settings:
Water Purge Settings
A, 1, 2, 3, 4, 5
De-Scale notification
- see table to the right
Prior Effective 11/6/08
3 months 1 year
4 months 0 or disabled
5 months 4 months
6 months (default) 6 months (default)
3. Push Off to confirm the selection.
November 2008 Page 22
Controller Information
Component Indicator Lights
Condenser Fan / Aux (Aux = liquid line solenoid when a remote condenser model)
Water Pump
Purge Valve
Water Solenoid
Hot Gas
Compressor
Ready to Harvest
Sump Empty
Sump Full
Curtain SW1
Curtain SW2
Component Indicator Lights
September 2006 Page 23
How It Works - Air Cooled
Freeze Cycle. At start up the controller drains and refills the reservoir. The reservoir refills
when the mid length water level sensor probe is uncovered and continues to fill until the top probe is in contact with water. When the reservoir has filled, the compressor and water pump start. After the discharge pressure has increased past the cut in point of the fan pressure control, the fan motor(s) will begin to operate and warm air will be discharged out the back of the cabinet. The fan motor will switch on and off as the discharge pressure rises and falls. Water flows over the evaporator as the refrigeration system begins to remove heat. When the water temperature falls to a preset point, as measured by the water temperature sensor, the controller shuts off the water pump for 30 seconds. The freeze cycle resumes when the pump restarts and ice begins to form on the evaporator. As it forms, the water flowing over the ice moves closer and closer to the metal tip of the ice thickness sensor. When it comes into contact with the sensor for a few continuous seconds, that signals the controller that the freeze cycle is complete.
The controller may shut the air cooled fan motor off for a variable period of time to build up heat for harvest. This is dependant upon the temperature of the discharge line sensor.
Harvest Cycle. When the harvest cycle begins, the controller shuts off the fan motor, switches on the hot gas valve, and through a parallel circuit, the harvest assist solenoid. After a few seconds the purge valve opens and water is drained from the reservoir. Based on either the automatic purge or manual purge setting, the pump and purge valve will be switched off at a time determined to have drained enough water for that setting. The inlet water valve will open to fill the reservoir anytime the mid length probe is uncovered, which occurs during the reservoir drain cycle. Harvest continues as the hot discharge gas flows into the evaporator serpentine, heating up the evaporator. At the same time the harvest assist solenoid is pushing against the back of the ice slab. When the ice releases from the evaporator, it harvests as a unit, and the harvest assist probe provides some additional force to push it off. When the ice falls off it will force the curtain(s) open. An open curtain during the harvest cycle signals the controller that the evaporator has released its ice. If this is a single evaporator machine the controller will terminate harvest. If it is a two evaporator machine, the controller will continue harvest until both curtains have opened. If one curtain remains open, the controller will shut the machine down on bin full. Anytime harvest is complete the hot gas valve and harvest assist solenoid are shut off. The harvest assist solenoid pin returns to its normal position by spring pressure.
If the curtain(s) re-close after harvest, the freeze cycle will restart.
September 2006 Page 24
How It Works - Water Cooled
Freeze Cycle. At start up the controller drains and refills the reservoir. The reservoir refills
when the mid length water level sensor probe is uncovered and continues to fill until the top probe is in contact with water. When the reservoir has filled, the compressor and water pump start. After the discharge pressure has increased past the set point of the water regulating valve, the water regulating valve will open and warm water will be discharged out the condenser drain. The water regulating valve will modulate to maintain a relatively constant discharge pressure. Water flows over the evaporator as the refrigeration system begins to remove heat. When the water temperature falls to a preset point, as measured by the water temperature sensor, the controller shuts off the water pump for 30 seconds. The freeze cycle resumes when the pump restarts and ice begins to form on the evaporator. As it forms, the water flowing over the ice moves closer and closer to the metal tip of the ice thickness sensor. When it comes into contact with the sensor for a few continuous seconds, that signals the controller that the freeze cycle is complete.
Harvest Cycle. When the harvest cycle begins, the controller switches on the hot gas valve, and through a parallel circuit, the harvest assist solenoid. After a few seconds the purge valve opens and water is drained from the reservoir. Based on either the automatic purge or manual purge setting, the pump and purge valve will be switched off at a time determined to have drained enough water for that setting. The inlet water valve will open to fill the reservoir anytime the mid length probe is uncovered, which occurs during the reservoir drain cycle. Harvest continues as the hot discharge gas flows into the evaporator serpentine, heating up the evaporator. At the same time the harvest assist solenoid is pushing against the back of the ice slab. When the ice releases from the evaporator, it harvests as a unit, and the harvest assist probe provides some additional force to push it off. When the ice falls off it will force the curtain(s) open. An open curtain during the harvest cycle signals the controller that the evaporator has released its ice. If this is a single evaporator machine the controller will terminate harvest. If it is a two evaporator machine, the controller will continue harvest until both curtains have opened. If a curtain remains open, the controller will shut the machine down on bin full. Anytime harvest is complete the hot gas valve and harvest assist solenoid are shut off. The harvest assist solenoid pin returns to its normal position by spring pressure.
If the curtain(s) re-close after harvest, the freeze cycle will restart.
January 2010 Page 25
How It Works - Remote
Freeze Cycle. At start up the controller drains and refills the reservoir. The reservoir refills
when the mid length water level sensor probe is uncovered and continues to fill until the top probe is in contact with water. When the reservoir has filled, the liquid line valve, compressor and water pump are switched on. After the discharge pressure has increased past the set point of the headmaster in the condenser, the headmaster will direct refrigerant gas into the condenser and warm air will be discharged out of the condenser. The headmaster will modulate to maintain a minimum discharge pressure. Water flows over the evaporator as the refrigeration system begins to remove heat. When the water temperature falls to a preset point, as measured by the water temperature sensor, the controller shuts off the water pump for 30 seconds. The freeze cycle resumes when the pump restarts and ice begins to form on the evaporator. As it forms, the water flowing over the ice moves closer and closer to the metal tip of the ice thickness sensor. When it comes into contact with the sensor for a few continuous seconds, that signals the controller that the freeze cycle is complete.
Harvest Cycle. When the harvest cycle begins, the controller switches on the hot gas valve, and through a parallel circuit, the harvest assist solenoid. After a few seconds the purge valve opens and water is drained from the reservoir. Based on either the automatic purge or manual purge setting, the pump and purge valve will be switched off at a time determined to have drained enough water for that setting. The inlet water valve will open to fill the reservoir anytime the mid length probe is uncovered, which occurs during the reservoir drain cycle. Harvest continues as the hot discharge gas flows into the evaporator serpentine, heating up the evaporator. At the same time the harvest assist solenoid is pushing against the back of the ice slab. When the ice releases from the evaporator, it harvests as a unit, and the harvest assist probe provides some additional force to push it off. When the ice falls off it will force the curtain(s) open. An open curtain during the harvest cycle signals the controller that the evaporator has released its ice. If this is a single evaporator machine the controller will terminate harvest. If it is a two evaporator machine, the controller will continue harvest until both curtains have opened. If a curtain remains open, the controller will shut the machine down. Anytime harvest is complete the hot gas valve and harvest assist solenoid are shut off. The harvest assist solenoid pin returns to its normal position by spring pressure.
If the curtain(s) re-close after harvest, the freeze cycle will restart.
Shut down occurs when a curtain remains open after a harvest cycle. The controller will switch off the liquid line solenoid valve and operate the compressor for 30 seconds, then shut it off.
November 2006 Page 26
Electrical Sequence - Air or Water Cooled
Power connected, unit previously switched Off.
Control board does a self check. If the self check fails, the unit displays an E and no further action will occur.
If the self check passes, the controller will display a 0, the curtain light(s) will be ON and the Power and Sump Empty lights will be ON.
Pushing and releasing the On button will start the ice making process.
The display will begin to blink F. The component indicator lights will switch on and off to match the following process:
The purge valve opens and the water pump starts to empty the reservoir. This is done to discharge any excess water from ice melting into the reservoir.
The hot gas valve and the harvest assist solenoid are energized.
The inlet water valve will open to fill the reservoir. The water valve can open any time the water level is low.
After a few seconds the purge valve closes and the pump shuts off.
When the reservoir is full the inlet water valve stops and the compressor switches on. Five seconds after the compressor starts the hot gas valve and the harvest assist solenoid are de-energized.
Light Information: The display shows a non-blinking F. The Power and Status Lights will be Green. The compressor, fan motor, water pump, sump full and one or two curtain switch lights will be ON.
The air cooled model's fan motor will start to turn when the discharge pressure has built up to the fan pressure control's cut in point. This is about 15 seconds after the compressor starts.
The Freeze cycle continues. The compressor, water pump, fan motor and curtain indicator lights will be ON. When the reservoir water temperature falls to a certain preset point, the water pump will shut off for 30 seconds. This is the anti-slush period. At this time the controller checks the conductivity of the water in the reservoir for the auto-purge feature. After the water pump restarts the Sump Full light will go out and neither sump lights will be on for the rest of the freeze cycle.
When the ice has built up enough so that the water flowing over the evaporator comes into continuous contact with the ice level sensor, the Ready to Harvest light will begin to blink on and off. When it has been On continuously for 5 seconds, the controller will switch the machine into a Harvest cycle.
September 2006 Page 27
Electrical Sequence - Air or Water Cooled
Indicator Information: The display shows a non-blinking H. The Power and Status Lights will be Green. The compressor, hot gas valve and one or two curtain switch lights will be ON. After a few seconds the water pump, purge valve and inlet water valve lights will come on.
The fan motor(s) shut off and remain off throughout the harvest cycle.
The harvest assist solenoid is connected in parallel with the hot gas valve. Although it is energized throughout the harvest cycle, its piston does not move until the ice has become partially loosened from the evaporator plate by the action of the hot refrigerant gas passing through the evaporator serpentine.
