Schwank deltaSchwank Series, 310U, 950U, 1260U, 320U Technical Manual

...
p
j
g
deltaSchwank
Radiant Tube Heater with pneumatic gas-/air ratio control
310U / 320U / 625U / 635U / 950U / 1260U
single heater and flue gas collection system [herringbone] type F
Version 003 deltaSchwank 16/19 INT
Technical s
ecification sub
Technical
Technical Instructions
Operating Instructions
Legal Requirements
Manual
Assembly Instructions
0085CS0487
Installation Instructions
Commissioning
Service Guide
ect to chan
e
SCHWANK GmbH
Bremerhavener Str. 43 • 50735 Cologne • Germany Postfach 62 02 49 • 50695 Cologne • Germany
Tel.: + 49 [0] 221 / 7176 0 Fax: + 49 [0] 221 / 7176 288 Internet: www.schwank.de
Schwank companies in: Austria Belgium ▪ Canada ▪ China Czech Republic France Germany Great Britain Hungary Netherlands Poland Romania Russia Slovakia Ukraine USA Distribution in more than 40 countries worldwide
deltaSchwank
1 Introduction .......................................................................................................................................................... 4
2 Your safety ............................................................................................................................................................ 4
Notes for your safety ................................................................................................................................ 4
General Notes .......................................................................................................................................... 4
3 Scope of Delivery ................................................................................................................................................ 5
4 Planning ................................................................................................................................................................ 7
Position of suspension .............................................................................................................................. 7
Positioning ................................................................................................................................................. 8
Air supply / Exhaust Requirements ......................................................................................................... 9
5 Legal Requirements .......................................................................................................................................... 18
6 Operation ........................................................................................................................................................... 19
Switching on the heater ........................................................................................................................ 19
Switching off the heater ........................................................................................................................ 19
Fault ......................................................................................................................................................... 19
Maintenance .......................................................................................................................................... 19
7 Technical specification .................................................................................................................................... 20
Technical data ....................................................................................................................................... 22
8 Operating description ...................................................................................................................................... 24
9 Assembly instructions ........................................................................................................................................ 25
10Installation instructions ...................................................................................................................................... 35
Gas-pipe-system and mounting of heaters ........................................................................................ 35
Exhaust flue installation single heater .................................................................................................. 37
Installation exhaust collecting system [herringbone] ....................................................................... 37
Electrical installation [wiring diagram] ............................................................................................... 38
Electrical connection Operation with MODBUS control ................................................................... 38
Electrical connection exhaust gas collecting system ....................................................................... 38
11Commissioning instructions .............................................................................................................................. 42
Before commissioning ........................................................................................................................... 42
Parameter IC 4000/1 and setting ......................................................................................................... 43
Assignment MODBUS address .............................................................................................................. 44
External identification MODBUS address ............................................................................................. 44
Adjusting nominal heat load / Modulating range ............................................................................ 45
Commissioning exhaust gas collecting system [herringbone] ......................................................... 47
12Service guide / Trouble shooting .................................................................................................................... 48
Version 003 deltaSchwank t6/19 Technical specification subject to change
13Change of gas type ......................................................................................................................................... 50
14 Accessory ........................................................................................................................................................... 51
15 Spare parts ......................................................................................................................................................... 52
16 EC type examination certificate ..................................................................................................................... 54
17 EC declaration of conformity .......................................................................................................................... 56
18 Product information related to Ecodesign Regulation No 2015/1188 ...................................................... 57
Maintenance and annual check [herringbone] ............................................................................... 48
Error codes .............................................................................................................................................. 49
Troubleshooting / Error cause ............................................................................................................... 50
tetraSchwank ......................................................................................................................................... 51
Spare parts radiant kit deltaSchwank ................................................................................................. 52
Spare part bluTek-burner kit deltaSchwank ...................................................................................... 53
3
deltaSchwank
1 Introduction
Thank you for choosing a high efficiency SCHWANK radiant tube.
Your deltaSchwank is a modern and low-pollution tube heater for economic and comfortable heating of industrial and commercial buildings.
The design and operation of the heater are according to the requirements of the existing standards.
Please read this manual carefully before using the heater. Please follow carefully all instructions and warnings. The manufacturer will not be held responsible for damages resulting from installation errors or failure to comply with the manufacturer’s instructions.
Follow carefully all warnings in chapter 2 “Your Safety”.
These tube heaters are constructed exclusively for the application of large industrial and commercial space heating. Any other use is not permitted and therefore Schwank is not liable for any improper use.
2 Your safety
You will find the following symbols in this manual:#
Danger!
Note that you and others can be hurt.
Attention! Note that the appliance can be
damaged.
Danger! Note that electrical shocks can be very dangerous. Pay attention while working on the electrical equipment.
Advice!
You find additional instructions about the application/handling of the heater.
Notes for your safety
This appliance is designed according to the requirements of the existing standards. Nevertheless it is possible that dangers for you and others result from the installation and/or operating errors.
To avoid this, please read and follow the instructions carefully.
General Notes
Only use the radiant tube if it is in a technically faultless condition.
Make sure that all persons who operate, assemble, install, commission, maintain or repair this device have read this technical manual and keep the technical instructions in the field. Observe the generally valid legal and other binding rules for accident prevention. Do not make any modifications, attachments or conversions to the device without the express permission of Schwank GmbH. Interventions or repairs to this equipment should only be made by authorized installers using spare parts specially approved for use with this equipment. Otherwise, the valid EC-Type Examination Certificate and the operating permit for this device will cease to exist and the manufacturer's liability for the product and its functional safety will be void.
Safety for the electrical equipment
Danger of electrical shocks! Electrical shocks can be very dangerous! The electrical installation must be carried out by a qualified service engineer following the existing national and international standards.
Check the electrical equipment regularly. Defect wires etc. must be replaced immediately.
The appliance must be cut off from the power supply while working with the electrical equipment. Make sure that nobody can connect the appliance to the power supply while you are installing or maintaining the unit.
After-sales Service
For all installation operations, start-up, gas changes, etc. always consult a qualified service engineer.
In case of doubt, contact SCHWANK GmbH, phone + 49 [0] 221 / 7176 0.
Version 003 deltaSchwank 16/19 Technical specification subject to change
4
deltaSchwank
change
3 Scope of Delivery
Fig 1: Radiant tube heater deltaSchwank
Radiant tube
full-isolated reflector
Combustion
bluTek­burner kit
Suspension bracket
Scope of Delivery
The radiant tube deltaSchwank consists of following main kits:
bluTek-burner kit:
with heat-input related bluTek-burner, gas-/air ratio control unit, automatic gas burner control IC 4000/1, wiring, operating indicator
Radiant kit:
combustion chamber with double tube design,
Version 003 deltaSchwank 16/19 Technical specification subject to
radiant tubes with U-bend element, flange gaskets, corrosion resistant, radiant-optimized and full-isolated reflector with end cap and suspension brackets
Accessories
Central control unit SchwankControl Touch with
temperatures and operating schedules, MODBUS control
Gas hose connection unit with integrated gas
cock and TSD
Gas filter Supply air- / exhaust -system Exhaust gas heat exchanger for the utilisation
of condensing technology - tetraSchwank
Fastening-suspension set [system Gripple]
5
deltaSchwank
Structure of bluTek-burner kit
14 15
Fig 2: bluTek-burner kit
13
1
1. Automatic burner controller IC 4000/1
2. Gas-/air ratio control unit
3. Test nipple connection pressure
4. Throttle screw gas volume
5. Adjustment screw OFFSET
6. Test nipple OFFSET
7. Measuring pipe negative pressure air intake side
8. bluTek burner
9. Ignition and ionisation electrode
10. Ignition cable
11. Air intake connection element
12. Adapter air intake / venturi
13. Corrugated gas pipe
14. Gas connection [bulk head fitting]
15. 4-pin power supply socket
16. Adapter fan / bluTek-burner
17. Perforated cover adapter
18. Top lid [access to gas valve]
18
2
Fig 3: View from above gas combination valve
16
34
gas-/air ration control unit
5
Version 003 deltaSchwank 16/19 Technical specification subject to change
8 9101112
17
6 7
6
deltaSchwank
change
4 Planning
Room temperature control
Radiant tube systems for the full heating of large rooms must be equipped with a temperature control.
Section heating is allowed without temperature control.
Position of suspension
Suspension height
Radiant tubes must be positioned so that no one in the radiation area is exposed to an extreme high heat level. This is ensured when the minimum suspension heights shown in the following table are adhered to:
Nominal thermal load in kW
Suspension height in m
[max. radiation 200 W/m2 ]
according to G 638-2
[t
=15°C, full heating]*
Ambient
A = horizontal suspension
Distances to flammable materials in the radiant area
Radiant tubes must be positioned so that the surface temperature of:
components with flammable materials, flammable equipment stored flammable materials
never rises above 85° C.
10 3,5 m 20 4,5 m 25 4,9 m 35 5,5 m 47 7,7 m 58 9,0 m
Tab 1: Minimum suspension heights [see Fig 4]
Key:
A = Minimum height when hanging horizontally * Please contact Schwank for determination of suspension
heights on other ambient temperatures
Type a [cm] b [cm] d [cm]
Version 003 deltaSchwank 16/19 Technical specification subject to
deltaSchwank 310U 130 40 20
deltaSchwank 320U 130 40 20
deltaSchwank 625U 145 40 20
deltaSchwank 635U 180 40 20
deltaSchwank 950U 280 40 20
Fig 4: Suspension heights and distances for horizontal
application
Direction of radiation
Radiant tubes deltaSchwank can be positioned only horizontal. For this purpose suspension steel chains and cables are installed at the suspension brackets.
deltaSchwank 1260U 350 40 20
Tab 2: Safe distances [see Fig 4]
Key:
a = Minimum radial safety distance [inside radiation area] b = Minimum upper safety distance when hanging horizontally d = Minimum lateral distance to supply pipes outside radiation
area
7
deltaSchwank
g
Positioning
The radiant tube can be mounted with
chain links [welded] min. 4 mm strong adjustable steel cable 3 mm strong
[Schwank accessories]
If you chose chains please use bolts with lock nuts for fixing the chain to the suspension bracket.
The radiant tube has to be fixed by vertical chains etc. to the roof or to supporting devices.
Chains and steel cables have to be fixed in vertical direction or slightly diagonally outwards above the fixing points of the suspension brackets to the roof or to supporting devices. Fixing of the suspension cables or chains diagonally inwards to the centre of the heater is not permitted [see Fig 5].
Please note that the radiant tube being in operation expands several centimetres because of thermal expansion. Avoid therefore inflexible suspension.
Do not use fixing elements like open hooks etc.
When fastening to trapezoidal sheet roofs, make sure that the maximum surface load is not exceeded, if necessary. The load must be distributed over a larger area by means of a substructure.
Hang the heater in balance. We recommend the use of turnbuckles or adjustable steel cable grips for ease of adjustment and balance.
Fixing points for chains or steel cables on the heater are shown in Fig 16, 17, 18 and 19 on pages 21 and
22.
x
Correct = vertical or slightly
onally outwards
dia
Wrong = diagonally inwards
Fig 6: Slope of radiant tube heater
Attention! If you do not align the bluTek-burner kit correctly the device can be damaged.
SCHWANK GmbH will not accept liability for damages caused by incorrect mounting of the burner unit. Correct mounting is the responsibility of the installer.
Attention! Please note that the radiant tubes in longitudinal direction must have a small slope [3 mm per meter] to the U-bend [Fig 6].
310U –625U: x=15 mm
635U: x=20 mm
950U - 1260U: x=30 mm
Version 003 deltaSchwank 16/19 Technical specification subject to change
x
Fig 5: Chains / steel cable mounting
8
deltaSchwank
change
Air supply / Exhaust Requirements
The calculation of air supply / exhaust requirements of a building heated by radiant tube heaters is subject of European Directive EN 13410. Please follow local by-laws as well.
