Schwank companies in: Austria ▪ Belgium ▪ Canada ▪ China ▪ Czech Republic ▪ France ▪ Germany ▪ Great
Britain ▪ Hungary ▪ Netherlands ▪ Poland ▪ Romania ▪ Russia ▪ Slovakia ▪ Ukraine ▪ USA ▪ Distribution in more
than 40 countries worldwide
2 Your Safety ........................................................................................................................................................... 4
Notes for your safety ................................................................................................................................. 4
3 Scope of Delivery ............................................................................................................................................... 5
Position of suspension ............................................................................................................................... 7
Technical data ........................................................................................................................................ 21
13 Change of gas family ....................................................................................................................................... 53
Set angled mounting tubes ................................................................................................................... 58
Gas filter groups ...................................................................................................................................... 58
Water protection box burner kit ........................................................................................................... 59
15 Spare parts ......................................................................................................................................................... 61
Spare parts infraSchwank D / calorSchwank D 15-60U .................................................................... 62
Spare parts burner kit infra D / calor D 15-60U ................................................................................... 62
16 EC type examination certificate ..................................................................................................................... 63
17 EC declaration of conformity .......................................................................................................................... 65
18 Product information related to Ecodesign Regulation No 2015/1188 ...................................................... 66
3
infraSchwank D / calorSchwank D shape U
1 Introduction
Thank you for choosing a high efficiency
SCHWANK radiant tube.
Your infraSchwank D / calorSchwank D is a modern
and low-pollution tube heater for economic and
comfortable heating of industrial and commercial
buildings.
The design and operation of the heater are
according to the requirements of the existing
standards.
Please read this manual carefully before using the
heater. Please follow carefully all instructions and
warnings. The manufacturer will not be held
responsible for damages resulting from installation
errors or failure to comply with the manufacturer’s
instructions.
Grey marked text shows information to
modulating operation for tube heaters
infraSchwank D / calorSchwank D.
Follow carefully all warnings in chapter 2 “Your
Safety”.
These tube heaters are constructed exclusively for
the application of large industrial and commercial
space heating. Any other use is not permitted and
therefore Schwank is not liable for any improper
use.
Notes for your safety
This appliance is designed according to the
requirements of the existing standards.
Nevertheless it is possible that dangers for you and
others result from the installation and/or operating
errors.
To avoid this, please read and follow the
instructions carefully.
General Notes
Only use the radiant tube if it is in a technically
faultless condition.
This manual is an integral and essential part of the
product and must be given to the user. Keep the
manual near the heater.
Any person pursuing any of the following tasks must
read this manual:
You need an explicit permission from the
manufacturer for any kind of changes and
reconstruction.
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
2 Your Safety
You will find the following symbols in this manual:
Danger!
Note that you and others can be hurt.
Attention!
Note that the appliance can be
damaged.
Danger!
Note that electrical shocks can be very
dangerous. Pay attention while working
on the electrical equipment.
Advice!
You find additional instructions about the
application/handling of the heater.
Use original spare parts only.
Safety for the electrical equipment
Danger of electrical shocks!
Electrical shocks can be very dangerous!
The electrical installation must be carried out by a
qualified service engineer following the existing
national and international standards.
Check the electrical equipment regularly.
Defect wires etc. must be replaced immediately.
The appliance must be cut off from the power
supply while working with the electrical equipment.
Make sure that nobody can connect the
appliance to the power supply while you are
installing or maintaining the unit.
After-sales Service
For all installation operations, start-up, gas
changes, etc. always consult a qualified service
engineer.
In case of doubt, contact SCHWANK GmbH,
phone + 49 [0] 221 / 7176 0.
4
infraSchwank D / calorSchwank D shape U
3 Scope of Delivery
turnaround box
Fig. 1: Tube heater infraSchwank D / calorSchwank D 20U
reflector long
turbulator
tube bar
reflector short
suspension bracket
radiant tube
burner kit
flange packing
Scope of delivery
The radiant tube infraSchwank D / calorSchwank D
consists of following kits:
Burner kit:
Burner-unit with gas-burner, pre-mixing
chamber, burner control unit IC 4000/1,
gas combination valve [single-stage or
modulating]
air differential pressure switch, electrical plug
connection and fan, burner kit complete
preassembled
Radiation kit:
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
Radiant tubes with turnaround box, flange
packing,
Corrosion resistant and radiant-optimized
reflector, end cap and brackets for hanging
[calorSchwank D: isolated reflectors]
Accessories
Central control unit SchwankControl Touch with
temperatures and operating schedules,
MODBUS control
Central control SRT-1 with temperatures and
operating schedules
Gas cock [gas connection] with thermal shut-off
device
Gas hose connection
Gas filter
Supply air- / exhaust flue-system
flue gas heat exchanger for the utilisation of
condensing technology – tetraSchwank
Adjustable steel wire suspension system [Gripple]
Brackets for wall mounting of angled position [15-
30°] for infraSchwank D / calorSchwank D 15-40U
Flue gas diverter [type A]
Ball protection grids [e.g. for sport halls]
Reflector elongations
Set for angled mounting
Water protection cover box for burner kit
[stainless steel]
Flue gas adapter
5
infraSchwank D / calorSchwank D shape U
Structure of burner kit
Fig. 2: Burner kit with burner control unit IC 4000/1
1. Burner control unit IC4000/1
2. Air pressure switch
3. Fan air restrictor plate
[incoming side, not shown]
4. Fan
5. Air baffle plate [only 15 / 20 / 30 / 40U]
6. Gas combination valve
[1-stage, modulating]
7. Test nipple connection pressure
8. Test nipple nozzle pressure
15. Ignition cable
16. Ionisation cable
17. 3-pin power supply socket
18. Locking screw
19. Venturi
20. Burner baffle [only 15 / 20 / 30 / 40U]
21. Gasket
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
9. Adjustment screw nozzle pressure
10. Adjustment screw start step valve
11. Inspection glass
12. Burner cup
13. Burner nozzle
14. Ignition and ionisation electrode
6
infraSchwank D / calorSchwank D shape U
4 Planning
Room temperature control
Radiant tube heating-systems must be equipped
with a temperature control.
Section heating is allowed without temperature
control.
Position of suspension
Suspension height
Radiant tubes must be positioned so that no one in
the radiation area is exposed to an extreme high
heat level. This is ensured when the minimum
suspension heights shown in the following table are
adhered to:
Nominal
thermal load in
kW
Suspension height in m
[max. radiation intensity 200 W/m2]
A = horizontal B = angled[30°]
Distances to flammable materials in the
radiant area
Radiant tubes must be positioned so that the
surface temperature of:
components with flammable materials,
flammable equipment, stored flammable
materials
never rises above 85° C.
15 3.5 m 3.1 m
20 4.0 m 3.6 m
30 4.8 m 4.3 m
40 5.5 m 4.9 m
50 6.8 m 6.2 m
60 8.0 m 7.3 m
Tab 1: Minimum suspension heights
Key:
A = Minimum height when hanging horizontally
B = Minimum height when hanging angled
Type
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
15 U
20 U
30 U
40 U
50 U
60 U
Tab 2: Safe distances
Key:
a = Minimum radial safety distance [inside radiation area]
b = Minimum upper safety distance when hanging horizontally
c = Minimum upper safety distance when hanging angled
d = Minimum lateral distance to supply pipes outside radiation
area
a
[cm]
1102010501515
1102010501515
1302010501515
1702510502515
2303510703515
30045101003515
b
[cm]
infracalorinfracalor
c
[cm]
d
[cm]
Fig. 3: Suspension heights and distances for horizontal
application
Fig. 4: Suspension heights and distances for angled application
Direction of radiation
Radiant tubes infraSchwank D / calorSchwank D
can be positioned horizontal or at an angle [max.
30° from vertical]. For this purpose suspension steel
chains and cables are installed at the suspension
brackets.
7
infraSchwank D / calorSchwank D shape U
/
Positioning
The radiant tube can be mounted with
chains [links min. 4 mm]
adjustable steel wire suspension system
[Schwank accessories]
If you chose chains please use bolts with lock nuts
for fixing the chain to the suspension bracket.
The radiant tube has to be fixed by
vertical chains etc. to the roof or to
supporting devices.
Chains and steel cables have to be fixed
in vertical direction or slightly diagonally
outwards above the fixing points of the
suspension brackets to the roof or to
supporting devices. Fixing of the
suspension cables or chains diagonally
inwards to the centre of the heater is not
permitted [see Fig 5].
Please note that the radiant tube being
in operation expands several
centimetres because of thermal
expansion. Avoid therefore inflexible
suspension.
Do not use fixing elements like open
hooks etc.
Hang the heater in balance. We recommend the
use of turnbuckles or adjustable steel cable grips
for ease of adjustment and balance.
Fixing points for chains or steel cables on the heater
are shown in Fig. 15 and 16 on pages 20 and 21.
Attention!
If you do not align the burner kit
correctly material damage and
destruction of the heater may occur.
Fig. 5: Chains and steel wire mounting
x
Correct = vertical or slightly
diagonally outwards
Wrong = diagonally inwards
Fig. 6: Slope of radiant tube heater
wrong
wrong
correct
SCHWANK GmbH will not accept liability
for damages caused by incorrect
mounting of the burner unit. Correct
mounting is the responsibility of the
installer.
Attention!
Make sure that the heater has in
longitudinal direction a slight slope
[3 mm per meter] to the turnaround box
[Fig. 6].
15/20/30U: x= 15 mm
40U: x= 20 mm
50
60U: x= 30 mm
x
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
8
infraSchwank D / calorSchwank D shape U
Air supply / Exhaust Requirements
The calculation of air supply / exhaust
requirements of a building heated by radiant tube
heaters is subject of European Directive EN 13410.
Please follow local by-laws as well.
Please see the max. lengths of combustion air
supply- and exhaust flue pipe on page 9 [Tab 3,
point 3].
Air supply / exhaust systems
For the radiant tube infraSchwank D / calor
SchwankD the following air supply / exhaust
systems are possible:
1. Indirect flue into the room
[Type A3 without exhaust system,
combustion air from inside the room]
2. Flued with individual exhaust system,
combustion air from inside the room
[Type B23]
Place of Installation
3. Flued with individual exhaust system,
The room to be heated must have an air volume of
minimum 10 m³ for each kW of the nominal
thermal load of the installed heater.
Air supply [combustion air from inside the
room, types A3 and B23]
Heating installations with combustion air from
inside the room are only allowed in rooms without
string air pollution. Otherwise use system with
combustion air from outside [type C].
In halls and buildings with a normal air change by
means of joints and gaps it is not necessary to
install additional equipment to ensure combustion
air supply.
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
combustion air from outside the room
[Type C]
4. Flued with flue collecting system and
central flue fan – combustion air either from
inside or from outside [according to EN 777,
Type F]
1. Indirect flue into the room
[Type A3 without exhaust system combustion
air from inside the room]
The exhaust air of the tube heater has to be
conducted from the inside of the room to the
outside.
Conduction of the exhaust air may be carried out
with one of the following 3 methods:
a) Thermal ventilation: Combustion air and
exhaust air are to be conducted through
fixed outlets positioned on the roof or on
the walls of the building.
b) Mechanical ventilation: Combustion air and
exhaust air are to be conducted through
one or more fans positioned on the roof or
on the walls of the building.
c) Natural ventilation: Combustion air and
exhaust air are to be conducted through
outlets as a result of differences in pressure
and in temperature between the internal
and external side of a building.