The water pump and purge valve will shut off when the purge level setting time has been reached, either the manual time or the automatic time. The inlet water valve will remain on until it fills the reservoir. The Ready to Harvest light will switch Off when the ice falls from the evaporator.
Harvest continues until the ice slab is ejected from the evaporator and falls, opening the curtain. When the curtain opens, the magnetic reed curtain switch opens, breaking the circuit to the controller. If the curtain re-closes within 30 seconds, the controller switches the machine back into another freeze cycle. If the curtain switch remains open, the controller shuts the machine down and puts it into a standby position.
September 2006 Page 28
Electrical Sequence - Remote Cooled
Power connected, unit previously switched Off.
Control board does a self check. If the self check fails, the unit displays an E and no further action will occur.
If the self check passes, the controller will display a 0, the curtain light(s) will be ON and the Power and Sump Empty lights will be ON.
Pushing and releasing the On button will start the ice making process.
The display will begin to blink F. The component indicator lights will switch on and off to match the following process:
The purge valve opens and the water pump starts to empty the reservoir. This is done to discharge any excess water from ice melting into the reservoir.
The hot gas valve and the harvest assist solenoid are energized.
The inlet water valve will open to fill the reservoir. The water valve can open any time the water level is low.
After a few seconds the purge valve closes and the pump shuts off.
When the reservoir is full the inlet water valve stops, the liquid line valve is opened and the compressor switches on. Five seconds after the compressor starts the hot gas valve and the harvest assist solenoid are de-energized.
Light Information: The display shows a non-blinking F. The Power and Status Lights will be Green. The compressor, fan motor, water pump, sump full and one or two curtain switch lights will be ON.
The Freeze cycle continues. When the reservoir water temperature falls to a certain preset point, the water pump will shut off for 30 seconds. This is the anti-slush period. At this time the controller checks the conductivity of the water in the reservoir for the auto-purge feature. After the water pump restarts the Sump Full light will go out and neither sump lights will be on for the rest of the freeze cycle.
When the ice has built up enough so that the water flowing over the evaporator comes into continuous contact with the ice level sensor, the Ready to Harvest light will begin to blink on and off. When it has been On continuously for 3 seconds, the controller will switch the machine into a Harvest cycle.
Indicator Information: The display shows a non-blinking H. The Power and Status Lights will be Green. The compressor, hot gas valve and one or two curtain switch lights will be ON. After a few seconds the water pump, purge valve and inlet water valve lights will come on.
September 2006 Page 29
Electrical Sequence - Remote Cooled
The harvest assist solenoid is connected in parallel with the hot gas valve. Although it is energized throughout the harvest cycle, its piston does not move until the ice has become partially loosened from the evaporator plate by the action of the hot refrigerant gas passing through the evaporator serpentine.
The remote condenser fan motor is powered by the compressor contactor, so it will be operating during the harvest cycle.
The water pump and purge valve will shut off when the purge level setting time has been reached, either the manual time or the automatic time. The inlet water valve will remain on until it fills the reservoir. The Ready to Harvest light will switch Off when the ice falls from the evaporator.
Harvest continues until the ice slab is ejected from the evaporator and falls, opening the curtain. When the curtain opens, the magnetic reed curtain switch opens, breaking the circuit to the controller. If the curtain re-closes within 30 seconds, the controller switches the machine back into another freeze cycle. If the curtain switch remains open, the controller shuts the machine down and puts it into a standby position.
September 2006 Page 30
Remote Schematics
Receiver
Evaporator
Compressor
Remote Condenser
Hot Gas
Valve
Suction
Discharge Line
Head Pressure Control Valve
Heat
Exchange
TXV
Liquid Line Valve
Receiver
Compressor
Remote Condenser
Hot Gas
Valv e
Hot Gas
Valv e
Discharge Line
Accumulator
Head Pressure Control Valv e
Heat
Exchange
Evaporator
Suction
TXV
Evaporator
Suction
TXV
Liquid Line Valve
C0522R, C0530R, C0630R and C1030R
C1448R, C1848R and C2148R
September 2006 Page 31
Electrical Component Details
Compressor
Operated by the compressor contactor. Single phase self contained models have PTCR
and run capacitor.
Contactor
Operated by the controller and the high pressure cut out switch. Line voltage coil. When
energized the Compressor indicator light will be ON.
Water Pump
Operated by the controller. When energized, the Water Pump indicator light will be ON.
Inlet Water Solenoid Valve
Operated by the controller. Line voltage coil. When energized, the Water Solenoid
indicator light will be ON.
Purge Valve
Operated by the controller. Line voltage coil. When energized, the Purge Valve indicator light will be ON. Energized for a time during harvest.
Fan Motor(s)
Operated by the controller and the fan pressure control. Can cycle on and off in the freeze cycle, always off during harvest. When the controller has energized it, the indicator light will be ON but the fan will not turn unless the discharge pressure is high enough to close the high pressure control.
Fan(s) may shut off near the end of the freeze cycle to build up heat for harvest. Time of shut off depends upon available heat, as measured by the discharge temperature.
High pressure cut out
Some air cooled and all remote and all water cooled models have a high pressure cut out switch that shuts the power off to the compressor contactor if the discharge pressure is too high. It is an automatic reset.
Harvest Assist Solenoid(s)
Operated by the controller in parallel with the hot gas valve. Cycles on and off at the beginning of a restart. Energized throughout the harvest cycle. Line voltage coil.
September 2006 Page 32
Electrical Component Details
Liquid Line Valve
Remote only. Opened by the controller to start a freeze cycle. Closed to shut unit off. Line
voltage coil.
Hot Gas Valve(s)
Operated by the controller in parallel with the harvest assist solenoid. Cycles on and off at
the beginning of a restart. Energized throughout the harvest cycle. Line voltage coil.
Controller
Senses ice thickness, water level, water temperature, discharge temperature. Controls
compressor contactor, fan motor, water pump, inlet water valve, hot gas valve, purge valve, harvest assist solenoid. Indicates status and component operation. 12 volt.
Transformer
12 volt secondary, supplies power to controller only.
Water Level Sensor
Three probe conductivity sensor. Bottom probe is common, mid probe is refill sump, top probe is full sump. Refill can occur at any time.
Ice Thickness Sensor
Single wire conductivity sensor. Circuit made from controller to ground to controller when water contacts a probe suspended over ice plate. Signals ready for harvest.
Curtain Switch(es)
Magnetic reed switch. Normally open, switch is closed when magnet is nearby. Models with two evaporators have two curtain switches. Single switch can be connected to either J8 or J7 of controller. Curtains may be removed in the freeze cycle without affecting controller harvest and shut the unit off. Two curtain models require both curtains to open to terminate harvest, and if either one remains open for 30 seconds that signals the controller to shut the unit off on bin full.
Water temperature sensor.
operation. A curtain removed during harvest will cause the controller to terminate
Thermistor inserted into the water pump discharge hose. Reported temperature used by the controller to determine anti-slush cycle start time.
January 2010 Page 33
Electrical Component Details
Discharge temperature sensor.
Thermistor attached to the discharge line near the compressor. Reported temperature
used by the controller to determine end-of-cycle-fan-off-delay time. If discharge temperature exceeds a preset maximum, controller will shut the machine off.
Note: Controller will operate machine in a default mode with thermistors disconnected from the controller. Diagnostic code #5 or 7 will be displayed during that time.
Component Indicator Light Table
System Indicator Light ON
Condenser Fan or Liquid Line Valve
Water Pump Pump Motor Powered
Purge Valve Purge Valve Opens
Inlet Water Solenoid Valve Inlet Water Valve Opens
Hot Gas Hot Gas Valve Opens
Compressor Contactor Contactor Closes
Ready to Harvest Water contacting ice thickness sensor probe
Sump Empty Open between mid sensor and common
Sump Full Closed between top probe and mid probe
Curtain Switch Curtain open
Fan Motor Powered or LLV open
Component Indicator Lights
September 2006 Page 34
Refrigeration
Refrigerant: R-404A
Compressors: Copeland or Tecumseh hermetic by model
Expansion valves: Non adjustable, internally equalized, one per evaporator.
Hot gas valves: Pilot operated, line voltage coils. One per plate.
Condensers: Forced draft air, counterflow water. All air cooled models have left side air inlet.
48” wide air cooled models also have front air inlet. All air cooled models exhaust air out the back.
Air filters: Surface mounted to panels. Filter media removable without removing panels.
Fan blades: Reduced vibration blades in most air cooled models.
Remote Systems: Head pressure control valves in condenser. No check valves. Headmaster
protected by filters (not filter driers). Controller pumps unit down by closing the liquid line valve and keeping the compressor on for a fixed time period at shut down.
Fan pressure control. All AC. Controls fan motor operation in the freeze cycle.
High pressure cut out. WC, RC, AC with Tecumseh compressors.
Evaporator: Unified cell plate. Nickel plated copper. Three heights: 6”, 12” and 18”. Small
cube = half dice, medium cube = full dice.
Small cube: 7/8" high x 7/8" deep x 3/8" high
Medium cube: 7/8" high x 7/8" deep x 7/8" high
September 2006 Page 35
Water System
Batch type. Insulated water reservoir contains full water charge for each ice making cycle.
Water valve: Solenoid type. Opens to fill reservoir when mid sensor probe no longer makes a
circuit to the bottom probe. Closes when reservoir is full and top probe makes circuit to mid probe.
Pump: Unsealed pedestal type, twist-release mounting
Water purge valve: Solenoid type. Opens to purge water during harvest cycle.
Water Level Sensor: Three probe conductivity.
Distributor: ABS plastic. Evenly distributes water over the evaporator surface. Slides off the
evaporator top. Removable cover for ease of cleaning.