Please see the max. lengths of combustion air supply- and exhaust flue pipe on page 9 [Tab 3, point 3].
Place of Installation
The room to be heated must have an air volume of minimum 10 m³ for each kW of the nominal thermal load of the installed heater.
Air supply [combustion air from inside the room, types A3 and B23]
Heating installations with combustion air from inside the room are only allowed in rooms without string air pollution. Otherwise use system with combustion air from outside [type C].
In halls and buildings with a normal air change by means of joints and gaps it is not necessary to install additional equipment to ensure combustion air supply.
Version 003 deltaSchwank 16/19 Technical specification subject to
Air supply / exhaust systems
For the radiant tube deltaSchwank the following air supply / exhaust systems are possible:
1. Indirect flue into the room
[Type A3 without exhaust system, combustion air from inside the room]
2. Flued with individual exhaust system, combustion air from inside the room
[Type B23]
3. Flued with individual exhaust system,
combustion air from outside the room [Type C]
4. Flued with exhaust collecting system and central flue fan – combustion air either from inside or from outside
[according to EN 777, Type F]
1. Indirect flue into the room
[Type A3 without exhaust system combustion air from inside the room]
The exhaust gas of the tube heater has to be conducted from the inside of the room to the outside.
Conduction of the exhaust air may be carried out with one of the following 3 methods:

a) Thermal ventilation: Combustion air and
exhaust gas are to be conducted through
fixed outlets positioned on the roof or on the walls of the building.
b) Mechanical ventilation: Combustion air
and exhaust gas are to be conducted through
one or more fans positioned on the roof or on the walls of the building.
c) Natural ventilation: Combustion air and
exhaust air are to be conducted through
outlets as a result of differences in pressure and in temperature between the internal and external side of a building.
For exact dimensioning and positioning of supply air and exhaust gas outlet of the building according to EN 13410 or G638-2 please contact Schwank GmbH, phone +49 [0] 221 / 7176 0.
9
deltaSchwank
2. Exhaust flue with individual exhaust system - combustion air from inside the room
[Type B23]
Only use this system in rooms with no air pollution and without relevant pressure differences to outside. Otherwise use type C.
3. Exhaust flue with individual exhaust system ­combustion air from outside the room
[Type C]
Combustion air and exhaust air are to be conducted by a temperature stable, concentric pipe from a wall or roof entrance.
Max. length of the concentric pipe can be 6 m plus two 90° elbows.
The concentric pipe ends at a bifurcated pipe. Please ensure that the connection for exhaust gas between heater and bifurcated pipe is a flexible pipe. This also applies for the incoming air pipe that are connected to the air inlet adapter bluTek-burner kit. Do not use back-pressure valves or dampers in the exhaust flue.
deltaSchwank
Max. length
between heater
and roof/wall
entrance
6 m 2 100 mm
Tab 3: Air/exhaust routing
max. number
of elbows
(90°)
Ø of
air/exhaust flue
4. Exhaust flue with exhaust gas collection system and central flue fan
[according to EN 777, Type F]
The heating installation must not exceed 10 radiant tubes. The exhaust gas of each tube is collected via a central collecting tube system by a central flue fan and led to the chimney. Planning, construction and layout of such installations must be carried out by Schwank employees, as well as commissioning. The strict observance of the Schwank layout-drawings and calculation figures are the precondition of the manufacturer’s warranty.
Please note that it be necessary to install in the collecting tube behind each radiant heater a throttle or a pressure-balancing device. This ensures a precise regulation and an even exhaust flue of each radiant tube.
see technical instruction

deltaSchwank with exhaust gas collection system
Version 003 deltaSchwank 16/19 Technical specification subject to change
Fig 7: Air/exhaust--system, version aluminium or stainless steel
10
Flexible exhaust system deltaSchwank [wall terminal]
- version aluminium -
deltaSchwank
Connection stainless steel flexible pipe to aluminium tube must be glued with heat-resistant sealing material and locked by means of self-tapping screws.
All socket connections on the exhaust and incoming air routes must be locked by means of self-tapping screws.
The 90° elbow at the sucking fan side is to mount with the opening on the top.
The wall terminal is mounted with a small gradient to outside to prevent intrusion of driving rain.
A vertical distance between exhaust gas outlet and wall terminal outlet of at least 50cm is mandatory.
For exhaust gas lengths> 1.5 m [without wall terminal] condensate drainage must be installed.
This is valid on principle for types deltaSchwank 310U and 320U.
The following components are required for mounting the wall terminal aluminum design [Distance heater- terminal approx. 1.5 m]:
Wall terminal M&G:Article no. 12221797
Testing set C 15-20kW: Article no. 12676660 Testing set C 30-40kW: Article no. 12676750
Control points
Please note the safety distance to flammable materials:
- single-wall exhaust pipe: 40 mm
- double-wall exhaust pipe + wall
terminal: 0 mm
System certification tube heater deltaSchwank with exhaust line system MUGRO CE 0432-CPD-217915,System 0.2 / 0.5 [Muelink&Grol]
The wall terminal is fastened to the building wall with screws by means of the integrated flange plate. The flange plate supports and secures the wall terminal.
Version 001 deltaSchwank 4117 Technische Änderungen vorbehalten
Fig 8: Position of control points [wall terminal], version aluminium
Connection stainless flexible pipe to aluminium
exhaust flue: stainless flexible pipe with connecting flange
tube
combustion air: dS 310 - 320U: aluminium pipe dS 625 - 1260U: stainless flexible pipe
11
deltaSchwank
g
Flexible exhaust system deltaSchwank [roof terminal]
- version aluminium -
Install stainless steel flexible pipe without sink.
Connection stainless steel flexible pipe to aluminium tube must be glued with heat-resistant sealing material and locked by means of self-tapping screws.
All socket connections on the exhaust and incoming air routes must be locked by means of self-tapping screws.
The 90° elbow at the sucking fan side is to mount with the opening on the top.
A vertical distance between exhaust gas outlet and roof terminal outlet of at least 50cm is mandatory.
For exhaust gas lengths> 1.5 m [without roof terminal] condensate drainage must be installed.
This is valid on principle for types deltaSchwank 310U and 320U.
Please note the safety distance to flammable materials:
- single-wall exhaust pipe: 40 mm
- double-wall exhaust pipe + wall
terminal: 0 mm
System certification tube heater deltaSchwank with exhaust line system MUGRO CE 0432-CPD-217915, System 0.2 / 0.5 [Muelink&Grol]
The roof terminal is slide in from above into the roof socket. in from above into the roof socket. The fixing inside the building takes place via a clamp to the building ceiling.
Version 001 deltaSchwank 4117 Technische Änderungen vorbehalten
The following components are required for mounting the roof terminal aluminum design [Distance heater- terminal approx. 1.5 m]:
Roof terminal M&G:Article no. 12221770 Testing set C 15-20kW: Article no. 12676660 Testing set C 30-40kW: Article no. 12676750
Dimension flat roof sockets
Fig 9: Position of control points [roof terminal], version aluminium
flat version
Control points
Connection stainless flexible pipe to aluminium
high version
exhaust gas: stainless flexible pipe with connectin
combustion air: dS 310 – 320U: aluminium pipe dS 625 – 1260U: stainless flexible pipe
tube
flange
12
deltaSchwank
Condensate drain deltaSchwank
- version aluminium -
For flue gas lengths > 1.5 m [exclusive chimney] a condensate line must be laid. In general this applies for types deltaSchwank 310U and 320U.
For this use a special cap with outlet spout for T-piece [ outdoor 32 mm] is available in order to connect a following condensate drainage.
A flexible stainless steel pipe as connection is recommended because higher temperatures in nominal load operation [200 ° C] can occur at the connection point.
Drain lines must be laid with a gradient to discharged inlet point into sewer.
Version 002 deltaSchwank 19/18 Technical specification subject to change
Fig. 10: Condensate drain deltaSchwank
13
deltaSchwank
Flexible exhaust system deltaSchwank [wall terminal]
- version stainless steel -
Install stainless steel flexible pipe without sink.
Join parts of the roof terminal strongly together by compression and using of jointing and sealing paste [e.g. Ceramax]!
All joints inside the building tighten securely with clamp fittings!
The 90° elbow at the sucking fan side is to mount with the opening on the top.
The wall terminal is mounted with a small gradient to outside to prevent intrusion of driving rain.
A vertical distance between exhaust gas outlet and wall terminal outlet of at least 50cm is mandatory.
For exhaust gas lengths> 1.5 m [without wall terminal] condensate drainage must be installed.
This is valid on principle for types deltaSchwank 310U and 320U.
Please note the safety distance to flammable materials:
-single-wall exhaust pipe: 80 mm
- double-wall exhaust pipe
+ wall terminal: 0 mm
System certification tube heater
The following components are required for mounting the wall terminal stainless steel design [Distance heater- terminal approx. 1.5 m]:
Stainless steel exhaust system wall terminal DN 100/160
deltaSchwank with exhaust line system Future ew CE 0432-CPR-00055-209 / Future ew-flex CE 0036-CPR-00055-207 / Future dw CE 0432- CPR-00055-301 [Schräder]
The wall terminal is fastened to the building wall with screws by means of the integrated flange plate. The flange plate supports and secures the wall terminal.
: Article no. 12202220
Version 002 deltaSchwank 19/18 Technical specification subject to change
Control points
Fig 11: Position of control points [wall terminal], version stainless steel
14
Flexible exhaust system deltaSchwank [roof terminal]
- version stainless steel -
deltaSchwank
Install stainless steel flexible pipe without sink.
Join parts of the roof terminal strongly together by compression and using of jointing and sealing paste [e.g. Ceramax]!
All joints inside the building tighten securely with clamp fittings!
The 90° elbow at the sucking fan side is to mount with the opening on the top.
A vertical distance between exhaust gas outlet and wall terminal outlet of at least 50cm is mandatory.
For exhaust gas lengths > 1.5 m [without roof terminal] condensate drainage must be installed.
This is valid on principle for types deltaSchwank 310U and 320U.
Please note the safety distance to flammable materials:
-single-wall exhaust pipe: 80 mm
- double-wall exhaust pipe
+ roof terminal: 0 mm
The following components are required for mounting the roof terminal stainless steel design[Distance heater- terminal approx. 1.5 m]:
Stainless steel exhaust system roof terminal DN 100/160 Article no. 12202080
System certification tube heater deltaSchwank with exhaust line system Future ew CE 0432-CPR-00055-209 / Future ew-flex CE 0036-CPR-00055-207 / Future dw CE 0432- CPR-00055-301 [Schräder]
The roof terminal is fastened with screws by means of the integrated flange plate on the building ceiling. The flange plate supports and secures the roof terminal.
Version 002 deltaSchwank 19/18 Technical specification subject to change
Fig 12: Position of control points [roof terminal], version stainless steel
Control points
15
deltaSchwank
Exhaust system deltaSchwank [roof terminal] with downstream heat exchanger tetraSchwank in room air operation and with outside
air intake in fresh air operation
- version stainless steel -
Install stainless steel flexible pipe without sink.
Join parts of the roof terminal strongly together by compression and using of jointing and sealing paste [e.g. Ceramax]!
All joints inside the building tighten securely with clamp fittings!
tetraSchwank heat exchanger should be mounted with slight slope [3 mm/1m] to the T-piece.
