Schneider Electric MA4D-хххх-ххх, F4D-хххх-ххх, S4D-хххх-ххх Installation Instructions

Installation Instructions
Specifications
Actuator Inputs Control Signal
Power Input
Connections
Actuator Outputs Electrical
Position Feedback Voltage (proportional or floating only)
Mechanical Timing
Travel
Manual Override
See Table-1 thru 4 for actuator mod-
els and control types.
are Class 2. All circuits 30 Vac and
above are Class 1.
3 ft (91 cm) appliance or plenum ca-
bles, enclosure accepts 1/2” (13 mm)
conduit connector. For M20 Metric
conduit, use AM-756 adaptor.
For voltage ranges, the feedback
signal is the same range as the input
signal. The 4 to 20 mA current range and floating actuators have a 2 to 10
Vdc feedback signal. The feedback
signal can supply up to 0.5 mA to
operate up to four additional slave
actuators.
See Figure-1 to Figure-4.
93° nominal.
Allows positioning of damper or valve
using manual crank.
Environment Ambient Temperature Limits Shipping & Storage
Operating
Humidity
Location
Agency Listings UL 873
CUL
European Community
Australia
-40 to 160°F (-40 to 71°C).
-22 to 140°F (-30 to 60°C).
15 to 95% RH, non-condensing.
NEMA 1. NEMA 2, UL Type 2 (IEC
IP54) with customer supplied water
tight conduit connectors. Enclosure is
air plenum rated.
Underwriters Laboratories (File
#E9429 Category Temperature-Indi-
cating and Regulating Equipment).
UL Listed for use in Canada by
Underwriters Laboratories. Canadian
Standards C22.2 No. 24-93.
EMC Directive (89/336/EEC). Low Voltage Directive (72/23/EEC). This product fits in Installation Category
(Overvoltage Category) II per EN
61010-1.
This product meets requirements to
bear the RCM according to the terms
specified by the Communications
Authority under the Radiocommuni-
cations Act 1992.
RA/DA Jumper
Permits reverse acting/direct acting
control (MS4D models only).
Table 1. 30 in-lb (3.4 N-m) Spring Return CCW Actuators (Viewed from cover side)
Part Number Control Signal Voltage Wiring System
50/60 Hz
VA W W
MA4D-7033-000
MA4D-7033-100 Plenum Cable
2
MA4D-7030-000
Position SPST
MA4D-7031-000
24 VAC +/-20% or 20-30 Vdc
120 Vac ± 10% 50/60 Hz
230 Va ± 10%
Appliance Wire
5.1 3.6 0.14 1.3
7.8 5.0 2.5
Appliance Wire
7.2 5.2 2.4
50/60 Hz MF4D-7033-000 MF4D-7033-100 Plenum Cable MS4D-7033-000 MS4D-7033-100 Plenum Cable MS4D-7033-020 MS4D-7033-120 Plenum Cable MS4D-7033-030 MS4D-7033-130 Plenum Cable MS4D-7033-050 MS4D-7033-150 Plenum Cable MS4D-7033-060
MS4D-7033-160 Plenum Cable
a Timing was measured with no load applied to actuator. b 4 to 20 mAdc with field-installed 500 ohm resistor.
Floating
2 to 10 Vdcb Proportional
0 to 3 Vdc Proportional
6 to 9 Vdc Proportional
0 to 10 Vdc Proportional
4 to 20 mAdc Proportional
24 Vac
+/-20%
or 20-30
Vdc
Appliance Wire
Appliance Wire
Appliance Wire
Appliance Wire
Appliance Wire
Appliance Wire
6.8 4.2 0.15 1.9
6.1 3.4 0.12 1.4
Actuator Power Input
Running Holding
DC
50/60 Hz
Amps
Approximate Timinga in
Sec. @ 70 °F (21 °C)
Pow-
ered
Spring Return
(CCW)
56 23
85 21
November, 2018 tc © 2018 Schneider Elect ric. All r ights res erved. A ll trade marks are o wned by Schneider Ele ctric Ind ustries S AS or its af filiat ed companies. Document Number: F-27170-7
Table 2. 30 in-lb (3.4 N-m) Spring Return CW Actuators (Viewed from cover side)
Part Number
Control
Signal
Voltage Wiring System
50/60 Hz
VA W W
MA4D-8033-000 MA4D-8033-100 Plenum Cable
MA4D-8030-000
2 Position SPST
MA4D-8031-000
MF4D-8033-000 MF4D-8033-100 Plenum Cable MS4D-8033-000 MS4D-8033-100 Plenum Cable MS4D-8033-020 MS4D-8033-120 Plenum Cable MS4D-8033-030 MS4D-8033-130 Plenum Cable MS4D-8033-050 MS4D-8033-150 Plenum Cable MS4D-8033-060
MS4D-8033-160 Plenum Cable
a Timing was measured with no load applied to actuator. b 4 to 20 mAdc with field-installed 500 ohm resistor.