Water Distributor Removal
September 2006 Page 36
Control Operation
Standard control:
Electronic controller operating from a 12 AC volt power supply. Will operate within a
voltage range between 10 and 15.5. User’s Indicator lights, four front visible: Power, Status, Water, De-scale/Sanitize.
Accessible On switch.
Accessible Off switch.
Code Display: Displays letters and numbers to indicate cycles and diagnostic codes.
Manual Harvest switch: Use to trigger harvest at any time.
Clean switch: Use to initiate and finish the de-scale or sanitizing cycles.
Component Operation Indicator Lights: Indicate the status of certain components; water
level; ready for harvest; curtain switch position. Power Light: On when power is being supplied to the controller.
Status Light: Green when machine is in ice making mode and is operating correctly. Blinks
red when a machine malfunction has been detected.
Water Light: Blinks red when reservoir does not fill with allowed time period.
De-scale / sanitize: Yellow when the controller has determined it is time to de-scale and
sanitize the machine. Use clean process to reset light. Time is determined by power up time and controller's setting. Standard setting is 6 months. See adjustment process
Controller Connections:
J1 – Ground and Power Supply
J2 – High voltage power harness to loads
J3 – Factory use
J4 – Optional board connector
J5 - Communications port
J6 – Thermistor connection
J7 – Curtain switch
J8 – Curtain switch
J9 – Water level sensor
J10 – Ice thickness sensor
J11 – Bin thermostat. Use with NO thermostat (closes on temperature fall) & specified harness.
September 2006 Page 37
Control Safeties
Max freeze time – 45 minutes
When exceeded, the controller will attempt another freeze cycle. If the next cycle's freeze time is less than maximum, the control will continue normal ice making. If the next freeze cycle was too long, the control will again attempt another freeze cycle. If the freeze cycle is too long three consecutive cycles, the controller will shut the unit off and it must be manually reset.
Min freeze time – 6 minutes
If the controller switches the machine into harvest within 20 seconds of the minimum freeze time, the controller will harvest for a preset time and does not stop if the curtain switch opens. If this occurs again in the next three cycles, the machine will shut down and must be manually reset.
Max harvest time – 3.5 minutes
If the harvest cycle has continued for 3.5 minutes without the curtain opening, the controller will shut the machine off for 50 minutes and then restart. If there is another the machine will shut the machine off for another 50 minutes and then restart. If it fails a third consecutive time the controller will shut the machine down and must be manually reset.
Time between resets – 50 minutes
Number of automatic resets – 2
Max water fill time – 5 minutes. Machine will attempt a restart every 20 minutes.
Max discharge temp – 250 degrees F.
Time interval between cleanings – 6 months power on time - adjustable in one month
increments, can be set at 6, 5, 4 or 3 months of power up time.
Manual harvest time – 3 minutes
Pump down interval – remote only. 12 hours. Pump down is 30 seconds of compressor only on time.
Minimum compressor off time – 4 minutes
Continuous Run Time Maximum Cycles - 200
October 2006 Page 38
Restarts
Power Interruption
The controller will automatically restart the ice machine after adequate voltage has been restored.
H blinks on code display
Status indicator light blinks
Reservoir is drained and refilled
Default harvest is initiated. The curtain switch does not have to open to terminate harvest, harvest will continue until the default harvest time expires. Default harvest time is 3 minutes. The machine will then return to a normal freeze cycle.
Water Interruption
The controller will attempt to fill the reservoir every twenty minutes until it is successful.
On-Off Switch Access
All models ship with the On and Off switches front accessible. If desired, the On and Off switches can be covered by changing the bezel in the front panel’s trim strip. A cover-up bezel ships loose with the machine.
September 2006 Page 39
Control Button Use (from standby)
Set purge level, 1-5 (1 is minimum, 5 is maximum) or Automatic:
Hold off button in for 3 seconds. Release.
Press and release the On button to cycle through and select one of the five purge settings
or to use the Automatic setting.
Recall diagnostic code:
Hold off button in for 3 seconds. Release.
Press and release the Harvest button to cycle through each of the last 10 error codes from
most recent to oldest.
Clear diagnostic code:
Hold Clean and Harvest buttons in for 3 seconds to clear all prior codes.
Reset control:
Depress and release Off, then depress and release On
Start Test Mode:
Hold Off button in for 3 seconds. Release.
Hold Clean button in for 3 seconds. Release.
Lock / Unlock control:
Hold On button in for 3 seconds, keep holding then press and release Off twice.
Empty reservoir:
Hold Clean button in for 3 seconds. Release. Pump and purge valve will be ON for 30 seconds. Repeat as needed.
Test Mode: See next page for Air and Water Cooled mode.
Depress Off for 3 seconds, release. Then depress Clean for 3 seconds.
The sump will fill the first 30 seconds of the test. If the sump is full it will overflow into the bin. At 30 seconds the WIV will shut off and the WP will turn on. You will be able to see and hear the water running over the plates. After 10 seconds the PV and HGV will turn on. Water will be purging from the machine. After 10 more seconds the compressor will start. 5 seconds later the HGV will close. The compressor will run for a total of 20 seconds. After which everything will turn off for 5 seconds. After that time the HGV will open and you’ll be able to hear the hissing as the pressure is equalized. 10 seconds later the fan will turn on (if air cooled and fan control jumped). After 10 seconds all will be off and the output test will be complete.
September 2006 Page 40
Control Button Use - continued
Change De-Scale Notification Interval
Like the others, this feature is accessible only from standby (Status Light Off).
1. Press and hold harvest button for 3 seconds.
Starts the Time to Clean Adjustment State and displays the current time to clean setting.
2. Press the clean button repeatedly to cycle through the 4 possible settings:
Rev 5 and up (10/08 production start)
1 year (8760 hours)
0 (disabled)
4 months (2920 hrs)
6 months (4380 hours) (default)
Prior
6 months
5 months
4 months
3 months
3. Press Off or leave untouched for 60 seconds to select the displayed interval
Test Mode Sequence Table - Air or Water Cooled
Time (seconds) On Off
0 WIV - 30 seconds WP, HGV, Comp, Fan, PV
30 WP - 10 seconds WIV, HGV, Comp, Fan, PV
40 WP, PV, HGV - 10 seconds WIV, Comp, Fan
50 HGV, Comp - 5 seconds WIV, WP, Fan, PV
55 Comp - 15 seconds WIV, HGV, WP, Fan, PV
70 None - 5 seconds All
75 HGV - 10 seconds WIV, WP, Comp, Fan, PV
85 Fan - 10 seconds WIV, HGV, WP, Comp, PV
95 None All – Test Complete
October 2008 Page 41
Diagnostics – Air Cooled
No ice
Problem Likely Cause Probable Solution
No power to unit Power disconnected
No power to controller Transformer open Replace transformer
Shut down on maximum water fill time
Water shut off Restore water supply
Water leak
Air filters clogged Clean air filters
Dirty condenser Clean condenser
Restricted location, intake air too hot
Ice thickness sensor dirty or disconnected
Water distributor dirty
Check breaker or fuse. Reset or replace, restart and check
Check purge valve, curtain, sump, pump hose
Have machine moved
Check ice thickness sensor probe
Remove and clean water distributor
Shut down on maximum freeze time
Inlet water valve leaks through during freeze
Connected to hot water
Incomplete harvest Check harvest system
High pressure cut out opened
Fan motor pressure control open
Fan motor not turning
Water pump not pumping
Check inlet water valve
Check for bleed thru from / missing check valve in building water supply
Check fan motor pressure control, check fan motor, check controller using test mode
Check fan pressure control
Check fan motor, check fan blade, check controller using test mode
Check pump motor, check controller using test mode
September 2006 Page 42
Diagnostics – Air Cooled
Problem Likely Cause Probable Solution
Pump hose disconnected Check hose
Check compressor contactor, check controller using test mode
Check compressor start
Shut down on maximum freeze time
Compressor not operating
Low refrigerant charge
components, check PTCR resistance and temperature
Check compressor voltage
Check compressor windings
Add some refrigerant and restart unit. If cycle time improves, look for leak.
Hot gas valve leaks through during freeze
Thermostatic expansion valve bulb loose
Thermostatic expansion valve producing very low or very high superheat
Compressor inefficient
Check hot gas valve for hot outlet during freeze
Check bulb
Check evaporator superheat, change TXV if incorrect
Check compressor amp draw, if low and all else is correct, change compressor
September 2006 Page 43
Diagnostics – Air Cooled
Problem Likely Cause Probable Solution
Shut down on maximum harvest time
Ice bridge thickness too small, not enough ice to open curtain
Ice bridge thickness too large, ice frozen to evaporator frame
Purge valve does not open, water melts ice bridge, not enough ice to open curtain
Incomplete ice formation
Curtain out of position
Curtain switch does not open when curtain does
Machine in very cold ambient
Hot gas valve does not open
Check and adjust if needed
Check and adjust if needed
Check purge valve
Check water distributor for partially plugged holes
Check curtain for swing restriction
Check switch with ohmmeter
Move machine to a warmer location
Check hot gas valve, check controller using test mode
Shut down on minimum freeze time
Harvest assist probe out of position – ejector pin not retracted
Damaged evaporator Check evaporator surface
Fan motor stays on during harvest
Grounded ice thickness sensor
Check harvest assist mechanism – spring should retract pin
Check controller using test mode
Check sensor for dirt and position. Clean and check gap to evaporator surface.