Fig 13: Installation tetraSchwank in room air operation, with roof
terminal stainless steel
Fig 14: Installation tetraSchwank with outside air intake in fresh air operation, with roof terminal stainless steel
Installations exhaust system with heat recovery:
1. flue gas heat exchanger tetraSchwank
- pre-assembled L= 4700 mm Article no. 62000020
2. ventilator tetraSchwank with protection grating
3. T-piece stainless steel with condensation outlet
connection R ½“
4. fastening clamp for suspension, premounted
5. single-wall roof terminal with in room air
operation Article no. 12201941 double wall roof terminal with outside air intake
in fresh air operation Article no. 62000090
Please note the safety distance to flammable materials:
-single-wall exhaust pipe: 80 mm
- double-wall exhaust pipe
+ roof terminal: 0 mm
System certification tube heater deltaSchwank with exhaust line system Future ew CE 0432-CPR-00055-209
The roof terminal is fastened with screws by means of the integrated flange plate on the building ceiling. The flange plate supports and secures the roof terminal.
Version 002 deltaSchwank 19/18 Technical specification subject to change
16
deltaSchwank
Exhaust pipe collecting system [herringbone] with central fan System F approved according to EN 777 and DIN EN 416
Exhaust pipe collecting system consist of following main components:
Tube heater deltaSchwank Spiral duct and connection elements for
exhaust collecting system [different dimensions]
Central low-pressure fan Fan monitoring
Article no. 700 0012 0
Central fan
Collecting exhaust pipe
Connecting pipe
Version 021 infra D Form_U 16/19 Technische Änderungen vorbehalten
Fig. 15: Installation exhaust collecting system with central fan , system F [principle scheme]
Damper behind heater
Planning and calculation of the complete system including collecting pipes, fans and chimneys must only be done by Schwank. Planning details have to be strictly adhered to during mounting and assembly. Commissioning of the system should be carried out by Schwank.
Exhaust gas terminal
Control point chimney sweeper
Damper in front of central fan
Tube heater
17
deltaSchwank
5 Legal Requirements
We recommend that these installation guidelines should be observed with the relevant Building Standards Regulations of your country. Comply with any local by-laws and the current IEE Wiring Regulations.
Notwithstanding their limited scope, the appliance should be installed by a competent person in accordance with the relevant provisions of the Gas Safety [Installation and Use] Regulations. Caution must also be taken of any obligations arising from the Health and Safety of Work Act. Full compliance with all relevant regulations, including amendments in force at the time of installation is a requirement of our warranty.
In Germany the following rules, standards and regulations must be observed.
EnEV Verordnung über
energiesparenden Wärmeschutz und energiesparende Anlagentechnik bei Gebäuden
DIN EN 12831 Heizungsanlagen in Gebäuden Verfahren zur Berechnung der Norm-Heizlast
DIN EN 13384 Abgasanlagen
DIN V 18599 Energetische Bewertung von Gebäuden – Berechnung des Nutz­ End- und Primärenergiebedarfs für Heizung, Kühlung, Trinkwasser und Beleuchtung
DVGW G 660 Technische Regeln für die mechanische Abführung der Abgase von Feuerstätten
Version 003 deltaSchwank 16/19 Technische Änderungen vorbehalten
VDE 0722 Elektrische Vorschriften
VDE 0100 Bestimmungen für das Errichten von Starkstromanlagen
Beachten Sie außerdem die Bestimmungen der jeweiligen
LBO Landesbauordnung
FeuVO Feuerungsverordnung der Länder
TAB Technische Anschluss­ bedingungen der örtlichen Energieversorgungs­ unternehmen
18
deltaSchwank
6 Operation
The installation must be carried out by a qualified engineer following the manufacturer’s instructions.
SCHWANK will not accept liability damages caused by improper assembly and/ or operating of the heater. Proper assembly and operation is the responsibility of the user.
Switching on the heater
First switch on the central control unit
SchwankControl Touch and activate a heating command. After a pre-purge period of about 25 sec. the ignition starts.
Switching off the heater
Maintenance
Servicing of the heater is essential for continued efficient operation. Servicing should be carried out not less than once a year by a qualified service engineer. After any servicing, the heater must be recommissioned as detailed in Chapter 12.
Version 003 deltaSchwank 16/19 Technical specification subject to change
Disable the heating command on central
control unit SchwankControl Touch.
If the radiant tube is controlled by a thermostat the heater will be switched on and off automatically.
Fault
If no flame is reported during the pre-purge period and the safety time [approx. 30 sec.] the heater repeats the ignition process. If there is no flame after the second ignition process the heater switches off automatically and is locked.
Investigation and repair must be carried
out by authorized personnel. After clearance of the fault the heater can be reset.
The cause of the fault / error code is
displayed on the central control unit SchwankControl Touch or can read out via corresponding service software IC 4000. See chapter 12 for error codes.
Lock release [Reset]
Activate the reset command via the
central control unit or interrupt the electric power supply for 3 seconds.
19
deltaSchwank
7 Technical
specification
Appliance Automatic heating device, heat
transfer by means of infrared dark radiation.
Fuel Types Natural gas Propane
Minimum connection pressure in front of valve
Attention!
Max. connection pressure: 65 hPa
Gas connection 15-35 kW R=1/2’’ male
50-60 kW R=3/4“ male [Connection fitting ¾”enclosed in burner kit cardboard]
deltaSchwank 310U / 320U
Fig 16: Dimension deltaSchwank 310U / 320U
Fig 17: Dimension deltaSchwank 625U / 635U
Gas type 310 – 1260U Natural Gas H 15 hPa Natural Gas L 20 hPa Propane 40 hPa
[view from below]
[view from below]
Electrical connection power supply
Single-phase AC 230 V, N, PE - 50Hz The connecting cable for the power supply is
connected to the IC 4000/1 burner control with the provided 4-pin plug.
The power supply for the heater must be flexible with maximal wire cross-section
- 3x 1.5 mm
2
Ölflex- or silicone cable
To set the bluTek-burner kit free of voltage it is only necessary to remove the plug of the power supply.
Regulation
The heating system is controlled via the central control unit SchwankControl Touch. The corresponding heating commands for the heater are sent via MODBUS.
Connection MODBUS control from SchwankControl Touch to IC 4000/1
Use for MODBUS transmission max. 3x 0.5 mm
2
cable. Route the cable through the lower cable gland into the housing of burner control unit IC 4000/1 and connected to the corresponding spring terminals on the circuit board.
Exhaust gas connection
Flange at radiant tube end for exhaust connection Ø 100 [flexible stainless steel pipe / exhaust gas adapter]
deltaSchwank 625U / 635U
Version 003 deltaSchwank 16/19 Technical specification subject to change
20
deltaSchwank
deltaSchwank 950U
Fig 18: Dimension deltaSchwank 950U
deltaSchwank 1260U
Fig 19: Dimension deltaSchwank 1260U
Version 001 deltaSchwank 4117 Technische Änderungen vorbehalten
[view from below]
[view from below]
DETAIL A Cross dimension
DETAIL B Tube overhang x on last suspension bracket
deltaSchwank 310U / 320U – 50 mm deltaSchwank 625U / 635U – 30 mm deltaSchwank 950U – 162 mm deltaSchwank 1260U - 140 mm
21
deltaSchwank
Technical data
Gasart
Nat. Gas H
G 20
1)
Nat. Gas L
G 25
2)
Propane
G 31
3)
Nominal heat input [kW]
modulating max./min. [kW]
Gas consumption [m3/h]
Nominal heat input [kW]
modulating max./min. [kW]
Gas consumption [m3/h]
Nominal heat input [kW]
modulating max./min. [kW]
Gas consumption [m3/h]
Weight [kg]
air-/ exhaust connection [mm]
Electrical consumption [W]
Protection class
Gas connection [male thread]
Electrical supply
Ignition / Control
CE-Identifikation
deltaSchwank
310 320 625 635 950 1260
10,0 20,0 25,0 35,0 48,0 58,0
10,0 -7,5 20,0 - 10,0 25,0 - 12,5 35,0 - 17,5 48,0 - 25,0 58,0 -29,0
1,00 2,00 2,51 3,51 4,81 5,82
10,0 20,0 25,0 35,0 48,0 58,0
10,0 -7,5 20,0 - 10,0 25,0 - 12,5 35,0 - 17,5 48,0 - 25,0 58,0 -29,0
1,17 2,33 2,92 4,08 5,60 6,77
10,0 20,0 25,0 35,0 48,0 58,0
10,0 -7,5 20,0 - 10,0 25,0 - 12,5 35,0 - 17,5 48,0 - 25,0 58,0 -29,0
0,78 1,55 1,94 2,72 3,73 4,51
114 114 181 186 254 326
Ø 100
30 45 55 75 175 300
IP 20
R½“
230 V/ 50 Hz ~
Spark ignition and ionisation control by automatic burner control IC 4000/1
CE 0085CS0487
3
/4“
R
Version 001 deltaSchwank 4117 Technische Änderungen vorbehalten
Tab. 4: Technical data deltaSchwank
1] H
= 9,97 kWh/m3 / 2] H
i,n
= 8,57 kWh/m3 / 3] H
i,n
= 12,87 kWh//kg
i,n
22
deltaSchwank
Gas Characteristic values
Nat. gas H
G 20
Nat. gas L
G 25
Propan e
Version 002 deltaSchwank 19/18 Technische Änderungen vorbehalten
G 31
Tab 5: Characteristic values bluTek-burner kit deltaSchwank 1] H
Start fan speed PP04 [value / RPM]
Minimum fan speed PP05 [value / RPM] Maximum fan speed PP06 [value / RPM] Installation C
/ C33 or B23
13
Gas-/air ratio control unit NRV 118 NRV 118 NRV 118 NRV 118 NRV 128 NRV 148
Premix bluTek-burner length [mm]
Volume flow fan nominal load [m3/h,n]
OFFSET, effective [Pa]
CO2-value[%] @ max Installation C
13
/ C33 CO2-value[%] @ min Installation C
13
/ C33 Exhaust temp. NL / PL [°C] 125 / 85 215 / 125 200 / 135 240 / 165 215 / 145 210 / 150
Start fan speed PP04 [value / RPM]
Minimumfan speed PP05 [value / RPM] Maximum fan speed PP06 [value / RPM] Installation C
/ C33 or B23
13
Gas-/air ratio control unit NRV 118 NRV 118 NRV 118 NRV 118 NRV 128 NRV 148 Premix bluTek-burner
length [mm] Volume flow fan
nominal load [m3/h,n]
OFFSET, effective [Pa]
CO2-value[%] @ max Installation C
13
/ C33 CO2-value[%] @ min
Installation C
13
/ C33
Exhaust temp. NL / PL [°C] 125 / 85 215 / 125 200 / 135 240 / 165 215 / 145 210 / 150
Startfan speed PP04 [value / RPM]
Minimum fan speed PP05 [value / RPM] Maximum fan speed PP06 [value / RPM] Installation C
/ C33 or B23
13
Gas-/air ratio control unit NRV 118 NRV 118 NRV 118 NRV 118 NRV 128 NRV 148 Premix bluTek-burner
length [mm] Volume flow fan
nominal load [m3/h,n]
OFFSET, effective [Pa]
CO2-value[%] @ max Installation C
13
/ C33 CO2-value[%] @ min Installation C
13
/ C33
Exhaust temp. NL/PL [°C] 125 / 85 215 / 125 200 / 135 240 / 165 215 / 145 210 / 150
310U 320U 625U 635U 950U 1260U
30 / 1800 30 / 1800 30 / 1800 40 / 2400 40 / 2400 40 / 2400
23 / 1380 30 / 1800 37 / 2250 50 / 3000 65 / 3900 65 / 3900
C: 30 /1800 B: 30 / 1800
C: 60 /3600 B: 57 / 3420
C: 72 /4350 B: 68 / 4080
C: 100 /6000
B: 95 / 5700
C: 123/7380 B: 117 /7020
128 128 128 212 288 288
14,3 28,7 36,0 50,3 68,9 83,4
+
10
/-2
[0.1 hPa]
+
10
/-2
[0.1 hPa]
+
10
/-2
[0.1 hPa]
+
10
/-2
[0.1 hPa]
+
10
/-2
[0.1 hPa]
8,5 +/-0,1 8,5 +/-0,1 8,5 +/-0,1 8,5 +/-0,1 8,5 +/-0,1 8,5
9,0 +/-0,1
@ PP05
9,0 +/-0,1
@ PP04
9,0 +/-0,1
@ PP04
9,0 +/-0,1
@ PP04
9,0 +/-0,1
@ PP04
30 / 1800 30 / 1800 30 / 1800 40 / 2400 40 / 2400 40 / 2400
23 / 1380 30 / 1800 37 / 2250 50 / 3000 65 / 3900 65 / 3900
C: 30 / 1800
B: 30 / 1800
C: 60 / 3600 B: 57 / 3420
C: 72 / 4350
B: 68 / 4080
C: 100/6000
B: 95 / 5700
C: 123/7380 B: 117 /7020
128 128 128 212 288 288
14,4 29,1 36,4 60,9 69,8 84,4
10+/-2
[0.1 hPa]
10 +/-2
[0.1 hPa]
10 +/-2
[0.1 hPa]
10 +/-2
[0.1 hPa]
10 +/-2
[0.1 hPa]
8,5 +/-0,1 8,5 +/-0,1 8,5 +/-0,1 8,5 +/-0,1 8,5 +/-0,1 8,5
9,0 +/-0,1
@ PP05
9,0 +/-0,1
@ PP04
9,0 +/-0,1
@ PP04
9,0 +/-0,1
@ PP04
9,0 +/-0,1
@ PP04
30 / 1800 30 / 1800 30 / 1800 40 / 2400 40 / 2400 40 / 2400
23 / 1380 30 / 1800 37 / 2250 50 / 3000 65 / 3900 65 / 3900
C: 30 / 1800
B: 30 / 1800
C: 57 / 3420 B: 54 / 3240
C: 68 / 4350
B: 65 / 3900
C: 95 / 6000
B: 90 / 5400
C: 117/7020
B: 111 / 660
128 128 128 212 288 288
13,3 26,5 32,8 46,4 63,7 76,9
+
10
/-2
[0.1 hPa]
+
10
/-2
[0.1 hPa]
+
10
/-2
[0.1 hPa]
+
10
/-2
[0.1 hPa]
+
10
/-2
[0.1 hPa]
9,9 +/-0,1 9,9 +/-0,1 9,9 +/-0,1 9,9 +/-0,1 9,9 +/-0,1 9,9
10,4 +/-0,1
@ PP05
10,4 +/-0,1
@ PP04
= 9,97 kWh/m3 / 2] H
i,n
10,4 +/-0,1
@ PP04
10,4 +/-0,1
@ PP04
= 8,57 kWh/m3 / 3] H
i,n
10,4 +/-0,1
@ PP04
= 12,87 kWh//kg
i,n
C: 135/8100 B: 130 /7800
+
10
/-2
[0.1 hPa]
+
/-0,1
+
/-0,1
9,0
@ PP04
C: 135/8100 B: 130 /7800
+
10
/-2
[0.1 hPa]
+
/-0,1
+
/-0,1
9,0
@ PP04
C: 130/7800 B: 124 /7440
+
10
/-2
[0.1 hPa]
+
/-0,1
+
/-0,1
10,4
@ PP04
23
deltaSchwank
8 Operating
description
Fault
Start-up
If heat demand exists, the fan of gas-/ air ratio unit will start up automatically.