For exact dimensioning and positioning
of supply air and exhaust air outlet of the
building according to EN 13410 or
G 638-2 please contact Schwank GmbH,
phone +49 [0] 221 / 7176 0.
9
infraSchwank D / calorSchwank D shape U
2. Exhaust flue with individual exhaust system -
combustion air from inside the room
[Type B23]
Only use this system in rooms with no air pollution
and without relevant pressure differences to
outside. Otherwise use type C.
3. Exhaust flue with individual exhaust system combustion air from outside the room
[Type C]
Combustion air and exhaust air are to be
conducted by a temperature stable, concentric
pipe from a wall or roof entrance.
Max. length of the concentric pipe can be 6 m
plus two 90° elbows.
The concentric pipe ends at a bifurcated pipe.
Please ensure that the connection for exhaust air
between heater and bifurcated pipe is a flexible
pipe. Do not use back-pressure valves or dampers
in the exhaust flue.
Tab. 3: air/exhaust routing
Fig. 7: Air/exhaust-system,
infraSchwankD/calorSchwankD,shapeU
Max.length
betweenheater
androof/wall
entrance
6m2100mm
version aluminium or stainless steel
max.number
ofelbows
(90°)
Flexible exhaust system with
wall terminal
Flexible exhaust system with
roof terminal
Øofair/exhaust
flue
4. Exhaust flue with flue collecting system and
central flue fan
[according to EN 777, Type F]
The heating installation must not exceed 10 radiant
tubes. The exhaust air of each tube is collected
via a central collecting tube system by a central
flue fan and led to the chimney. Planning,
construction and layout of such installations must
be carried out by Schwank employees, as well as
commissioning. The strict observance of the
Schwank layout-drawings and calculation figures
are the precondition of the manufacturer’s
warranty.
With system F the radiant heaters will be installed
with their individual flue fans. Please note that it
necessary to install in the collecting pipe behind
each radiant heater and in the following collection
pipes damper or a pressure-balancing device. This
ensures a precise regulation and an even exhaust
flue of each radiant tube.
For detailed information regarding
setting up and commissioning of a flue
collection system please see
corresponding sections in chapters
4, 10 and 11.
Flexible exhaust system with
wall terminal
Flexible exhaust system with
roof terminal
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
10
infraSchwank D / calorSchwank D shape U
Flexible exhaust system infraSchwank D / calorSchwank D 15-40U [wall terminal]
- version aluminium -
The stainless flexible pipe [exhaust
line] must be installed uncut for the
heater 40/50/60U. Make sure that
there is no sink in the pipe.
Connection stainless steel flexible
pipe to aluminium tube must be
glued with heat-resistant sealing
material and locked by means of
self-tapping screws.
All socket connections on the
exhaust and air line must be locked
by means of self-tapping screws.
The wall terminal is mounted with a
small gradient to outside to prevent
intrusion of driving rain.
The 90° elbow at the sucking fan side is
to mount with the opening on the top.
infraSchwank D / calorSchwank D
type 50– 60 U cannot be operated
using a wall terminal.
Following components are required for mounting
the wall terminal aluminum design
[Distance heater- terminal approx. 1.5 m]:
Wall terminal M&G: Article no. 12221797
Testing set C 15-20kW: Article no. 12676660
Testing set C 30-40kW: Article no. 12676750
Please note the safety distance to
flammable materials:
- single-wall exhaust pipe: 40 mm
- double-wall exhaust pipe + wall
terminal: 0 mm
System certification tube heater
infraSchwank D/ calorSchwank D with
exhaust line system
CE 0432-CPD-217915, System 0.2 / 0.5
[Muelink&Grol]
The wall duct is fastened with screws
by means of the integrated flange
plate on the building wall. The flange
plate supports and secures the wall
duct.
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
Fig 8: Position of control points 15 – 40U [wall terminal], version aluminium
Transition stainless steel
flexible pipe on aluminum
pipe
Control points
Exhaust gas:
Stainless steel flexible pipe with
connecting flange
Flexible exhaust system infraSchwank D / calorSchwank D 15-60U [roof terminal]
- verison aluminium -
The stainless flexible pipe [exhaust line]
must be installed uncut. Make sure that
there is no sink in the pipe.
Connection stainless steel flexible pipe
to aluminium tube must be glued with
heat-resistant sealing material and
locked by means of self-tapping screws.
All socket connections on the exhaust
and air line must be locked by means of
self tapping screws.
The 90° elbow at the sucking fan side is
to mount with the opening on the top.
System certification tube heater
infraSchwank D/ calorSchwank D with
exhaust line system
CE 0432-CPD-217915, System 0.2 / 0.5
[Muelink&Grol]
Following components are required for mounting
the roof terminal aluminum version
[Distance heater- terminal approx. 1.5 m]:
Roof terminal M&G: Article no. 12221770
Testing set C 15-20kW: Article no. 12676660
Testing set 30-60kW: Article no. 12676750
Fig. 9: Position of control points [roof terminal], version aluminium
Dimension flat roof sockets
Flat version – Article no. 12201087
h version – Article no. 12201788
Hi
Transition stainless steel
flexible pipe on
aluminum pipe
Exhaust gas:
Stainless steel flexible pipe
Control points
Please note the safety distance to
flammable materials:
- single-wall exhaust pipe: 40 mm
- double-wall exhaust pipe + roof
terminal: 0 mm
The roof terminal is slide in from above
into the roof socket. in from above into
the roof socket. The fixing inside the
building takes place via a clamp to the
building ceiling.
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
12
infraSchwank D / calorSchwank D shape U
Flexible exhaust system deltaSchwank [wall terminal]
infraSchwank D / calorSchwank D 15-60U
- version stainless steel -
Install stainless steel flexible pipe
without sink.
Join parts of the roof terminal strongly
together by compression and using
of jointing and sealing paste
[e.g. Ceramax]!
All joints inside the building tighten
securely with clamp fittings!
The 90° elbow at the sucking fan side is to
mount with the opening on the top.
The wall terminal is mounted with a
small gradient to outside to prevent
intrusion of driving rain.
The wall terminal is fastened to the
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
Fig. 10: Position of control points 15 – 60U [wall terminal], version stainless steel
building wall with screws by means of
the integrated flange plate. The flange
plate supports and secures the wall
terminal.
Following components are required for mounting
the wall terminal stainless steel version
[Distance heater- terminal approx. 1.5 m]:
Stainless steel exhaust system wall terminal
DN 100/160
Please note the safety distance to
flammable materials:
- single-wall exhaust pipe: 80 mm
- double-wall exhaust pipe
+ wall terminal: 0 mm
System certification tube heater
infraSchwank D/ calorSchwank D with
exhaust line system
Future ew CE 0432-CPR-00055-209 /
Future ew-flex CE 0036-CPR-00055-207 /
Future dw CE 0432- CPR-00055-301
[Schräder]
: Article no. 12202220
13
infraSchwank D / calorSchwank D shape U
Flexible exhaust system [roof terminal]
infraSchwank D / calorSchwank D 15- 60U
- version stainless steel -
Install stainless steel flexible pipe
without sink.
Join parts of the roof terminal strongly
together by compression and using
of jointing and sealing paste
[e.g. Ceramax]!
All joints inside the building tighten
securely with clamp fittings!
The 90° elbow at the sucking fan side is
to mount with the opening on the top.
The roof terminal is fastened with screws
Following components are required for mounting
the roof terminal stainless steel version
[Distance heater- terminal approx. 1.5 m]:
by means of the integrated flange plate
on the building ceiling. The flange plate
supports and secures the roof terminal.
Fig. 11: Position of control points 15 – 60U [roof terminal], version stainless steel
Please note the safety distance to
flammable materials:
- single-wall exhaust pipe: 80 mm
- double-wall exhaust pipe
+ roof terminal: 0 mm
System certification tube heater
infraSchwank D/ calorSchwank D with
exhaust line system
Future ew CE 0432-CPR-00055-209 /
Future ew-flex CE 0036-CPR-00055-207 /
Future dw CE 0432- CPR-00055-301
[Schräder]
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
14
infraSchwank D / calorSchwank D shape U
1,0m
Exhaust system deltaSchwank [roof terminal]
with downstream heat exchanger tetraSchwank in room air operation and with outside
air intake in fresh air operation
- version stainless steel -
Install stainless steel flexible pipe
without sink.
Join parts of the roof terminal strongly
together by compression and using
of jointing and sealing paste
[e.g. Ceramax]!
All joints inside the building tighten
securely with clamp fittings!
tetraSchwank heat exchanger should be
mounted with slight slope [3 mm /1 m] to
the T-piece.
Fig 12: Installation tetraSchwank in room air operation, with roof
terminal stainless steel
Installation tetraSchwank _TA _Frisc hluft_4817
>
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
Fig 13: Installation tetraSchwank with outside air intake in fresh air operation, with roof terminal stainless steel
Installations exhaust system with heat recovery:
1. flue gas heat exchanger tetraSchwank
- pre-assembled
L= 4700 mm Article no. 62000020
2. ventilator tetraSchwank with protection grating
3. T-piece stainless steel with condensation outlet
connection R ½“
4. fastening clamp for suspension, premounted
5. single-wall roof terminal with in room air
operation Article no. 12201941
double wall roof terminal with outside air intake
in fresh air operation Article no. 62000090
Please note the safety distance to
flammable materials:
-single-wall exhaust pipe: 80 mm
-double-wall exhaust pipe
+ roof terminal: 0 mm
System certification tube heater
infraSchwank D/ calorSchwank D with
exhaust line system
Future ew CE 0432-CPR-00055-209
The roof terminal is fastened with
screws by means of the integrated
flange plate on the building ceiling.
The flange plate supports and secures
the roof terminal.
15
infraSchwank D / calorSchwank D shape U
Exhaust pipe collecting system [herringbone] with central fan
System F approved according to EN 777 and DIN EN 416
Exhaust pipe collecting system consist of
following main components:
Tube heater infraSchwank D/ calorSchwank D
Spiral duct and connection elements for
exhaust collecting system [different
dimensions]
Central low-pressure fan
Fan monitoring kit
Planning and calculation of the
complete system including collecting
pipes, fans and chimneys
must only be done by Schwank.
Planning details have to be strictly
adhered to during mounting and
assembly. Commissioning of the system
should be carried out by Schwank.
Article no. 700 0012 0
Central fan
Collecting exhaust pipe
Fig. 14: Installation exhaust collecting system with central fan , system F [principle scheme]
Damper behind heater
Connecting pipe
Exhaust gas
Control point chimney
sweeper
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
Damper in front of central
fan
Tube heater
16
infraSchwank D / calorSchwank D shape U
5 Legal Requirements
We recommend that these installation guidelines
should be observed with the relevant Building
Standards Regulations of your country. Comply
with any local by-laws and the current IEE Wiring
Regulations.
Notwithstanding their limited scope, the
appliance should be installed by a competent
person in accordance with the relevant
provisions of the Gas Safety [Installation and Use]
Regulations. Caution must also be taken of any
obligations arising from the Health and Safety of
Work Act. Full compliance with all relevant
regulations, including amendments in force at
the time of installation is a requirement of our
warranty.