September 2006 Page 44
Low Ice Making Capacity - Air Cooled
Problem Likely Cause Probable Solution
Dirty air filters Clean filters
Dirty condenser Clean condenser
Hot ambient Reduce room air temperature
Long freeze cycle
Long Harvest Cycle
Water leak
Water inlet valve leaks through Check inlet valve
Low on refrigerant
Incorrect superheat
Fan(s) cycle on and off
Dirty evaporator De-scale water system
No harvest assist Check harvest assist solenoid
Bridge thickness too big
Machine in very cool ambient Increase room temperature
Check purge valve, check curtain
Add refrigerant, if cycle time drops, check for leak
Check evaporator superheat, if significantly low or high, replace TXV
Check pressures fans cycle at. Replace fan pressure switch if too low
Check and adjust bridge thickness
False bin full signal
Ice jammed in between curtain and sump
Curtain does not close correctly Check curtain for proper swing
September 2006 Page 45
Clear ice away
Makes Excessive Noise - Air Cooled
Problem Likely Cause Probable Solution
Blade is bent Replace fan blade
Fan blade vibrates
Fan motor mount is broken Replace motor mount
Compressor vibrates Mounting bolts loose Tighten bolts
Water pump vibrates Pump bearings worn Replace pump
Panels vibrate Mounting screws loose Tighten screws
September 2006 Page 46
Diagnostics - Water Cooled
No Ice
Problem Likely Cause Probable Solution
No power to unit Power disconnected
No power to controller Transformer open Replace transformer
Shut down on maximum water fill time
Water shut off Restore water supply
Water leak
Ice thickness sensor dirty or disconnected
Water distributor dirty
Inlet water valve leaks through during freeze
Connected to hot water
Check breaker or fuse. Reset or replace, restart and check
Check purge valve, curtain, sump, pump hose
Check ice thickness sensor probe
Remove and clean water distributor
Check inlet water valve
Check for bleed thru from / missing check valve in building water supply
Shut down on maximum freeze time
Incomplete harvest Check harvest system
High pressure cut out opened
Water pump not pumping
Pump hose disconnected Check hose
Compressor not operating
Water supply cut off, restore water supply to condenser
Check pump motor, check controller using test mode
Check compressor contactor, check controller using test mode
Check compressor start components, check PTCR resistance and temperature
Check compressor voltage
Check compressor windings
September 2006 Page 47
Diagnostics - Water Cooled
Problem Likely Cause Probable Solution
Add some refrigerant and
Low refrigerant charge
restart unit. If cycle time improves, look for leak.
Shut down on maximum freeze time
Hot gas valve leaks through during freeze
Thermostatic expansion valve bulb loose
Thermostatic expansion valve producing very low or very high superheat
Compressor inefficient
Ice bridge thickness too small, not enough ice to open curtain
Ice bridge thickness too large, ice frozen to evaporator frame
Purge valve does not open, water melts ice bridge, not enough ice to open curtain
Check hot gas valve for hot outlet during freeze
Check bulb
Check evaporator superheat, change TXV if incorrect
Check compressor amp draw, if low and all else is correct, change compressor
Check and adjust if needed
Check and adjust if needed
Check purge valve
Shut down on maximum harvest time
Incomplete ice formation
Curtain out of position
Curtain switch does not open when curtain does
Machine in very cold ambient
Hot gas valve does not open
Harvest assist probe out of position – ejector pin not retracted
Damaged evaporator
September 2006 Page 48
Check water distributor for partially plugged holes
Check curtain for swing restriction
Check switch with ohmmeter
Move machine to a warmer location
Check hot gas valve, check controller using test mode
Check harvest assist mechanism – spring should retract pin
Check evaporator surface
Diagnostics - Water Cooled
Problem Likely Cause Probable Solution
Shut down on minimum freeze time
Test Mode Sequence: - Air or Water Cooled
Time (seconds) On Off
0 WIV - 30 seconds WP, HGV, Comp, Fan, PV
30 WP - 10 seconds WIV, HGV, Comp, Fan, PV
40 WP, PV, HGV - 10 seconds WIV, Comp, Fan
50 HGV, Comp - 5 seconds WIV, WP, Fan, PV
55 Comp - 15 seconds WIV, HGV, WP, Fan, PV
70 None - 5 seconds All
75 HGV - 10 seconds WIV, WP, Comp, Fan, PV
Grounded ice thickness sensor
Check sensor for dirt and position. Clean and check gap.
85 Fan - 10 seconds WIV, HGV, WP, Comp, PV
95 None All – Test Complete
September 2006 Page 49
Low ice Making Capacity - Water Cooled
Problem Likely Cause Probable Solution
Long freeze cycle
Long Harvest Cycle
False bin full signal
Water leak
Water inlet valve leaks through Check inlet valve
Low on refrigerant
Incorrect superheat
Dirty evaporator De-scale water system
No harvest assist Check harvest assist solenoid
Bridge thickness too big
Machine in very cool ambient Increase room temperature
Ice jammed in between curtain and sump
Curtain does not close correctly Check curtain for proper swing
Check purge valve, check curtain
Add refrigerant, if cycle time drops, check for leak
Check evaporator superheat, if significantly low or high, replace TXV
Check and adjust bridge thickness
Clear ice away
September 2006 Page 50
Makes Excessive Noise - Water Cooled
Problem Likely Cause Probable Solution
Compressor vibrates Mounting bolts loose Tighten bolts
Water pump vibrates Pump bearings worn Replace pump
Panels vibrate Mounting screws loose Tighten screws
September 2006 Page 51
Diagnostics - Remote Air Cooled
No Ice
Problem Likely Cause Probable Solution
No power to unit Power disconnected
No power to controller Transformer open Replace transformer
Shut down on max. water fill time
Water shut off Restore water supply
Water leak
Dirty condenser Clean condenser
Restricted location, intake air too hot
Ice thickness sensor dirty or disconnected
Water distributor dirty
Inlet water valve leaks through during freeze
Check breaker or fuse. Reset or replace, restart and check
Check purge valve, curtain, sump, pump hose
Have condenser moved
Check ice thickness sensor probe
Remove and clean water distributor
Check inlet water valve
Shut down on maximum freeze time
Check for bleed thru from /
Connected to hot water
Incomplete harvest Check harvest system
High pressure cut out opened
Fan motor not turning
Water pump not pumping
Pump hose disconnected Check hose
Liquid line valve does not open
Compressor not operating
missing check valve in building water supply
Check check fan motor
Check quick connects for complete piercing
Check fan motor, check fan blade
Check pump motor, check controller using test mode
Check coil of valve, check controller using test mode.
Check compressor contactor, check controller using test mode
September 2006 Page 52
Diagnostics - Remote Air Cooled
Problem Likely Cause Probable Solution
Check compressor start
components, check PTCR Compressor not operating (continued)
Low refrigerant charge
resistance and temperature
Check compressor voltage
Check compressor windings
Add some refrigerant and
restart unit. If cycle time
improves, look for leak.
Shut Down on Maximum Freeze Time (continued)
Hot gas valve leaks through during freeze
Thermostatic expansion valve bulb loose
Thermostatic expansion valve producing very low or very high superheat
Compressor inefficient
Debris in refrigeration system
Ice bridge thickness too small, not enough ice to open curtain
Check hot gas valve for hot
outlet during freeze
Check bulb
Check evaporator superheat,
change TXV if incorrect
Check compressor amp draw,
if low and all else is correct,
change compressor
Recover charge. Open quick
connects, check for loose or
missing foil. Open liquid line
and hot gas valves. Check for
debris.
Replace drier, evacuate and
weigh in nameplate charge.
Check and adjust if needed
Shut down on maximum harvest time
Ice bridge thickness too large, ice frozen to evaporator frame
Purge valve does not open, water melts ice bridge, not enough ice to open curtain
Incomplete ice formation
Curtain out of position
September 2006 Page 53
Check and adjust if needed
Check purge valve
Check water distributor for
partially plugged holes
Check curtain for swing
restriction
Diagnostics - Remote Air Cooled
Problem Likely Cause Probable Solution
Shut down on maximum harvest time (continued)
Shut down on minimum freeze time
Curtain switch does not open when curtain does
Machine in very cold ambient
Hot gas valve does not open
Harvest assist probe out of position – ejector pin not retracted
Damaged evaporator Check evaporator surface
Grounded ice thickness sensor
Check switch with ohmmeter
Move machine to a warmer
location
Check hot gas valve, check
controller using test mode
Check harvest assist
mechanism – spring should
retract pin
Check sensor for dirt and
position. Clean and adjust gap
to evaporator surface using
13/64” drill bit as a gauge
September 2006 Page 54
Low Ice Making Capacity - Remote
Problem Likely Cause Probable Solution
Dirty condenser Clean condenser
Hot ambient Check condenser inlet temp.
Long freeze cycle
Long Harvest Cycle
Water leak
Water inlet valve leaks through Check inlet valve
Low on refrigerant
Incorrect superheat
Fan(s) cycle on and off
Dirty evaporator De-scale water system
No harvest assist Check harvest assist solenoid
Bridge thickness too big
Machine in very cool ambient Increase room temperature
Check purge valve, check curtain
Add refrigerant, if cycle time drops, check for leak
Check evaporator superheat, if significantly low or high, replace TXV
Check pressures fans cycle at. Replace fan pressure switch if too low
Check and adjust bridge thickness
False bin full signal
Ice jammed in between curtain and sump
Curtain does not close correctly Check curtain for proper swing
Clear ice away
September 2006 Page 55
Makes Excessive Noise - Remote
Problem Likely Cause Probable Solution
Blade is bent Replace fan blade
Fan blade vibrates
Fan motor mount is broken Replace motor mount
Compressor vibrates Mounting bolts loose Tighten bolts
Water pump vibrates Pump bearings worn Replace pump
Panels vibrate Mounting screws loose Tighten screws
Test Mode Sequence - Remote
Test Time (seconds) On Off
0 WIV - 30 seconds WP, HGV, Comp, BV, PV
30 WP - 10 seconds WIV, HGV, Comp, BV, PV
40
50 HGV, Comp - 5 seconds WIV, WP, BV, PV
55 Comp - 15 seconds WIV, HGV, BV, WP, PV
70 None - 5 seconds All
75 HGV - 5 seconds WIV, WP, Comp, BV, PV
80 BV - 5 seconds WIV, HGV, WP, Comp, PV
85 None All – Test Complete
WP, PV, HGV - 10 seconds
WIV, Comp, BV
September 2006 Page 56
Test Procedures - Sensors
All electrical components in this ice machine can be diagnosed with a volt-ohmmeter.