Floating
2 to 10 Vdcb Proportional
0 to 3 Vdc Proportional
6 to 9 Vdc Proportional
0 to 10 Vdc Proportional
4 to 20 mAdc Proportional
24 VAC +/-20% or 20-30 Vdc
120 Vac ± 10% 50/60 Hz
230 Va ± 10% 50/60 Hz
24 Vac +/-20% or 20-30 Vdc
Appliance Wire
Appliance Wire
Appliance Wire
Appliance Wire
Appliance Wire
Appliance Wire
Appliance Wire
Appliance Wire
5.1 3.6 0.14 1.3
7.8 5.0 2.5
7.2 5.2 2.4
6.8 4.2 0.15 1.9
6.1 3.4 0.12 1.4
Actuator Power Input Approximate Timing
Running Holding
DC
50/60
Hz
Amps
in Sec. @ 70 °F (21
°C)
Pow-
ered
Spring Re-
turn (CW)
56 23
85 21
Installation Instructions
a
Table 3. Non-Spring Return 35 in-lb (4 N-m) Actuators.
Part Number
MF4D-6043-000 MF4D-6043-100 Plenum Cable MS4D-6043-000 MS4D-6043-100 Plenum Cable MS4D-6043-020 MS4D-6043-120 Plenum Cable MS4D-6043-030 MS4D-6043-130 Plenum Cable MS4D-6043-050 MS4D-6043-150 Plenum Cable MS4D-6043-060
MS4D-6043-160 Plenum Cable
a Timing was measured with no load applied to actuator. b 4 to 20 mAdc with field-installed 500 ohm resistor.
Control
Signal
Floating
2 to 10 Vdcb Proportional
0 to 3 Vdc Proportional
6 to 9 Vdc Proportional
0 to 10 Vdc Proportional
4 to 20 mAdc Proportional
Voltage Wiring System
Appliance Wire
Appliance Wire
Appliance Wire
24 Vac +/-20% or 20-30 Vdc
Appliance Wire
Appliance Wire
Appliance Wire
Actuator Power Input
Running Holding
50/60 Hz
VA W W
DC
Amps
4.4 2.7 0.1 1.7
4.2 2.2 0.08 1.2
50/60
Hz
Approximate Timinga
in Sec. @ 70 °F (21
°C)
85
© 2018 Schneider Elect ric. All r ights res erved. A ll trade marks are o wned by Schneider Ele ctric Ind ustries SAS or its af filiat ed companies. Novemb er, 2018 tc Docume nt Number : F-27170-7
Installation Instructions
Table 4. Non-Spring Return 70 in-lb (8 N-m) Actuators.
Part Number
MF4D-6083-000 MF4D-6083-100 Plenum Cable MS4D-6083-000 MS4D-6083-100 Plenum Cable MS4D-6083-020 MS4D-6083-120 Plenum Cable MS4D-6083-030 MS4D-6083-130 Plenum Cable MS4D-6083-050 MS4D-6083-150 Plenum Cable MS4D-6083-060
MS4D-6083-160 Plenum Cable
a Timing was measured with no load applied to actuator. b 4 to 20 mAdc with field-installed 500 ohm resistor.
Control
Signal
Floating
2 to 10 Vdcb Proportional
0 to 3 Vdc Proportional
6 to 9 Vdc Proportional
0 to 10 Vdc Proportional
4 to 20 mAdc Proportional
Voltage Wiring System
Appliance Wire
Appliance Wire
Appliance Wire
24 Vac +/-20% or 20-30 Vdc
Appliance Wire
Appliance Wire
Appliance Wire
Actuator Power Input
Running Holding
50/60 Hz
VA W W
5.9 3.6 0.13 1.6
5.2 2.7 0.10 1.4
DC
Amps
50/60
Hz
Approximate Timing
in Sec. @ 70 °F (21
°C)
85
a
Ball Valve Close-Off Pressures: For close-off pressure ratings on Schneider Electric VB2000 ball valves, consult Schneider Elec­tric VB2000 Ball Valve Assemblies Ball Valve Body/Linkage Selection Guide F-27086.
Accessories
AM-763 1/8” Hexcrank for manual override AM-756 Metric Conduit Adapter M20 x 1.5 to 1/2” NPT AM-771 Crank Arm and bracket kit AM-772 Bracket for reverse mounting AM-714 Weathershield Kit
MS4D-xxx3-xxx
AM-703 Input rescaling module, adjust signals to 2-10 Vac, zero and span adjust AM-704 Interface, pulse width modulation (PWM) AM-705 Positioner (NEMA 4 housing) AM-706 Min and/or manual positioner for flush panel mount AM-708 500 Ω resistor for 4 to 20 mA control signal
November, 2018 tc © 2018 Schneider Elect ric. All r ights res erved. A ll trade marks are o wned by Schneider Ele ctric Ind ustries S AS or its af filiat ed companies. Document Number: F-27170-7