In Germany the following rules, standards and
regulations must be observed.
EnEV Verordnung über
energiesparenden Wärmeschutz
und energiesparende
Anlagentechnik bei Gebäuden
DIN EN 12831 Heizungsanlagen in Gebäuden
Verfahren zur Berechnung der
Norm-Heizlast
DIN EN 13384 Abgasanlagen
DIN V 18599 Energetische Bewertung von
Gebäuden – Berechnung des
Nutz End- und Primärenergiebedarfs
für Heizung, Kühlung, Trinkwasser
und Beleuchtung
DVGW G 660 Technische Regeln für die
mechanische Abführung der
Abgase von Feuerstätten
VDE 0722 Elektrische Vorschriften
VDE 0100 Bestimmungen für das Errichten
von Starkstromanlagen
Beachten Sie außerdem die Bestimmungen der
jeweiligen
LBO Landesbauordnung
FeuVO Feuerungsverordnung der
Länder
TAB Technische Anschluss bedingungen der örtlichen
Energieversorgungs-
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
unternehmen
17
infraSchwank D / calorSchwank D shape U
6 Operation
The installation must be carried out by
a qualified engineer following the
manufacturer’s instructions.
SCHWANK will not accept liability damages
caused by improper assembly and/ or operating
of the heater. Proper assembly and operation is
the responsibility of the user.
Switching on the heater
First switch on the central control unit
SchwankControl Touch and activate a
heating command.
After a pre-purge period of about 25 sec.
the ignition starts.
Switching off the heater
Maintenance
Servicing of the heater is essential for continued
efficient operation. Servicing should be carried
out not less than once a year by a qualified
service engineer. After any servicing, the heater
must be recommissioned as detailed in
Chapter 12.
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
Disable the heating command on central
control unit SchwankControl Touch.
If the radiant tube is controlled by a thermostat
the heater will be switched on and off
automatically.
Fault
If no flame is reported during the pre-purge
period and the safety time [approx. 30 sec.] the
heater repeats the ignition process. If there is no
flame after the second ignition process the
heater switches off automatically and is locked.
Investigation and repair must be carried
out by authorized personnel. After
clearance of the fault the heater can be
reset.
The cause of the fault / error code is
displayed on the central control unit
SchwankControl Touch or can read out via
corresponding service software IC 4000.
See chapter 12 for error codes.
Lock release [Reset]
Activate the reset command via the
central control unit or interrupt the electric
power supply for 3 seconds.
18
infraSchwank D / calorSchwank D shape U
7 Technical
Electrical connection power supply
Single-phase AC 230 V, N, PE - 50Hz
specification
Appliance Automatic heating device, heat
transfer by means of infrared dark
radiation.
The connecting cable for the power supply is
connected to the IC 4000/1 burner control with
the provided 4-pin plug.
The power supply for the heater must be flexible
with maximal wire cross-section
Fuel Types Natural gas
Propane
Minimum connection pressure in front of valve
Gas type 15-50U 60U
Natural Gas H 15 hPa 20 hPa
Natural Gas L 20 hPa 30 hPa
Propane 40 hPa 40 hPa
Attention!
Max. connection pressure: 60 hPa
- 3x 1.5 mm
To set the bluTek-burner kit free of voltage it is
only necessary to remove the plug of the power
supply.
Regulation
The heating system is controlled via the central
control unit SchwankControl Touch.
The corresponding heating commands for the
heater are sent via MODBUS communication.
Connection MODBUS control from
2
Ölflex- or silicone cable
SchwankControl Touch to IC 4000/1
Gas connection 15-30U R=1/2’’ male
40-60U R=3/4’’ male
Exhaust gas Flange at radiant tube end
connection for exhaust connection Ø
100 [flexible stainless steel
pipe / exhaust gas adapter]
infraSchwank D / calorSchwank D 15U
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
infraSchwank D / calorSchwank D 20U
Fig. 15: Measurements infraSchwank D / calorSchwank D 15U, 20U [view from below]
Use for MODBUS transmission max. 3x 0.5 mm
cable.
Route the cable through the lower cable gland
into the housing of burner control unit IC 4000/1
and connected to the corresponding spring
terminals on the circuit board.
Detail A
Cross dimensions at burner kit
15-40U A=80 mm
Detail A / B
50-60U A=100 mm
Detail B
Cross dimensions reflector
valid for all types
2
19
infraSchwank D / calorSchwank D shape U
infraSchwank D / calorSchwank D 30U
infraSchwank D/ calorSchwank D 40U
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
infraSchwank D / calorSchwank D 50U
infraSchwank D / calorSchwank D 60U
Fig. 16: Measurements infraSchwank D / calorSchwank D 30U, 40U, 50U and 60U [view from below]
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
22
infraSchwank D / calorSchwank D shape U
8 Operating
description
Start-up
If heat demand exists, the fan will start up
automatically. A differential pressure arises in the
burner box, which is reported to the ignition unit via
the differential pressure switch.
After a pre-purge period of about 25 seconds the
automatic ignition starts [max. ignition time 5 sec.].
The twin solenoid valve with pressure regulator
opens the gas supply to the burner in 2 steps. The
burner flame is controlled by an ionisation
electrode. The ignition is switched off, if the
ionisation electrode reports a flame to the burner
control unit IC 4000/1 within the safety time.
If the ignition process fails, the burner control IC
4000/1 repeats the start-up for one more time.
Operation
A very long laminar flame is created in the first
tube by the special burner construction. The hot
flue heats the tube surface while being fed
through the tubes by the fan. The hot tubes emit
long-waved infrared radiation which is directed to
the room by the reflector construction.
Fault
If no flame is reported during the pre-purge period
[including 1 repetition of ignition process], the
burner control unit IC 4000/1 will switch off the
radiant tube, error will give, fan runs in post-purge
time for 30 seconds and then heater will lock it.
Investigation and repair must be carried out by
authorized personnel only. After clearance of the
fault, the lock can be reset.
The cause of the fault / error code is displayed on
the central control unit SchwankControl Touch or
can read out via corresponding service software.
See chapter 12 for error codes.
Lock release can carry out by activate the reset
command via the central control unit
SchwankControl Touch or an interruption of the
electric power supply for 3 sec. A new start-up
begins. If no flame signal is reported to the burner
control unit IC 4000/1 during operation, the gas
valve shuts and stops the gas supply immediately.
A new start-up process is repeated.
Error codes and troubleshooting on
pages 51 - 52
The radiant tube infraSchwank D / calorSchwank D
work with a closed combustion system. The
combustion air is taken from the room or from the
outside. The flue is evacuated indirectly into the
room or directly by the exhaust pipe or by a
special air/exhaust pipe system.
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
For optimal adaption of heaters´ performance to
the heat demand of the building heaters are
offered in modulating operation.
Start and ignition of the heater has always to be in
full load. After a time of minimal 1 minute the
heater can be switched to small step.
Monitoring of the combustion air supply
The combustion air supply is permanently
controlled by the differential pressure switch during
the operation.
If the differential pressure switch is not in rest
position during the start-up the operation will not
start. If the operating contact is not closed during
the pre-purge the system will set in interference
release.
If combustion air supply fails during operation [lack
of air], the differential pressure switch will close the
gas combination valve and stop the gas supply. A
new start-up process is to be repeated.
23
infraSchwank D / calorSchwank D shape U
9 Assembly instructions
Assembly radiant and burner kit
Assembly
infraSchwank D / calorSchwank D 15U
Tools you need
• hexagonal wrench or ratchet
[width: 10, 13]
• socket wrench [width: 7 and 8]
Note before mounting
Note the distance measure of suspension
brackets.
Flanges are mounted with flange packing
[each 4 screws/washers/lock washers/nuts M8].
Start mounting the heater at the turnaround
box connection.
Turn welding line of the tubes to the side.
Tube with turbulator [with paint mark] has to be
mounted behind the turnaround box [flow
direction]. The paint mark showing to the
turnaround box!
Tube bars have to be fixed by nuts/lock
washers/3D-washers M8 on the suspension
bracket.
First the reflector will be fixed on the U-bend
connection by screws/self-locking nuts/lock
washers/3D-washers M5. For insulated reflectors
[calorSchwank D] the reflector end with notch
on sides shows to the turnaround box.
The other reflector ending will be shoved under
the clip of the suspension brackets. Reflector
and front plate have to be fixed by screws/selflocking nuts/lock washers/3D-washers M5.
Mounting of burner unit with valve on the top.
Fig. 17: Mounting of infraSchwank D / calorSchwank D 15U
[all dimensions in mm]
Flue gas connection [Type B23, C]
Accessory
Flue gas diverter code-no. 126 7018 0 or
flue gas adapter code-no. 126 7035 0
Note that the flue gas diverter is mounted in a
Flexible stainless steel pipe with connector
flange has to be mounted at the end of the
tube with a gasket.
for indirect flue into the room [Type A]
Note that the flue gas diverter or adapter is
mounted at the end of the tube.
position so that the flue gas is diverted from the
burner.
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
24
infraSchwank D / calorSchwank D shape U
Assembly
infraSchwank D / calorSchwank D 20U
Tools you need
• hexagonal wrench or ratchet
[width: 10, 13]
• socket wrench [width: 7 and 8]
Note before mounting
Note the distance measures of suspension
brackets.
Flanges are mounted with flange packing
Flue gas connection [type B23, C]
Flexible stainless steel pipe with connector
flange has to be mounted at the end of the
tube with a gasket.
[each 4 screws/washers/lock washers/nuts M8].
Start mounting the heater at the turnaround
box connection.
Turn welding line of the tubes to the side.
Tube with turbulator [with paint mark] has to be
mounted behind the turnaround box [flow
direction]. The paint mark showing to the
turnaround box!
Tube bars have to be fixed by nuts/3D-
washers/lock washers M8 on the suspension
brackets.
Start the reflector mounting at the turnaround
box connection with the longest reflector
L=3000 mm. Reflector will be fixed on the
turnaround box connection by screws/selflocking nuts/lock washers/3D-washers M5. For
insulated reflectors [calorSchwank D] the
reflector end with notch on sides shows to the
Accessory
for indirect flue into the room [type A]
Flue gas diverter code-no. 126 7018 0 or
flue gas adapter code-no. 126 7035 0
Note that the flue gas diverter or adapter is
mounted at the end of the tube.
Note that the flue gas diverter is mounted in a
position so that the flue gas is diverted from the
burner.
turnaround box.
The other reflector endings will be shoved under
the clips of the suspension brackets.
The short reflector L=1500mm is mounted at the
front of the heater.
Reflectors will be jointly fixed by 3x M 5 screws
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
Fig. 18: Mounting of infraSchwank D / calorSchwank D 20U
[all dimensions in mm]
25
infraSchwank D / calorSchwank D shape U
Assembly
infraSchwank D / calorSchwank D 30U
Tools you need
• hexagonal wrench or ratchet
[width: 10, 13]
• socket wrench [width: 7 and 8]
hand rivet tool, drill machine,
drill 4.9 mm
Note before mounting
Note the distance measures of suspension
brackets.