Curtain Switch:
1. Test using the controller’s indicator lights. Observe SW1 and SW2. Open and close the curtain in question. When the curtain is opened, the SW light will be ON. When the curtain gets to within a half inch of closing (at the switch) the SW light will go OUT.
2. Test with an ohmmeter. Disconnect electrical power. Open the control box cover. Unplug the curtain switch lead from the controller. Connect an ohmmeter to the leads of the switch. Open and close the curtain. When the curtain is closed, the switch is closed and there will be continuity. When the curtain is open, the switch is open and the circuit will be open.
3. Test the controller’s curtain switch circuit by jumping the connectors on J1 or J2 together. Reconnect electrical power. When jumped, the matching SW light will go out. When unplugged or open, the SW light will be ON.
Curtain Switch Indicator Lights
Light is ON when curtain is OPEN
Single curtain models have one indicator light ON all the time.
Curtain Switch
September 2006 Page 57
Ice Thickness Sensor
1. Test using the controller’s indicator light. Observe the Ready To Harvest light. Shut the machine off. Use a wire to connect the metal part of the Ice Thickness sensor to the evaporator or simply remove the Ice Thickness Sensor and touch its metal surface to the metal control box wall. The Ready for Harvest light should go ON.
2. Test with an Ohmmeter. Disconnect electrical power. Open the control box cover. Unplug the ice thickness sensor lead from the controller. Connect an ohmmeter lead to the ice thickness sensor lead, touch the other ohmmeter lead to the ice machine chassis. There must be an open circuit. If there is continuity, the sensor must be replaced. If there is no continuity, touch the ohmmeter lead to the metal part of the ice thickness sensor. There should be continuity. If open, check the ice thickness sensor for scale build up. Clean and recheck. If still open, replace the ice thickness sensor.
3. Test the controller’s ice thickness sensor circuit by connecting a wire from J10 to ground. Reconnect electrical power. The Ready for Harvest light should go ON.
Ready To Harvest light is ON when water contacts ice thickness sensor.
Ice Thickness Sensor
September 2006 Page 58
Water Level Sensor
1. Test using the controller’s indicator lights (sump empty and sump full). Unit must be powered up and there must be water in the sump. Add some manually if needed. Locate water level sensor. Release from sump cover and slowly lift up until the mid-length probe is out of the water. The sump empty light should come on, and if the unit is on the inlet water solenoid valve will open to fill the reservoir. Return the water level sensor to its normal position. If the unit is on and calling for ice the water will fill until the top probe is in contact with it, at that time the sump full light will switch ON.
2. Test with an ohmmeter. Disconnect electrical power. Open the control box cover. Unplug the connector at J9. Locate water level sensor and remove it from the sump cover. Test 1: Place one lead of the ohmmeter on the longest probe and the other on the controller end of the red wire, there should be continuity. Test 2: Place one lead on the controller end of the white wire and the other on the mid-length probe, there should be continuity. Test 3: Place on lead on the controller end of the black wire and the other on the shortest probe, there should be continuity. If not, clean the probes and recheck.
3. Test the controller’s water level sensor circuit. Reconnect electrical power. Unplug harness from water level sensor, the sump empty light should be ON. Jump harness wires white and black. The sump full light should be ON. Jump harness wires white and red, the sump full and sump empty lights will be OFF. Check harness wire by wire for continuity if there is no reaction from the controller during this test.
Sump Empty Light
Sump Full Light
December 2008 Page 59
Temperature Sensors
1. Check controller. If the sensor calibration is completely out of range, the code display will read either 5 or 7.
2. Check with an ohmmeter. Open control box cover, unplug sensor from J6. Water temperature probe: Measure the temperature of the water. Push and release the clean button. Wait one minute. Measure the resistance of the water probe (two leads next to the open socket) and compare to the resistance in the chart for that temperature. Any reading within 1000 ohms is acceptable. Discharge sensor: Measure the temperature of the discharge line as close to the sensor as possible. Measure the resistance of the discharge temperature sensor (two leads farthest away from the open socket on the harness connector) and compare to the resistance in the chart for that temperature. Any reading within 1000 ohms is acceptable.
3. Alternate procedure: Remove both water and discharge sensors from their places on the ice machine. Put both into a container of ice water. Put a thermometer in the water. When the thermometer is at 32 degrees F., check the resistance of each sensor. The resistance should be within 1000 ohms of 32649.
Water Temperature Sensor Set
Discharge Temperature Sensor Set
Back of Controller
September 2006 Page 60
Test Procedures - Loads
Compressor
Failure to start.
Single phase models. All have resistance start, capacitor run type motors. Check voltage to compressor at the contactor. Compare the idle voltage (compressor off) to the active voltage (compressor starting). The supply voltage must not be less than the lowest rated voltage for the ice machine. If the voltage is correct, proceed to the next step.
Check starting components. Most models use a PTCR to cut power to the start winding after the compressor has started. Check the PTCR for resistance. The resistance check must be when the PTCR is at room temperature – any temperature between 50 and 100.
At that temperature resistance should be very low between 25 and 50 ohms. Also check resistance to ground, it should be infinite. If the PTCR is good, check the compressor windings.
Measure resistance from Common to ground. It should be infinite. Measure resistance from Common to Run – compare to the chart. Measure resistance from Common to Start – compare to the chart.
Compressor check for high amp draw. Measure amp draw of starting circuit. If it does not drop off immediately after start up, the PTCR should be replaced. It is not practical to check a PTCR for resistance at high temperatures as the resistance drops very fast as the PTCR’s temperature falls. If the compressor is drawing excessive amps but is operating, the run capacitor may be open. Disconnect electrical power, discharge the capacitor and measure its resistance. If open, replace it. If shorted to ground, replace it.
Any time the compressor is replaced, the PTCR and run capacitor should also be replaced, or if the model was equipped with a potential relay, start capacitor and run capacitor, those should be replaced with the compressor. Most Scotsman service compressors include those parts.
Some systems use a potential start relay and start capacitor in place of the PTCR.
Potential relay. If the compressor will not start, check the amp draw of the starting circuit. If very low, the potential relay contacts or start capacitor may be open. Measure the resistance of the potential relay contacts and the start capacitor. If either is open it should be replaced. If the compressor starts but draws very high amps from the starting circuit, the potential relay may not switch off. In that case the relay should be replaced.
September 2006 Page 61
Compressor Electrical Chart
Resistance reading tolerance is +- 10%
Ice Machine Voltage/Hz/Phase Compressor
C0330-1 115/60/1 AKA9438ZXA 4.22 .59
C0330-6 230/50 AKA9438ZXC 7.11 2.69
C0330-32 208-230/60/1 AKA9468ZXD 10.43 1.77
C0530-1 A or B 115/60/1 AKA9451ZXA 5.95 .69
C0530-6 A or B 230/50 AKA9451ZXC 7.11 2.69
C0530-32 A or B 208-230/60/1 AKA9451ZXD 10.43 1.77
C0530 -1 C 115/60/1 RST45C1E-CAA
C0530-6C 230/50/1 RST45C1E-CAB
C0530 - 32 C 208-230/60/1 RST45C1E-CAV
C0630-32 208-230/60/1 AJA7490ZXD 2.74 1.52
C0630-6 230/50 AJA7490ZXC 2.23 2.02
C0830-32 208-230/60/1 CS10K6EPFV 3.10 1.16
C0830-6 230/50 CS10K6EPFJ 3.79 1.39
C0830-3 208-230/60/3 CS10K6ETF5 - 1.77
C1030-32 208-230/60/1 CS12K6EPFV 3.10 1.16
Start Winding Ohms
Run Winding Ohms
C1030-6 230/50 CS12K6EPFJ 3.79 1.39
C1030-3 208-230/60/3 CS12K6ETF5 - 1.77
C1448-32 208-230/60/1 CS14K6EPFV 2.66 1.08
C1448-6 230/50 CS14KSEPFJ 2.64 1.4
C1448-3 208-230/60/3 CS14K6ETF5 - -
C1848-32 208-230/60/1 CS20K6EPFV 2.37 .65
C1848-6 230/50 CS20K6EPFZ
C1848-3 208-230/60/3 CS20K6ETF5 - -
C2148-32 WC 208-230/60/1 CS24K6EPFV 2.35 .53
C2148-6 WC 230/50 CS24K6EPFZ
C2148-3 WC 208-230/60/3 CS24K6ETF5 - -
C2148-32 R 208-230/60/1 CS27K6EPFV 2.35 .53
C2148-6 R 230/50 CS27K6EPFZ
C2148-32 R 208-230/60/3 CS27K6ETF5 - -
May 2011 Page 62
Refrigerant Charges
Model R-404A in ounces
C0322A 14
C0322W 11
C0330A 14
C0330W 11
C0522A 17
C0522W 14
C0522R 160
C0530A (A or B series) 22
C0530A C series 21
C0530W (A thru C series) 11
C0530R (A thru C series) 160
C0630A 36
C0630W 14
C0630R 160
C0830A 46
C0830W 34
C0830R 208
C1030A 48
C1030W 38
C1030R 208
C1448A 62
C1448W 56
C1448R 256
C1848A 62
C1848W 63
C1848R 320
C2148W 69
C2148R 320
May 2011 Page 63
Test Procedures - Loads
Fan motor
1. Test using the controller’s indicator lights.
Note: Fan pressure control connection must be jumped to perform this test.