After a pre-purge period of 20 seconds in start speed [PP04] the automatic ignition starts [max. ignition time 5 sec.]. The gas valve with pressure regulator opens the gas supply to venturi mixer. The burner flame is controlled by an ionisation electrode. The ignition is switched off, if the ionisation electrode reports a flame to the burner control unit IC 4000/1 within the safety time.
If the ignition process fails, the burner control IC 4000/1 repeats the start-up for one more time.
Operation
The heater continues to run after successful ignition at the start speed for one minute, regardless of the heat requirement. Combustion takes place through the bluTek burner within the special combustion chamber design. The hot flue gas heats the tube surface while being fed through the tubes by the fan. The hot radiant tubes emit long-waved infrared radiation which is optimal directed into the room by the reflector construction.
The heater is operated in a modulation ratio of 1:2 for optimum adaptation to the heat demand. The heater starts always at start speed for a period of 1 minute and then according to the applied heating signal.
If no flame is reported during the pre-purge period [including 1 repetition of ignition process], the burner control unit IC 4000/1 will switch off the radiant tube, error will give, fan runs in post-purge time for 3 minutes in maximum speed [PP06] and then heater will lock it.
Investigation and repair must be carried out by authorized personnel only. After clearance of the fault, the lock can be reset. The cause of the fault / error code is displayed on the central control unit SchwankControl Touch or can read out via corresponding service software. See chapter 12 for error codes.
Lock release can carry out by activate the reset command via the central control unit SchwankControl Touch or an interruption of the electric power supply for 3 sec. A new start-up begins. If no flame signal is reported to the burner control unit IC 4000/1 during operation, the gas valve shuts and stops the gas supply immediately. A new start-up process is repeated.

Error codes and troubleshooting on pages 49 -50
The radiant tube heater deltaSchwank works with a closed combustion system. The combustion air is taken from outside [or from the room]. The exhaust gas is evacuated directly by a special air/exhaust pipe system through roof, wall or indirectly into the room.
24
9 Assembly
instructions
For the assembly of the heater is a
Scope of delivery
deltaSchwank 310U / 320U
- 1x Reflector section combustion chamber [FERAN]
- 1x Reflector end section L=440mm
- 1x Outer combustion chamber tube
140mm / L= 3050mm
lifting platform with work surface from min. 1.5m width and 4.0m length necessarily. For the assembly are needed 2 people.
deltaSchwank
- 1x bluTek-burner kit in cardboard [including bluTek-burner, burner baffle + gasket]
tube 1
Version 003 deltaSchwank 16/19 Technical specification subject to change
- 1x Inner combustion chamber tube stainless steel L= 1500mm
- 1x Radiant tube L= 3050mm with turbulator [coloured ring marking]
- 2x Intermediate reflector
- 1x Mounting set deltaSchwank 310U / 320U
- 1x bluTek-burner kit in cardboard
[including bluTek-burner, burner baffle + gasket]
deltaSchwank 625U / 635U
- 1x Reflector section combustion chamber [FERAN]
- 1x Reflector section
- 1x Reflector end section L=440mm
- 1x Outer combustion chamber tube
140mm / L= 5950mm
- 1x Inner combustion chamber tube stainless steel
deltaSchwank 625: L= 1500mm deltaSchwank 635: L= 2500mm
tube 2
tube 1
tube 2
- 1x Radiant tube L= 5950mm with 2x turbulator
[2x coloured ring marking]
- 2x Intermediate reflector
- 1x Mounting set deltaSchwank 625U / 635U
25
deltaSchwank
deltaSchwank 950U
- 1x Reflector section combustion chamber [FERAN]
- 2x Reflector section
- 1x Reflector end section L=550mm
- 1x Outer combustion chamber tube
140mm / L= 5950mm
- 1x Inner combustion chamber tube stainless steel L= 3000mm
- 2x Radiant tube L= 3050mm with turbulator [coloured ring marking]
- 1x Radiant tube L= 5950mm
- 1x Trapezoidal sheet for combustion chamber
L=1000mm
- 4x Intermediate reflector
- 1x Mounting set deltaSchwank 950U
- 1x bluTek-burner kit in cardboard
[including bluTek-burner, burner baffle + gasket]
tube 1
tube 2
tube 4
tube 3
deltaSchwank 1260U
- 1x Reflector section combustion chamber [FERAN]
- 2x Reflector section
- 1x Reflector end section L=550mm
- 1x Outer combustion chamber tube
140mm / L= 5950mm
- 1x Inner combustion chamber tube stainless steel L= 3000mm
- 2x Radiant tube L= 5950mm with 2x turbulator [2x coloured ring marking]
- 1x Trapezoidal sheet for combustion chamber L=1000mm
- 4x Intermediate reflector
- 1x Mounting set deltaSchwank 950U
- 1x bluTek-burner kit in cardboard
[including bluTek-burner, burner baffle + gasket]
tube 1
tube 2
26
tube 4
tube 3
deltaSchwank
Version 001 Schwank superTube 50/09 Technische Änderungen vorbehalten
deltaSchwank 310U / 320U
Tools you need

• hexagonal wrench or ratchet [width: 10, 13]
• socket wrench [width: 7 and 8]
• hand riverter
Note before mounting
Hang first the suspension brackets and observe
the specified distance dimension between them.
Fix the guide shell on the first suspension bracket
[direct after burner kit] with 2x screws M8x16 / washers / lock washers / nut for guide the outer combustion chamber tube.
The outer tube combustion chamber
L = 3050 mm has to be mount on the right side of the suspension bracket [in the flow direction]
- check the correct stud bolt position on the bracket!
Flanges are mounted with flange packing
[each 8 or 4 screws/washers/lock washers/nuts M8].
Observe the respective flange positions of the
outer combustion chamber tube during assembly ­8-hole flange shows to the bluTek-burner kit!
Turn welding seam of the tubes to the side. Tube with turbulator [colored ring marking] has
to be mounted behind the turnaround box [in flow direction]. The coloured ring showing to the turnaround box!
During mounting turnaround box to outer
combustion chamber tube observe the position of the opposite 8-hole flange. Vertical position of a hole with simultaneous sideways position of the welding seam is to be kept.
Inner combustion chamber tube [stainless steel]
L=1500 mm will be slide in outer combustion chamber tube, position from inner to outer tube will be ensured with final assembly bluTek-burner kit and bluTek- burner!
Tube bars and bracket bars have to be fixed by
nuts/3D-washers/lock washers M8 on the suspension brackets.
Clamping bars [black painted or with colored
dot] for tubes 140 and 100 mm are mounted on the last suspension bracket. Observe the specified mounting distance between suspension bracket and turn aroundbox of 50mm before tightening!
The intermediate reflectors have to be fixed into
the reflector. At both ends of the reflector sheet
the intermediate reflector will riveted with 2 stainless steel rivets [reflector has already holes to set the rivets]. An additional short angle bracket is to be fixed by rivets in the centre of the main reflector to hold the intermediate reflectors.
The combustion chamber reflector is placed on
suspension brackets and have to be fixed with the bracket bars by 6x M5 [screws/washers/ self-locking nuts]. Reflector end with notch on sides shows to the turnaround box.
The reflector end segment L = 440mm is placed
on the reflector and have to be fixed with 3x M5 screws.
Both front plates have to be fixed by 6x M5
[screws/washers/self-locking nuts].
Insert bluTek-burner L=128 mm with its
3 stud bolts into the corresponding flange holes of inner combustion chamber tube. Place between tube flange and bluTek-burner a gasket.
In addition a burner baffle together with gasket
has to mount in front of the bluTek burner whereby the flap shows diagonally downwards.
The bluTek-burner kit [first without mounted
igniter] is mounted to 8-hole flange and burner gasket by 8x M8 [screws / washers / lock washers / nuts]. Now insert smoothly the igniter through the corresponding holes in the connection adapter, avoiding destruction of the igniter ceramic.
Now firmly screw bluTek-burner kit with 8-hole
flange.
Fit the igniter and igniter gasket with 2x M4 nuts
to the stud bolts of the connection adapter.
Connect the straight ignition cable plug with
igniter and ionisation cable with burner control unit IC 4000/1.
Remove the protective foil from the housing
flap bluTek-burner kit and stick the “Schwank” foil on bottom of this flap.
Remove the remaining protective foils from
bluTek-burner kit.
The perforated adapter covering is to fit at the
mounting angle of the bluTek-burner kit by means of tapping screws.