Flanges are mounted with flange packing
[each 4 screws/washers/lock washers/nuts M8].
Start mounting the heater at the turnaround
box connection.
Turn welding line of the tubes to the side.
Tube with turbulator [with paint mark] has to be
mounted behind the turnaround box [flow
direction]. The paint mark showing to the
turnaround box!
Supporting sleeve for first flange connection:
Insert half of the supporting sleeve into first
heater tube [slot on top]. Drill Ø 4.9 mm hole
through the tube and sleeve and fix it by rivet.
Mount the second tube and fix the sleeve by
the rivet as well. Fix the rivets always in the
opposite position lateral to the tube. Use only
stainless rivets.
Tube bars have to be fixed by nuts / 3D washers /
lock washers M8 on the suspension brackets.
Start the reflector mounting at the turnaround
box connection. Reflector will be fixed on the
turnaround box connection by by screws/selflocking nuts/lock washers/3D-washers M5. For
insulated reflectors [calorSchwank D] the
reflector end with notch on sides shows to the
turnaround box.
The other reflector endings will be shoved under
the clips of the suspension brackets.
Reflectors will be jointly fixed by 3x M 5 screws
and self-locking nuts.
Fig. 18: Mounting of infraSchwank D / calorSchwank D 30U
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
26
infraSchwank D / calorSchwank D shape U
Assembly
infraSchwank D / calorSchwank D 40U
Tools you need
• hexagonal wrench or ratchet
[width: 10, 13]
• socket wrench [width: 7 and 8]
Note before mounting
Note the distance measures of suspension
brackets.
Flanges are mounted with flange packing
[each 4 screws/washers/lock washers/nuts M8].
Start mounting the heater at the turnaround
box connection.
Turn welding line of the tubes to the side.
Tube with turbulator [with paint mark] has to be
mounted behind the turnaround box [flow
direction]. The paint mark showing to the
turnaround box!
Tube bars have to be fixed by nuts/3D-
washers/lock washers M8 on the suspension
brackets.
Start the reflector mounting at the turnaround
box connection. Reflector will be fixed on the
turnaround box connection by screws/selflocking nuts/lock washers/3D-washers M5. For
insulated reflectors [calorSchwank D] the
reflector end with notch on sides shows to the
turnaround box.
The other reflector endings will be shoved under
the clips of the suspension brackets.
Reflectors will be jointly fixed by 3x M 5 screws
and self-locking nuts.
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
Fig. 19: Mounting of infraSchwank D / calorSchwank D 40U
[all dimensions in mm]
Flue gas connection [Type B23, C]
Flexible stainless steel pipe with connector
flange has to be mounted at the end of the
tube with a gasket.
Accessory
for indirect flue into the room [Type A]
Flue gas diverter code-no. 126 7018 0 or
flue gas adapter code-no. 126 7035 0
Note that the flue gas diverter or adapter is
mounted at the end of the tube.
Note that the flue gas diverter is mounted in a
position so that the flue gas is diverted from the
burner.
.
27
infraSchwank D / calorSchwank D shape U
Assembly
infraSchwank D / calorSchwank D 50U
Tools you need
• hexagonal wrench or ratchet
[width: 10, 13, 17]
• socket wrench [width: 7 and 8]
Note before mounting
Note the distance measures of suspension
brackets.
Flanges are mounted with flange packing
[each 4 screws/washers/lock washers/nuts M8].
Start mounting the heater at the turnaround
box connection.
Turn welding line of the tubes to the side.
Tube with turbulator [with paint mark] has to be
mounted behind the turnaround box [flow
direction]. The paint mark showing to the
turnaround box!
Tubes with length L=5950 mm are mounted
parallel at the beginning of the heater.
Tube bars have to be fixed by nuts/3D-
washers/lock washers M8 on the suspension
brackets.
Bracket bars have to be fixed by
screws/washers/
lock washers/nuts M8 on all suspension brackets.
Start the reflector mounting at the turnaround
box connection. Reflector will be fixed on the
turnaround box connection by screws/selflocking nuts/lock washers/3D-washers M5. For
insulated reflectors [calorSchwank D] the
reflector end with notch on sides shows to the
turnaround box.
The other reflector endings lie on top to each
other on the bracket bars.
Reflectors will be jointly fixed by 3x M 5 screws
and self-locking nuts.
Front plate, reflector and bracket bar have to
be fixed by screws/self-locking nuts/lock
washers/3D-washers M5.
Mounting of burner unit with valve on the top.
Flue gas connection [Type B23, C]
Flexible stainless steel pipe with connector
flange has to be mounted at the end of the
tube with a gasket.
Accessory
for indirect flue into the room [Type A]
Flue gas diverter code-no. 126 7018 0 or
flue gas adapter code-no. 126 7035 0
Note that the flue gas diverter or adapter is
mounted at the end of the tube.
Note that the flue gas diverter is mounted in a
position so that the flue gas is diverted from the
burner.
Fig. 20: Mounting of infraSchwank D / calorSchwank D 50U
[all dimensions in mm]
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
28
infraSchwank D / calorSchwank D shape U
Assembly
infraSchwank D / calorSchwank D 60U
Tools you need
• hexagonal wrench or ratchet
[width: 10, 13]
• socket wrench [width: 7 and 8]
• hand rivet tool
Note before mounting
Note the distance measures of suspension
brackets.
Flanges are mounted with flange packing
[each 4 screws/washers/lock washers/nuts M8].
Stainless steel tube L=5950 mm is the first tube
after the burner unit. Tubes with same length
are mounted parallel.
Start mounting the heater at the turnaround
box connection.
Turn welding line of the tubes to the side.
Tube bars have to be fixed by nuts/3D-
washers/lock washers M8 on the suspension
brackets.
Bracket bars have to be fixed by
screws/washers/ lock washers/nuts M8 on all
suspension brackets.
Start the reflector mounting at the turnaround
box connection. Reflector will be fixed on the
turnaround box connection by screws/selflocking nuts/lock washers/3D-washers M5. For
insulated reflectors [calorSchwank D] the
reflector end with notch on sides shows to the
turnaround box.
The other reflector endings lie on top to each
other on the bracket bars.
The short reflector L=1500 mm is mounted in the
middle of the heater. Note the distance
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
measure of suspension brackets.
The intermediate reflectors have to be fixed
with the both front reflectors [each reflector
with 2 middle reflectors]. At the end of the main
reflector sheet the middle reflector is riveted by
2 stainless steel rivets [this reflectors have
already bores to accept the rivets]. At the other
end an additional short angled bracket either
shape V is fixed at the centre of the main
reflector.
Reflectors and bracket bar will be jointly fixed
by 3x M 5 screws and self-locking nuts.
Front plate, reflector and bracket bar have to
be fixed by screws/self-locking nuts/lock
washers/3D-washers M5.
Mounting of burner unit with valve on the top.
Flue gas connection [Type B23, C]
Flexible stainless steel pipe with connector
flange has to be mounted at the end of the
tube with a gasket.
Accessory
for indirect flue into the room [Type A]
Flue gas diverter code-no. 126 7018 0 or
flue gas adapter code-no. 126 7035 0
Note that the flue gas diverter or adapter is
mounted at the end of the tube.
Note that the flue gas diverter is mounted in a
position so that the flue gas is diverted from the
burner.
Fig. 21: Mounting of infraSchwank D / calorSchwank D 60U
[all dimensions in mm]
29
infraSchwank D / calorSchwank D shape U
Assembly burner kit exhaust gas
collection system
Conversion kit burner kit single heater to
exhaust gas collection system
Article No. 126999 9
Conversion kit includes the components for
converting the burner kit for use in an exhaust gas
collection system and provides the parts for
connecting the exhaust side.
The following steps are required to convert the
burner kit.
Remove the self-tapping screws of the air
pressure switch [APS] fastening and fasten the
2/2-way valve bracket together with APS with
added longer self-tapping screws [Fig. 24].
Fix 2/2-way valve with added 2x M4 screws to
the bracket. Connection bushing with hole
0.6 mm must be showing to the right [Fig. 25
and 26].
Remove the measuring pipe differential
pressure [- contact] between venturi fan and
APS.
Now fit two new measuring pipes between
venturi fan / 2-2-way valve / APS[- contact].
Making sure that the measuring pipe with
damping nozzle 0.6mm is mounted on the
right side.
Attention: Do not cover the bore of the
connecting bushing [Fig. 26]!
Place additional cable gland on right housing
wall IC 4000/1.
Connect connection cable 2/2-way valve [L, N]
to the existing plug-in terminals within IC 4000/1
[type: WAGO, fan voltage output], clamp PE on
PE GV 2, connect plug with 2/2-way valve and
secure with screws.
Close the housing lid IC 4000/1.
After burner kit conversion the exhaust
components must be assembled [adaptor and
damper]. Adaptor is mounted with the seal on
the loose flange of the last radiant tube
[Fig. 28].
Fig. 23 : Scope of delivery conversion kit
Fig. 24: Fit bracket for APS
Fig. 25 : Assembled APS on bracket
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
Bohrung 0,6 mm
Hole 0,6 mm
30
Fig. 26: Hole position connection bushing on right side
infraSchwank D / calorSchwank D shape U
Fig. 27: View burner kit after conversion
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
Fig. 28: Assembly connection parts exhaust gas
31
infraSchwank D / calorSchwank D shape U
3
3
10 Installation
Please consider the pressure drop of the upstream
instructions
Danger of fire and explosion!
Unprofessional handling of gas pipes,
gas connections and the appliance can
produce gas leaks. It is highly dangerous
if gas is ignited!
Working on gas pipes and the
appliances is only allowed by approved
installers.
Mount the flexible connection, so that it
can compensate the longitudinal
expansion of the tube.
Only use flexible connections for the
radiant tube regarding:
• gas
• electricity and
• air [if necessary]
a
Fig. 29: Longitudinal expansion
Gas-pipe-system and mounting of
heaters
Connection of gas pipes to the appliance, supply
and the mounting of the appliance is only allowed
by professional personnel who is registered, holding
a current certificate of competence and in
accordance with the relevant provisions of the gas
safety [installation and use] regulations.
Additional installation notices of national or local
institutions must be observed. The pipe must be
dimensioned in a way that the minimum
connection pressure in front of the gas
combination valve of the individual devices is
available at the nominal thermal load of the entire
system, according to table 6.
b
mounted gas connection and gas filter. For the
detailed pressure drop value of the Schwank gaspipe-systems see table 7.
Minimum connection pressures in front of valve
Natural
gas H*
Natural
gas L*
Propane 15 - 60U
* Natural gas H: Hi,n: 9.97 kWh/m
Tab. 6: min. connection pressures with single-, two-stage or
Pressure drop Schwank gas-pipe-systems
Type Gas pipe system
Natural
gas H
Natural
gas L
Propane 15 - 30U 1/2" / L=800 mm
40 - 60U 3/4" / L=800 mm
Tab. 7: Pressure drop Schwank gas-pipe-systems
infraSchwank D / calorSchwank D shape U
min.
type
15 - 50U
60U
15 - 50U
60U
modulating operation in front of gas combination
valve
infraSchwank D / calorSchwank D shape U
connec-
tion
pressure
[hPa]
151010 - 74 - 5
201414 - 75
2015.215.2 -106 - 7
3021.421.4 - 148
403737 - 2522
15 - 30U 1/2" / L=800 mm
40 - 60U 3/4" / L=800 mm
15 - 30U 1/2" / L=800 mm
40 - 60U 3/4" / L=800 mm
nozzle pressure
single
stage
[hPa]
Natural gas L: Hi,n: 8.57 kWh/m
modulating
max -min.