Put the controller into test mode (depress Off for 3 seconds then depress Clean for 3 seconds). At the end of the test cycle, the fan motor will be powered and the Condenser Fan motor indicator light will be on. The fan motor should start and run at that time. If it does not, repeat the test but check the voltage to the fan motor, it must receive full voltage at the fan motor lead connection at the end of the test. If there is voltage and the motor does not operate, replace the motor. If there is no voltage, check the controller high voltage harness connection. The fan motor lead is the top wire. Check voltage from it to ground, at the end of the test, when the fan motor indicator light is On, there must be voltage from this pin to ground. Note: high voltage power is supplied to the bottom pin from the contactor line. Refer to the machine wiring diagram as needed.
2. Test using an ohmmeter. Disconnect electrical power. Unplug fan motor from harness. Measure fan motor winding resistance. If open, replace the fan motor.
This light is ON when the fan motor should be in operation.
September 2006 Page 64
Fan Pressure Control
must CLOSE to operate
fan motor.
Test Procedures - Loads
Water Pump
1. Test using the controller’s indicator lights. Check the indicator light during the freeze cycle. The light will be On for all but the 30 second anti-slush period, so observe the light for one minute. When it is On, check the water pump, it should be operating. If not, check voltage to the pump. If low check the voltage from the controller to ground. The water pump pin is number 6. If there is voltage at that pin to ground, but very low voltage at the pump motor, there must be a broken wire in the harness. If the voltage is low at pin 6, the controller should be replaced.
2. Test using an ohmmeter. Disconnect electrical power. Unplug the water pump motor leads from the harness. Measure the resistance of the motor windings. If open, replace the pump. Measure resistance to ground. If there is any, replace the pump.
Water pump light is ON when pump is in operation.
September 2006 Page 65
Test Procedures - Loads
Purge valve
1. Test using the controller’s indicator lights. Shut unit off by holding the Off button for 3 seconds. Wait four minutes. Push and release the On button, observe the Purge Valve indicator light. As the unit drains the reservoir, the purge valve will be powered. When it gets power, the indicator light will be ON. If the purge valve does not open to drain the reservoir when its indicator light is on, do a voltage check. Shut the unit down by holding the Off button in for 3 seconds. Unplug the harness connection from the purge valve. Wait four minutes. Push and release the On button to restart the machine. As the unit drains the reservoir, the purge valve connection should receive full voltage. If it does, the purge valve should be replaced. If there is no voltage, check voltage from the controller to ground. The purge valve pin is 3 (dump valve on wiring diagram). If there is voltage from that pin to ground, but low voltage at the valve harness connection, the harness has a broken wire or poor connection and must be replaced. If the voltage to ground is low, the controller should be replaced.
Note: The coil of this valve is internally rectified, and will normally show infinite resistance when tested with an ohmmeter.
This light will be ON when the Purge Valve is in operation.
September 2006 Page 66
Test Procedures - Loads
Compressor contactor
1. Test using the controller’s indicator lights. When the unit is in ice making mode the compressor contactor will have power. Check the Compressor indicator light, when it is on the compressor contactor will have pulled in. If it is not, do a voltage check. Place voltmeter leads on the coil of the contactor. There should be full voltage . If there is full voltage present and the contactor has not pulled in, replace the contactor. If there is no voltage check if the high pressure cut out is open. If the high pressure cut out is closed, check for voltage from the controller to ground. The contactor pin is 4. Check from 4 to ground when the compressor indicator light is on. There should be voltage. If not, replace the controller. If there is voltage at the controller but not at the contactor coil, the harness wires or connectors are damaged and must be replaced.
2. Test using an ohmmeter. Test the coil of the contactor for continuity or shorts to ground. Replace if open or shorted.
3. Check connections and contacts. Be sure connections are tight and that the contacts are not burnt. Replace any contactor with burnt contacts.
This light will be ON when the compressor contactor is powered.
September 2006 Page 67
Test Procedures - Loads
Pressure switches
There are two pressure switches: Fan and High Pressure cut out.
Fan. The fan pressure switch will open to shut the fan motor off at a certain pressure and re-close at a preset higher pressure.
High pressure cut out. The high pressure cut out switch will open at a preset pressure, shutting off power to the compressor contactor. After the pressure has fallen to another preset level, the switch will re-close and the contactor coil will be engergized.
To Test Fan Pressure Switch:
A. Attach refrigeration gauge set to high side port.
B. Unplug both wires from fan pressure control. Be SURE the wire's terminals are wrapped
in electrical tape to prevent short circuits to ground during the test.
C. Connect ohmmeter to terminals of fan pressure control..
D. Switch ice machine on, observe pressure that the pressure control closes at, compare to spec. Switch unit off, allow system to equalize, observe pressure the pressure control opens at, compare to spec.
To Test High Pressure Switch:
A. Attach refrigeration gauge set to high side port.
B. Unplug fan motor or shut water off if water cooled.
C. Measure voltage between contactor side terminal of high pressure control and ground.
D. Switch ice machine on, observe pressure that the pressure control opens at, compare to spec. Allow system to equalize, observe the pressure that the pressure control closes at, compare to spec.
Transformer
Check secondary voltage, it must be between 10 and 15.5 AC volts. Replace if no voltage is output or if above or below the acceptable voltage..
Controller
The controller’s software operation is confirmed if it is functioning. Execute the test to confirm its operation of the loads. Illumination of a diagnostic code (other than E) is not an indication of controller failure. Each code requires its own diagnosis.
September 2006 Page 68
Test Procedures - Loads
Liquid Line Solenoid (remote only)
1. Test using the controller’s indicator lights. Put the controller into test mode (depress Off for 3 seconds then depress Clean for 3 seconds). At the end of the test cycle, the liquid line valve will be powered and the Condenser Fan motor indicator light will be on. The liquid line valve should be open at that time. If it is not, repeat the test but check the voltage to the liquid line valve coil, it must receive full voltage at the liquid line lead connection at the end of the test. If there is voltage and the valve does not operate, replace the valve coil. If there is no voltage, check the controller high voltage harness connection. The liquid line solenoid lead is the top wire. Check voltage from it to ground, at the end of the test, when the Condenser Fan indicator light is On, there must be voltage from this pin to ground. Note: high voltage power is supplied to the bottom pin from the contactor line. Refer to the machine wiring diagram as needed.
2. Test using an ohmmeter. Disconnect electrical power. Unplug liquid line coil from harness. Measure liquid line coil resistance. If open, replace the liquid line valve coil.
This light will be ON when the liquid line solenoid has power.
September 2006 Page 69
Test Procedures - Loads
Inlet Water Solenoid Valve
1. Test using the controller’s indicator lights. Shut unit off by holding the Off button for 3 seconds. Wait four minutes. Push and release the On button, observe the Water Solenoid indicator light. After the unit drains the reservoir, the inlet water valve will be powered to refill the reservoir. When it gets power, the indicator light will be ON. If the water valve does not open to fill the reservoir when its indicator light is on, do a voltage check. Shut the unit down by holding the Off button in for 3 seconds. Unplug the harness connection from the inlet water valve. Wait four minutes. Push and release the On button to restart the machine. After the unit drains the reservoir, the inlet water valve connection should receive full voltage. If it does, the inlet water valve should be replaced. If there is no voltage, check voltage from the controller to ground. The inlet water solenoid valve pin is 7. If there is voltage from that pin to ground, but low voltage at the valve harness connection, the harness has a broken wire or poor connection and must be replaced. If the voltage to ground is low, the controller should be replaced.
2. Test using an ohmmeter. Disconnect electrical power. Unplug coil from harness. Measure coil resistance. If open, replace the inlet water solenoid.
Light is ON when inlet water solenoid is in operation.
September 2006 Page 70
Test Procedures - Loads
Harvest assist solenoid
1. Test using the controller’s indicator lights. Push and release the Harvest button. The Hot Gas indicator light will be on. At the same time the Harvest Assist Solenoid will be powered. If the ice on the evaporator is thin, the solenoid will extend. If the ice is nearly full sized, the solenoid will press against the ice until it releases from the evaporator, then the solenoid probe will extend. If the probe extends, the solenoid is good. If not, do a voltage check. Unplug the high voltage harness from the harvest assist solenoid. Attach a voltmeter to the harness connector. Push and release the Harvest button. There should be full voltage at the connector. If there is and the solenoid does not extend, replace the solenoid. If full voltage is not present, check voltage at the controller. If there is no voltage, check voltage from the controller to ground. The hot gas / harvest assist pin is 5. If there is voltage from that pin to ground, but low voltage at the solenoid harness connection, the harness has a broken wire or poor connection and must be replaced. If the voltage to ground is low, the controller should be replaced.
Note: The coil of this valve is internally rectified, will normally show infinite resistance when tested with an ohmmeter.
This light will be ON during harvest. Both the Hot Gas Valve coil and the Harvest assist solenoid coil will have power when this light is ON.
Hot Gas or Vapor Valve
1. Test using the controller’s indicator lights. If the unit is running, or has been off for more than 4 minutes, push and release the Harvest
button. The Hot Gas indicator light will be on and the hot gas valve will be energized. The compressor will force discharge gas into the evaporator inlet, warming it. If the evaporator inlet does not warm up, do a voltage check. Shut the unit off by holding the Off button in for 3 seconds. Unplug the high voltage harness from the hot gas solenoid. Attach a voltmeter to the harness connector. Wait 4 minutes. Push and release the Harvest button. There should be full voltage at the connector. If there is and the solenoid does not open, replace the solenoid coil. If full voltage is not present, check voltage at the controller. If there is no voltage, check voltage from the controller to ground. The hot gas pin is 5. If there is voltage from that pin to ground, but low voltage at the solenoid harness connection, the harness has a broken wire or poor connection and must be replaced. If the voltage to ground is low, the controller should be replaced.