For a quick external identification of the
assigned MODBUS address stick the provided address-sticker [number] on the bottom bluTek­burner housing and enter there the corresponding address by number stickers or with marker.
27
deltaSchwank
g
Fig 20: Mounting deltaSchwank 310U / 320U
Fig 21: Mounting interface combustion chamber
deltaSchwank 310U / 320U
Exhaust gas connection [Type B23, C]:
Note that the stainless steel flexible pipe mounted at the end of the tube with a gasket.
Accessory
Exhaust gas adapter code-no. 126 7035 0
Mount the exhaust gas adapter at the end of the tube with a gasket. Ensure a vertical exhaust gas extension of at least 0.5m.
Clamping bar [black painted or with coloured dot]
bluTek-burner L=128 mm Inner combustion chamber tube
stainless steel 100 mm, L=1500 mm
Gasket tube 140 mm 8-hole flan
e outer tube combustion chamber
Version 003 deltaSchwank 16/19 Technical specification subject to change
28
deltaSchwank
Version 001 Schwank superTube 50/09 Technische Änderungen vorbehalten
deltaSchwank 625U / 635U
Tools you need

• hexagonal wrench or ratchet [width: 10, 13]
• socket wrench [width: 7 and 8]
• hand riverter
Note before mounting
Hang first the suspension brackets and observe
the specified distance dimension between them.
Fix the guide shell on the first suspension bracket
[direct after burner kit] with 2x screws M8x16 / washers / lock washers / nut for guide the outer combustion chamber tube.
The outer tube combustion chamber
L= 5950 mm has to be mount on the right side of the suspension bracket [in the flow direction] ­check the correct stud bolt position on the bracket!
Flanges are mounted with flange packing
[each 8 or 4 screws/washers/lock washers/nuts M8].
Observe the respective flange positions of the
outer combustion chamber tube during assembly ­8-hole flange shows to the bluTek-burner kit!
Turn welding seam of the tubes to the side. Tube with turbulator [colored ring marking] has
to be mounted behind the turnaround box [in flow direction]. The coloured ring showing to the turnaround box!
During mounting turnaround box to outer
combustion chamber tube observe the position of the opposite 8-hole flange. Vertical position of a hole with simultaneous sideways position of the welding seam is to be kept.
Inner combustion chamber tube [stainless steel]
deltaSchwank 625U: L=1500 mm deltaSchwank 635U: L=2500 mm
will be slide into outer combustion chamber
tube, position from inner to outer tube will be ensured at final assembly bluTek-burner kit and bluTek- burner!
Tube bars and bracket bars have to be fixed by
M8 nuts/3D-washers/lock washers on the suspension brackets.
Clamping bars [black painted or with colored
dot] for tubes 140 and 100 mm are mounted on the last suspension bracket. Observe the specified mounting distance between suspension bracket and turnaround box of 30 mm before tightening!
The intermediate reflectors have to be fixed into
the second reflector [not combustion chamber reflector]. At both ends of the second reflector sheet the intermediate reflector will riveted with 2 stainless steel rivets [reflector has already holes to set the rivets]. An additional short angle bracket is to be fixed by rivets in the centre of the second reflector to hold the intermediate reflectors.
Start the reflector mounting at the turnaround
box side. Reflector with intermediate reflectors is placed on suspension brackets and have to be fixed with the bracket bars by 6x M5 [screws/washers/self-locking nuts]. Reflector end with notch on sides shows to the turnaround box.
Following combustion chamber reflector is
placed on suspension brackets and have to be fixed with the bracket bars by 6x M5 [screws/washers/self-locking nuts].
The reflector end segment L= 440 mm is placed
on the reflector and have to be fixed with 3x M5 screws.
Both front plates have to be fixed by 6x M5
[screws/washers/self-locking nuts].
Insert following bluTek-burner
deltaSchwank 625U: L=128 mm
deltaSchwank 635U: L=212 mm
with its 3 stud bolts into the corresponding
flange holes of inner combustion chamber tube. Place between tube flange and bluTek­burner a gasket.
In addition a burner baffle together with gasket
has to mount in front of the bluTek burner whereby the flap shows diagonally downwards.
The bluTek-burner kit [first without assembled
igniter] is mounted to 8-hole flange and burner gasket by 8x M8 [screws / washers / lock washers / nuts].
Now insert smoothly the igniter through the
corresponding holes in the connection adapter, avoiding destruction of the igniter ceramic.
Now firmly screw bluTek-burner kit with 8-hole
flange.
Fit the igniter and igniter gasket with 2x M4 nuts
to the stud bolts of the connection adapter.
Connect the straight ignition cable plug with
igniter and ionisation cable with burner control unit IC 4000/1.
Remove the protective foil from the housing
flap bluTek-burner kit and stick the “Schwank” foil on bottom of this flap.
Remove the remaining protective foils from
bluTek-burner kit.
29
deltaSchwank
g
The perforated adapter covering is to fit at the
mounting angle of the bluTek-burner kit by means of tapping screws.
For a quick external identification of the assigned MODBUS address stick the provided address-sticker [number] on the bottom bluTek­burner housing and enter there the corresponding address by number stickers or with marker.
Fig 22 : Mounting deltaSchwank 625U / 635U
Clamping bar [black painted or with coloured dot]
bluTek-burner
deltaSchwank 625U L=128 mm deltaSchwank 635U L=212 mm
Inner combustion chamber tube, stainless steel
deltaSchwank 625U 100mm, L=1500 mm deltaSchwank 635U 100mm, L=2500 mm
Fig 23: Mounting interface combustion chamber
deltaSchwank 625U / 635U
Gasket tube 140 mm 8-hole flan
Exhaust gas connection [Type B23, C]:
Note that the stainless steel flexible pipe mounted at the end of the tube with a gasket.
Accessory
Exhaust gas adapter code-no. 126 7035 0
Mount the exhaust gas adapter at the end of the tube with a gasket. Ensure a vertical exhaust gas extension of at least 0.5m.
Version 003 deltaSchwank 16/19 Technical specification subject to change
e outer tube combustion chamber
30
deltaSchwank
Version 001 Schwank superTube 50/09 Technische Änderungen vorbehalten
deltaSchwank 950U
Tools you need

• hexagonal wrench or ratchet [width: 10, 13]
• socket wrench [width: 7 and 8]
• hand riverter
Note before mounting
Hang first the suspension brackets and observe
the specified distance dimension between them. Note there are two different types of suspension brackets [tube pair combination 140/100 mm or 100/100 mm]!
hole on the left or right side of most right
the located stay bolt on suspension bracket. Hole on the left side identified tube pair combination 100 / 100 mm. Hole on the right side bolt identified tube pair combination
140 / 100 mm.
Fix the guide shell on the first suspension bracket
[direct after burner kit] with 2x screws M8x16 / washers / lock washers / nut for guide the outer combustion chamber tube.
The outer tube combustion chamber
L= 5950 mm has to be mount on the right side of the suspension bracket [in the flow direction] ­check the correct stud bolt position on the bracket!
Flanges are mounted with flange packing
[each 8 or 4 screws/washers/lock washers/nuts M8].
Observe the respective flange positions of the
outer combustion chamber tube during assembly, 8-hole flange shows to the bluTek­burner kit!
Turn welding seam of the tubes to the side.
Welding seam of outer combustion
chamber tube is to be mounted upwards at 45°!
Both tubes with turbulator [coloured ring
marking] have to be mounted in front and
behind the turnaround box. The coloured ring showing to the turnaround box! Joint between outer tube combustion chamber 140 mm and following radiant tube 100 mm is carried out by stainless steel flange adapter!
Place the enclosed stainless steel trapezoidal
sheet on top of the inner combustion chamber tube and insert the flap through the slot of the flange and bend it over for fixation!
Inner combustion chamber tube [stainless steel]
L=3000 mm inclusive trapezoidal sheet
Optical distinctive feature is
will be slide into outer combustion chamber tube, position from inner to outer tube will be ensured at final assembly bluTek-burner kit and bluTek- burner!
Tube bars and bracket bars have to be fixed by
M8 nuts/3D-washers/lock washers on the suspension brackets.
Clamping bars [black painted or with colored
dot] for tubes 140 and 100 mm are mounted on the last suspension bracket. Observe the specified mounting distance between suspension bracket and turnaround box of 162 mm before tightening!
The intermediate reflectors have to be fixed into
the second and third reflector [not combustion chamber reflector]. At both ends of the reflector sheets the intermediate reflector will riveted with 2 stainless steel rivets [reflector has already holes to set the rivets]. An additional short angle bracket is to be fixed by rivets in the centre of the second reflector to hold the intermediate reflectors.
Start the reflector mounting at the turnaround
box side. Reflectors with intermediate reflectors are placed on suspension brackets and have to be fixed with the bracket bars by 6x M5 [screws/washers/self-locking nuts]. Reflector end with notch on sides shows to the turnaround box.
Following combustion chamber reflector is
placed on suspension brackets and have to be fixed with the bracket bars by 6x M5 [screws/washers/self-locking nuts].
The reflector end segment L= 550 mm is placed
on the reflector and have to be fixed with 3x M5 screws.
Both front plates have to be fixed by 6x M5
[screws/washers/self-locking nuts].
Insert following bluTek-burner L=288mm with its
3 stud bolts into the corresponding flange holes of inner combustion chamber tube. Place between tube flange and bluTek-burner a gasket.
In addition a burner baffle together with gasket
has to mount in front of the bluTek burner whereby the flap shows diagonally downwards.
Now firmly screw bluTek-burner kit with 8-hole
flange.
Fit the igniter and igniter gasket with 2x M4 nuts
to the stud bolts of the connection adapter.
Connect the straight ignition cable plug with
igniter and ionisation cable with burner control unit IC 4000/1.
Remove the protective foil from the housing
flap bluTek-burner kit and stick the “Schwank” foil on bottom of this flap.
31
deltaSchwank
g
S
S
Remove the remaining protective foils from
bluTek-burner kit.
The perforated adapter covering is to fit at the
mounting angle of the bluTek-burner kit by means of tapping screws.
For a quick external identification of the assigned MODBUS address stick the provided address-sticker [number] on the bottom bluTek­burner housing and enter there the corresponding address by number stickers or with marker.
Fig 24: Mounting deltaSchwank 950U
Fig 25 : Mounting interface combustion chamber
deltaSchwank 950U
bluTek-burner deltaSchwank 950U L=288 mm Inner combustion chamber tube
stainless steel 100 mm, L=3000 mm
Gasket tube 140 mm 8-hole flan
Exhaust gas connection [Type B23, C]:
Note that the stainless steel flexible pipe mounted at the end of the tube with a gasket.
Accessory
Exhaust gas adapter code-no. 126 7035 0
Mount the exhaust gas adapter at the end of the tube with a gasket. Ensure a vertical exhaust gas extension of at least 0.5m.
Clamping bar
uspension bracket
tube pair combination
uspension bracket
tube pair combination 140 /  100 mm
e outer tube combustion chamber
Version 003 deltaSchwank 16/19 Technical specification subject to change
100 / 100 mm
32
deltaSchwank
Version 005 Schwank superTube 20/15 Technische Änderungen vorbehalten
deltaSchwank 1260U
Tools you need

• hexagonal wrench or ratchet [width: 10, 13]
• socket wrench [width: 7 and 8]
• hand riverter
Note before mounting
Hang first the suspension brackets and observe
the specified distance dimension between them. Note there are two different types of suspension brackets [tube pair combination 140/100 mm or 100/100 mm]!
hole on the left or right side of most right
the located stay bolt on suspension bracket. Hole on the left side identified tube pair combination 100 / 100 mm. Hole on the right side bolt identified tube pair combination
140 / 100 mm.