[hPa]
start step
pressure
Pressure drop
[hPa]
The max. connection pressure is 60 hPa!
In case of contaminated gas pipes and
generally at gas pipes of welded black
steel have to be mounted gas filtergroups directly in front of the heater.
[see page 59].
[hPa]
2
2.5
2
3
1
1
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
32
infraSchwank D / calorSchwank D shape U
[
Note the following points while installing the
gas-pipe-system:
Use only gas lines as per national standards.
Never hang heaters on the gas pipes.
Mount a manual gas cock upstream of every
radiant tube.
Close all gas cocks before carrying out the
leak test and disconnect the connection
between the gas cock and the burner to
avoid damages to the gas regulator and gas
combination valve.
Clean gas pipes before the installation of the
heater. Reconnection after pressure control
and expansion.
Please observe the national standards.
430 mm
Fig. 31: Sideways connection 90° bend
[+/- 10%]
430 mm
[+/- 10%]
Connect the heater with an approved
flexible hose!
Use the following hose length for
infraSchwank D / calorSchwank D shape U
15-30 kW R ½“ length
800 mm
40-60 kW R ¾“
length
800 mm
Article no.
19208450
Article no.
19208460
Mount a flexible hose only with 90° bend or
with 2 x 90° elbow fittings in a 180° bend
according to Fig 30, 31 and 32.
Keep the specified installation dimensions.
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
Incorrect mounting of flexible hoses shown in
Fig 33 [sketches
to ].
430 mm
Fig. 30: Standard connection [vertical] 90° bend
[+/- 10%]
430 mm
+/- 10%]
Fig. 32: Alternative flexible hose 180° -bend with 2 x 90° elbow
Fig. 33: Incorrect mounting of flexible hoses
33
infraSchwank D / calorSchwank D shape U
Gas connection has to be positioned
with 90° or 180° bend in the axle of the
heater to compensate the thermal
expansion of the heater. Otherwise
torsional forces will operate on the hose!
Avoid twisting of the flexible hose!
When tightening the union, counter hold
the nipple on the hose.
Pay attention that the flexible hose will
not be mechanically damaged by tools
etc. Do not buckle the hose.
Do not mount damaged flexible hoses!
Damaged hoses can break due to the
movement of the heater.
Exhaust flue installation single heater
The exhaust system is available an accessory of
the radiant tube heaters. The flue system is
connected at the end of the radiant tube. Note the
information in Chapter 4 „Planning“.
Installation
exhaust collecting system
[herringbone]
The installation of the flue collecting system must
be carried out according to the planning of
Schwank.
After mounting the heaters with their burner kits
including the 2/2-way valve [see page 30] the
connection set F [adapter and damper] have
to be mounted at the end of the tube heater.
The adapter must be fixed with a gasket at the
flange of the last radiant tube.
The spiral tubes for the flue collecting system
with different lengths and dimensions must be
mounted according to Schwank planning.
When assembling the tube elements any burrs
or residue of oil and grease must be eliminated.
All connecting tubes and collecting tubes must
be mounted with a small slope towards the
central exhaust fan [about 0,3 %, means 30 mm
per 10m]. Any dips and sinks in the tubes must
be avoided [to prevent collection of
condensate].
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
The spiral tube elements are connected by
couplings. Each tube element must be fixed by
two self-tapping screws at opposite sides.
Screws may not be fixed at the bottom of the
tubes.
After fixing the tube elements with screws all
tube connections must be sealed carefully with
high temperature silicon [temperature resistant
at least up to 200 °C, named f.e. NOVASIL].
When starting the central exhaust fan for the first
time all tube connections have to be checked
for tightness.
If the Schwank planning requires a condensate
run off, this part must be mounted directly in
front of the exhaust fan [deepest point of the
system]. The condensate run off has to be
connected to a condensate pump or a siphon
[min. water barrier height 30 cm].
34
infraSchwank D / calorSchwank D shape U
Electrical installation
[wiring diagram]
Danger of electric shock!
Electric shocks are highly dangerous!
Working at the electrical equipment of
the appliance is only allowed by
professional personnel observing the
current IEE regulations.
Isolate the electrical supply while
working at the electrical equipment of
the appliance and safeguard the
appliance against unintentional
connection to the circuit.
The gas supply and electrical cable
must be situated on the outside of the
radiation and combustion heat. Only use
heat-resistant cables near the tubes.
The power supply for the heater must be
flexible connected with Ölflex- or
silicone cable.
Modulating operation
lambdaPlus
In the standard case 230 VAC error signal is
given via contact 3 at 4-pin plug.
For modulating operation without MODBUS
communication the modulation signal must
now be connected to contact 3 of 4-pin plug
[Fig. 34].
The wiring between the plug socket and board
is already factory-made. For modulating
operation without MODBUS communication the
red cable on board IC 4000/1 has to be
changed from LO [lock out] to M [modulating]!
Parameter value PP01 of burner control unit
IC 4000/1 is 1 as factory setting [Modbus
communication]. Therefore parameter value
PP01 must be set as 0 for modulating operation
without MODBUS communication [for
procedure, see page 45].
Heater must be connected in such a way that it
always starts at full load. This is ensured by
central control unit SchwankControl Touch or
manual control unit moduSchwank. After a
time delay of at least 2 minutes you can switch
to the partial load stage.
For necessary settings SchwankControl Touch
without MODBUS communication please refer
manual SchwankControl Touch.
Make sure that the polarity of power
Electrical connection
Operation without MODBUS control
1-stage operation
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
Route a flexible 3-wire electrical connection
cable [max. 3 x1.5 mm
kit to the four-pin plug and connect the cable
according to connecting scheme [Fig 34].
Connect 4-pin GDM socket with housing plug on
burner control unit IC 4000/1 of the burner kit.
The power supply for the heater must be flexible
with maximal wire cross-section of 3x 1.5 mm
Ölflex- or silicone cable
In order to disconnect burner kit from the
electrical supply pull the plug out from IC 4000/1.
The 4-pin GDM plug for the power supply
burner kit is included in delivery of the
kit.
2
] for power supply burner
2
Figures 36 and 37 show a complete wiring scheme
without MODBUS communication [relay control]
between the central control unit SchwankControl
Touch and burner kits with burner control IC 4000/1.
Figure 39 shows a complete wiring scheme
between the alternative control unit SRT-1 and
burner kits with IC 4000/1 burner control unit.
supply is correct. If polarity incorrect
control unit IC 4000/1 will not detect the
modulation signal!
35
infraSchwank D / calorSchwank D shape U
Electrical connection
Operation with MODBUS control
Route a flexible 3-wire electrical connection
cable [max. 3 x1.5 mm
kit to the four-pin plug and connect the cable
according to connecting scheme [Fig 34].
Connect 4-pin GDM socket with housing plug on
burner control unit IC 4000/1 of the burner kit.
The power supply for the heater must be flexible
with maximal wire cross-section of 3x 1.5mm
Ölflex- or silicone cable
In order to disconnect burner kit from the
electrical supply pull the plug out from IC 4000/1.
The 4-pin GDM plug for the power supply
Route a flexible 3-wire MODBUS cable
[max 3x 0.5mm
the free cable gland of the burner control unit
IC 4000/1 and connect it according to the
connection diagram [Fig 36].
Maximum length between junction box MODBUS
and connection burner control unit IC 4000/1
may be 0.5m.
At the of each MODBUS communication circuit a
terminal resistance 120 must be set on the
relevant burner control unit IC 4000/1. Resistor is
already loosely plugged into each socket KN 8 of
the burner control unit IC 4000/1. This socket must
then be closed with the resistor.
The necessary MODBUS address assignment is
explained on page 45.
Electrical connection 4-pin plug
1 = neutral N
2 = phase L
3 = optional: error signal output 230 V
= PE
Fig 34: Electrical connection 4-pin plug
burner kit is included in delivery of the
kit.
2
] for the Modbus connection into
2
] for power supply burner
2
Electrical connection
exhaust gas collecting system
[herringbone system]
After conversion of the heaters to operation with
exhaust gas collection system they can be
electrically connected as described above.
Fig. 38 shows the wiring diagram between the
central control unit SchwankControl Touch control
and the peripherally required SchwankControl SAV
1 extension kit and SAV fan monitoring kit.
Further information and wiring schemes for
more different electrical connection
options [e.g. multi-zone operation,
grouping of several central control units
SchwankControl Touch,…] can be found
in „Electrical Compendium“
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
36
infraSchwank D / calorSchwank D shape U
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
Fig. 35: Wiring scheme burner kit infraSchwank D / calorSchwank D with MODBUS control to SchwankControl Touch
37
infraSchwank D / calorSchwank D shape U
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
Fig. 36: Wiring scheme burner kit infraSchwank D / calorSchwank D 1-stage via relay control SchwankControl Touch -
without MODBUS control
38
infraSchwank D / calorSchwank D shape U
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
Fig. 37: Wiring scheme burner kit infraSchwank D / calorSchwank D modulating via relay control SchwankControl Touch -
without MODBUS control
39
infraSchwank D / calorSchwank D shape U
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
Fig. 38: Wiring scheme burner kit infraSchwank D / calorSchwank D exhaust gas collecting system with SchwankControl Touch /
extension kit Fan Control SAV1
40
infraSchwank D / calorSchwank D shape U
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
Fig. 39: Wiring scheme burner kit infraSchwank D / calorSchwank D 1-stage with alternative control unit SRT-1
Fig. 40: Wiring diagram burner kit 1-stage
infaSchwank D / calorSchwank D
Fig. 41: Wiring diagram burner kit modulating
infraSchwank D / calorSchwank D
41
infraSchwank D / calorSchwank D shape U
11 Commissioning
instructions
Before commissioning
A qualified service engineer must carry out this
operation. The correct operation and fixing of the
heater is prerequisite for the warranty. Checking
gas lines and flue system is not included in this
service.
The heaters are only pre-set by the
Check the function of the following equipment:
Exhaust flue
Combustion air supply
Control unit
Safety equipment
manufacturer and must be adjusted for
proper operation according to gas
quality site on site.
For this information contact your local
gas company.
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
Safety of electrical circuit
Pay attention when commissioning!
Vaporization of remaining grease of
metal units may cause greasy mist. This
kind of mist disperses after approx. 30
minutes. During this time the room has to
be ventilated.
42
infraSchwank D / calorSchwank D shape U
Parameter IC 4000/1 and setting
The burner control unit IC 4000/1 is already factory
preset.
The parameters can be read out by the Schwank
Service Software IC 4000 [RS-485 interface board]
and if necessary to be changed.
Parameter selection and settings can made
manually direct at IC 4000/1 by the two push
buttons SW 2 and SW 3 and the 7-segment display.
For this, unscrew the lid of the IC 4000/1 burner
control.