2. Test with an ohmmeter. Disconnect electrical power. Unplug high voltage harness from hot gas or vapor valve. Measure resistance of hot gas or vapor valve coil. If open, replace the coil.
September 2006 Page 71
Technical Information
Pressure Switches Cut In, Cut Out
Cut In (PSIG) Cut Out (PSIG
Fan Pressure Control, 22" and 30" 240 190
Fan Pressure Control, 48" 280 220
High Pressure Cut Out AC 390 500
High Pressure Cut Out WC 300 400
High Pressure Cut Out, Remote 350 450
Compressor Amp Draws
Voltage Brand Base Model Freeze Harvest
C0322 115
230 same
C0522 115 AKA9451 7.9-6.5 7.2
230 same
Tecumseh
C0330 115 AKA9438 6.2-4.8 5.7
230 same
C0530 A or B 115 AKA9451 8-6.5 9.3
230 same
C0530 C 115
Copeland
230 RST45
C0630 230 Tecumseh AJA7490 5.8-5.0 6.8
C0830 single phase
three phase same
C1030 single phase CS12 7.3-4.8 6.2
three phase same
C1448 single phase CS14 12.5-7.6 9.2
three phase same
Copeland
C1848 single phase CS20 16-10 15
AKA9438 7.3-4.8 6.2
RST45 6.9-5.5 6.6-7.0
CS10 6.4-5.3 6.6
three phase same
C2148 W single phase CS24 15.4-12.6 16.2
three phase same
C2148R single phase CS27
three phase same
May 2011 Page 72
Heat Load & Condenser Water GPM
Air Cooled - Average heat load for air conditioning unit sizing
Model BTUH
C0322 4000
C0522 6800
C0330 4000
C0530 6800
C0630 8800
C0803 10800
C1030 12000
C1448 17200
C1848 22000
Water Cooled Water Use - condenser only,
o
F.
GPM, 70 inlet temp
Model
GPM, 45 water inlet temp
C0322 .2 .3
C0522 .3 .7
C0330 .1 .3
C0530 .3 .5
C0630 .4 .7
C0803 .4 .8
C1030 .4 1.0
C1448 .6 1.1
C1848 1.0 1.8
C2148 1.0 2.0
o
F. water
May 2008 Page 73
Controller Differences
The controllers are programmed at the factory for the model they are installed on, they cannot be moved from one model to another due to differences in:
Water purge time per setting
Maximum harvest time
Number of evaporator plates
The service controller has a selector switch that allows it to be used as a replacement part in any of the Prodigy models in production at the time the controller was manufactured. As new Prodigy models are introduced, those models will be added to the list of models new service controllers will work with.
The Service Controller includes a selector switch. The switch must be set to the model the
controller is being installed on. As new models are introduced, their setting will be added to
service controllers produced after that point.
September 2006 Page 74
Thermistor Values
Deg. F . . Ohms Deg. F . . Ohms Deg. F. . Ohms Deg. F. . Ohms Deg. F. . Ohms
0......85325
1
......82661
2......80090
3......77607
4......75210
5......72896
6......70660
7......68501
8......66415
9......64400
10.....62453
11.....60571
12.....58752
13.....56995
14.....55296
15.....53653
16.....52065
17.....50529
18.....49043
19.....47607
20.....46217
21.....44872
22.....43571
23.....42313
24.....41094
25.....39915
26.....38774
27.....37669
28.....36600
29.....35564
30.....34561
31.....33590
32.....32649
33.....31738
34.....30855
35.....30000
36.....29171
37.....28368
38.....27589
39.....26835
40.....26104
41.....25395
42.....24707
43.....24041
44.....23394
45.....22767
46.....22159
47.....21569
48.....20997
49.....20442
50.....19903
51.....
19381
52.....18873
S3.....18381
54.....17903
55.....17439
56.....16988
57.....16551
58.....16126
59.....15714
60.....15313
61.....14924
62.....14546
63.....14179
64.....13823
65.....13476
66.....13139
67.....12812
68.....12494
69.....12185
70.....11884
71.....11592
72.....11308
73.....11031
74.....10763
75.....10502
76.....10247
77.....10000
78.....9760
79.....9526
80.....9299
81.....9077
82.....8862
83.....8652
84.....8448
85.....8250
86.....8056
87.....7868
88.....7685
89.....7507
90.....7333
91.....7164
92.....6999
93.....6839
94.....6683
95.....6530
96.....6382
97.....6238
98.....6097
99.....5960
100....5826
101....5696
102....5569
103....5446
104....5325
105....5208
106....5093
107....4981
108....4872
109....4766
110....4663
111....4562
112....4463
113....4367
114....4273
115....4182
116....4093
117....4006
118....3921
119....3838
120....3757
121....3678
122....3601
123....3526
124....3452
125....3381
126....3311
127....3243
128....3176
129....3111
130....3047
131....2985
132....2924
133....2865
134....2807
135....2751
136....2696
137....2642
138....2589
139....2537
140....2487
141....2438
142....2390
143....2343
144....2297
145....2252
146....2208
147....2165
148....2123
149....2082
150....2042
151....2003
152....
153....1927
154....1890
155....1855
1965
September 2006 Page 75
156....1819
157....1785
158....1752
159....1719
160....1687
161....1655
162....1624
163....1594
164....1565
165....1536
166....1508
167....1480
168....1453.
169....1427
170....1401
171....1375
172....1350
173....1326
174....1302
175....1279
176....1256
177....1234
178....1212
179....1190
180....1169
181....1149
182....1129
183....1109
184....1090
185....1071
186....1052
187....1034
188....1016
189....998
190....981
191....965
192....948
193....932
194....916
195....901
196....885
197....871
198....856
199....842
200....828
201....814
202....800
203....787
204....774
205....761
206....749
207....737
208....724
209....713
210....701
211....690
212....679
213....668
214....657
215....646
216....636
217....626
218....616
219....606
220....597
221....587
222....578
223....569
224....560
225....551
226....543
227....534
228....526
229....518
230....510
231....502
232....495
233....487
234....480
235....472
236....465
237....458
238....451
239....444
240....438
241....431
242....425
243....419
244....412
245....406
246....400
247....394
246....389
249....383
250....377
Performance Data
C0322A
Water Temp
Cycle Time (minutes)
50 70 80 90
10-12 11-12 12-13 13-14
Ambient Air Temp., Degrees F.
70 80 90
12-13 13-14 14+ 14-15
13-14 14-16 15-16 16-17
Suction Pressure (PSIG)
Discharge Pressure (PSIG)
C0322W
Cycle Time (minutes)
Suction Pressure (PSIG)
Discharge Pressure (PSIG)
End of Freeze Harvest
End of Freeze Harvest
Water Temp
50 70 80 90
End of Freeze Harvest
End of Freeze Harvest
26 105
235 150
9-11 11+ 12+ 12-13
32 95-100
245 140
32 130
250 200
Ambient Air Temp., Degrees F.
70 80 90
11+ 12+ 13+ 13-14
10-11 10-12 12-13 13+
32 100-110
245 150
Ice per cycle weight: 2-4 to 2.6 lb.
September 2006 Page 76
Performance Data
C0522A
Water Temp
Cycle Time (minutes)
50 70 80 90
11-13 13 14 15
Ambient Air Temp., Degrees F.
70 80 90
13 14 15 16
16 16-18 18 19
Suction Pressure (PSIG)
Discharge Pressure (PSIG)
C0522W
Cycle Time (minutes)
Suction Pressure (PSIG)
Discharge Pressure (PSIG)
End of Freeze Harvest
End of Freeze Harvest
Water Temp
50 70 80 90
End of Freeze Harvest
End of Freeze Harvest
32 105
228 180
13-15 15 16 16-17
23 85
235 115
34 120
270 210
Ambient Air Temp., Degrees F.
70 80 90
15 16 17 17
14 14-15 15 16
36 110
245 200
Ice per cycle weight: 4.5 to 5 lb.
September 2006 Page 77
Performance Data
C0330A
Water Temp
Cycle Time (minutes)
50 70 80 90
9-10 10-11 11-12 12-13
Ambient Air Temp., Degrees F.
70 80 90
10-11 11-12 12-13 13-14
11-12 12-13 13-14 14-15
Suction Pressure (PSIG)
Discharge Pressure (PSIG)
C0330W
Cycle Time (minutes)
Suction Pressure (PSIG)
Discharge Pressure (PSIG)
End of Freeze Harvest
End of Freeze Harvest
Water Temp
50 70 80 90
End of Freeze Harvest
End of Freeze Harvest
28 110
200 150
8-10 10 11 11
33 95
235 130
Ambient Air Temp., Degrees F.
70 80 90
10 11 11 11
10 10-11 11 12
35 110
235 150
Ice per cycle weight: 2.4 to 2.6 lb
September 2006 Page 78
Performance Data
C0530A
Water Temp
Cycle Time (minutes)
50 70 80 90
13 14 15 16
Ambient Air Temp., Degrees F.
70 80 90
14 15 16 17
16 17 18 19
Suction Pressure (PSIG)
Discharge Pressure (PSIG)
C0530W
Cycle Time (minutes)
Suction Pressure (PSIG)
Discharge Pressure (PSIG)
End of Freeze Harvest
End of Freeze Harvest
Water Temp
50 70 80 90
End of Freeze Harvest
End of Freeze Harvest
33 95
230 130
10 11 12 13
33 100
235 140
32 105
260 190
Ambient Air Temp., Degrees F.
