Page 12
INSTALLATION
Page 12
GAS CONNECTION
To perform these operations the qualied installer
will follow the indications given in the “Adaptation
to the various types of gas” section (see pg. 15). For
safer operation make sure that the supply pressure
respects the values given in the “Table of burner
and injector characteristics” (see pg. 15).
The appliance must be connected to the gas supply
or the cylinder according to the specications of
the standards and after checking that it is adjusted
for the type of gas available.
The gas connection is male 1/2” BSP and is
situated 55mm from the right and 565mm from
the oor. There are two ways to carry out the
connection to the main gas line:
A. The cooktop can be connected with rigid pipe
as specied in AS5601 - table 3.1.
B. The cooktop can be connected with a Flexible
Hose, which complies with AS/NZS 1869 (AGA
Approved), 10mm ID, class B or D, no more than
1.2m long and in accordance with AS5601.
Ensure that the Hose does not contact the
hot or sharp surfaces of the hotplate, oven,
dishwasher or other appliance that may be
installed underneath or next to the cooktop.
The isolating manual shut-o valve
connection point must be accessible when
the appliance is installed�
WARNING: Ensure that the hose assembly is
restrained from accidental contact with a ue
or ue outlet of an underbench oven. The gas
hose should not be subjected to abrasion, kinking
or permanent deformation and should be able
to be inspected along its entire length. Unions
compatible with the hose ttings must be used
and connections tested for gas leaks. The supply
connection point shall be accessible with the
appliance installed.
The appliance is factory set for Natural Gas. The
test point pressure should be adjusted to 1.00kPa
with 50% of the burners burners operating at
maximum.
The appliance is set up to operate with the gas
specied on the gas type label placed on the back
of the appliance.
When the type of gas available does not
correspond to that for which the appliance is set
up, replace the corresponding injectors (provided),
being careful to put on the new label (provided)
and remove the old one.
UNIVERSAL GAS - ULPG
When converting from Natural Gas to Universal
LPG ensure that the NG regulator is removed
and replaced with the Test Point Assembly. An
AGA Approved gas regulator suitable for a supply
pressure of 2.75kPa should be part of the gas
tank supply and the test point pressure should be
adjusted to 2.75kPa.
Before Leaving - Gas leakage and operation of the
appliance must be tested by the installer before
leaving. Check burner ames are blue in colour,
stable and completely ignite at both high and low
ame setings with no appreciable yellow tipping,
carbon deposition, lifting, oating, lighting back
or objectionable odour. Test burners individually
and in combination. When satised with the
operation of the cooker, please instruct the user
on the correct method of the operation in case
the appliance fails to operate correctly after all
checks have been carried out, call the Schweigen
Customer Service Team.
NATURAL GAS
Natural Gas installation requires the connection
of a gas regulator. Only use the Natural Gas
regulator supplied with this appliance. Assemble
the regulator (noting the gas ow direction) and
transition pieces (supplied with the appliance),
in accordance with Figure 1 below. The transition
piece on the supply side of the regulator must be
provided by the installer. The appliance has been
tted with injectors for natural gas. Universal ULPG
gas injectors (if required) have been included with
the cooktop. Gas pressure must be adjusted to
1.0kPa when approximately 50% of the burners
are on high ame, the appliance test point is
located on the regulator.
Test point
Fig� 1