After power supply IC 4000/1 following sequence is
shown on the 7-segment display:
1. segment test, all 7 segments light up
2. software version [two successive numbers]
3. burner control software: 1
Parameter Parameter name and
parameter value definitions
Factory
setting
Set
range
PP01 Setting Communication
1 0 - 1
0: No MODBUS control [e.g. ThermoControl M+]
1: MODBUS contol by SchwankControl Touch
PP02 Drive Fan
1 0 -1
0: Phase angle control driven
1: PWM driven
PP03
[Note 1]
Value phase angle control fan
0 – 80
@ power supply 230V:
value „0” = 153 V, value „80“ = 230 V
according to
type
see Tab. 5,
0 - 80
page 22
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
PP07
[Note 1]
minimal modulation current
40 mA – “PP08 max modulation current – 5 mA”
[Note 2]
according to
type
40 - 160
see Tab. 5,
page 22
PP08
[Note 1]
maximal modulation current
“PP07 min modulation current + 5 mA” – 165 mA
[Note 2]
according to
type
45 - 165
see Tab. 5,
page 22
Note 1: Parameter PP03, 07 and 08 only relevant for modulating operation lambdaPlus
Note 2: PP08 MAX MODULATION CURRENT > = [PP07 MIN MODULATION CURRENT + 5]
Tab 8: Parameter level IC 4000/1
43
infraSchwank D / calorSchwank D shape U
Fig 42: 7-segment display and push buttons IC 4000/1
ON normal working mode DISP1 is blank.
When you need to enter parameter setting:
- Press SW2 and SW3 buttons together for 3
seconds.
- Parameter number “1” is displayed on DISP1.
- Press SW2 to increase the parameter number,
press SW3 to decrease the parameter number.
- When you reached the target parameter
number, press SW2 and SW3 buttons together
for 3 seconds to reach the setting level for the value.
- For parameters PP03, PP07, PP08 parameter number starts to flash on DISP1.
- For parametersPP01 und PP02 parameter value starts to flash on DISP1.
- Now you can increase the parameter value by
pressing SW2, and decrease it by pressing
SW3.
- To store the new parameter setting, press SW2
and SW3 buttons together for 3 seconds.
- Parameter menu is closed and DISP1 is blank
again.
Parameter settings menu has 10
minutes timeout. If you don’t press
any button for 10 minutes, control
exits from parameters menu
automatically without saving the
settings.
Fig 43: MODBUS addressing IC 4000/1 by
External identification
MODBUS address
For a quick external identification of the
assigned MODBUS address, please enter the
corresponding address [number] on the
provided MODBUS-address label by number
stickers or with marker pen.
MODBUS-address label is to stick on side panel
IC 4000/1 housing.
Assignment MODBUS address
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
DIP switches
Dip switch position below
Dip switch position above
For every heater [= burner control unit] it is
mandatory to assign an MODBUS address if it
controlled by SchwankControl Touch.
All heaters are assigned with the MODBUS
address 1 in the delivery state. To change the
MODBUS address, the lid of the IC 4000/1 burner
control unit must be opened.
The MODBUS address is set by the DIP switches
in the lower right side of the board. A maximum
of 31 addresses can be assigned per heating
zone.
44
infraSchwank D / calorSchwank D shape U
Adjusting nominal thermal load at
single-stage operation
Attention!
The pressure control unit is pre-adjusted
on natural gas / propane. Do not put the
appliance into operation uncontrolled.
Adjusting the nozzle pressure
1. Open first the gas cock which is at the end of
the flexible gas hose [Fig. 44].
2. Open the test nipple connection pressure.
Connect the pressure measuring instrument to
the test nipple and determine the connection
pressure.
Close the test nipple after the measurement!
3. Open the test nipple nozzle pressure.
Connect the pressure measuring instrument to
the test nipple and determine the nozzle
pressure.
4. Turn the adjusting screw on the pressure
regulator slowly in the “+” or “-” -direction while
continuously watching the pressure measuring
instrument. Stop turning as soon as the required
nozzle pressure is reached. The required test
nipple nozzle pressure for natural gas H
=14.85 kWh/m3] and natural gas L
[W
o
=12.15 kWh/m3] is shown in Table 5. For
[W
o
natural gas with other Wo-Index [information
from local gas company] you have to
determine the required nozzle pressure based
on the diagram on page 50.
5. Remove the protection cap A [Fig. 45]
6. Put the radiant tube into operation
7. Turn the adjusting screw B [Fig. 45] on the
pressure regulator slowly in the “+” or “-” direction while continuously watching the
pressure measuring instrument. Stop turning as
soon as the required nozzle pressure is reached.
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
8. Put the protection cap A on the valve after the
adjusting.
9. Close the test nipple after the measurement and
check if the test nipple is gas-tight.
Checking adjustment
1. Turn the adjustment screw slightly to “-“
-direction. Nozzle pressure must drop
immediately. If this does not happen, you must
readjust the jet pressure until the point is
reached at which a decrease or increase in the
nozzle pressure is noticeable on the measuring
instrument.
2. Close test nipple after the measurement!
3. Remove the measuring instrument and check if
the test nipple is gas-tight.
Adjusting thermal loads
for modulating operation
lambdaPlus
It is necessary in addition to the mechanical
factory setting of the modulating gas pressure to
adjust the modulating regulator output current
range and the corresponding fan voltage to
match the existing gas quality and electrical
power supply.
Proceed as follows
[Example: 30U; nozzle pressure: 12 / 8,5mbar;
minimum fan voltage: 180 VAC value True RMS]
1. Open lid IC 4000/1.
2. Make sure that gas cock is closed.
3. Put the radiant tube into operation by
activating chimney sweep command on
SchwankControl Touch.
4. Select the parameter level. Press SW2 and SW3
buttons together for 3 seconds
[Fig. 42] until PP01 is shown on the
7-segment display.
5. Press button SW2 [+] to reach PP03.
6. Select the setting level for parameter.
Press SW2 and SW3 buttons together for 3
seconds [fig. 10, p. 15] until PP03 starts flash on
the display.
Now press buttons SW3 [-] oder SW2 [+] until
the observed voltage reaches the required
minimum value for phase angle control drive
[180V].
7. To store the new parameter setting, press SW2
and SW3 buttons together for 3 seconds and
leave the setting level.
8. Open the gas cock which is at the end of the
flexible gas hose.
9. Open the test nipple connection pressure.
Connect the pressure measuring instrument to
the test nipple and determine the connection
pressure.
10. Close test nipple after the measurement and and check that the test nipple is gas-tight.
11. Open the test nipple nozzle pressure.
Connect the pressure measuring instrument to
the test nipple and determine the nozzle
pressure.
12. Put the protection cap A on the valve after the
adjusting.
13. Switch on again the heater by a short dis- and
reconnecting of the power plug [min. 3 sec.].
14. Similar to points 4 – 6 select the setting level for parameterPP08.
45
infraSchwank D / calorSchwank D shape U
Now press buttons SW3 [-] oder SW2 [+] so that
the measured nozzle pressure will be 1 mbar
above the required maximum value
[e.g. 13 hPa].
15. If the value cannot be reached, the maximal mechanical limitation at the modulating
regulator [large adjusting screw C] needs to be
amended.
Afterwards continue with adjusting to the
required minimum value.
16. To store the new parameter setting, press SW2
and SW3 buttons together for 3 seconds and
leave the setting level.
17. Select the setting level for parameterPP07.
Now press buttons SW3 [-] oder SW2 [+] so that
the measured nozzle pressure will be 1 mbar
below the required minimum value
[e.g. 7,5 hPa].
18. If the value cannot be reached, the minimal mechanical limitation at the modulating
regulator [small adjusting screw B] needs to be
amended.
Afterwards continue with adjusting to the
required minimum value.
19. To store the new parameter setting, press SW2
and SW3 buttons together for 3 seconds and
leave the setting level.
20. Adjustment of the mechanical pressure range of modulating regulator: Be left in chimney
sweep mode and disconnect the power supply
modulating regulator.
21. Turn the large, outer adjusting screw B on the
regulator slowly in the “+” or “-” -direction while
continuously watching the pressure measuring
instrument. Stop turning as soon as the required
nozzle pressure for minimum load is reached
[e.g. 8,5mbar].
22. Re-connect power supply and turn the small,
inner adjusting screw C on the regulator slowly
in the “+” or “-” -direction while continuously
watching the pressure measuring instrument.
Stop turning as soon as the required nozzle pressure for maximum load is reached
[e.g. 12mbar].
23. To check the settings, repeat the procedure
again.
Put the protection cap A on the valve after the
24.
adjusting.
25. Close the test nipple after the measurement and check that the test nipple is gas-tight.
26. Switch off the heater by deactivating chimney
sweep command.
Fig. 44: Gas cock with integrated TSD
Fig. 45: modulating regulator with adjustment screws
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
46
infraSchwank D / calorSchwank D shape U
Fig. 46:
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
Dia. 1:
Board IC4000/1 with 7-segment display and push buttons SW 2 / SW 3
Fan voltage phase angle control drive vs. value PP03
47
infraSchwank D / calorSchwank D shape U
Commissioning exhaust gas
collecting system [herringbone]
Before first start up
For first start up and commissioning of the system
please request a Schwank service engineer to
attend Adjustment by Schwank is a condition of
our warranty.
Gas fired radiant tube heater systems have to be
installed by a qualified engineer according to
local laws and rules in force.
Start up
First check the complete electrical supply and
connections of the system. All plugs at the
burner units must be taken off. Check the
correct connection of the plugs. After this the
room temperature regulation system is switched
on. Check the connection and the direction of
the rotation of the central exhaust fan.
Check the complete connecting and
collecting tube system for a small slope towards
the central fan [no sinks for condensate!].
Check the slope from central exhaust fan to the
chimney.
Check the complete flue gas system for
tightness with central exhaust fan on [burners
off]. In case of leaks ensure tightness by high
temperature silicon.
Correct start up and commissioning without
system tightness is not possible!
Commissioning
The safe evacuation of the exhaust gases of all
heaters is ensured by correct adjusting of
negative pressure. This is done by fixing the
dampers at the end of the heaters and may be
also the damper in front of the central exhaust
fan at the following values.
Required negative pressure level at test nipple
nozzle pressure [cold conditions]:
- infra/calorSchwank D 15-60U: -0,8…-1,5 hPa
Adjustment with central fan on, burners off.
Start the adjustment with the heater furthest
away from the central exhaust fan. Take the
negative pressure at the measurement nipple
at the bottom of the burner unit. Therefore take
off the silicon tube between nipple and
solenoid valve. Negative pressure is adjusted by
moving the damper at the end of the tube
heater. After adjustment the silicon tube has to
be connected again between the nipple and
solenoid valve.
Adjustment of the other burner now follows with
the same procedure.
Having adjusted all the heaters the negative
pressure of the units may have changed. A
second thorough check and adjustment of the
negative pressure of the units is necessary. Then
the positions of the dampers must be fixed by
the screw.
Now the heaters can be started up [opposite
sequence to adjustment].
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
Now the negative pressure at test nipple nozzle
pressure is checked [burners off, dampers at the
end of the tubes completely open]. The
minimum negative pressure under these
conditions must be >1hPa.
In case the negative pressure level is lower
please check again the tightness of the
complete system. Also check that the damper
in front of the central exhaust fan is open.