Fix the guide shell on the first suspension bracket
[direct after burner kit] with 2x screws M8x16 / washers / lock washers / nut for guide the outer combustion chamber tube.
The outer tube combustion chamber
L= 5950 mm has to be mount on the right side of the suspension bracket [in the flow direction] ­check the correct stud bolt position on the bracket!
Flanges are mounted with flange packing
[each 8 or 4 screws/washers/lock washers/nuts M8].
Observe the respective flange positions of the
outer combustion chamber tube during assembly ­8-hole flange shows to the bluTek-burner kit!
Turn welding seam of the tubes to the side.
Welding seam of outer combustion
chamber tube is to be mounted upwards at 45°!
Both tubes with turbulator [coloured ring
marking] have to be mounted in front and
behind the turnaround box. The coloured ring showing to the turnaround box! Joint between outer tube combustion chamber 140 mm and following radiant tube 100 mm is carried out by stainless steel flange adapter!
Place the enclosed stainless steel trapezoidal
sheet on top of the inner combustion chamber tube and insert the flap through the slot of the flange and bend it over for fixation!
Inner combustion chamber tube [stainless steel]
L=3000mm inclusive trapezoidal sheet
Optical distinctive feature is
will be slide into outer combustion chamber tube, position from inner to outer tube will be ensured at final assembly bluTek-burner kit and bluTek- burner!
Tube bars and bracket bars have to be fixed by
M8 nuts/3D-washers/lock washers on the suspension brackets.
Clamping bars [black painted or with colored
dot] for tubes 140 and 100 mm are mounted on the last suspension bracket. Observe the specified mounting distance between suspension bracket and turnaround box of 140 mm before tightening!
The intermediate reflectors have to be fixed into
the second, third and fourth reflector [not combustion chamber reflector]. At both ends of the reflector sheets the intermediate reflector will riveted with 2 stainless steel rivets [reflector has already holes to set the rivets]. An additional short angle bracket is to be fixed by rivets in the centre of the second reflector to hold the intermediate reflectors.
Start the reflector mounting at the turnaround
box side. Reflectors with intermediate reflectors are placed on suspension brackets and have to be fixed with the bracket bars by 6x M5 [screws/washers/self-locking nuts]. Reflector end with notch on sides shows to the turnaround box.
Following combustion chamber reflector is
placed on suspension brackets and have to be fixed with the bracket bars by 6x M5 [screws/washers/self-locking nuts].
The reflector end segment L= 550 mm is placed
on the reflector and have to be fixed with 3x M5 screws.
Both front plates have to be fixed by 6x M5
[screws/washers/self-locking nuts].
Insert following bluTek-burner L=288 mm with its
3 stud bolts into the corresponding flange holes of inner combustion chamber tube. Place between tube flange and bluTek-burner a gasket.
In addition a burner baffle together with gasket
has to mount in front of the bluTek burner whereby the flap shows diagonally downwards.
Now firmly screw bluTek-burner kit with 8-hole
flange.
Fit the igniter and igniter gasket with 2x M4 nuts
to the stud bolts of the connection adapter. Connect the straight ignition cable plug with
igniter and ionisation cable with burner control unit IC 4000/1.
Remove the protective foil from the housing
flap bluTek-burner kit and stick the “Schwank” foil on bottom of this flap.
33
deltaSchwank
g
S
S
Remove the remaining protective foils from
bluTek-burner kit.
The perforated adapter covering is to fit at the
mounting angle of the bluTek-burner kit by means of tapping screws.
For a quick external identification of the assigned MODBUS address stick the provided address-sticker [number] on the bottom bluTek­burner housing and enter there the corresponding address by number stickers or with marker.
Fig 26: Mounting deltaSchwank 1260U
Fig 27: Mounting interface combustion chamber
deltaSchwank 1260U
bluTek-burner deltaSchwank 1260U L=288 mm Inner combustion chamber tube
stainless steel 100 mm, L=3000 mm
Gasket tube 140 mm 8-hole flan
Exhaust gas connection [Type B23, C]:
Note that the stainless steel flexible pipe mounted at the end of the tube with a gasket.
Accessory
Exhaust gas adapter code-no. 126 7035 0
Mount the exhaust gas adapter at the end of the tube with a gasket. Ensure a vertical exhaust gas extension of at least 0.5m.
Clamping bar [black painted or with coloured dot]
uspension bracket
tube pair combination
100 / 100 mm
uspension bracket
tube pair combination 140 / 100mm
e outer tube combustion chamber
Version 003 deltaSchwank 16/19 Technical specification subject to change
34
10 Installation instructions
* Nat. Gas H: H
97 kWh/
3
/ Nat. Gas L: H
57 kWh/
3
3
Danger of fire and explosion! Unprofessional handling of gas pipes, gas connections and the appliance can produce gas leaks. It is highly dangerous if gas is ignited! Working on gas pipes and the appliances is only allowed by approved installers.
Expansion of the heater! When installing the heater, take into account the thermal expansion of the heater during operation.
Mount the flexible connections so that those can compensate the longitudinal expansion of the tube.Only use flexible connections for the radiant tube regarding:
• gas
• electricity and
• air [if necessary]
a
deltaSchwank
connection pressure in front of the gas combination valve of the individual devices is available at the nominal thermal load of the entire system, according to table 6.
Please consider the pressure drop of the upstream mounted gas connection and gas filter. For the detailed pressure drop value of the Schwank gas­pipe-systems see table 7.
Minimum connection pressures in front of valve
deltaSchwank
heater type
Nat. Gas H*
310U - 1260U Nat. Gas L* 310U - 1260U Propane 310U - 1260U
: 9,
i,n
Tab 6: Min. connection pressures in front of
gas combination valve
m
Pressure drop Schwank gas-pipe-systems
deltaschwank
heater type connection unit
Nat. Gas H*
Nat. Gas L* 310 - 635 1/2" / L=800 mm
Propane 310 - 635 1/2" / L=800 mm
* Nat. Gas H: H
310 - 635 1/2" / L=800 mm
950 - 1260 3/4" / L=800 mm
950 - 1260 3/4" / L=800 mm
950 - 1260 3/4" / L=800 mm
: 9,97 kWh/m3 / Nat. Gas L: H
i,n
min. connection
pressure
[hPa]
15 20 40
: 8,
i,n
: 8,57 kWh/m
i,n
m
pressure drop
[hPa]
2
2,5
2 3 1 1
Version 005 Schwank superTube 20/15 Technische Änderungen vorbehalten
b
FIg 28: Longitudinal thermal expansion
Gas-pipe-system and mounting of heaters
Connection of gas pipes to the appliance, supply and the mounting of the appliance are only allowed by professional personnel who is registered, holding a current certificate of competence and in accordance with the relevant provisions of the gas safety [installation and use] regulations.
Additional installation notices of national or local institutions must be observed. The pipe must be dimensioned in a way that the minimum
Tab 7: Pressure drop Schwank gas-pipe-systems
The max. connection pressure is 65 hPa!
In case of contaminated gas pipes and generally at gas pipes of welded black steel have to be mounted gas filter­groups directly in front of the heater.
35
deltaSchwank
[
]
h
Note the following points while installing the gas-pipe-system:
Use only gas lines as per national standards. Never hang heaters on the gas pipes. Mount a manual gas cock upstream of every
radiant tube.
Close all gas cocks before carrying out the
leak test and disconnect the connection between the gas cock and the burner to avoid damages to the gas regulator and gas combination valve.
Clean gas pipes before the installation of the
heater. Reconnection after pressure control and expansion.
Please observe the national standards.
Connect the heater with an approved flexible hose!
Use the following hose length for
deltaSchwank:
310 - 635 R ½“ length
800 mm
950 - 1260 R ¾“ length
800 mm
Mount a flexible hose only with 90° bend or
with 2 x 90° elbow fittings in a 180° bend according to Fig 29, 30 and 31.
Keep the specified installation dimensions. Wrong mounting of flexible hoses shown in
Fig 32 [sketches
Fig 29: Vertical connection with 90° bend
430 mm
+/- 10 %
[+/- 10 %]
430 mm
to ].
Art.-No 192 0845 0
Art.-No 192 0846 0
Abb. 38: seitlicher Anschluss im 90°-Bogen
Fig 30: Sideward connection with 90° bend
Fig 31: Alternative connection 180° -bend with 2 x 90° elbow
Fig 32: Wrong mounting of flexible hoses
430 mm
(+/- 10%)
430 mm
[+/- 10%]
fittings
a
Version 003 deltaSchwank 16/19 Technical specification subject to change
a = 320 mm +/- 10%
h = 150 mm h:
allowable height
displacement for mounting
h
36
Gas connection has to be positioned with 90° or 180° bend in the axle of the heater to compensate the thermal expansion of the heater. Otherwise torsional forces will operate on the hose!
Avoid twisting of the flexible hose! When tightening the union, counter hold the nipple on the hose.
Pay attention that the flexible hose will not be mechanically damaged by tools etc. Do not buckle the hose.
Do not mount damaged flexible hoses! Damaged hoses can break due to the movement of the heater.
Exhaust flue installation single heater
The exhaust system is available as variation of the radiant heaters. The flue system is connected at the end of the radiant tube. Note the information in chapter 4 “Planning”.
deltaSchwank
Installation exhaust collecting system [herringbone]
The installation of the flue collecting system must be carried out according to the planning of Schwank.
After mounting the heaters with their burner kits
the connection sets F [adapter and damper] have to be mounted at the end of the tube heater. The adapter must be fixed with a gasket at the flange of the last radiant tube..
The spiral tubes for the flue collecting system
with different lengths and dimensions must be mounted according to Schwank planning. When assembling the tube elements any burrs or residue of oil and grease must be eliminated.
All connecting tubes and collecting tubes must
be mounted with a small slope towards the central exhaust fan [about 0,3 %, means 30 mm per 10m]. Any dips and sinks in the tubes must be avoided (to prevent collection of condensate).
The spiral tube elements are connected by
couplings. Each tube element must be fixed by two self-tapping screws at opposite sides. Screws may not be fixed at the bottom of the tubes.
Version 003 deltaSchwank 16/19 Technical specification subject to change
After fixing the tube elements with screws all
tube connections must be sealed carefully with high temperature silicon [temperature resistant at least up to 200 °C, named f.e. NOVASIL]. When starting the central exhaust fan for the first time all tube connections have to be checked for tightness.
If the Schwank planning requires a condensate
run off, this part must be mounted directly in front of the exhaust fan [deepest point of the system]. The condensate run off has to be connected to a condensate pump or a siphon [min. water barrier height 30 cm].
37
deltaSchwank
Electrical installation [wiring diagram]
Danger of electric shock! Electric shocks are highly dangerous! Working at the electrical equipment of the appliance is only allowed by professional personnel observing the current IEE regulations.
Isolate the electrical supply while working at the electrical equipment of the appliance and safeguard the appliance against unintentional connection to the circuit.
The gas supply and electrical cable must be situated on the outside of the radiation and combustion heat. Only use heat-resistant cables near the tubes.
The power supply for the heater must be flexible connected with Ölflex- or silicone cable.
Electrical connection Operation with MODBUS control
Power supply
Route a flexible 3-wire electrical connection
cable [max. 3 x1.5 mm kit to the four-pin plug and connect the cable according to connecting scheme [Fig 33].
Connect 4-pin GDM socket with housing plug on
burner control unit IC 4000/1 of the burner kit.
The power supply for the heater must be flexible
with maximal wire cross-section of 3x 1.5 mm Ölflex- or silicone cable
In order to disconnect the bluTek burner kit from
the electrical supply pull the plug out from IC 4000/1.
The 4-pin GDM plug for the power supply
bluTek burner kit is included in delivery of the kit.