70 80 90
12 13 13 13
12 13 13 14
34 110
235 150
Ice per cycle weight: 4.5 to 5 lb
September 2006 Page 79
Performance Data
C0630A
Water Temp
Cycle Time (minutes)
50 70 80 90
9-10 10-11 11-12 12-13
Ambient Air Temp., Degrees F.
70 80 90
10-11 11-12 12-13 13-14
10-11 11-12 12-13 13-14
Suction Pressure (PSIG)
Discharge Pressure (PSIG)
C0630W
Cycle Time (minutes)
Suction Pressure (PSIG)
Discharge Pressure (PSIG)
End of Freeze Harvest
End of Freeze Harvest
Water Temp
50 70 80 90
End of Freeze Harvest
End of Freeze Harvest
21 85
200 160
9 10 11 11
25 75
235 140
27 115
255 200
Ambient Air Temp., Degrees F.
70 80 90
10 11 11 11
10 11 12 13
22 80
235 155
Ice per cycle weight: 4.5 to 5 lb
September 2006 Page 80
Performance Data
C0830A
Water Temp
Cycle Time (minutes)
50 70 80 90
11 12 13 14
Ambient Air Temp., Degrees F.
70 80 90
12 13 14 15
13 14 15 16
Suction Pressure (PSIG)
Discharge Pressure (PSIG)
C0830W
Cycle Time (minutes)
Suction Pressure (PSIG)
Discharge Pressure (PSIG)
End of Freeze Harvest
End of Freeze Harvest
Water Temp
50 70 80 90
End of Freeze Harvest
End of Freeze Harvest
26 80
204 160
11 12 13 14
30 85
235 175
30 100
260 195
Ambient Air Temp., Degrees F.
70 80 90
12-13 13-14 13-14 14
13 13 14 15
31 90
237 178
Ice per cycle weight: 7 - 7.3 lb
September 2006 Page 81
Performance Data
C1030A
Water Temp
Cycle Time (minutes)
50 70 80 90
9-10 10-11 11-12 10-13
Ambient Air Temp., Degrees F.
70 80 90
10-11 11-12 12-13 13-14
11-12 12-13 13 14-15
Suction Pressure (PSIG)
Discharge Pressure (PSIG)
C1030W
Cycle Time (minutes)
Suction Pressure (PSIG)
Discharge Pressure (PSIG)
End of Freeze Harvest
End of Freeze Harvest
Water Temp
50 70 80 90
End of Freeze Harvest
End of Freeze Harvest
26 80
210 165
10 11 11-12 12
26 70
240 145
30 90
260 190
Ambient Air Temp., Degrees F.
70 80 90
11 11-12 12 12-13
11 11 12 13
30 75
240 155
Ice per cycle weight: 7 - 7.3 lb
September 2006 Page 82
Performance Data
C1448A
Water Temp
Cycle Time (minutes)
50 70 80 90
12-13 13-14 14-15 15-16
Ambient Air Temp., Degrees F.
70 80 90
13-14 14-15 15-16 16-17
14-15 15-16 16-17 17-18
Suction Pressure (PSIG)
Discharge Pressure (PSIG)
C1448W
Cycle Time (minutes)
Suction Pressure (PSIG)
Discharge Pressure (PSIG)
End of Freeze Harvest
End of Freeze Harvest
Water Temp
50 70 80 90
End of Freeze Harvest
End of Freeze Harvest
38 100
250 150
13-14 14-15 15-16 15-16
36 105
235 170
40 100
270 160
Ambient Air Temp., Degrees F.
70 80 90
14-15 15-16 15-16 15-16
15-16 15-16 16-17 17-18
35 100
235 165
September 2006 Page 83
Performance Data
C1848A
Water Temp
Cycle Time (minutes)
50 70 80 90
10-11 11-12 12-13 13-14
Ambient Air Temp., Degrees F.
70 80 90
11-12 12-13 13-14 14-15
12-13 13-14 14-15 15-16
Suction Pressure (PSIG)
Discharge Pressure (PSIG)
C1848A
Cycle Time (minutes)
Suction Pressure (PSIG)
Discharge Pressure (PSIG)
End of Freeze Harvest
End of Freeze Harvest
50 70 80 90
End of Freeze Harvest
End of Freeze Harvest
30 90
227 170
10-11 11-12 12-13 12-13
30 80
240 155
32 100
285 195
Ambient Air Temp., Degrees F.
70 80 90
11-12 12-13 12-13 12-13
11-12 11-12 12-13 13-14
30 85
240 165
14 lb / cycle.
September 2006 Page 84
Performance Data
C2148W
Water Temp
Cycle Time (minutes)
50 70 80 90
9-10 10-11 11-12 11-12
Ambient Air Temp., Degrees F.
70 80 90
10-11 11-12 11-12 11-12
11 11 12 13
Suction Pressure (PSIG)
Discharge Pressure (PSIG)
Ice weight per cycle: 14.2
End of Freeze Harvest
End of Freeze Harvest
27 75
235 160
27 75
240 160
September 2006 Page 85
Performance Data - Remotes
C0522R
Water Temp
Cycle Time (minutes)
50 70 80 90
Condenser Intake Air Temp., Degrees F.
-20 70 80 90 120
10 12-13
13-14 14-15 15-16
13-14 13-14 14-15 17-18
14 14-15 15-16 18-19 23
Suction Pressure (PSIG)
Discharge Pressure (PSIG)
Ice per cycle, 4.4 to 4.6 lb
End of Freeze Harvest
End of Freeze Harvest
Min 205
35 85
230 215
35 90
245 225
Peak at 360
September 2006 Page 86
Performance Data - Remotes
C0530R
Water Temp
Cycle Time (minutes)
50 70 80 90
Condenser Intake Air Temp., Degrees F.
-20 70 80 90 120
10 11-13
14 15 16
13-14 14-15 15-16 17-18
13-14 14 15-16 17-18 27
Suction Pressure (PSIG)
Discharge Pressure (PSIG)
End of Freeze Harvest
End of Freeze Harvest
207 min
30 145
230 200
35 100
245 220
Peaks at 350
September 2006 Page 87
Performance Data - Remotes
C0630R
Water Temp
Cycle Time (minutes)
50 70 80 90
Condenser Intake Air Temp., Degrees F.
-20 70 80 90 120
7-8 9
9-10 10-11 12
9 9-10 11-12 14
9-10 10 11 13-14 16-17
Suction Pressure (PSIG)
Discharge Pressure (PSIG)
End of Freeze Harvest
End of Freeze Harvest
Min 204
30 110
240 200
30 120
245 220
Peaks at 370
September 2006 Page 88
Performance Data - Remotes
C0830R
Water Temp
Cycle Time (minutes)
50 70 80 90
Condenser Intake Air Temp., Degrees F.
-20 70 80 90 120
8-9 9-11
11 12-13 13-14
10-11 11-12 12-13 15
12 13 13-14 16-17 21-22
Suction Pressure (PSIG)
Discharge Pressure (PSIG)
End of Freeze Harvest
End of Freeze Harvest
Min at 205
32 100
240 200
32 110
245 210
Peak at 360
September 2006 Page 89
Performance Data - Remotes
C1030R
Water Temp
Cycle Time (minutes)
50 70 80 90
Condenser Intake Air Temp., Degrees F.
-20 70 80 90 120
9 10-11
11 12-13 13-14
11 11-12 12-13 15-16
12-13 12-13 14 16-17 20-21
Suction Pressure (PSIG)
Discharge Pressure (PSIG)
End of Freeze Harvest
End of Freeze Harvest
Min 207
28 95
230 200
27 100
240 215
Peaks at 380
September 2006 Page 90
Performance Data - Remotes
C1448R
Water Temp
Cycle Time (minutes)
50 70 80 90
Condenser Intake Air Temp., Degrees F.
-20 70 80 90 +120
911
11-12 13 14
11-12 11-12 13 15-16
14-15 14-15 16 18-19 22
Suction Pressure (PSIG)
Discharge Pressure (PSIG)
Ice per cycle, 12 lb.
End of Freeze Harvest
End of Freeze Harvest
Min 207
40 100
240 150
40 125
270 200
Peak at 405
September 2006 Page 91
Performance Data - Remotes
C1848R
Water Temp
Cycle Time (minutes)
50 70 80 90
9 10-11
Condenser Intake Air Temp., Degrees F.
-20 70 80 90 120
13 13 14-15 17 19
11-12 13 14
11-12 12 13-14 16
Suction Pressure (PSIG)
Discharge Pressure (PSIG)
Ice per cycle 14 lb.
End of Freeze Harvest
End of Freeze Harvest
Min 210
32 85
240 170
33 105
245 205
Peak at 370
August 2011 Page 92
Performance Data - Remotes
C2148R
Water Temp
Cycle Time (minutes)
50 70 80 90
Condenser Intake Air Temp., Degrees F
-20 70 80 90 120
910
9-10 11-12 12-13
10 10 11 14
11 12 13 15-16 18-19
Suction Pressure (PSIG)
Discharge Pressure (PSIG)
Ice per cycle, 14-15 lb.
End of Freeze Harvest
End of Freeze Harvest
Min 217
24 80
240 190
24 95
250 220
Peaks at 410
September 2006 Page 93
Wiring Diagrams
C0322, C0522, C0330, C0530, C0630, C0830, C1030 - Single Phase
September 2006 Page 94
Wiring Diagrams
C0530 C Air or Water Cooled 60 Hz
May 2011 Page 95
Wiring Diagram
C0830, C1030 - Three Phase
September 2006 Page 96
Wiring Diagram
C0522R, C0530R, C0630R, C0830R, C1030R - Single Phase
September 2006 Page 97
Wiring Diagrams
C0530R C
May 2011 Page 98
Wiring Diagram
C0522R, C0530R, C0630R, C0830R, C1030R Single Phase after 9/09
September 2009 Page 99
Loading...