48
infraSchwank D / calorSchwank D shape U
Determination of nozzle pressure
Example for the determination of the nozzle pressure
Diagram 2: Wobbe-Index profile Natural gas infraSchwank D / calorSchwank D 15 – 50U
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
Diagram 3: Wobbe-Index profile Natural gas infraSchwank D / calorSchwank D 60U
49
infraSchwank D / calorSchwank D shape U
12 Service guide /
Trouble shooting
Maintenance and annual check
A regular maintenance is the requirement for a
faultless operation of the appliance.
According to the National Standard Regulations,
heating-systems with radiant tubes must be
checked at least once a year.
Maintenance and troubleshooting is only allowed
by professional personnel that is competent and
instructed in radiant tubes.
Before starting work on the heater the
gas cock has to be closed.
Maintenance must include the following checks:
Check surface of combustion chamber
tubes/radiant tubes and if fit necessary clean up.
Check the slope of the tubes [3 mm/m in
direction of the turnaround box connection]
Check correct and firm connection of the
reflectors and intermediate reflectors.
Check tightness of gas-carrying parts and
connections.
Check the flexible gas hose for correct
installation and tightness.
Check electrical connection to the burner kit.
Check the air/flue-system
Check firm mounting and tightness of fan
burner kit.
Visual check impeller fan for damage traces
and balanced run
Check condensation pipes.
Check the safety functions of the ignition- and
ionisation-controls, gas valves and operation
indicator
Check functionality Functional test of control
and regulation equipment, switchgear and
signal lights
Check gas filter in case of reduced line
pressure, in case of pollution change filter pad
[spare part kits gas filter]
Check correct parameter setting.
Check safety distances and information boards.
Any deviations must be fixed immediately. Defect
parts must be changed directly.
Maintenance work on gas valves, flame sensing
and safety devices can only be maintained by the
manufacturer or authorized personnel.
After the end of the maintenance work,
the device must be put back into
operation!
Version 021 infra D Form_U 16/19 Technische Änderungen vorbehalten
50
infraSchwank D / calorSchwank D shape U
Error codes
If an error occurs, all gas valves are closed and the
lockout message output [230V] is activated and
the error code is stored internally and transmitted
by MODBUS to the central control unit
SchwankControl Touch.
The fan still runs for 180 seconds in the post-purge
time with maximum fan speed. After that, the
heater is completely switched off and locked
The lock can be reset by activating the reset
function SchwankControl Touch or switching off
the power supply [min. 3 seconds] of the heater.
Error code "A" does not put the heater in a resetrequiring lock, but only switches off the heater.
Error
code
1
2
3 APS
4 APS
Error name Description
Ionization error
during start
Ionization error
during operation
open error
[APS=
air pressure switch]
closed error
If flame is not
detected for the 2
ignition attempts
during start
If flame is not
detected for the 2
ignition attempts
after a flame loss
Error Is given if phase
angle control type is
selected [PP02=0]
Error is given if APS
contact opens
during start or
operation
Error Is given if phase
angle control type is
selected [PP02=0]
7 Gas valve
feedback error
8
10
Ionization
component error
MODBUS signal
missing error
Tab 9: Error code IC 4000/1
Error in gas valve
drive or feedback
check circuitry
Ionization signal is
out of range
If PP01=01 selected
as MODBUS control
and for more than
3 minutes no
MODBUS signal has
been received this
error is given and
heater switch off.
Burner control is not
locked.
Error is given if APS
contact already
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
5 Encoder signal
missing error
6 Unexpected
“encoder signal
”error
closed during start
Error Is given if PWM
control is selected
[PP02=1]
Error is given if no
encoder signal
detected or fan
speed < 10 RPS.
This error is given
after 3 sec.
Error Is given if phase
angle control type is
selected [PP02=0]
and encoder signal
is detected > 30 RPS.
This error is given
after 3 sec.
51
infraSchwank D / calorSchwank D shape U
Troubleshooting / Error causes
Error code 1:
- no gas [e.g. gas line not vented, gas cock
closed]
- faulty gas valve
- Ignition and ionization electrodes damaged /
dirty
- wrong setting gas throttling screw
- poor grounding
Error code 2:
- poor low ionization current [<0,7A DC]
- too low connection pressure
Error code 5:
- PWM fan don’t run
[e. g. impeller broken , motor broken]
- PWM cable broken
Error code 7 + 8:
- internal error IC 4000/1
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
Error code 9:
- Wrong setting fan speed parameters
[PP04, PP05, PP06]
- Damaged fan [e.g. bearing failure]
Error code 10:
- interruption MODBUS connection >3 minutes
- wrong wiring between IC4000/1 and
SchwankControl Touch
Example: right connection B and - / A and +
MODBUS Assignment
IC 4000/1
B A COM
+ - REF
MODBUS Assignment
SchwankControl
Tab 10: Error causes
52
infraSchwank D / calorSchwank D shape U
_g
13 Change of gas family
Fig. 47: Change of gas family
Burner baffle [only 15 / 20 / 30 / 40U]
Burner cup
Burner nozzle
Air baffle plate [only 15 / 20 / 30 / 40U]
Fan air restrictor
Instruction to change the gas family
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
1. Change the burner nozzle
2. Change the burner ceramic tile or the whole
burner cup only for 50 / 60U
3. Adjust the new nozzle pressure
[see Tab. 5, page 23]
4. Adjust the new start step pressure
[see Tab. 5, page 23]
5. Stick on the new rating label
53
infraSchwank D / calorSchwank D shape U
14 Accessories
Ball guards
Ball protection grids acc.18032-3 for using heaters in
sport halls [grid 40x40mm].
Delivery scope
Mounting set complete for each type of heater
existing of:
infra/calorSchwank D shape U 15U 20U 30U 40U 50U 60U
[Description for heater infra/calorSchwank D 30 U,
other types similar]
1. Mounting heater as described in chapter 9,
page 24-29].
Note the required sideways slope of the heater of
20mm in ball protection grid application [Fig. 48].
2. Fix end bracket at inner side of turnaround box,
open and close again 4 nuts M8 [Fig. 50]
3. Fix two angle brackets at each tube hanger
[screws M8 x 60, nuts] [Fig. 51]
Screw on angled brackets at the inner holes of
suspension bracket
NOTE 50-60kW: Screws to fixing suspension bracket
bars must be inserted from below.
4. Holding bracket put loose on the first reflector [view
from burner unit] and screw together with two
angle brackets [screws M8 x 60, nuts], holding
bracket remain axially movable
12670800 1267435012670810126708201267083012674360
NOTE: Use the right holding bracket –
difference infraSchwank D or calorSchwank D
– both in the delivery scope [Fig. 52]!
5. At all junctions ball protection segment to the
angle brackets the grid edges must be cut
free to ensure a gap-free fitting of the ball
protection segments grid to the reflector.
6. Assembling segments ball protection grids
starts on the turnaround box [last suspension bracket for shape L]. Put first segment ball
protection grid L=2963 mm from below on
end bracket and angle brackets of the next
suspension bracket – Put clamps on stud
bolts M8 and mount with self-locking nuts
Mount clamp loose on one stud bolt of angle
bracket for further assembling next
protection grid [Fig. 53].
7. Put next segment ball protection grid
L= 1843 mm from below on angle brackets
and mount clamp with self-locking nuts M8,
clamp and angle bracket connect two
segments ball protection grid to each other.
Mount clamp loose on one stud bolt of angle
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
54
infraSchwank D / calorSchwank D shape U
bracket for further assembling next
protection grid.
8. Put next segment ball protection grid
L= 1843mm from below on angle brackets
and mount clamps with self-locking nuts M8
Last segment ball protection grid L= 1843mm
protects the burner unit at the bottom.
NOTE 50-60kW: Ball protection grid on fan
side has to be cut for mounting and
compensation thermal length expansion of
max. 8cm [Fig. 54]!
9. After finish assembling of all ball protection
grids fix holding bracket with 3x self-tapping
screws on the reflector.
10. Push on protection grid burner top from
behind over ball protection grid and burner
up to the suspension bracket. Note that the
lower short bending is on the left side in view
from behind.
Fix burner protection grid burner top with
supplied cable straps or similar at bottom
protection grid.
11. Protection grid burner top has to be cut
holes depends on installation on-site for flue
system and may be gas line. Connect flue
system pipes and gas line.
NOTE: Select the cutouts large enough to
compensate the thermal length expansion of
the heater!
12. Insert front protection cover burner between
front cover plate reflector and burner unit
and fix it with supplied cable straps or similar
on protection grid burner top [Fig. 55].
13. Protection grid burner end side has to be cut
hole depends on installation on-site for gas
line.
Fix with supplied cable straps or similar on
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
protection grid burner top.
Please note the required number and
length of segments ball protection grids
for each type of heater. Compare this to
the tabular and graphical overview.
Fig. 48: sideways slope heater in ball protection application
Fig. 49: Overview of ball guards
55
infraSchwank D / calorSchwank D Form U
Fig. 50: Fixed end bracket on turnaround box
Fig. 51: Fixed angle bracket on suspension bracket
Fig. 52: Holding bracket infra D and calor D
Holding bracket calor D shape U
Holding bracket infra D shape U
Fig. 53: Loose mounted clamp
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
Cut out on fan side
Fig. 54: Cut out on fan side for mounting and compensation
Fig. 55: Fixing front protection cover burner on protection grid
thermal length expansion - only 50/60kW
burner top
56
infraSchwank D / calorSchwank D shape U
Reflector elongation
Vertical elongation of reflectors b=415mm for
thermal protection.
The numbers of reflector elongation [single sheets]
is depending on required protection [one side
both side, protection length] and the power of
the radiant heater.
Delivery scope
The required reflector elongation can be
compiled depending on the extent of necessary
protection out of the following basic elements:
02676300 reflector elongation L= 3000 mm
02676310 reflector elongation L= 3000 mm
End segment U [only for for end segment
heater shape U with turn around box]
2. Mount bolts with spacer sleeves and mounting
brackets A at required positions [Fig. 56].
3. If required fasten mounting bracket B to turn
around box by losing 4 lower hex. nuts M8,
placing mounting bracket on tube flanges and
fastening hex. Nuts [Fig. 58].
4. Place reflector elongation C on mounting
brackets A and bolt them together with
reinforcement plates D [self-securing nut M8]
[Fig. 56].
5. Bolt reflector elongation loosely together at
overlapping by means of M8 bolt/nuts.
6. In case of one-sided load on bolts mount
additional mounting bracket E [Fig. 57].
7. If using mounting bracket B mount safety lock F
[Fig. 58].
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
In the case of heaters with end reflector
the last hanger at the burner side must be
placed at the junction of the reflector
and the end reflector.
A
D
Fig. 56: Mounting of reflector elongation on hanger
C
Fig. 57: Mounting of reflector elongation on first hanger with
additional bracket
E
F
Fig. 58: Mounting of reflector elongation on turn around box
with safety lock
B
57
infraSchwank D / calorSchwank D shape U
Set angled mounting tubes
Bracket to ensure form and position of reflectors
when the heater is mounted angled [>15°].
Mount bracket to at each junction point
reflector/reflector, not at reflector end caps.
Set is only required for heaters 15 – 40kW.