2
] for power supply burner
2
Electrical connection 4-pin plug
1 = neutral N
2 = phase L
3 = optional: error signal output 230 V
= PE
Fig 33: Electrical connection 4-pin plug
MODBUS communication
Route a flexible 3-wire MODBUS cable
[max 3x 0.5 mm the free cable gland of the burner control unit IC 4000/1 and connect it according to the connection diagram [Fig 36].
Maximum length between junction box MODBUS
and connection burner control unit IC 4000/1 may be 0.5 m.
At the of each MODBUS communication circuit a
terminal resistance 120 must be set on the relevant burner control unit IC 4000/1. Resistor is already loosely plugged into each socket KN 8 of the burner control unit IC 4000/1. This socket must then be closed with the resistor.
The necessary MODBUS address assignment is
explained on page 45.
2
] for the Modbus connection into
Electrical connection exhaust gas collecting system
After conversion of the heaters to operation with exhaust gas collection system they can be electrically connected as described above.
Fig. 35 shows the wiring diagram between the central control unit SchwankControl Touch control and the peripherally required SchwankControl SAV 1 extension kit and SAV fan monitoring kit.
Further information and wiring schemes for more different electrical connection
options [e.g. multi-zone operation,
grouping of several central control units SchwankControl Touch,…] can be found in „Electrical Compendium“.
Version 003 deltaSchwank 16/19 Technical specification subject to change
38
deltaSchwank
Version 003 deltaSchwank 16/19 Technische Änderungen vorbehalten
Fig. 34 : Connection scheme bluTek burner kit with MODBUS control to SchwankControl Touch
39
deltaSchwank
Version 003 deltaSchwank 16/19 Technical specification subject to change
Fig. 35: Connection scheme bluTek burner kit exhaust collecting system with SchwankControl Touch / Extension kit Fan Control SAV1
40
Fig 36: Internal wiring diagram bluTek-burner kit deltaschwank
deltaSchwank
Version 003 deltaSchwank 16/19 Technische Änderungen vorbehalten
41
deltaSchwank
11
Commissioning
instructions
Before commissioning
A qualified service engineer must carry out this operation. The correct operation and fixing of the heater is prerequisite for the warranty. Checking gas lines and flue system is not included in this service.
The heaters are only pre-set by the
Check the function of the following equipment:
Exhaust flue Combustion air supply Control unit Safety equipment
manufacturer and must be adjusted for proper operation according to gas quality site on site. For this information contact your local gas company.
Version 002 deltaSchwank 19/18 Technical specification subject to change
Safety of electrical circuit
Pay attention when commissioning! Vaporization of remaining grease of metal units may cause greasy mist. This kind of mist disperses after approx. 30 minutes. During this time the room has to be ventilated.
42
Parameter IC 4000/1 and setting
The burner control unit IC 4000/1 is already factory preset. The parameters can be read out by the Schwank Service Software IC 4000 [RS-485 interface board] and if necessary to be changed.
Parameter selection and settings can made manually direct at IC 4000/1 by the two push buttons SW 2 and SW 3 and the 7-segment display. For this, unscrew the lid of the IC 4000/1 burner control.
After power supply IC 4000/1 following sequence is shown on the 7-segment display:
1. segment test, all 7 segments light up
2. software version [two successive numbers]
3. burner control software: 1
deltaSchwank
Parameter Parameter name and
Factory setting Set range
parameter value definitions
PP01 Setting Communication
0: No MODBUS control [e.g. ThermoControl M+] 1: MODBUS contol by SchwankControl Touch
PP02 Drive Fan
0: Phase angle control driven 1: PWM driven
PP04 PWM FAN START SPEED
Version 002 deltaSchwank 19/18 Technical specification subject to change
PP05 PWM FAN MIN SPEED
PP06 PWM FAN MAX SPEED
20 – [“PP06 PWM FAN MAX SPEED” or 180]
[Note 1]
20 – [“PP06 Fan PWM FAN MAX SPEED” oder 130]
[Note 2]
[“PP04 PWM FAN START SPEED” or “PP05 PWM MIN SPEED or 30] –180
[Note 1], [Note 2]
1 0 - 1
1 0 -1
xx according to type see Tab 5, page 23 xx according to type see Tab 5, page 23 xx according to type
see Tab 5, page 23
20 - 180
20 - 130
30 - 180
PP09 APS monitoring for PWM driven fan
0: APS disabled for PWM fan 1: APS enabled for PWM fan
Tab 8: Parameter level IC 4000/1
Note 1: PP06 >= PP04 Note 2: PP06 >= PP05
0 0 -1
43
deltaSchwank
Fig 37: 7-segment display and push buttons IC 4000/1
ON normal working mode DISP1 is blank.
When you need to enter parameter setting:
- Press SW2 and SW3 buttons together for 3 seconds.
- Parameter number “1” is displayed on DISP1.
- Press SW2 to increase the parameter number, press SW3 to decrease the parameter number.
- When you reached the target parameter number, press SW2 and SW3 buttons together for 3 seconds to reach the setting level for the value.
- For parameters PP03, PP07, PP08 parameter number starts to flash on DISP1.
- For parameters PP01 und PP02 parameter value starts to flash on DISP1.
- Now you can increase the parameter value by pressing SW2, and decrease it by pressing SW3.
- To store the new parameter setting, press SW2 and SW3 buttons together for 3 seconds.
- Parameter menu is closed and DISP1 is blank again.
Parameter settings menu has 10 minutes timeout. If you don’t press any button for 10 minutes, control exits from parameters menu automatically without saving the settings.
Fig 38: MODBUS addressing IC 4000/1 by
DIP switches
Dip switch position below
Dip switch position above
External identification MODBUS address
For a quick external identification of the assigned MODBUS address, please enter the corresponding address [number] on the provided MODBUS-address label by number stickers or with marker pen. MODBUS-address label is to stick on the bottom side bluTek-burner kit housing.
Version 002 deltaSchwank 19/18 Technical specification subject to change
Assignment MODBUS address
For every heater [= burner control unit] it is mandatory to assign an MODBUS address if it controlled by SchwankControl Touch. All heaters are assigned with the MODBUS address 1 in the delivery state. To change the MODBUS address, the lid of the IC 4000/1 burner control unit must be opened. The MODBUS address is set by the DIP switches in the lower right side of the board. A maximum of 31 addresses can be assigned per heating zone.
44
deltaSchwank
Version 003 deltaSchwank 16/19 Technical specification subject to change
Adjusting nominal heat load / Modulating range
Note! Gas flow are factory set to natural gas or propane. You may only commission the system after adjustment.
Check connection pressure
Open first the gas cock which is at the end of
the flexible gas hose [Fig.39].
Open the test nipple connection pressure.
Connect the pressure measuring instrument to
the test nipple connection pressure.
Close the test nipple after the measurement
and check if the test nipple is gas-tight.
Adjusting nominal maximum load
[see Fig. 40]
Switch heater in full load [MAX Speed PP06]
means by of a) activating chimney sweep mode on central control unit SchwankControl Touch or b) selection PP06 on Schwank service software IC 4000 or c) selection PP06 directly with pushbuttons on board IC 4000/1 [see page 44]
Adjustment CO
after about ca. 10 minutes operation,
according to values Tab 5, page 24
by small slot screwdriver or hex wench 2mm
higher CO2-value: turn gas throttling screw lower CO2-value:
turn gas throttling screw anti clockwise [+]
and determine the
-value at gas throttling screw
2
clockwise [+]
Adjusting OFFSET in lowest speed
[see Fig. 40]
Switch heater in lowest speed
means by of
a) selection START speed PP04 or MIN speed
PP05 [whatever is lower] on central control unit SchwankControl Touch or
b) selection START speed PP04 or MIN speed
PP05 directly with pushbuttons on board IC 4000/1 [see page 44] or d) restart heater and use start speed sequence of 1 minute
Control CO
necessary adjustment with OFFSET-screw according to values Tab. 5, page 24
by hex wench 2mm
Measure CO
pressure [differential pressure] via
[Recommendation to use differential pressure gauge with max. 5 hPa measuring range]
higher CO2-value and p-OFFSET: turn OFFSET-screw
lower CO2-value and p-OFFSET: turn OFFSET-screw
Check adjustment CO2-values in minimal and
maximal speed again. If it necessary repeat procedure.
Close test nipple
and check if the test nipple is gas-tight. Reconnect the pressure air intake measuring tube to the regulator.
Fig. 39: Gas cock
-value and p-OFFSET and if it
2
-value and effective OFFSET-
2
and -.
clockwise [+]
anti-clockwise [-]
after the measurement
,
45
deltaSchwank
Fig 40: Measuring set up adjusting nominal load /
modulating range
Version 003 deltaSchwank 16/19 Technical specification subject to change
46
deltaSchwank
Commissioning exhaust gas collecting system [herringbone]
Before first start up
For first start up and commissioning of the system please request a Schwank service engineer to attend Adjustment by Schwank is a condition of our warranty.
Gas fired radiant tube heater systems have to be installed by a qualified engineer according to local laws and rules in force.
Start up
First check the complete electrical supply and
connections of the system. All plugs at the burner units must be taken off. Check the correct connection of the plugs. After this the room temperature regulation system is switched on. Check the connection and the direction of the rotation of the central exhaust fan.
Check the complete connecting and
collecting tube system for a small slope towards the central fan [no sinks for condensate!].
Check the slope from central exhaust fan to
the chimney.
Check the complete flue gas system for
tightness with central exhaust fan on [burners off]. In case of leaks ensure tightness by high temperature silicon.
Correct start up and commissioning without system tightness is not possible!
Commissioning
The safe evacuation of the exhaust gases of
all heaters is ensured by correct adjusting of negative pressure. This is done by fixing the dampers at the end of the heaters and may be also the damper in front of the central exhaust fan at the following values.
Required negative pressure level at test nipple OFFSET [cold conditions]:
- deltaSchwank 310U..1260U: -1.0 hPa
Adjustment with central fan on, burners off.
Start the adjustment with the heater furthest
away from the central exhaust fan. Take the negative pressure at the measurement nipple at the bottom of the burner unit. Therefore take off the silicon tube between nipple and solenoid valve. Negative pressure is adjusted by moving the damper at the end of the tube heater. After adjustment the silicon tube has to be connected again between the nipple and solenoid valve.
Adjustment of the other burner now follows
with the same procedure.
Having adjusted all the heaters the negative
pressure of the units may have changed. A second thorough check and adjustment of the negative pressure of the units is necessary. Then the positions of the dampers must be fixed by the screw.
Now the heaters can be started up [opposite
sequence to adjustment].
Now the negative pressure at test nipple
nozzle pressure is checked [burners off, dampers at the end of the tubes completely
Version 002 deltaSchwank 19/18 Technical specification subject to change
open]. The minimum negative pressure under these conditions must be >1 hPa. In case the negative pressure level is lower please check again the tightness of the complete system. Also check that the damper in front of the central exhaust fan is open.
47
deltaSchwank
12 Service guide /
Trouble shooting
Maintenance and annual check [herringbone]
A regular maintenance is the requirement for a faultless operation of the appliance.
According to the National Standard Regulations, heating-systems with radiant tubes must be checked at least once a year.
Maintenance and troubleshooting is only allowed by professional personnel that is competent and instructed in radiant tubes.
Before starting work on the heater the gas cock has to be closed.
Maintenance must include the following checks: Check surface of combustion chamber
tubes/radiant tubes and if fit necessary clean up.
Check the slope of the tubes [3 mm/m in
direction of the turnaround box connection]
Check correct and firm connection of the
reflectors and intermediate reflectors.
Check tightness of gas-carrying parts and
connections.
Check the flexible gas hose for correct
installation and tightness.
Check electrical connection to the burner kit. Check the air/flue-system
Check firm mounting and tightness of gas-/air
ratio control unit within burner kit.
