SCHURTER 5200 Technical data

5522000
0
POWER ENTRY MODULES WITH LINE FILTER
Inlet filter, front side mounting, fuseholder 5x20 mm
replacement
Type 5200, Fuseholder 1-pole with spare compart­ment
Type 5200, Fuseholder 1-pole with spare compart­ment
C14
70° C
DDeessccrriippttiioon
- Panel Mount: Snap-in or screw-on mounting from front side
- 3 Functions: Inlet Protection class I, Fuseholder for fuse-links 5 x 20 mm 1-pole, Line filter in standard and medical version
- Quick connect terminals 6.3 x 0.8 mm
- Alternative: version without line filter 6200
AApppprroovvaalls
- VDE License Number: 101307
- UL License Number: E72928
TTeecchhnniiccaall DDaatta
Ratings IEC 1 - 10 A @ Ta 40 °C / 250 VAC; 50 Hz Ratings UL/CSA 1 - 10 A @ Ta 40 °C / 125 VAC; 60 Hz Leakage Current standard < 0.5 mA (250 V / 60 Hz)
Dielectric Strength > 1.7 kVDC between L-N
Allowable Operation Temp. -25 °C to 85 °C Climatic Category 25/085/21acc. to, IEC 60068-1 Degree of Protection from front side IP 40 acc. to IEC 60529 Protection Class Suitable for appliances with protection
Terminal Quick connect terminals 6.3 x 0.8 mm Panel Thickness s Screw-on: max 8 mm
Material: Housing Thermoplastic, black, UL 94V-0
n
s
a
medical < 5 µA (250 V / 60 Hz)
> 2.7 kVDC between L/N-PE Test voltage (2 sec)
class I acc. to IEC 61140
Mounting screw torque max 0.5 Nm Snap-in: 0.8 mm to 3 mm
CChhaarraacctteerriissttiiccs
- All single elements are already wired
- Plug removal necessary for fuse-link replacement Fuse drawer meets requirements of medical standard IEC/EN 60601-1 The fuseholder is accessible from the equipment front
- Qualified for use in equipment according IEC/EN 60950
WWeebblliinnkks
Approvals: http://www.schurter.com/approvals RoHS: http://www.schurter.com/rohs
Appliance-Inlet /-Outlet C14 acc. to IEC/EN 60320-1,
Fuseholder 1 pole, Shocksafe category PC2 acc. to
Rated Power Acceptance @ Ta 23 °C Power Acceptance @ Ta > 23°C Admissible power acceptance at higher
Line Filter Standard and Medical Version, IEC
MTBF > 2'300'000 h acc. to MIL-HB-217 F
s
s
UL 498, CSA C22.2 no. 42 (for cold con­dition) pin-temperature 70 °C, 10 A, Pro­tection class I
IEC 60127-6, for fuse-links 5 x 20 mm 5 x 20: 2 W (1 pole)
ambient temperature see derating curves
60939, IEC 60601-1, UL 1283, UL 544, EN 133 200, CSA C22.2 no. 8
Technical details
1
www.schurter.com
5522000
ø 6.3x90˚
29
34
36
36
44
ø 3.5
M3
+0.50
0
max.R3
32
+0.2
0
43.7
5
2.5
29
34
36
+0.20
0
max.R3
32
+0.20 0
43.7
5
3.5
0
POWER ENTRY MODULES WITH LINE FILTER
DDiimmeennssiioonns
s
Screw-on mounting type 5200
Snap-in mounting type 5200
Length 48.7 mm
TTeecchhnniiccaall DDaattaa ooff FFiilltteerr--CCoommppoonneenntts
RRaatteedd CCuurrrreenntt
[[AA]]
10 Standard Version 2 x 0.4 47 2.2 -
10 Medical Version (M5) 2 x 0.4 47 - 1
FFiilltteerr--TTyyppee IInndduuccttaanncceess
1 Standard 2 Standard 4 Standard Version 2 x 1.6 47 2.2 ­6 Standard Version 2 x 0.7 47 2.2 ­8 Standard Version 2 x 0.6 47 2.2 -
1 Medical Version (M5) 2 x 11 47 - 1 2 Medical Version (M5) 2 x 4 47 - 1 4 Medical Version (M5) 2 x 1.6 47 - 1 6 Medical Version (M5) 2 x 0.7 47 - 1 8 Medical Version (M5) 2 x 0.6 47 - 1
Version Version
s
CCaappaacciittaannccee
LL [[mmHH]]
2 x 11 47 2.2 -
2 x 4 47 2.2 -
CCXX [[nnFF]]
CCaappaacciittaannccee
CCYY [[nnFF]]
2
www.schurter.com
RR [[MMΩ]]
Loading...
+ 2 hidden pages