Delivery scope
Mounting set consist of:
numbers of brackets
mounting material
Assembling instruction
1. Assembling and mounting of tubes complete
without [see chapter 9, page 24-27].
2. Lay first reflector on turnaround box and first
hanger, fix it at turnaround box with two
screws.
3. Fix angled bracket E with screws and nuts M8
at first hanger, bracket under reflector.
4. Put on next reflector, reflectors are fixed to
another by 3 screws/nuts M5, middle screw
through angled bracket.
5. Further assembling as described in chapter 9,
page 24-27.
E
Fig. 59, 60: Assembling order reflector elongation
Gas filter groups
To avoid technical problems with the gas
combination valves which are caused by
pollution of dust or rust coming out of the gas pipe
have to be mounted a
gas filter group ¾“ [gas filter + premounted
double nipple] for each tube heater 50/60U.
For tube heaters 15-30U a similar gas filter group
½“ has to be ordered in case the gas pipe is
made of black steel [welded].
gas filter group Rp ½“
for 15-30kW
gas filter group Rp 3/4“
for 40-60kW
Assembly instruction
Direct installation between flexible gas pipe and
valve burner unit, with a slight radial slope for
better cleaning the filter bottom! In case of strong
polluted filter pad use the corresponding spare
part set for gas filter.
Pay attention to the flow direction of the filter!
Fig. 61: Mounted gas filter group at tube heater
Art.-no: 192 0756 0
Art.-no: 192 0757 9
58
infraSchwank D / calorSchwank D shape U
Water protection cover burner kit
Protection cover of the burner kit 15-60U with
protection class IP 55 against water or aggressive
mediums, cover complete in stainless steel.
In delivery scope a mounting set existing of:
Protection cover with inlet air adapter
[premounted and sealed]
,
hinged cover plate and premounted
surrounding rubber seal
Gas inlet connection with union fitting
[premounted]
Gasket
for mounting water protection cover
and radiant tube
Montagehinweise
,
2
1. Divide gas inlet connection at the union
fitting.
2. Install with sealant the half of the divided gas
Fig. 62: Scope of delivery water protection cover
inlet connection with coupling fitting to male
thread gas connection burner unit.
Note 40-60kW: First replace reducing nipple
¾“x ½“ from burner unit!
3. Install with sealant the half of the divided gas
inlet connection with coupling fitting to male
thread gas connection burner unit.
Note 40-60kW: First replace reducing nipple
¾“x ½“ from burner unit!
4. Pass other half gas inlet connection through PG
gland and connect with burner unit. Union
fitting first tighten by hand.
Access to the burner kit for assembling is given
via the inspection opening on the top of the
cover.
5. Stick gasket
on protection box with silicon.
Mount complete protection box with burner kit
inside at radiant tube flange with gasket
between tube flange and protection box. Fix
front fixing bolt of the burner unit tight with
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
flange radiant tube.
6. Tighten union fitting of the gas inlet connection
with tool.
7. Assemble electrical connection through PG
grand and connect with device plug, if
necessary pass MODBUS communication cable
through the second PG grand.
8. Fit tight the counter nuts of all PG glands.
9. Connect the heater with an approved flexible
gas hose.
Note 40-60kW: Mount reducing nipple
¾“x ½“on outer thread gas inlet connection with
sealant!
10. Start tube heater, check gas pressures.
Fig. 63: Mounted burner kit in protection cover with
gas inlet and electrical connections
Fig. 64: Complete mounted and closed water protection cover
11. Close hinged cover plate and inspection
opening water protection box with wing screws.
1
3
59
infraSchwank D / calorSchwank D shape U
tetraSchwank
Increase energy efficiency through utilisation of
condensing technology from the exhaust gas heat
by counter flow exchanger between the heater
and wall/roof terminal.
Assembly instruction
Before starting installation tetraschwank the
ventilator must be plugged with high-temperature
resistant sealing compound and secured with at
least 3 sheet metal screws.
Mount grating of suction opening and fixing
bracket on the ventilator with sheet metal screws.
Ventilator must be hang separate.
Note the suction direction of the ventilator.
Note the outflow direction downwards of the
ventilator.
tetraSchwank heat exhanger should be mounted
with slight slope [3 mm/1m] to the T-piece.
An extension of the flue gas installation is
permitted only in exceptional cases.
tetraSchwank must be suspended by two
premounted fastening clamps. Chains or steel
cables have to be fixed in vertical direction.
A condensate drain must be fitted with a siphon
at the T-piece.
Condensate pipes must be installed with a slope
to the discharge into the sewer system.
Connect the ventilator as shown in Fig. 41 to the
central control unit Schwank Control Touch.
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
Electrical connection ventilator
Fig. 65: Electrical connection tetraSchwank to SchwankControl Touch
60
infraSchwank D / calorSchwank D shape U
13
11 19
15 Spare parts
10
Fig. 66: Spare parts infra D / calor D 20U
9
8
Pos. Part Art.-No.
Burner kit infra D / calor D 15U Natural Gas H 126 9211 1
Burner kit infra D / calor D 20U Natural Gas H 126 9221 1
1
2 Radiant tube L 3050 mm infra D / calor D [not in Fig. 66] 126 7020 0
3 Radiant tube L 3050 mm with turbulator infra D / calor D [not in Fig. 66] 126 7055 0
4 Radiant tube L 4540 mm infra D / calor D 126 4722 0
5 Radiant tube L 4540 mm infra D / calor D with turbulator 126 7056 0
6 Radiant tube L 5950 mm infra D / calor D [not in Fig. 66] 126 7199 0
7 Radiant tube L 5950 mm stainless steel with welded flanges [not in Fig. 66] 126 7220 0
8 Gasket between tubes and burner infra D / calor D 126 7048 0
9 Turnaround box 126 7015 0
10 Reflector infra D shape U [L 3000mm] 126 7011 0
11 Reflector calor D shape U [L 3000mm] 126 7062 0
12 Reflector short infra D 20U and 60U [L 1500 mm] 126 7221 0
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
13 Reflector short calor D 20U and 60U [L 1500 mm] 126 7234 0
14 Intermediate reflector infra D / calor D 60U L 1500mm [not in Fig. 66] 126 7224 0???
15 Mounting sheet for in intermediate reflector [not in Fig. 66] 126 7464 0
16 Suspension bracket infra D / calor D shape U 15- 40 kW 126 7012 0
17 Suspension bracket infra D / calor D shape U 50- 60 kW 126 7707 0
18 Suspension bracket bar 50-60 kW [not in Fig. 66] 126 7708 0
19 Tube bar 126 4529 5
20 Mounting set infra D / calor D 15U [not in Fig. 66] 126 7102 0
21 Mounting set infra D / calor D 20U [not in Fig. 66] 126 7129 0
22 Mounting set infra D / calor D 30U [not in Fig. 66] 126 7103 0
23 Mounting set infra D / calor D 40U [not in Fig. 66]) 126 7116 0
24 Mounting set infra D / calor D 50U [not in Fig. 66] 126 7111 0
25 Mounting set infra D / calor D 60U [not in Fig. 66] 126 7222 0
Tab. 12: Spare parts infraSchwank D / calorSchwank D 15 -60U
Burner kit infra D / calor D 30U Natural Gas H 126 9231 1
Burner kit infra D / calor D 40U Natural Gas H 126 9241 1
Burner kit infra D / calor D 50U Natural Gas H 126 9251 1
Burner kit infra D / calor D 60U Natural Gas H 126 9261 1
12
8
16
61
infraSchwank D / calorSchwank D shape U
Spare parts infraSchwank D / calorSchwank D 15-60U
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
Fig. 67: Spare parts burner kit
Spare parts burner kit infra D / calor D 15-60U
Pos. Part Art.-No.
1 Spark igniter with ionisation cable 127 0246 9
2 Ignition wiring with plug 126 7021 5
3 Spare part burner control unit IC 4000/1 for infraSchwank D / calorSchwank D 126 7496 5
4 Pressure switch DL1E with damping nozzle 192 0217 8
5
6
7
8 Spare part HONEYWELL for HONEYWELL 1-stage / modulating VK 4105N 5016 192 0761 3
9 Spare part gas valve HONEYWELL for HONEYWELL2-stage/ Natural gas VK 4115Q 2004 192 0766 0
10 Spare part gas valve HONEYWELL for HONEYWELL2-stage/ Propane VK 4105Q 2010 192 0766 1
11 Connection cable modulating regulator 192 1144 5
12 Burner cup steel complete infra D / calor D 15-40U Natural gas, 50-60U Propane 126 7219 0
13 Burner cup steel complete infra D / calor D 50-60U Natural gas 126 7468 0
14 Fan complete with venturi infra D / calor D 15-40U with transport lock - in cardboard126 7684 0
15 Fan complete with venturi infra D / calor D 50-60U 126 7053 0
16 Gas filter group ½“ [for infra D / calor D 15–30U] 192 0756 0
17 Gas filter group ¾“ [for infra D / calor D 40–60U] 192 0757 9
18 Spare part kit for gas filter ½“ 192 0758 0
19 Spare part kit for gas filter ¾“ 192 0759 0
20 Replacement kit faulty Modulation Box to IC 4000/1 126 7496 6
Tab. 13: Spare parts infraSchwank D / calorSchwank D 15 - 60U
Spare part gas valve cpl. premounted – replacement HONEYWELL for SIT
infra D / calor D 15-60U / 1-stage with cable valve – in cardboard
Spare part gas valve cpl. premounted - replacement HONEYWELL for SIT 2-stage / Natural gas
infra D / calor D 15-60U / with cable for valve and 2-stage coil – in cardboard
Spare part gas valve cpl. premounted - replacement HONEYWELL for SIT 2-stage / Propane
infra D / calor D 15-60U / with cable for valve and 2-stage coil – in cardboard
126 7532 1
126 7536 1
126 7536 2
The reducing nipple ¾” to ½” installed on site for heaters 40U to 60U has to be used again
[position 5-7].
62
infraSchwank D / calorSchwank D shape U
16 EC type examination certificate
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
63
infraSchwank D / calorSchwank D shape U
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
64
infraSchwank D / calorSchwank D shape U
17 EC declaration of conformity
Version 021 infra D Form_U 16/19 _INT Technical specification subject to change
65
infraSchwank D / calorSchwank D shape U
p
]
p
]
18 Product information related to Ecodesign
Regulation No 2015/1188
Values
Nominal heat input [kW] @ NCV
Minimum heat input [kW] @ NCV
Minimum heat input as percentage of
nominal heat in
h
Therm al
at nominal heat input
h
Therm al
at minimal h eat input
Radiant factor RF
at nominal heat input
Radiant factor RF
at minimal h eat input
Auxiliary electricity consumption
at nominal heat input
Auxiliary electricity consumption
at minimal h eat input
Heat output control type
Space heating emissions NOx @ GCV
[mg/kWh]
Seasonal energy efficiency [%]
[%] @ GCV
[%] @ GCV
ut [%
nom
min
[%]
[%]
@ NCV
@ NCV
el
[kW]
max
el
[kW]
max
15/1 U 15/M+ U 20/1 U 20/M+ U 30/1 U 30/M+ U 40/1 U 40/M+ U 50/1 U 50/M+ U 60/1 U 60/M+ U