Check condensation pipes. Check the safety functions of the ignition- and
ionisation-controls, gas valves and operation indicator
Check functionality Functional test of control
and regulation equipment, switchgear and signal lights
Check gas filter in case of reduced line
pressure, in case of pollution change filter pad [spare part kits gas filter]
Check correct parameter setting. Check safety distances and information boards.
Any deviations must be fixed immediately. Defect parts must be changed directly.
Maintenance work on gas valves, flame sensing and safety devices can only be maintained by the manufacturer or authorized personnel.
After the end of the maintenance work,
the device must be put back into operation!
Version 002 deltaSchwank 19/18 Technical specification subject to change
48
deltaSchwank
Error codes
If an error occurs, all gas valves are closed and the lockout message output [230 V] is activated and the error code is stored internally and transmitted by MODBUS to the central control unit SchwankControl Touch.
The fan still runs for 180 seconds in the post-purge time with maximum fan speed. After that, the heater is completely switched off and locked The lock can be reset by activating the reset function SchwankControl Touch or switching off the power supply [min. 3 seconds] of the heater.
Error code "A" does not put the heater in a reset­requiring lock, but only switches off the heater.
Error code
1
2
3 APS
4 APS
Error name Description
Ionization error during start
Ionization error during operation
open error
[APS= air pressure switch]
closed error
If flame is not detected for the 2 ignition attempts during start
If flame is not detected for the 2 ignition attempts after a flame loss
Error Is given if phase angle control type is selected [PP02=0]
Error is given if APS contact opens during start or operation
Error Is given if phase angle control type is selected [PP02=0]
7 Gas valve
feedback error
8
10
Ionization component error
MODBUS signal missing error
Tab 9: Error code IC 4000/1
Error in gas valve drive or feedback check circuitry
Ionization signal is out of range
If PP01=01 selected as MODBUS control and for more than 3 minutes no MODBUS signal has been received this error is given and heater switch off. Burner control is not locked.
Error is given if APS contact already
Version 002 deltaSchwank 19/18 Technical specification subject to change
5 Encoder signal
missing error
6 Unexpected
“encoder signal ”error
closed during start Error Is given if PWM
control is selected [PP02=1]
Error is given if no encoder signal detected or fan speed < 10 RPS.
This error is given after 3 sec.
Error Is given if phase angle control type is selected [PP02=0] and encoder signal is detected > 30 RPS.
This error is given after 3 sec.
49
deltaSchwank
Troubleshooting / Error cause
Error code 1:
- no gas [e.g. gas line not vented, gas cock
closed]
- faulty gas valve
- Ignition and ionization electrodes damaged /
dirty
- wrong setting gas throttling screw
- poor grounding
Error code 2:
- poor low ionization current [<0,7A DC]
- too low connection pressure
Error code 5:
- PWM fan don’t run
[e. g. impeller broken , motor broken]
- PWM cable broken
Error code 7 + 8:
- internal error IC 4000/1
Error code 9:
- Wrong setting fan speed parameters
[PP04, PP05, PP06]
- Damaged fan [e.g. bearing failure]
13
In case of change of gas type the corresponding CO2 value has to be set by means by of gas throttling screw and the parameters burner control IC 4000/1 according to Tab. 5, page 24.
Change of gas type
Version 002 deltaSchwank 19/18 Technical specification subject to change
Error code 10:
- interruption MODBUS connection >3 minutes
- wrong wiring between IC4000/1 and
SchwankControl Touch
Example: right connection B and - / A and +
MODBUS Assignment
IC 4000/1
B A COM
Tab 10: Error causes
+ - REF
MODBUS Assignment
SchwankControl
50
deltaSchwank
14 Accessory
tetraSchwank
Increase energy efficiency through utilisation of condensing technology from the exhaust gas heat by counterflow exchanger between the heater and wall/roof terminal.
Assembly instruction
Before starting installation tetraschwank the
ventilator must be plugged with high-temperature resistant sealing compound and secured with at least 3 sheet metal screws. Mount grating of suction opening and fixing
bracket on the ventilator with sheet metal screws. Ventilator must be hang separately. Note the suction direction of the ventilator.
Note the outflow direction downwards of the
ventilator. tetraSchwank heat exhanger should be mounted
with slight slope [3 mm/1m] to the T-piece. An extension of the flue gas installation is
permitted only in exceptional cases. tetraSchwank must be suspended by two
premounted fastening clamps. Chains or steel cables have to be fixed in vertical direction. A condensate drain must be fitted with a siphon
at the T-piece. Condensate pipes must be installed with a slope
to the discharge into the sewer system. Connect the ventilator as shown in Fig. 41 to the
central control unit Schwank Control Touch.
Electrical connection ventilator
Version 021 infra D Form_U 16/19 Technische Änderungen vorbehalten
Fig. 41: Electrical connection tetraSchwank to SchwankControl Touch
51
deltaSchwank
15 Spare parts
1
Fig 42: Spare parts deltaSchwank 635U
22
2
16 17 18
24
10
20
28
2625
12
Spare parts radiant kit deltaSchwank
Pos. Part Art.-No
bluTek-burner kit deltaSchwank 310U Natural Gas 026 1000 0 bluTek-burner kit deltaSchwank 320U Natural Gas 026 1001 0
1
2 3 4 5 6 7 Trapezoidal sheet for combustion chamber deltaschwank 950U und 1260U [not in Fig 42] 126 1074 0 8 9 10 11 12 13 14 15 16 Reflector section combustion chamber 126 1058 0 17 Reflector 126 1059 0 18 Reflector end section L=440 mm 126 1060 0 19 Reflector end section L=550 mm [not in Fig 42] 126 1061 0 20 Intermediate reflector 126 1062 0 21 Mounting bracketl intermediate reflector [not in Fig 42] 126 1062 1 22 23 24 Suspension bracket bar 126 1078 0 25 26 27 28 29 Mounting set deltaSchwank 310U / 320U [not in Fig 42] 126 1063 0 30 Mounting set deltaSchwank 625U / 635U [not in Fig 42] 126 1064 0 31 Mounting set deltaSchwank 950U [not in Fig 42] 126 1065 0 32 Mounting set deltaSchwank 1260U [not in Fig 42] 126 1066 0
bluTek-burner kit deltaSchwank 625U Natural Gas 026 1002 0 bluTek-burner kit deltaSchwank 635U Natural Gas 026 1003 0 bluTek-burner kit deltaSchwank 950U Natural Gas 026 1004 0 bluTek-burner kit deltaSchwank 1260U Natural Gas 026 1005 0 Outer combustion chamber radiant tube FAL Outer combustion chamber radiant tube FAL Inner combustion chamber tube stainless steel Inner combustion tube stainless steel 100mm / L=2500 mm [not in Fig 42] Inner combustion chamber tube stainless steel
Radiant tube FAL 100mm / L=3050 mm with turbulator [not in Fig 42] Radiant tube FAL 100mm / L=5950 mm [not in Fig 42] Radiant tube FAL 100mm / L=5950 mm with 2 turbulators Tube connector from 140mm to 100 mm [not in Fig 42] Turn around box tube combination 140 mm / Turn around box tube combination 100 mm / Gasket tube 140 mm [8-holes] [not in Fig 42] Gasket tube 100 mm [not in Fig 41]
Suspension bracket for tube combination Suspension bracket for tube combination
Tube bar 140 mm Clamping tube bar 140 mm [black painted or with coloured dot] Tube bar 100mm Clamping tube bar 100mm [black painted or with coloured dot]
140 mm / L= 5950 mm 140 mm / L= 3050 mm [not in Fig 42]
100 mm / L=3000 mm [not in Fig 42]
100 mm / L=1500 mm [not in Fig 42]
100 mm 100 mm [not in Fig 42]
140 mm / 100 mm 100 mm / 100 mm [not in Fig 42]
126 1001 0 126 1000 0 126 1069 0 126 1068 0 126 1067 0
126 7055 0 126 7199 0 126 1057 0 126 1056 0 126 1004 0 126 1003 0 126 1005 0 126 7048 0
126 1007 0 126 1006 0
126 1008 0 126 1009 0 126 1008 0 126 4529 5
Version 003 deltaSchwank 16/19 Technical specification subject to change
52
Spare part bluTek-burner kit deltaSchwank
14
4 - 6
deltaSchwank
11
Version 003 deltaSchwank 16/19 Technical specification subject to change
Fig 43: Spare part bluTek-burner kit
3
10 12
12
7- 9
Pos. Part Art.-No
1 Spark igniter with ionisation cable deltaSchwank 126 1023 0 2 Ignition cable with straight plug 126 1051 0 3 Automatic burner control IC 4000/1 deltaSchwank [without mounting plate and wiring] 126 1091 1 4 Gas- / air ratio control unit NRV 118 [in cardboard] 126 1083 0 5 Gas- / air ratio control unit NRV 128 [in cardboard] 126 1083 1 6 Gas- / air ratio control unit NRV 148 [in cardboard] 126 1083 2
7 bluTek-burner L=128 mm 126 1013 1 8 bluTek-burner L=212 mm 126 1014 1 9 bluTek-burner L=288 mm 126 1015 1 10 Gasket bluTek-burner 126 1018 0 11 Gasket igniter 126 1019 0 12 Perforated cover adapter 126 1050 0 13 LED-operation indicator [not in Fig 43] 126 1024 0 14 Corrugated gas pipe with gaskets 126 1027 0 15 Spare part kits for gas filter ½“ [not in Fig 43] 192 0758 0 16 Spare part kits for gas filter ¾“ [not in Fig 43] 192 0759 0
Please only use Schwank original spare parts. The installation of spare parts which are not named or recommended by the manufacturer can lead to failure or damage of the heater.
53
deltaSchwank
16 EC type examination certificate
Version 003 deltaSchwank 16/19 Technical specification subject to change
54
deltaSchwank
Version 003 deltaSchwank 16/19 Technical specification subject to change
55
17 EC declaration of conformity
deltaSchwank
Version 003 deltaSchwank 16/19 Technical specification subject to change
56
deltaSchwank
p
]
18 Product information related to Ecodesign
Regulation No 2015/1188
Fuel Natural gas / Propane
Values
310U 320U 625U 635U 950U 1260U
deltaSchwank
Nominal heat input [kW] @ NCV
Minimum heat input [kW] @ NCV
Minimum heat input as percentage of
nominal heat in h
[%] @ GCV
Therm al
at nominal heat input h
[%] @ GCV
Therm al
at minimal heat input
Radiant factor RF
at nominal heat input
Radiant factor RF
at minimal heat input
Auxiliary elect ricity consumption
at nominal heat input
Auxiliary elect ricity consumption
at minimal heat input
Heat output control type
Space heating emissions NOx @ GCV [mg/kWh]
ut [%
nom
min 
[%]
[%]
@ NCV
@ NCV
el
el
max
max
[kW]
[kW]
10,0 20,0 25,0 35,0 48,0 58,0
7,5 10,0 12,5 17,5 25,0 29,0
25% 50% 50% 50% 48% 50%
86,8% 83,2% 83,0% 80,9% 82,3% 83,1%
87,2% 86,8% 85,9% 84,4% 84,6% 85,8%
80,6% 78,1% 80,3% 78,6% 83,7%
80,9% 80,6% 82,2% 83,2% 82,0% 83,4%
0,03 0,04 0,04 0,08 0,17
0,03 0,03 0,02 0,03 0,05 0,11
modulat ing modulat ing modulat ing modulating modulating modulating
60 60 60 60 60
80,9%
0,29
60
Version 003 deltaSchwank 16/19 Technical specification subject to change
NCV=Netcalo rif icvalue GCV=Gros scalo rif icvalue
Tab 11: Characteristic values energy performance deltaSchwank
99,0%Seasonal energy efficiency [%] 98,2% 99,0% 98,9% 97,4% 97,6%
57
Loading...